TM
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. 
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. 
 DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
CURRENT MONITORING
INSTALLATION GUIDE
H909HV
909HV
Split-Core Current Switch, Adjustable Trip Point
with 250VAC/DC Output
Installer’s Specifications
Amperage Range  2.5 to 135A Continuous 
Sensor Power  Induced from monitored conductor 
Max. Current 200A 
Frequency  50/60 Hz 
Switch Output  Max. current: 1A; max. voltage: 250VAC/DC 
Hysteresis  10% of setpoint, typical 
Insulation Class  300V (CE); 600VAC RMS 
Temperature Range  -15° to 60° C (-5° to 140° F) 
Humidity Range  10-90% RH non-condensing 
Output Resistance - O -State  0 (open switch represents 1+ MΩ of resistance) 
Terminal Block Maximum Wire Size  14 AWG 
Terminal Block Torque (nominal)  4 in-lbs (0.45 N-m)
For CE compliance, conductor shall be insul ated according to IEC 61010‑1:2001, Installation 
Category III or equivalent. 
The product design provi des for basic insulation only. 
INSTALLATION
Disconnect and lock out power to the conductor to be monitored. 
1. Locate a mounting surface for the removable mounting bracket that will allow 
the monitored conductor to pass through the center window when it is installed 
and that will keep the device at least 1/2” from any uninsulated conductors. 
Determine cable routing for the output connection, allowing wiring to reach the 
mounting location.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
WIRING EXAMPLE
CONTACTOR 
Insulated Conductor 
DDC CONTROLLER
DI
Z205454-0E  PAGE 1  ©2012 Veris Industries  USA 800.354.8556 or +1.503.598.4564 / support@veris.com  02121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other countri es.
MOTOR 
Fan or Pump 
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections between the sensor and the controller (solid-state 
contact).
4. Snap the sensor over the wire to be monitored and clip the assembly to the 
mounting bracket.
5. Calibrate the sensor (see page 2) with the load running normally.
DIMENSIONS
Removable Mounting Bracket
1.0”
3.1”
(79 mm)
Ø = 0.3”
(8 mm)
1.1”
(26 mm)
(21 mm)
(70 mm)
3.0”
(76 mm)
(25 mm)
0.8”
2.8”
2.5”
(64 mm)
Bracket can be mounted 
on three sides for added 
installation exibility.
Self-gripping 
Iris
1.4” 
(36 mm)
Use DIN Rail 
Mounting clip 
(Veris part 
number AH01) to 
mount on stan‑
dard DIN rail.

TM
H909HV
INSTALLATION GUIDE
OPERATION
The H909HV is a current-sensitive switching device that monitors current (amperage) 
in the conductor passing through it. A change in amperage in the monitored 
conductor which crosses the switch (trip point) threshold plus the hysteresis value 
will cause the resistance of the status output to change state, similar to the ac tion of 
a mechanical switch. In this model, the trip point is adjustable through the action of 
a twenty (20) turn potentiometer (see the CALIBRATION section). The status output is 
suitable for connection to building controllers or other appropriate data acquisition 
equipment operating at up to 250 volts. The H909HV requires no external power 
supply to generate its output.
The H909HV housing oers unprecedented mounting exibility. The mounting 
bracket can be attached in three dierent places. Additionally, the bracket is 
compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.
NOTES
For load currents greater than sensor maximum rating: 
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be 
combined with wrapping (see below) when added safety is desired for a low current 
load on a high current source.
240A 
> 135A (Sensor max.)
CALIBRATION
Before beginning calibration, establish normal load conditions.
OK!
A
Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)
!
OK!
A
1. Turn setpoint screw 
counter-clockwise until 
Status OPEN LED turns ON.
2. Slowly turn the screw clockwise until the Status CLOSED LED just turns ON.
Setpoint 
Status 
Closed 
B. To monitor over-current (mechanical problems, seized impeller)
OK!
STOP 
+
Status 
Open 
Setpoint
STATUS
Setpoint 
1/4
OK!
STOP 
3. Turn the screw 
an additional 1/4 
turn clockwise for 
operational margin.
5A 
 4A 
300A:
H68xx‑5A CT
DANGER: 5A CTs can present hazardous voltages. 
Install CTs in accordance with manufacturer's instructions. 
Terminate the CT secondary before applying current.
CAUTION 
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns 
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating 
and permanent equipment damage.
For load currents less than sensor minimum rating: 
Wrap the monitored conductor through the center window and around the sensor 
body to produce multiple turns. This increases the current measured by the 
transducer.
Program controller to account 
for the extra turns. e.g., if four 
turns pass through the sensor 
(as shown) divide the normal 
controller reading by 4.
< 2.5 A (Sensor Min.)
1A
4x
!
OK!
A
1. Turn setpoint screw clockwise until 
Status CLOSED LED turns ON.
Setpoint 
Status 
Closed 
STATUS
OK!
STOP 
2. Slowly turn the setpoint screw counter-clockwise until the Status OPEN LED just 
turns ON.
Status 
Open 
Setpoint 
Setpoint
+
3. Turn the setpoint 
screw an additional 
1/4 turn counter-
STOP 
1/4
clockwise for 
operational margin.
TROUBLESHOOTING
Problem Solution
No Reading at Controller • Check sensor calibration (see above)
• Check for control voltage at sensor (250V)
• Check for amperage in monitored conductor (> 2.5A)
• Assure that sensor core mating surfaces are clean and 
that the core clamp is completely closed
Setpoint screw has no stops The setpoint screw has a slip-clutch at both ends of its 
Both LEDs are lit Setpoint screw is too far clockwise. See solution above.
travel to avoid damage. Twenty turns CCW will reset 
the sensor to be most sensitive. Repeat calibration 
above.
Z205454-0E  PAGE 2  ©2012 Veris Industries  USA 800.354.8556 or +1.503.598.4564 / support@veris.com  02121