Veris H921 Installation Instructions

VERIS INDUSTRIES
CURRENT MONITORING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
Fan or Pump
CONTROLLER
4-20m A DC
Analog
Input
MOTOR
CONTACTOR
Removable Mounting Bracket
Self-gripping
Iris
1.0”
(25 mm)
0.8”
(21 mm)
1.1”
(26 mm)
3.1”
(79 mm)
2.8”
(70 mm)
Ø = 0.3” (8 mm)
1.4”
(36 mm)
2.5”
(64 mm)
3.0”
(76 mm)
Bracket can be mounted on either side for added installation flexibility.
INSTALLATION GUIDE
H921 921
Split-Core Current Transducer
Installer’s Specifications
Sensor Power 30mA (max.)@12-30VDC Insulation Class 600VAC rms (UL), 300VAC rms (CE) Frequency 50/60 Hz Temperature Range -15° to 60°C (5° to 140°F) Humidity Range 10-90% RH non-condensing Amperage Range 0-30/60/120 Amps (slide-switch selectable) Output 4 -20mA DC Hysteresis 10% of setpoint, typical Off-State Leakage 1+ MΩ Safety UL 508, IEC 61010-1: 2001 CAT III
Specification Note: For CE compliance, conductor sha ll be insulated according to IEC 61010‑1:2001, Installation Category III o r equivalent. The product design provi des for basic insulation only.
Quick install
Wiring ExamplE
Disconnect and lock out power to the conductor to be monitored. 1.
Plan the installation: 2.
Locate a mounting surface for the removable mounting bracket that will allow the monitored conductor to pass through the iris, or “window” when it is installed and keep the product at least ½” (13mm) from any uninsulated conductors (CE). Determine cable routing for the controller connection, allowing wiring to reach the mounting location.
Install mounting bracket 3.
Drill holes to mount the bracket to the chosen surface using the included screws.
Set the desired amperage range (30, 60, or 120 Amps).4.
Wire the output connec tions between the sensor and the controller (4-20mA).5.
Snap the sensor over the wire to be monitored and clip the assembly to the 6.
mounting bracket.
Scale the controller software to match the selected output.7.
DimEnsions
Z201166-0E PAGE 1 ©2010 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com 01101
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
Use DIN Rail
Mounting clip
(Veris part
number AH01) to
mount on stan‑
dard DIN rail.
VERIS INDUSTRIES
H921
3x
1A
240A
300A:
5A
4A
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating and permanent equipment damage.
DDC
CONTROLLER
12-30VDC
Power Supply
AI
120
60 30
DDC
CONTROLLER
AI
COMM
4-20mA Out
120
60 30
DDC
CONTROLLER
AI
V(COM)
4-20mA in Return
120
60 30
120
60 30
Amperage Range Selector Switch
120
60 30
SENSED AMPS
Selected Range*
4mA
0A
20mA
SENSOR OUTPUT
*Factory calibrated ranges selected
with the amperage range switch
INSTALLATION GUIDE
opEration
The H921 is a current transducer that senses current (amperage) in any of three field-selectable ranges; zero-to-thirty, zero-to-sixty, or zero-to-one hundred twenty amperes. These ranges represent the maximum current that can be applied to the monitored conductor. The H921 transforms the monitored current into 4-20mA DC output suitable for connection to building controllers or other appropriate data acquisition equipment. The H921 requires 12-30VDC external power to generate its output.
The H921 housing offers unprecedented mounting flexibility. The mounting bracket can be attached in three different places. Additionally, the bracket is compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.
notEs
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown.
> 120A (Sensor max.)
Wiring
External Power
Sourcing Panel
(‑Common)
Sinking Panel
(+Common)
H68xx‑5A CT
DANGER: 5A CTs can present hazardous voltages. Install CTs in accordance with manufacturer's instructions. Terminate the CT secondary before applying current.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center hole and around the sensor body to produce multiple turns through the "window." This increases the current measured by the transducer.
Controller must be programmed to account for the extra turns. e.g., if three turns pass through the sensor (as shown) the normal controller reading must be divided by 3.
Z201166-0E PAGE 2 ©2010 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com 01101
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
< 3 A (Sensor Min.)
*A resistor can be added in parallel to convert the 4‑20mA signal to a VDC signal (250 ohm= 1‑5VDC); (500 ohm = 2‑10VDC)
scaling
Set range switch.1.
Scale controller 2.
software to match selected output.
troublEshooting
Problem Solution
No Reading at Controller •Conrm that you have 12-30VDC in series with the
sensor output terminals and the control panel analog input
• Assure that sensor core mating surfaces are clean and
that the core clamp is completely closed.
Check polarity of sensor output connections