Product IdentIfIcatIon
EnvironmEntal SEnSorS
Accuracy
HEW
2 = 2%
3 = 3%
5 = 5%
Output Temp.
S
M = 4-20mA
V = 0-5V/0-10V
= Standard
T = Temp
X = No Temp
(Stop here)
inStallation GUiDE
Economy Wall Mount Humidity Sensor
Installer’s Specifications
Input Power:
Input Power, Voltage Version 12-24 VDC or 24 VAC
Input Power, mA Version 12-24 VDC
AC Voltage Tolerance ±10%
AC Frequency 50-60 Hz
Max. Inrush Cur rent After 1 msec (mA version) 25 mA
Output Power:
mA Output 4-20 mA, 2-wire, polarit y insensitive
mA Max. Loop Resistance 500 Ω at 24 VDC input voltage; 250 Ω at 12 VDC input voltage
Volt age Output 0-5 V or 0-10 V (jumper s electable)
Volt age Min. Load Resistance 5 kΩ
Volt age Min. Sinking Current 0.2 mA
Humidity:
HS Element Digitally proled thin-lm capacitive, non-removable
Accuracy ±2%, 3% or 5% (10-90% RH, 20° to 30°C (68° to 8 6°F))
Temperature Eect (Outside 20 ° to 30°C) ≤0.1% RH per °C
Response Time (to 90% change at 20°C) 110 sec
Annual Drift ≤1%
Output Scaling 0-100% RH
Temperature:
Active Output Accuracy ±0.5°C
Active Out put Temperature Scaling 10° to 35°C (50° to 95°F)
Resistive Temperature Accuracy see thermistor table
Self-Heating Error (Resistive Temperature Only) ≤±0.5°C at 20° to 30°C (68° to 86°F);
≤±0.75°C outside of 20° to 30°C (68° to 86°F)
Operating Environment:
Operating Temperature 0° to 50°C (32° to 122°F)
Operating Humidit y 0-100% RH (non-condensing) (Unit will recover from saturation)
Housing:
Material ABS plastic with UL V-0, 5VB Flame Class
Mounting Holes US and European junction box
EMC Conformance: EN61000-6-3:2007+A1:2011 Class B, EN61326-1:2006 Class B; EN61000- 61:2007
1-year limited warranty.
Sensor Type
A = Temp Transmitte r
B = 100R Platinu m, RTD
C = 1k Platinum, RTD
D = 10k T2, Therm istor
E = 2.2k, Ther mistor
F = 3k, Therm istor
G = 10k CPC Ther mistor
H = 10k T3, Thermi stor
J = 10k Dale, Ther mistor
K = 10k with 11k shunt, Ther mistor
M = 20k NTC, Ther mistor
N = 1800 ohm TAC, Therm istor
R = 10k US, Thermis tor
S = 10k 3A 221 Thermis tor
T = 100k, The rmistor
U = 20k “D”, Thermis tor
W = 10k T2 high acc uracy, Thermist or
Y = 10k T3 high acc uracy, Thermist or
Z = 10k E1, Thermisto r
Temp Cert
Blank = None
1 = 1 pt cal
2 = 2 pt cal
quIck Install
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Mount the backplate on the wall in an appropriate location. Place so that the
“Install This End Up” statement on the board is in the upper right corner.
2. Wire the unit as shown (see Wiring section).
3. Attach the front plate.
Z205847-0C PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
HEW SEriES
inStallation GUiDE
oPeratIon
The HEW series economy wall mount humidity sensors measure the levels of RH
and temperature (if equipped) in the air inside a room. HEWs are warranted to meet
accuracy specications for 1 year. To maintain accurate functionality, keep all pickup
vents clear and free of dust, debris, etc.
dImensIons
1.3"
(34 mm)
4.9"
(123 mm)
InstallatIon
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Remove the cover by pressing the tab on the bottom of the
sensor while pulling outward on the bottom edge of the
cover.
2. Position the sensor vertically on the wall, 4 ½ feet (1.5 m) above the oor. Place so
that the “Install This End Up” statement on the board is in the upper right corner.
3.2"
(82 mm)
3. Mount the backplate onto the wall using the screws provided.
Six screwholes available; use
a minimum of two for secure
mounting.