Veris HS Installation Instructions

HS
VERIS INDUSTRIES
Replaceable Humidity Element
Provides Easy Field Replacement For Veris Deluxe Humidity Sensors
DESCRIPTION
These humidity elements are calibrated in a high accuracy, NIST traceable, humidity generator. Each sensor is digitally calibrated at four dierent relative humidity levels over an eight-hour period. Calibration data is programmed into the replaceable sensing element. This computer-controlled digital calibration eliminates errors associated with manual “trimming.” A certicate of calibration is provided with the device.
Veris’ calibration system produces known humidity values using the fundamental principle of the “two pressure” generator developed by NIST (H-4622). The two-pressure method involves saturating air with water vapor at a given pressure and temperature. Saturated gas then ows through an expansion valve where it is isothermally reduced to chamber pressure. Gas temperature is held constant during
HUMIDITY
pressure reduction, so relative humidity at chamber pressure is calculated as the ratio of two absolute pressures.
HS
ORDERING INFORMATION
Accuracy NIST
HS X
1 = 1%* 2 = 2% 3 = 3% 5 = 5%
HS 5 X X
N = NIST (1% and 2% models only) X = None (2%, 3%, and 5% models only)
Exam ple:
Conformal Coating
= None
* 1% HS sensors used in outdoor a pplications are limited by the dev ice to 2% accuracy.
Thin-lm ca pacitive technology
provides superior accuracy and
resistance to contaminants
U.S. Patent No. 5,844,138
Yea r
1
Warranty
Temperature uniformity in the chamber is maintained by circulating a temperature controlled uid through a shell surrounding the test space. Highly accurate pressure measurements are made using NIST traceable piezoresistive transducers. The resulting system accuracy is better than 0.5% RH over all ranges and temperatures.
This system is capable of continuously supplying accurate humidity values for instrument calibration, evaluation, and verication.
800.354.8556
+1 503.598.4564
www.veris.com
HQ0001794.B 01131
800.354.8556
HS Digital Humidity Sensor
Serial Number:
This digital sensor has been computer profiled and calibrated at multiple relative humidity levels using standards traceable to the National Institute of Standards and Technology through test #H-4622.
The humidity standard produces an atmosphere of known humidity based on the "two-pressure" principal which is to saturate an air stream with water vapor at a given pressure and temperature. The saturated air stream is then reduced to test pressure. The humidity at test pressure is then the ratio of the two absolute pressures, corrected for vapor pressure and enhancement factor ratios.
Date: Accepted by:
Certificate of Performance
HOURS
2
4
6
0%
-3%
10% 30% 50% 70% 90%
-2%
-1%
0%
+1%
+2%
+3%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Sample interval: 3 minutes
Reference
12.0%
20.0%
30.0%
40.0%
50.0%
60.0%
70.0%
80.0%
90.0%
Reading
12.53%
20.44%
29.94%
40.12%
49.80%
59.98%
69.84%
79.43%
88.80%
Difference
+0.53%
+0.44%
+0.06%
+0.12%
+0.20%
-0.02%
-0.16%
-0.57%
-1.20%
+1 503.598.4564
www.veris.com
HUMIDITY
HQ0001794.B 01131