Veris H923 Installation Instructions

CURRENT MONITORING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
H923
TM
923
Split-Core Current Transducer,
0-10VDC Output
Installer’s Specifications
For applications requiring double or reinforced insulation, please contact the factory
INSTALLATION
Disconnect and lock out power to the enclosure containing the conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow the monitored conductor to pass through the center window when it is installed and that will keep the device at least 1/2” from any uninsulated conductors. Determine cable routing for the controller connection, allowing wiring to reach the mounting location.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
WIRING EXAMPLE
CONTACTOR
CONTROLLER
AI
COMMON
0-10VDC
+
Z202365-0H PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Fan or Pump
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Set the desired amperage range (20, 100, or 150 Amps).
4. Wire the output connections between the sensor and the controller (0-10VDC).
5. Snap the sensor over the conductor to be monitored and clip the assembly to the mounting bracket.
6. Scale the controller software to match the sensor output.
7. Secure enclosure and reconnect power.
DIMENSIONS
(26 mm)
3.1”
(79 mm)
Ø = 0.3”
(8 mm)
1.1”
Removable Mounting Bracket
1.0”
(25 mm)
0.8”
(21 mm)
2.8”
(70 mm)
2.5”
(64 mm)
3.0”
(76 mm)
Bracket can be mounted on three sides for added installation exibility.
Self-gripping
Iris
1.4”
(36 mm)
Use DIN Rail
Mounting clip
(Veris part
number AH01) to
mount on stan-
dard DIN rail.
H923
20 100 150
Amperage Range Selector Switch
20 100 150
AMPERAGE RANGE
AMPERAGE RANGE
SENSOR OUTPUT
Selected Range
0V
0A
10V
SENSED AMPS
DDC
CONTROLLER
AI
COMM
0-10VDC Input
+
Self-Powered Output
20 100 150
OUTPUT 0-10VDC
AMPERAGE RANGE
TM
INSTALLATION GUIDE
OPERATION
The H923 is a current transducer that senses current (amperage) in any of three eld-selectable ranges; 0-to-20, 0-to-100, or 0-to-150 Amps. These ranges represent the maximum current that can be applied to the monitored conduc tor. The H923 transforms the monitored current into a 0 to 10 VDC output suitable for connection to building controllers or other appropriate data acquisition equipment. The H923 requires no external power supply to generate its output.
The H923 housing oers unprecedented mounting exibility. The mounting bracket can be attached in three dierent places. Additionally, the bracket is compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be combined with wrapping (see below) to add range for a low current load on a high current source.
240A
> 150A (Sensor max.)
5A
4A
300A:
H68xx-5A CT
WIRING
SCALING
1. Set range switch.
DANGER: 5A CTs can present hazardous voltages. Install CTs in accordance with manufacturer's instructions. Terminate the CT secondary before applying current.
2. Scale controller software to match selected output.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating and permanent equipment damage.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor body to produce multiple turns. This increases the current measured by the transducer.
Program the controller to account for the extra turns,
< 1.5 A (Sensor Min.)
1A
e.g., if four turns pass through the sensor (as shown) then divide the normal controller reading by 4.
Z202365-0H PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
4x
TROUBLESHOOTING
Problem Solution
No Reading at Controller • Check polarity of sensor output connections
• Check for output voltage at sensor
• Check for amperage in monitored conductor
• Assure that sensor core mating surfaces are clean and
that the core clamp is completely closed
Loading...