POWER MONITORING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.
Ø 0.17”
(4.4mm)
5.6”
(143mm)
6.6”
(168mm)
6.1”
(154mm)
3.0”
(76mm)
4.3”
(110mm)
INSTALLATION GUIDE
H8830
H8830
Wireless Modbus/Pulse Transceiver
Installer’s Specifications
Input Power 110 to 120 VAC
Processor ARM
Firmware Field-upgradeable
Inputs Pulse (2x dry contact), Modbus RS-4 85
Modbus Input 2-wire RS-4 85 (9600 or 19200 baud)
LED 2x RF, 2x RS-485, 2x pulse, Alive, Alarm
Radio Frequency 900 MHz ISM band
Radio Output Power 1 mW (optional 150 mW, consult factory)
Radio Max Range 1500 ft. (457 m) per hop
quick install
Set the Modbuss address and system switches.1.
Connect the pulse and Modbus hookups.2.
Attach the antenna.3.
Connect power to the H8830.4.
Product identification
MODEL DESCRIPTION
H8830 Wireless Modbus/Pulse Transceiver
ZL0069-0A PAGE 1 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10102
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
dimensions
H8830
oPeration
The H8830 wireless Modbus®/pulse transceiver from Veris Industries is perfect for
submetering commercial and industrial facilities and adding Modbus devices to
any network without the need for costly communications wiring. The input port
on the H8830 easily connects to new or existing Modbus and pulse devices (meters,
sensors, etc.) to automatically detect the optimum route for reliable and timely data
communications. Data from each H8830 passes from one transceiver to another to
reach its ultimate destination. This self-managed mesh network allows the system
to function with high reliability where other wireless systems fail due to short- or
long-term interference from radio signals
installation
Modbus Address:1. Every Modbus device in the system
must have a unique address. This includes each H8830 and
every attached RS-485/Modbus device. Select an address
and set the DIP switches to match. The sum of the value
of the switches is the address. In the example to the right,
set address 52 by placing switch 4, 16, and 32 to the ON
position.
System Switches: 2. For most systems, set all of the system switches to the “OFF”
position. The only required switch is the RS-485 baud rate option. Set this to “OFF”
for 19200 or to “ON” for 9600. The example below is a default configuration for
9600 baud on the RS-485 connection.
INSTALLATION GUIDE
Modbus Hookup:4. Attach any Modbus slave or master devices to the RS-485
terminals as shown in the wiring diagram. Multiple Modbus devices may be
attached to each H8830.
Note: When attaching Modbus devices, it is not necessary to specify if the device
is a master (H8820, PLC, etc) or a slave device (power meter, sensor, etc). The
H8830 will automatically detect the master and handle it appropriately.
Attach the Antenna:5. Attach the antenna to the side of the H8830. The antenna
should be finger tight and be placed in a vertical position.
Power up the H8830: 6. Attach the power brick to the power jack on the H8830.
The device should power up and be ready in a few seconds. The LEDs should blink
in the following manner.
The Alive LED should start to blink about once per •
second.
The Alarm LED will blink if transmission errors occur.•
The RF TX/RX LEDs will blink when the radio is •
receiving or transmitting data.
The RS-485 LEDs will blink for local Modbus activity.•
The Pulse input LEDs will light when the •
corresponding pulse input terminals are closed.
Pulse Hookup:3. Attach any dry contact pulse
output meters to the pulse input terminals as
shown in the wiring diagram to the right. The
H8830 can support two pulse devices.
The H8830 can be attached to many types of
pulse output meter. Power, water, gas, etc. For
“KYZ” type power meters, use the normally
open contacts, usually labeled “K and Z”.
register functions
Pulse Count: The pulse count is stored as an unsigned 32-bit integer. This allows 1.
for 232 pulses (4.2 billion) to be counted before rollover. On Modbus systems
that do not allow you to read 32-bit values, you can calculate the pulse count as
follows:
count = MSW * 65535 + LSW
Instantaneous Pulse Rate: The pulse rate values for instantaneous, minimum, and 2.
maximum rates are calculated based on the time between arriving pulses. For
example, if InstPulse1 = 30 and InstPulse count size = 5, then the average rate for
the last 5 pulses is 6 sec/pulse. To convert the register values (in seconds) to a rate
value, use the following formula:
Rate/hour = (N * 60 * 60 / InstRegister)
where InstRegister is any of the 6 register values 4 through 9, and N is the
instantaneous pulse count size at offset 10.
Min/Max Pulse Rate: These 4 registers are calculated from the instantaneous pulse 3.
rate. These latching registers are updated whenever the minimum or maximum
rate fields are exceeded by the instantaneous rate. These four registers may be
cleared by writing a zero to the register. Writing to one min./max. register clears
all four min./max. registers.
ZL0069-0A PAGE 2 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10102
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.