Veris H906 Installation Instructions

Installation Guide
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the use of this material.
DANGER
Current Monitoring
Product Overview
The H906 is a current-sensitive switching device that monitors current (amperage) in the conductor passing through it. A change in amperage in the monitored conductor that crosses the switch (setpoint) threshold plus the hysteresis value causes the resistance of the FET status output to change state, similar to the action of a mechanical switch. In this model, the setpoint is adjustable through the action of a twenty (20) turn potentiometer (see the Calibration section). The status output is suitable for connection to building controllers or other appropriate data acquisition equipment operating at up to 30 volts. The H906 requires a 5-30 VDC external power supply to generate its output.
The H906 housing oers unprecedented mounting exibility. The mounting bracket can be attached in three dierent places. Additionally, the bracket is compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.
TM
TM
H906
Split-Core Current Switch, Adjustable Trip Point,
N.C. Status Output
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
Specifications
Sensor Power
Amperage Range
Status Output Ratings
Insulation Class
Setpoint
Frequency Range
Temperature Range
Humidity Range
Hysteresis
Off State Leakage
On State Voltage Drop
Terminal Block W ire Size
Terminal Block Torque
Agency Approvals
Installation Category
The product design provides basic insulation only. Do not use the LED indicators as evidence of applied voltage.
5- 30 VD C
2.5 to 135 A continuous
N.C. 0.1 A@ 30 V DC, polarity sensitive
600 VAC RMS (UL); 300 VAC (CE)
Adjustable, 2.5 A or less
50 /6 0 Hz
-15° to 60°C ( 5° to 140 °F)
10-9 0% RH non-condensing
10% t ypical
34μA@ 5VDC, 200μA@ 30VDC
1.9VDC max.@0.1A
24 to 14 AWG (0.2 to 2.1 mm2)
3.5 to 4.4 in-lbs (0. 4 to 0.5 N-m)
COMPLIANCE INFORMATION
UL508 open device listing, CE: EN61010-1
Cat. III, pollution degree 2
Z201573-0D Page 1 of 4 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07132
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
3.0”
Fan or Pump
CONTROLLER
Insulated Conductor Only!
DI
Motor
-
-
Observe Polarity!
5-30VDC
POWER SOURCE
+
-
+
+
CONTACTOR
Current Monitoring H906
TM
Dimensions
Installation
Removable Mounting Bracket
3.1”
(79 mm)
Ø 0.3”
(8 mm)
1.1”
(26 mm)
0.8”
(21 mm)
2.8”
(70 mm)
2.5”
(64 mm)
1.0”
(25 mm)
Bracket can be mounted on three sides for added installation exibility.
Self-gripping Iris
1.4”*
(36 mm)
Use DIN Rail Mounting clip (Veris part number AH01) to mount on standard DIN rail.
Disconnect and lock out power to the enclosure containing the conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow the monitored conductor to pass through the center window when it is installed and that will keep the product at least ½” (13 mm) from any uninsulated conductors. Determine cable routing for the controller connection, allowing the wiring to reach the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections from the sensor to the controller (solid-state contact) and to the external power supply. Observe polarity.
4. Snap the sensor over the conductor and clip the assembly to the mounting bracket.
5. Secure the enclosure and reconnect power.
6. Calibrate the sensor with the load running normally.
Z201573-0D Page 2 of 4 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07132
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Loading...
+ 2 hidden pages