Veris H948 Installation Instructions

VERIS INDUSTRIES
CURRENT MONITORING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
Removable Mounting Bracket
Self-gripping
Iris
1.0”
(25 mm)
0.8”
(21 mm)
1.1”
(26 mm)
3.1”
(79 mm)
2.8”
(70 mm)
Ø = 0.3”
(8 mm)
1.4”
(36 mm)
2.5”
(64 mm)
3.0”
(76 mm)
Bracket can be mounted on either side for added installation flexibility.
Fan or Pump
CONTR OLLER
Motor
CONT ACTOR
DI
(Statu s)
DO
(Relay
Co il)
CONTR OL POWER
INSTALLATION GUIDE
H948 948
Split-Core Current Switch, Adjustable Output,
with Command Relay
Sensor Power Induced from monitored conductor Insulation Class 600VAC RMS Frequency Range 50/60Hz Temperature Range -15° to 60°C (5° to 140°F) Humidity Range 10-90% RH, non-condensing Hysteresis 10% Typical Terminal Block Maximum Wire Size 14 AWG Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m) Agency Approvals UL 508 open device listing
Do not use the LED status indicators as evidence of app lied voltage.
quick install
Disconnect and lock out power to the conductor to be monitored. 1.
Wiring ExamplE
Z2 01499- 0A PAGE 1 ©2009 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / support@veris.com 07091
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
Plan the installation: 2.
Locate a mounting surface for the removable mounting bracket that will allow the monitored conductor to pass through the iris, or “window” when it is installed and keep the product at least ½” (13mm) from any uninsulated conductors (CE). Determine cable routing for the controller connection, allowing wiring to reach the mounting location.
Install mounting bracket 3.
Drill holes to mount the bracket to the chosen surface using the included screws.
Wire the output connec tions between the sensor and the controller.4.
Snap thesensor over the wire to be monitored and clip the assembly to the 5.
mounting bracket.
Close up and power up.6.
DimEnsions
Use DIN Rail
Mounting clip
(Veris part
number AH01) to
mount on stan-
dard DIN rail.
VERIS INDUSTRIES
H948
4x
1A
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating and permanent equipment damage.
A
OK!
!
A
OK!
!
OK!
STATUS
OK!
STATUS
Setpoint
Status
Open
STOP
Setpoint
Status Closed
STOP
1/4
Setpoint
Setpoint
Status
Closed
STOP
Setpoint
Status
Open
STOP
1/4
Setpoint
OK!
A
OK!
240A
300A:
5A
4A
INSTALLATION GUIDE
opEration
The H948 is a current-sensitive switching device with integral command relay that monitors current (amperage) in the conductor passing through it. A change in amperage in the monitored conductor that crosses the switch (setpoint) threshold plus the hysteresis value will cause the resistance of the status output to change state, similar to the action of a mechanical switch. This status information can be fed back to a building controller that interprets the signal and separately switches the relay. The status output can also be used to switch the relay directly.
In this model, the setpoint is adjustable through the action of a twenty (20) turn potentiometer (see the CALIBRATION section). The status output is suitable for connection to building controllers or other appropriate data acquisition equipment operating at up to 30 volts. The H948 relay requires a 12VDC external power supply for operation.
The H948 housing offers unprecedented mounting flexibility. The mounting bracket can be attached in three different places. Additionally, the bracket is compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.
notEs
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown.
> 135A (Sensor max.)
calibration
Before beginning calibration, establish normal load conditions.
Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)
1. Turn setpoint screw clockwise until Status OPEN LED turns ON.
2. Slowly turn the screw counter-clockwise until the Status CLOSED LED just turns ON.
3.Turn the screw an additional ¼ turn
+
counter-clockwise for operational margin.
H68xx-5A CT
DANGER: 5A CTs can present hazardous voltages. Install CTs in accordance with manufacturer's instructions. Terminate the CT secondary before applying current.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center hole and around the sensor body to produce multiple turns through the "window." This increases the current measured by the transducer.
Controller must be programmed to account for the extra turns. e.g., if four turns pass through the sensor (as shown) the normal controller reading must be divided by 4.
Z2 01499- 0A PAGE 2 ©2009 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / support@veris.com 07091
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
< 2.5 A (Sensor Min.)
B. To monitor over-current (mechanical problems, seized impeller)
1.Turn setpoint screw counter-clockwise until Status CLOSED LED turns ON.
2. Slowly turn the setpoint screw clockwise until the Status OPEN LED just turns ON.
3. Turn the setpoint
+
screw an additional ¼ turn clockwise for operational margin.
troublEshooting
Problem Solution
No Reading at Controller • Check sensor calibration (see above)
• Check for control voltage at sensor (<30V)
• Check for amperage in monitored conductor (>2.5A)
• Assure that sensor core mating surfaces are clean and
that the core clamp is completely closed
Setpoint screw has no stops The setpoint screw has a slip-clutch at both ends of its
Both LEDs are lit Setpoint screw is too far clockwise. See solution above.
travel to avoid damage. Twenty turns CCW will reset the sensor to be most sensitive. Repeat calibration above.