MODBUS
OP
Hawkeye® 8920 Series
POWER MONITORING
INSTALLATION GUIDE
H8920-3
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of Veris Industries nullify this statement.
H8920-3
LONTalk Integration Node
For Use With H8163 Energy Meters
Installer’s Specifications
LonWor ks® Network Free topolog y transceiver, 78 kbps Modbus Network RTU 9600 BAUD, 8N1 format Network Variable Type Float Input Power 16-24 VAC/DC, 100mA (max.) Temperature Range 0 to 60°C (32 to 140°F) Humidity Range 0 - 95% non-condensing
METER DATA NETWORK VARIABLES
kWh, Consumption kW, Real Power kVAR, Reactive power kVA, Apparent power Power fac tor Voltage, line to line Voltage, line to neutral Amps, Average current kW, Power ØA kW, Power ØB kW, Power ØC Power factor ØA Power factor ØB Power factor ØC Voltage, ØA to ØB Voltage, ØB to ØC Voltage, ØA to ØC
Voltage, ØA to Neutral Voltage, ØB to Neutral Voltage, ØC to Neutral Amps, Current ØA Amps, Current ØB Amps, Current ØC Present kW Demand Subinterval Present kW Demand Peak kW Demand Present kVAR Demand Subinterval Present kVAR Demand Peak kVAR Demand
DIMENSIONS
PRODUCT IDENTIFICATION
MODEL DESCRIPTION
H8920-3 H8163 Energy Meter to LonTalk® integration node
Z203538-0F PAGE 1 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07111
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H8920-3
TB1
TB2
TB3
TB4
OP
POWER MB
+
SHIELD B A
SERVICE
RX
TX
TB5
TB6
TB7
TB8
-
LON
TM
INSTALLATION GUIDE
OPERATION
The H8920-3 LONTalk Integration Node allows the integration of Veris Industries H8163 Series energy meters with a LON Works control/monitoring system. The H8163 must be equipped with the H8163-CB communication board for this integration to work. The H8920-3 converts the metering data network variables collected by the H8163 as Modbus protocol to LONTalk. Using an indexing technique, the H8920-3 reports the data from up to 63 H8163 meters on the downstream Modbus network. Adjusting an input variable allows selection of the Modbus address of the desired meter. The data is then recorded before selecting another H8163. The H8920-3 can also be used for binding purposes with a single H8163 meter.
The H8920-3 polls the H8163 meter for its full data set approximately once per second. All output data network variables are immediately updated with this received data. Data exchanged between the node and the meter are fully checksummed to ensure integrity. If corrupt data is detected, the output network variables are not updated and retain their previous value.
PRODUCT DIAGRAM
1. LON Talk Terminal Block: Connect to the LON network at these terminals. This
connection is not polarity sensitive.
2. Shield Terminal Block: Communications shielding for both the LONTalk and
Modbus communications networks.
3. Modbus Terminal Block: Connect to the H8163-CB Modbus network. This
connection is polarity sensitive; ensure correct polarit y.
4. 16-24 VAC/DC Power: Two-wire system power terminal block.
5. TX LED: Indicates transmission of Modbus network data
6. RX LED: Indicates reception of Modbus network data
7. Service LED: Standard LON Works Service LED. Used in concert with the Service
Switch to locally view the commissioning status of the device. LED status after the service switch is pushed:
ON, then OFF solid = Device has been commissioned by a network tool.
BLINK at 1/2 Hz rate = Device has not been commissioned by a network tool.
ON, OFF, then solid ON = Device does not have an application.
8. Identification Service Switch: Standard LonWorks Service Switch. Used in
concert with the Service LED to locally view the commissioning status of the device.
9. OP LED: Normally on. The OP LED will blink o when there is an incomplete data
exchange between the meter and the LON node. If this LED is always o, then the meter is not responding to data requests (i.e., the meter is disconnected, unpowered, or incorrectly wired).
Z203538-0F PAGE 2 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07111
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H8920-3
TM
INSTALLATION GUIDE
INSTALLATION
1. Remove screws from the lid of the H8920-3 housing. Lift lid and remove wire guide caps. Set aside with the lid.
2. Bring the H8163-CB RS-485 network cable to the Modbus terminal block marked +MB-. Thread wires through wire guide before terminating. Connect the (+) to TB6. Connect the (-) wire to TB5. Connect the shield wire to TB4.
3. Bring the LON Works network cable to the terminal block marked BA LON. Thread wires through wire guide before terminating. Connect the A wire to TB1. Connect the B wire to TB2. Connect the LON network shield wire to TB3.
4. Connect the 16-24 VAC/DC power wires to TB7 and TB8. The power terminals are not polarity sensitive. This power source must be separate and isolated from other circuits to prevent unwanted "ground loops."*
5. Thread wires through the most convenient openings in the housing.
6. Re-attach the lid and snap wire guides into place. Replace screws to hold the housing together.
7. Mount the H8920-3. The device can be ush mounted to a wall, screw mounted to a 2 or 4s electrical encosure, or nipple mounted to an existing enclosure. Mount the H8920-3 in a class 2 environment.
8. Refer to the H8163-CB installation instructions for connection of the LON node to the H8163 power meter.
* Veris transformers such as X020xxx, X040 xxx or X050xxx or DC power sup plies such as PS-24-7.5, 15, or 30 fulll these requirements. IIf the installatio n only has non-isolated 24 VAC available, then a Veris transformer such as X020ADA can provide the necessary isolation.
LON A
LON B
Shield
Modbus –
Modbus +
Power
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
CONFIGURATION
1. Upon powering up, the OP-LED is lit.
2. During operation, the OP-LED turns o if either of the following occurs:
a) No Modbus requests are generated by the unit for 10 seconds. This occurs with new units (which have yet to be commissioned) or any units which are in "Uncongured," "O-Line" or "Disabled" LonTalk states. Under these conditions, the neuron chip will not generate requests to the Modbus network.
b) No response or an error response from the Modbus network (e.g. no meter attached, wrong type of meter (H8035 instead of H8163-CB), broken RS-485 wir es, etc.).
3. If the OP-LED is OFF for any reason covered in step 2 above, it will be re-lit when a correct response is received from the Modbus network.
4. Under Condition 2b above, the oating-point SNVT data will be replaced with oating-point-not-a-number (NaN,0x7FC00000), indicating to the remote user that the data is no longer valid.
Index Feature
By adjusting the network input variable nviMeter Index, the Modbus address used to populate all of the NVOs can be changed. This option is used to view and archive data from a Modbus network of up to 63 H8163 power meters. Using this feature eliminates the possibility of binding any points from the node. If the application requires binding, the LON node can only view one meter.
Using the Meter-Index Function
To ensure that the data read from the unit corresponds to the correc t meter, follow this algorithm:
1. Change nviMeter Index to the desired meter.
2. Wait for nvoMeter Index to change to the same value as nviMeter Index. Do not read data from the unit until this occurs: You will not be able to determine which meter the data corresponds to until nvoMeter Index=nviMeter Index. Do not use "time-delays" to wait for the new data to be valid.
3. Once nvoMeter Index=nviMeter Index, you may poll values with the assurance that the data corresponds to the desired meter.
Power Meter Configuration
If binding is required, use Modbus address 1 for the H8163-CB power meter. When employing the indexing method, use addresses 1-63. Please refer to the H8163 Installation Instructions for meter addressing information.
Auto Propagate Feature
The H8920-3 automatically propagates all network variables. If nciMaxSendTg is set above zero (default is zero), all variables are propagated periodically. Units are in tenths of a second. For example, if nciMaxSendTg is set to 100, the H8920-3 will automatically propagate all variables every 10 seconds.
Z203538-0F PAGE 3 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07111
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H8920-3
Up to 63 H8163 meters with H8163-CB installed
H8920-3 LON Node
LON Talk® Network
Modbus Network
Lon Talk® Controller
TM
INSTALLATION GUIDE
NETWORK OPTIONS
Node Identification
Wink: The LON Node will light its service LED for 5 seconds in response to a WINK command.
Service Pin: A ser vice pushbutton is provided for this method of identication. (See Product Diagram section).
Neuron ID: The Neuron ID is located on a label on the back of the device. It can be written down or peeled o as a removable sticker with bar code for easy insertion to your network.
Program ID
The standard program ID for this product is 90:00:14:8A:0F:02:04:01
Indexing Option: Allows the node to access up to 63 H8163 meters for
viewing and archiving purposes only
Bound Option: For all applications requiring binding*
Lon Talk® Controller
Modbus Network
H8163 with
H8163-CB installed
LON Talk® Network
H8920-3 LON Node
H8163 with
H8163-CB installed
Z203538-0F PAGE 4 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07111
*If employing the bound o ption, address each H8163-CB at 1.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H8920-3
VERIS H8920-3
MANUFACTURER-
SPECIFIC
NETWORK
VARIABLES
CONFIGURATION PROPERTIES
Nv2
Nv1 Nv3 Nv4 Nv5 Nv6 Nv7 Nv8 Nv9 Nv10 Nv11 Nv12 Nv13 Nv14 Nv15 Nv16 Nv17 Nv18 Nv19 Nv20 Nv21 Nv22 Nv23 Nv24 Nv25 Nv26 Nv27 Nv28 Nv29
nvoPower_f
nviSubIntLen nviNumSubInts nviCommand nviMeterIndex
SNVT_count SNVT_count SNVT_count SNVT_count
nvoEgyWH nvoVAR nvo VA nvoPF nvoLLVolts nvoLNVolts nvoAmps nvoAPower nvoBPower nvoCPower nvoAPF nvoBPF nvoCPF nvoABVolts nvoBCVolts nvoACVolts nvoANVolts nvoBNVolts nvoCNVolts nvoAAmps nvoBAamps nvoCAmps nvoDmdSubInt nvoCurrDmd nvoPeakDmd nvoRDmdSubIntv nvoRCurrDmd nvoRPeakDmd
SNVT_power_f
SNVT_elec_whr_f SNVT_power_f SNVT_power_f SNVT_pwr_fact_f SNVT_volt_f SNVT_volt_f SNVT_amp_f SNVT_power_f SNVT_power_f SNVT_power_f SNVT_pwr_fact_f SNVT_pwr_fact_f SNVT_pwr_fact_f SNVT_volt_f SNVT_volt_f SNVT_volt_f SNVT_volt_f SNVT_volt_f SNVT_volt_f SNVT_amp_f SNVT_amp_f SNVT_amp_f SNVT_power_f SNVT_power_f SNVT_power_f SNVT_power_f SNVT_power_f SNVT_power_f
Nv30 Nv31 Nv32 Nv33
nc49 nc52 nc88 nc49
nciMaxSendT nciMinSendT nciMinDelta nciMaxSendTg
SNVT_time_sec SNVT_time_sec SNVT_lev_cont SNVT_ time_sec
MANDATORY
NETWORK VARIABLE
Nv34
nvoMeterIndex SNVT_count
TM
INSTALLATION GUIDE
Z203538-0F PAGE 5 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07111
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H8920-3
TM
INSTALLATION GUIDE
NETWORK VARIABLE DETAILS
Name Type Range Description
nv1 nvoEgyWH 0-1e38kWH Total Accumulated Energy
nv2 nvoPower 0-1e38kW Power
nv3 nvoVAR 0-1e38kW Reactive Power
nv4 nvo VA 0-1e38kW Apparent Power
nv5 nvoPF 0-1 Power Factor
nv6 nvoLLVolts 0-1e38V Voltage, Line to Line
nv7 nvoLNVolts 0-1e38V Voltage, Line to Neutral
nv8 nvoAmps 0-1e38A Amps
nv9 nvoAPower 0-1e38kW Power, Phase A
nv10 nvoBPower 0-1e38kW Power, Phase B
nv11 nvoCPower 0-1e38kW Power, Phase C
nv12 nvoAPF 0-1 Power Factor, Phase A
nv13 nvoBPF 0-1 Power Factor, Phase B
nv14 nvoCPF 0-1 Power Factor, Phase C
nv15 nvoABVolts 0-1e38V Voltage, Phase A to Phase B
nv16 nvoBCVolts 0-1e38V Voltage, Phase B to Phase C
nv17 nvoACVolts 0-1e38V Voltage, Phase A to Phase C
nv18 nvoANVolts 0-1e38V Voltage, Phase A to Neutral
nv19 nvoBNVolts 0-1e38V Voltage, Phase B to Neutral
nv20 nvoCNVolts 0-1e38V Voltage, Phase C to Neutral
nv21 nvoAAmps 0-1e38A Amperage, Phase A
nv22 nvoBAamps 0-1e38A Amperage, Phase B
nv23 nvoCAmps 0-1e38A Amperage, Phase C
nv24 nvoDmdSubInt 0-1e38kW Present Real Subinterval Demand
nv25 nvoCurrDmd 0-1e38kW Current Real Demand
nv26 nvoPeakDmd 0-1e38kW Peak Real Demand
nv27 nvoRDmdSubInt 0-1e38kW Present Reactive Subinterval Demand
nv28 nvoRCurrDmd 0-1e38kW Current Reactive Demand
nv29 nvoRPeakDmd 0-1e38kW Peak Reactive Demand
nv30 nviSubIntLen 0-65535 * Length of Subinterval multiplied by 5 sec.
nv31 nviNumSubInts 0-6 * Number of Subintervals per Demand
nv32 nviCommand 0-65535 * Command Register
nv33 nviMeterIndex 1-63 Selects Modbus address
nv34 nvoMeterIndex 1-63 Reports selected Modbus address
nc49 nciMaxSendT 0.0-6553.4 sec Maximum time between nvoPower updates. Default is 0 sec (disabled).
nc52 nciMinSendT 0.0-6553.4 sec Minimum time between nvoPower updates. Default is 15 sec.
nc88 nciMinDelta 0.0-100.0% Percent change in nvoPower that will force an nvoPower update. Default is 5%. Set to 0.0% to disable.
nc49 nciMaxSendTg 0.0-6553.4 sec Maximum time between updates to all network variables. Default is 0 sec (disabled).
* See H8163-CB documentation fo r further details. Do not bind to these meter conguratio n variable, because demand calculation restarts each ti me the meter writes these variables, and bound variables are re-writ ten at regular inter vals.
Z203538-0F PAGE 6 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07111