Veris H932 Installation Instructions

Installation Guide
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2011 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the use of this material.
DANGER
3.0”
Current Monitoring
Product Overview
The H932 is a current-sensitive device that monitors current (amperage) in any of three eld-selectable ranges; 0-30, 0-60, or 0-120 amperes. These ranges represent the maximum current that can be applied to the monitored conductor. The H932 transforms the monitored current into a 0-5 VDC output suitable for connection to building controllers or other appropriate data acquisition equipment. It is also equipped with a command relay.
The H932 housing oers unprecedented mounting exibility. The mounting bracket can be attached in three dierent places. Additionally, the bracket is compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.
Specifications
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
TM
H932
Split-Core Current Transducer with Relay,
0-5 VDC Output
Sensor Power
Amperage Range
Insulation Class
Frequency Range
Temperature Range
Humidity Range
Accuracy
Response Time
Terminal Block Wire Size
Terminal Block Torque
Agency Approvals
Induced from monitored conductor
0 to 30/60 /120 A (selectable)
60 0VAC RMS
Relay
SPST, N.O., 24 VAC/ DC
50 /60 Hz
-15° to 60°C ( 5° to 140°F)
10 - 90% RH , non-condensing
±2% full scale from 10% to 100% ( selected range )
2 sec.
24-14 AWG ( 0.2 to 2.1 mm2)
3.5 to 4.4 in-lbs ( 0.4 to 0.5 N- m)
UL 508 open device listing
TM
Z201169-0B Page 1 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09133
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Dimensions
Removable Mounting Bracket
1.0”
(25 mm)
1.1”
(26 mm)
3.1”
(79 mm)
0.8”
(21 mm)
2.8”
(70 mm)
Ø 0.3”
(8 mm)
2.5”
(64 mm)
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Bracket can be mounted on three sides for added installation exibility.
Self-gripping Iris
1.4”
(36 mm)
Use DIN Rail Mounting clip (Veris part number AH01) to mount on standard DIN rail.
Installation Guide Current Monitoring H932
TM
Installation
Notes
Disconnect and lock out power to the enclosure containing the conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow the monitored conduc tor to pass through the center window when it is installed and that will keep the product at least ½” (13 mm) from any uninsulated conductors. Determine cable routing for the controller connection, allowing wiring to reach the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Set the desired amperage range (30, 60, or 120 Amps).
4. Wire the output connections between the sensor and the controller (0-5 VDC).
5. Snap the sensor over the wire to be monitored and clip the assembly to the mounting bracket.
6. Scale the controller software to match the sensor’s output.
7. Secure the enclosure and reconnect power.
CONTACTOR
Fan or Pump
Motor
CONTROLLER
DO
(Relay Coil)
AI
(0-5VDC)
CONTROL POWER
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) current transformer (CT) as shown. This technique can be combined with wrapping (see below) to add range for a low current load on a high current source.
240A
>120 A (senso r max.)
DANGER: 5A CTs can present hazardous voltages. Install
5A
4A
300A:
H68 xx-5A CT
CTs in accordance with manufacturer's instructions. Terminate the CT secondary before applying current.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor body to produce multiple turns. This increases the current measured by the transducer. Program the controller to account for the extra turns (e.g., if four turns pass through the sensor (as shown), divide the normal reading by 4).
< 1.5 A (Sensor Min.)
1A
4x
• Derate the product’s maximum current for the number of turns through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating and permanent equipment damage.
CAUTION
RISK OF EQUIPMENT DAMAGE
Z201169-0B Page 2 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09133
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Loading...
+ 1 hidden pages