Veris H8822 Datasheet

H8822 ACQUISUITE
Data Acquisition Systems
VERIS INDUSTRIES
Modbus Protocols, Data Logging and Server Capabilities
DESCRIPTION
The H8822 AcquiSuite™ data acquisition system is the perfect do-it-yourself solution for your energy logging needs. This server combines the exibility of Ethernet LAN, WAN, or internet communication paths with the lowest total installed cost on the market. It is the ideal device for recording electrical, natural gas, water, and other building energy usages.
The AcquiSuite has eight exible I/O options. After installation, data from a connected device is time-stamped and stored in nonvolatile memory at user­selected intervals until the next scheduled upload to the SQL database server. Using the built-in phone modem, Ethernet port, or cellular modem, the AcquiSuite sends data to the Building Manager Online™ server or to other third party software
providers (cellular modem is only available on the H8822GSM model).
network integration
H8822
APPLICATIONS
Aggregating energy and operational information from remote sites
Gathering “near real-time” performance data
Measurement and verication
FEATURES
Simple plug-and-play connec tivity...install and congure in minutes
Hardware and software provide data in exible, industry-standard formats for
databases, spreadsheets, etc.
LCD display for easy installation and troubleshooting
Integrated web server provides setup and conguration using any standard
web browser (e.g. Safari™ or Internet Explorer™)
SPECIFICATIONS
Input Power 120-240V 50/60 Hz transformer to 24VDC, included
Processors:
Main Processor ARM 9 I/O Co-Processor ARM 7 Operating System Linux Flash ROM 16MB NOR Flash (expandable w ith USB memory device) Memory 32MB RAM LEDs 8x pulse input, 4 modem activity, Modbus TX/ RX, power status LCD 2 x 16 LCD Character, two but tons LAN 10/100, Auto crossover detection
Modem:
Phone V.34 bis, 33,600 bps (H8822) Cellular GSM/GPRS Class 10, 85 kbps (H8 822GSM) Protocols Modbus/RTU, Modbus/TCP, TCP/IP, PPP, HTTP/HTML, FTP, SNMP, SMTP, XML Serial Port RS-485 Modbus Interval Recording User selectable 1-60 minutes. Default 15 minute interval Inputs 8x, user selectable: 0-10V - Min/Max/Ave/Instant aneous; 4-20mA- Min/Max/Ave/Instantaneous; Pulse - Consumption, Rate;
Resistance - Min/Max/Ave/Instantaneous; Runtime - Runtime, Status
Outputs 2x, Dry contact 30VDC, 150mA max. Agency Approvals FCC Part 15, Class A
800.354.8556
Year
2
Warranty
+1 503.598.4564
www.veris.com
HQ0001803.B 01131
800.354.8556
+1 503.598.4564
www.veris.com
APPLICATION/WIRING EXAMPLES
The Internet
Dial-up PPP
BMO Webserver
Cellular
(H8822GSM)
AcquiSuite™ Server
E5xCx
H81xx with H8163-CB
or
WAN
4-20mA
Local Area
Network
®
Ethernet
Analog devices can connect to on-board H8923-4 as well
DIMENSIONAL DRAWING
8.2 in
(209 mm)
H8036
2.0 in
(51 mm)
9.3 in
(77 mm)
Pulse
A8332
Modbus Converter
PULSE DEVICES
(Gas/Water Meters)
THE ACQUISUITE SYSTEM ALLOWS...
...Internet Display of Data Using the BMO Website
...Security and Flexibility
...Compatibility with Existing Systems
View performance data in an easy graphical format. Store, display, and download historical data in a secure SQL database. Design custom views of data from one or more buildings or systems.
Store data on board in nonvolatile memory. Protect information in the event of a power failure. Time-stamp all interval data with an on-board real-time clock.
Use the I/O module to connect to existing sensors and meters. Use TCP/IP protocols to interface with spreadsheets, databases, text les, etc.
Analog
E3x
ANALOG DEVICES
(Temperature, Humidity, Air Quality, etc.)
network integration
ORDERING INFORMATION
MODEL DESCRIPTION
H8822 AcquiSuite Demand Response System: 8 Flexible I/O Inputs
H8822GSM AcquiSuite Demand Response System; GSM/GPRS cellular modem
HQ0001803.B 01131
Loading...