TM
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
CURRENT MONITORING
INSTALLATION GUIDE
H909
TM
909
Split-Core Current Switch, Adjustable Trip Point,
120VAC/DC Output
Installer’s Specifications
Sensor Power Induced from monitored current
Insulation Class 600VAC RMS (UL)
Frequency Range 50/60Hz
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Amperage Range 2.5 - 135A Continuous
Output N.O. 200mA@120VAC/DC, not polarit y sensitive
Hysteresis 10% of setpoint, typical
Output Resistance - O -State >1 MΩ
Terminal Block Maximum Wire Size 14 AWG
Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m)
Agency Approvals UL 508, IEC 61010-1: 2001 CAT III
The product design provi des for basic insulation only.
INSTALLATION
Disconnect and lock out power to the conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the center window when it is installed
and that will keep the device at least 1/2” from any uninsulated conductors.
Determine cable routing for the output connection, allowing wiring to reach the
mounting location.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
WIRING EXAMPLE
CONTACTOR
Insulated Conductor
Z201495-0C PAGE 1 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08114
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
MOTOR
CONTROLLER
Digital
Input
Fan or Pump
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections between the sensor and the controller (solid-state
contac t).
4. Snap the sensor over the wire to be monitored and clip the assembly to the
mounting bracket.
5. Calibrate the sensor (see page 2) with the load running normally.
DIMENSIONS
Removable Mounting Bracket
1.0”
3.1”
(79 mm)
Ø = 0.3”
(8 mm)
1.1”
(26 mm)
(21 mm)
(70 mm)
3.0”
(76 mm)
(25 mm)
0.8”
2.8”
2.5”
(64 mm)
Bracket can be mounted
on either side for added
installation flexibility.
Self-gripping
Iris
1.4”
(36 mm)
Use DIN Rail
Mounting clip
(Veris part
number AH01) to
mount on stan-
dard DIN rail.
TM
H909
INSTALLATION GUIDE
OPERATION
The H909 is a current-sensitive switching device that monitors current (amperage) in
the conductor passing through it. A change in amperage in the monitored conductor
that crosses the switch (setpoint) threshold plus the hysteresis value will cause
the resistance of the FET status output to change state, similar to the action of a
mechanical switch. In this model, the setpoint is adjustable through the action of a
twenty (20) turn potentiometer (see the CALIBRATION section). The status output is
suitable for connection to building controllers or other appropriate data acquisition
equipment operating at up to 120 volts. The H909 requires no external power supply
to generate its output.
The H909 housing oers unprecedented mounting exibility. The mounting bracket
can be attached in three dierent places. Additionally, the bracket is compatible with
the Veris AH01 DIN Rail clip, allowing DIN mounting.
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) when added safety is desired for a low current
load on a high current source.
240A
> 135A (sensor max.)
CALIBRATION
Before beginning calibration, establish normal load conditions.
OK!
A
Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)
!
OK!
A
1. Turn setpoint screw
clockwise until Status OPEN
LED turns ON.
2. Slowly turn the screw counter-clockwise until the Status CLOSED LED just
turns ON.
Setpoint
Status
Closed
OK!
STOP
+
Status
Open
Setpoint
1/4
STATUS
OK!
Setpoint
STOP
3.Turn the screw an
additional 1/4 turn
counter-clockwise for
operational margin.
B. To monitor over-current (mechanical problems, seized impeller)
5A
4A
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
300A:
H68xx-5A CT
!
OK!
A
1.Turn setpoint screw
counter-clockwise until Status
CLOSED LED turns ON.
Setpoint
Status
Closed
STATUS
OK!
STOP
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the center window. This increases the current
measured by the transducer.
Program controller to account
for the extra turns. e.g., if four
< 2.5 A (Sensor Min.)
1A
turns pass through the sensor
(as shown) divide the normal
controller reading by 4.
Z201495-0C PAGE 2 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08114
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
4x
2. Slowly turn the setpoint screw clockwise until the Status OPEN LED just turns ON.
Status
Setpoint
Open
Setpoint
+
3. Turn the setpoint
screw an additional
1/4 turn clockwise for
STOP
1/4
operational margin.
TROUBLESHOOTING
Problem Solution
No Reading at Controller • Check sensor calibration (see above)
• Check for control voltage at sensor (<120V)
• Check for amperage in monitored conductor (> 2.5A)
• Assure that sensor core mating surfaces are clean and
that the core clamp is completely closed
Setpoint screw has no stops The setpoint screw has a slip-clutch at both ends of its
Both LEDs are lit Setpoint screw is too far clockwise. See solution above.
travel to avoid damage. Twenty turns CCW will reset
the sensor to be most sensitive. Repeat calibration
above.