Veris HED Datasheet

HED SERIES
Standard Duct
VERIS INDUSTRIES
Humidity Sensors
2%, 3%, and 5% Accuracies
DESCRIPTION
HED Standard Series duct mount humidity transmitters oer high performance in an easy to install housing at an aordable price. The thin-lm capacitive sensor element provides high accuracy and performance, great long-term stability, and full recovery from saturation. Temperature sensing options are also available.
The duct-mounted HED includes a rugged all plastic housing with a tool-less gasketed entry lid, large cage clamp terminal blocks, and sturdy ABS material. All Standard models come with a standard one-year warranty.
APPLICATIONS
HVAC economizer control
Managing energy systems
Facilitating ASHRAE standards for environmental control
Ideal
for Bid
Spec!
HED
FEATURES
Monitor humidity and temperature with a single device...reduce installation
costs
sensors available
Tool-less gasketed entry lid...no more lost screws
Large cage clamp terminal blocks...easy hoop-up with no wire nuts
Circuitry is embedded in the probe for durability and protection
HUMIDITY
Yea r
1
SPECIFICATIONS
Input Power:
Input Power, Voltage Version 12-24VD C or 24VAC Input Power, mA Version 12-24V DC AC Voltage Tolerance ±10% AC Frequency 50-60 Hz Max. Inrush Current after 1 msec (mA version) 25mA
Output Power:
mA Output 4-20mA, 2-wire, not polar ity sensitive mA Max. Loop Resistance 500Ω at 24VDC input volt age; 250Ω at 12VDC input voltage Voltage Output 0 -5V or 0-10V (jumper selectable) Voltage Min. Load Resistance 5kΩ Voltage Min. Sinking Current 0.2mA
Humidity:
RH Element Digitally proled thin-lm capacitive, non-removable Accurac y ±2%, 3%, or 5% (10-90% RH, 20° to 30°C ) Temperature Effec t (Outside 20° to 30°C) ≤0.1% RH per °C Response Time (to 90% change at 20°C) 110 sec Annual Drift ≤1% Output Scaling 0-10 0% R H
Temperature:
Active Output Accuracy ±0.5°C Active Output Temperature Scaling Type 1: -40° to 50°C (-40° to 122°F); Type 2: 0° to 50°C (32° to 122°F) Self-Heating Error (Resistive Temperature Only) ≤±0.5°C at 20° to 30°C (68° to 86°F); ≤±0.75°C outside of 20° to 30°C (68° to 86°F)
Operating Environment:
Operating Temperature -40° to 50°C (-40° to 122°F) Operating Humidity 0-100% RH noncondensing (Unit will recover from saturation)
Housing:
Material ABS plastic with UL V-0 5VA Flame Class
Warranty
EMC Conformance: EN61000-6-3:2007+A1:2011 Class B; EN61326-1:2006 Class B; EN61000-6-1:2007 Meets UL requirements for plenum rating.
800.354.8556
+1 503.598.4564
www.veris.com
HQ0001719.E 01131
800.354.8556
+1 503.598.4564
APPLICATION/WIRING DIAGRAMS
0–5V/0–10V Models, No Thermistor
Digital Control
Temp In
RH In
Power Source
AC/DC
RTD Temp/RTD RH GND PWR
www.veris.com
Digital Control
Power Source
Thermistor In
Thermistor In
RH In
AC/DC
0–5V/0–10V Models, Thermistor
RTD Temp/RTD RH GND PWR
4-20mA Models, No Thermistor
Digital Control
Temp Return
RH Return
Power Source
DC
DIMENSIONAL DRAWING
4.9"
(123 mm)
3.2"
(82 mm)
ORDERING INFORMATION
2.1"
(53 mm)
T­T+ RH­RH+
RoHS
Compliant
6.1"
(155 mm)
Digital Control
Thermistor
Thermistor
RH Return
Power Source
DC
Sensor Type
= Temp. transmitter
4-20mA Models, Thermistor
1.0"
(25 mm)
A
Temp Range
1 = -40° to 50 °C (-40° to 122°F) 2 = 0° to 50°C (32° to 122°F )
T­T+ RH­RH+
HUMIDITY
Temp Cert
Blank = None 1 = 1 pt cal 2 = 2 pt cal
Output US or EU Temp. Accuracy
HED
2 = 2% 3 = 3% 5 = 5%
M = 4 -20mA V = 0-5VDC/0-10VDC
Exam ple:
With Temp
HED 3 M S T C
Without Temp
HED 3 V S X
HQ0001719.E 01131
S
= Standard
Stop Here
T = Temp X = No Temp
(Stop here)
Sensor Type
B = 100R Platinu m, RTD C = 1k Platinum, RTD D = 10k T2, Therm istor E = 2.2k, Ther mistor F = 3k, Therm istor G = 10k CPC Ther mistor H = 10k T3, Thermi stor J = 10k Dale, Ther mistor K = 10k with 11k shunt, Ther mistor M = 20k NTC, Ther mistor N = 1800 ohm TAC, Therm istor R = 10k US, Thermis tor S = 10k 3A 221 Thermis tor T = 100k, The rmistor
U = 20k “D”, Thermis tor W = 10k T2 high acc uracy, Thermist or Y = 10k T3 high acc uracy, Thermist or Z = 10k E1, Thermisto r
Temp Cert
Blank = None 1 = 1 pt cal 2 = 2 pt cal