Installation Guide
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2011 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
DANGER
Current Monitoring
Product Overview
The H931 is a current-sensitive device that monitors current (amperage) in any of three eld-selectable ranges:
0-30, 0-60, or 0-120 amperes. These ranges represent the maximum current that can be applied to the monitored
conductor. The H931 transforms the monitored current into a 4-20mA output suitable for connection to building
controllers or other appropriate data acquisition equipment operating at up to 30 volts. It is also equipped with a
command relay. The H931 requires a 12-30VDC power supply to generate its output.
The H931 housing oers unprecedented mounting exibility. The mounting bracket can be attached in three
dierent places. Additionally, the bracket is compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.
Specifications
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
TM
H931
Split-Core Current Transducer with Relay,
4-20mA Output
Sensor Power
Insulation Class
Frequency Range
Temperature Range
Humidity Range
Accuracy
Response Time
Terminal Block Wire Size
Terminal Block Torque
Agency Approvals
30mA (max.)@12-30VDC
60 0VAC RMS
Relay
SPST, N.O., 24 VAC/ DC
50/60Hz
-15° to 60°C ( 5° to 140°F)
10 - 90% RH , non-condensing
±2% full scale from 10% to 100% ( selected range )
2 sec.
24-14 AWG ( 0.2 to 2.1 mm2)
3.5 to 4.4 in-lbs ( 0.4 to 0.5 N- m)
UL 508 open device listing
TM
Z201168-0E Page 1 of 4 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Do not use LED status indicators as evidence of applied voltage
Dimensions
Removable Mounting Bracket
1.0”
(25 mm)
1.1”
(26 mm)
3.1”
(79 mm)
0.8”
(21 mm)
2.8”
(70 mm)
Ø 0.3”
(8 mm)
2.5”
(64 mm)
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Bracket can
be mounted
on three sides
for added
installation
exibility.
Self-gripping Iris
1.4”*
(36 mm)
Use DIN Rail Mounting clip
(Veris part number AH01) to
mount on standard DIN rail.
Installation Guide
Current Monitoring
H931
TM
Installation
Notes
Disconnect and lock out power to the enclosure containing the conductor to be
monitored.
1. Locate a mounting surface for the removable mounting bracket
that will allow the monitored conduc tor to pass through the center
window when it is installed and that will keep the product at least
½” (13 mm) from any uninsulated conduc tors. Determine cable
routing for the controller connection, allowing wiring to reach the
mounting location. If using with a variable frequency drive, then
mount the sensor on the line side.
2. Drill holes to mount the bracket to the chosen surface using the
included screws.
3. Set the desired amperage range (30, 60, or 120 Amps).
4. Wire the output connections between the sensor and the controller
(4-20 mA).
5. Snap the sensor over the wire to be monitored and clip the assembly
to the mounting bracket.
6. Scale the controller software to match the sensor’s output.
7. Secure the enclosure and reconnect power.
CONTACTOR
Motor
12-30 VDC
Power Source
Fan or Pump
CONTROLLER
AI
(4-20mA)
DO
(Relay Coil)
CONTROL POWER
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) current transformer (CT) as shown. This technique can be combined with wrapping (see below) to add
range for a low current load on a high current source.
240A
>120 A (sensor max.)
DANGER: 5A CTs can present
hazardous voltages. Install
5A
4A
300A:
H68 xx-5A CT
CTs in accordance with
manufacturer's instructions.
Terminate the CT secondary
before applying current.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor body to produce multiple turns. This increases
the current measured by the transducer. Program the controller to account for the extra turns (e.g., if four turns pass through the
sensor (as shown), divide the normal reading by 4).
< 1.5 A (Sensor Min.)
1A
4x
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
CAUTION
RISK OF EQUIPMENT DAMAGE
Z201168-0E Page 2 of 4 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08131