HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
DANGER
Fan or Pump
CONTROLLER
Motor
CONTACTOR
DI
(Status)
DO
(Relay
Coil)
CONTROL
POWER
CURRENT MONITORING
TM
940
Split-Core Current Switch, Fixed Trip Point,
with Command Relay
INSTALLATION GUIDE
SPECIFICATIONS
Sensor Power Induced from monitored conductor
Relay Coil Power 24VAC/DC
Amperage Range 1.5 to 200 A
Status Output Ratings N.O. 1.0A@30VAC/DC, not polarity sensitive
Insulation Class 600VAC RMS
Tri p Point Fixed at 1.5 A
Frequency 50/60 Hz
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH, non-condensing
O State Resis tance Open switch represents 1+ MΩ
On State Resistance Closed switch represents <200 mΩ
Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals UL 508 open device listing
Installation Categor y Cat III, pollution degree 2
Do not use the LED status indicators as evidence of ap plied voltage.
The product design provi des for basic insulation only.
INSTALLATION
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
WIRING EXAMPLE
Z201498-0B PAGE 1 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01132
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
Disconnect and lock out power to the enclosure
containing the conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through center window when it is installed and
that will keep the product at least ½” (13 mm) from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections between the sensor and the controller and between
the sensor the the relay power source.
4. Snap the sensor over the wire to be monitored and clip the assembly to the
mounting bracket.
5. Secure the enclosure and reconnect power.
DIMENSIONS
Removable Mounting Bracket
3.1”
(79 mm)
Ø 0.3”
(8 mm)
1.1”
(26 mm)
0.8”
(21 mm)
2.8”
(70 mm)
2.5”
(64 mm)
1.0”
(25 mm)
Bracket can
be mounted
on three sides
for added
installation
exibility.
Self-gripping Iris
1.4”*
(36 mm)
Use DIN Rail
Mounting clip
(Veris part
number AH01) to
mount on stan-
dard DIN rail.
TM
H940
INSTALLATION GUIDE
PRODUCT OVERVIEW
The H940 is a current-sensitive switching device with integral command relay that
monitors current (amperage) in the conductor passing through it. A change in
amperage in the monitored conductor that crosses the switch (setpoint) threshold
plus the hysteresis value will cause the resistance of the status output to change
state, similar to the action of a mechanical switch. This status information can be fed
back to a building controller that interprets the signal and separately switches the
relay. The status output can also be used to switch the relay directly.
In this model, the setpoint is xed at 1.5 A. The status output is suitable for
connection to building controllers or other appropriate data acquisition equipment
operating at up to 30 volts. The H940 relay requires a 24 VAC/VDC external power
supply for operation.
The H940 housing oers unprecedented mounting exibility. The mounting bracket
can be attached in three dierent places. Additionally, the bracket is compatible with
the Veris AH01 DIN Rail clip, allowing DIN mounting.
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) to add range for a low current load on a high
current source.
>200A (Sensor max.)
240A
RELAY RATINGS
RELAY CONTACT RATINGS
Resistive.................................. 8A@250VAC, 30VDC
Inductive................................. 3.5A@250VAC, 30VDC
TYPICAL COIL PERFORMANCE
Voltage AC DC
24V................................... 10mA 10mA
12V.................................................................... 20mA
Pull In Voltage................................................. 20.1VDC
Drop Out Voltage............................................. 5.2VDC
TROUBLESHOOTING
Problem Solution
No Reading at Controller • Check for control voltage at sensor (<30V)
• Check for amperage in monitored conductor (>1.5A)
• Assure that sensor core mating surfaces are clean and
that the core clamp is completely closed
300A:
4A
5A
H68xx-5A CT
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer.
Program the controller to
account for the extra turns,
e.g., if four turns pass through
the sensor (as shown) them
divide the controller reading
by 4.
< 1.5 A (Sensor Min.)
1A
4x
Z201498-0B PAGE 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01132