Veris H970HCA Installation Instructions

CURRENT MONITORING
TM
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
Fan or Pump
CONTROLLER
4-20m A D C
Analog
Input
MOTOR
CONTACTOR
Removable Mounting Bracket
Self-gripping
Iris
1.0”
(25 mm)
0.8”
(21 mm)
1.1”
(26 mm)
3.1”
(79 mm)
2.8”
(70 mm)
Ø = 0.3” (8 mm)
1.4”
(36 mm)
2.5”
(64 mm)
3.0”
(76 mm)
Bracket can be mounted on either side for added installation flexibility.
INSTALLATION GUIDE
H970HCA
970HCA
Split-Core Low Current 4-20mA & 0-5VDC
DC Current Transducer
Technology Open loop Hall effect Amperage Range 0 to 50/100/200 ADC (slide swi tch selectable) Sensor Supply Voltage 15-30VAC/DC for 4 -20mA output; 12-30VAC/DC for 0-5VDC output Supply Current 35mA max. Isolation 600VAC rms Temperature Range -15° to 60°C (5° to 140°F) Humidity Range 10-90% RH non- condensing Output 4-20mA and/or 0-5VDC Accuracy ±3% F.S. combined linearity, hysteresis, and repeatability
The product design provi des for basic insulation only.
quick install
Disconnect and lock out power to the conductor to be monitored.1.
Choose a location for the sensor. The monitored conductor must pass through the 2.
iris, and the sensor must be at least ½” from any uninsulated conductors.
Wiring ExamplE
Z203256- 0E PAGE 1 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10101
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
Install the adjustable mounting bracket to the back of the enclosure using the 3.
included screws.
Connect supply voltage wires to the terminals marked Power (+) and Gnd (-).4.
Wire the output (mA or VDC) connections between the sensor and the controller.5.
Snap the sensor over the conductor to be monitored and clip the assembly to the 6.
mounting bracket.
Set the field-selectable switch to the desired amperage level (see page 2).7.
DimEnsions
Use DIN Rail
Mounting clip
(Veris part
number AH01) to
mount on stan-
dard DIN rail.
H970HCA
TM
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating and permanent equipment damage.
4x
1A
Slide Switch Amp Ranges
0-50 0-100 0-200
Amperage Range Selector Switch
Amp Ranges
0-50 0-100 0-200
To
Load
To
Load
4-20mA0-5
VDC
Gnd Power
15-24 VAC/DC
Blink=Normal Off=No Power Solid=Overrange
Wiring Diagram
Digital Control
(+) Power
(-) GND
0-5 VDC
4-20mA
AI
Amp Ranges
0-50 0-100 0-200
To
Load
To
Load
4-20mA0-5
VDC
Gnd Power
15-24 VAC/DC
Blink=Normal Off=No Power Solid=Overrange
SENSED AMPS
50/100/200A*
4mA/0VDC
0A
20mA/5VDC
SENSOR OUTPUT
*Slide-Switch Selectable
INSTALLATION GUIDE
opEration
The H970HCA is a current-sensitive device that monitors DC current (amperage) in the conductor passing through it. The unit combines a Hall Effect sensor with proven transducer circuitry, with a status output suitable for connection to building controllers or other appropriate data acquisition equipment operating at up to 30 volts. The H970HCA requires supply voltage to generate its output. Selectable amperage ranges and output types maximize the installation flexibility.
The H970HCA housing offers unprecedented mounting flexibility. The mounting bracket can be attached in three different places. Additionally, the bracket is compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.
notEs
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center hole and around the sensor body to produce multiple turns through the “window.” This increases the current measured by the transducer.
Controller must be programmed to account for the extra turns. e.g., if four turns pass through the sensor (as shown) the normal controller reading must be divided by 4.
< 3.5 A (Sensor Min.)
sEt-up anD Wiring
Failure to observe the following can result in distorted product calibration:
Observe the arrow on the product showing orientation to current source.1.
Do not expose the product to current levels greater than the maximum amperage 2.
range.
Z203256- 0E PAGE 2 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10101
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
scaling
troublEshooting
Problem Solution
The LED is off and no signal is
produced
The LED is on solid and the output
is at maximum
Verify that power is applied to PWR (+) and GND (-)
terminals
Verify that the amperage range selection switch is
in the proper position for the current applied to the conductor.