SENSED AMPS
30/60/120A*
4mA
0A
20mA
SENSOR OUTPUT
*Factory calibrated ranges selected
with the amperage range switch
H931 & H951
VERIS INDUSTRIES
Current Sensors with Relay:
4-20mA Analog Output
Load Trending And Control
Relay In One Package
DESCRIPTION
The Hawkeye 931 and 951 provide accurate load trending information with a
proportional 4-20mA output signal. These devices oer three amperage ranges for
versatility, with easy slide-switch selection. The command relay is fully integrated in
the device, but it is isolated from the current sensor. This combination makes these
products ideal for start/stop control and status monitoring of motors, using one
device instead of two.
APPLICATIONS
● Load trending
● Motor control
● Positive proof of ow
current monitoring
EXAMPLE LINEAR OUTPUT
Scale software as shown
TM
H931
FEATURES
● Loop-powered analog current sensor with integral start/stop command relay
● Reduces the number of installed components...saves time and space
● Self-gripping split-core for fast retrot installation...no need to remove
conductor
● One device to install for start/stop & status...reduces installation charges
● Power the current sensor and receive the 4-20mA signal with only two wires...
fewer wires required than with traditional 3-wire sensors
● Selectable factory calibrated ranges up to 120A for increased exibility and
resolution
● Factory calibrated switch-selec t able ranges (30/60/120A) for high resolution and
installation ea se
● No jumpers on unit...reduce installation error
● Removable mounting bracket for installation exibility
● Bracket can be installed in three dierent congurations...added exibility
● Command relay switches up to 5A@250VAC
● 5-year warranty
SPECIFICATIONS
Sensor Power 30mA (max.)@12-30VDC
Insulation Class 60 0VAC RM S
Frequency Range 50/60 H z
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Accurac y ±2% F.S. from 10% to 100% (selecte d range)
Response Time 2 sec.
Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals UL 508 open device listing
Do not use LED status indicators as evidence of applied voltage
800.354.8556
Year
5
Warranty
+1 503.598.4564
www.veris.com
Maximize Reliability
Minimize Installed Cost
HQ00 0176 6.C 08131
800.354.8556
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWING
H931/H951
Removable Mounting Bracket
1.1”
(26 mm)
*3.1”
(79 mm)
Ø 0.3”
(8 mm)
* Terminal block may extend up to 1/8” over the height dimensions shown.
** Slide switch may extend up to 1/4” over the height dimensions shown
(21 mm)
(70 mm)
3.0”
(76 mm)
0.8”
2.8”
2.5”
(64 mm)
RELAY CONTACT RATINGS (N.O.)
Resistive........ 5A@240 VAC
5A@30 VDC
Inductive........ 2A@240 VAC
2A@30 VDC
1.0”
(25 mm)
Bracket can
be mounted
on three sides
for added
installation
exibility.
Self-gripping Iris
1.4”*
(36 mm)
APPLICATION/WIRING DIAGRAM
Trending & Controlling Motor Loads
12-30 VDC
Power Source
CONTACTOR
Fan or Pump
Motor
CONTROLLER
AI
(4-20mA)
DO
(Relay Coil)
CONTROL POWER
TYPICAL COIL PERFORMANCE
Voltage AC DC
24 ......................................................
12
....................................................................
Pull In Voltage (H951 only)
12VDC .............................................................. 8.4VDC
Drop Out Voltage (H951 only)
12VDC .............................................................. 3.0VDC
ORDERING INFORMATION
MODEL AMPERAGE RANGE SENSOR
H931
H951 12VDC nom.
0 - 30/60/120A 4 - 20mA SPST, N.O.
OUTPUT
15
15
20
RELAY
TYPE
RELAY COIL RELAY RELAY POWER LED UL
24VAC/DC
n n n
n n n
current monitoring
ACCESSORIES
DIN Rail Clip Set (AH01)
DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ00 0176 6.C 08131
AH01
AV02
AV01