Veris H932 Datasheet

SENSED AMPS
30/60/120A*
0V
0A
5V
SENSOR OUTPUT
*Factory calibrated ranges selected
with the amperage range switch
H932 & H952
Current Sensors with Relay: 0-5VDC Analog Output
Load Trending And Control Relay In One Package
VERIS INDUSTRIES
TM
H932
DESCRIPTION
The Hawkeye 932 and H952 Series provide accurate load trending information with a proportional 0-5VDC output signal. This feature combined with an integrated command relay makes these products ideal for start/stop and status monitoring of motors.
The relay is fully isolated from the current sensor, and all relay connections are externally available for maximum exibility.
APPLICATIONS
Load trending
Motor control
Fan/Pump status
current monitoring
H932/952 LINEAR OUTPUT
Scale software as shown
FEATURES
Self-powered analog current sensor with integral start/stop command relay
Reduces the number of installed components... saves time and space
Self-gripping split-core for fast retrot installation...no need to remove
conductor
One device to install for start/stop and status...reduces installation charges
No external power required for current sensor
Selectable factory calibrated ranges up to 120A for increased exibility
and resolution
Factory calibrated switch-selectable ranges (30/60/120A) for high resolution
and installation ease
No jumpers on unit...reduces installation error
Removable mounting bracket for installation exibility
Bracket can be installed in three dierent congurations...added exibility
Command relay switches up to 5A@250VAC
5-year warranty
Maximize Reliability
Minimize Installed Cost
SPECIFICATIONS
Sensor Power Induced from monitored conductor Insulation Class 60 0VAC RM S Frequency Range 50/60 Hz nominal Temperature Range -15° to 60°C (5° to 140°F) Humidity Range 10-90% RH non-condensing Accurac y ±2% F.S. from 10% to 100% (selecte d range) Response Time 2 sec. Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm2) Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m) Agency Approvals UL 508 open device listing; CE: EN61010-1:2001-2, CAT III, pollution degree 2, basic insulation
800.354.8556
Year
5
Warranty
+1 503.598.4564
www.veris.com
HQ00 01767.B 01131
800.354.8556
E150462
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWING
H932/H952
Removable Mounting Bracket
1.1”
(26 mm)
**3.1”
(79 mm)
Ø 0.3”
(8 mm)
* Terminal block may extend up to 1/8” over the height dimensions shown. ** Slide switch may extend up to 1/4” over the height dimensions shown
RELAY
CONTACT RATINGS (N.O.)
Resistive........ 5A@250
Inductive........ 2A@250
(76 mm)
5A@30
2A@30
(21 mm)
(70 mm)
3.0”
VAC
VDC
VAC
VDC
0.8”
2.8”
2.5”
(64 mm)
1.0”
(25 mm)
Bracket can be mounted on three sides for added installation exibility.
Self-gripping Iris
1.4”*
(36 mm)
APPLICATION/WIRING DIAGRAM
Trending & Controlling Motor Loads with the Hawkeye 932
CONTROLLER
DO (Relay Coil)
AI (0-5VDC)
CONTROL
POWER
CONTACTOR
Fan or Pump
Motor
TYPICAL COIL PERFORMANCE
Voltage
24 ......................................................
12
....................................................................
Pull In Voltage (H952 only)
12VDC .............................................................. 8.4VDC
Drop Out Voltage (H952 only)
12VDC .............................................................. 3.0VDC
ORDERING INFORMATION
MODEL AMPERAGE RANGE SENSOR OUTPUT RELAY TYPE R ELAY COIL HOUSING UL
H932
H952 12VDC
0 - 30/60/120A 0 - 5VDC SPST, N.O.
AC DC
15mA
15mA 20mA
24VAC/DC
Split-core
current monitoring
n
n
ACCESSORIES
DIN Rail Clip Set (AH01) DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ00 01767.B 01131
AH01
AV02
AV01
Loading...