Veris H84xxVBS Datasheet

HxxV, HxxVB, & HxxVBSSERIES
VERIS INDUSTRIES
Maximize System Efficiency and Gain Precise Power Quality with 1% Energy and Power Accuracy
DESCRIPTION
The H84xxV, H84xxVB, and H84xxVBS Series digital power meters deliver high accuracy and high value at a competitive price.
Whether you are looking for a 1-phase pulse output meter to monitor kWh, or a 3-phase communicating meter to monitor THD, the H84xxV Series has the right meter for you, in panel and wall mounting styles for your convenience.
The pulse output unit oers two pulse outputs. While kWh is standard, the second pulse output provides a eld-selectable choice between phase loss or kVARh.
The Modbus communications unit oers a choice between two data outputs, Full Data Set (FDS) or Extended Data Set (EDS). Data points are listed on the next page.
power/energy monitoring
APPLICATIONS
Energy management and performance contrac ting
Submetering for commercial tenants
Activity-based costing in commercial and industrial facilities
BACne t
connectivity
via new
E8950
Gat e way
H84xx
H84xxVBS
FEATURES
Revenue Grade measurements
Intuitive navigation with context-sensitive menus for easy use
Panel, wall, DIN rail mount...provide mounting exibility
Digital power meters automatically detect and correct phase reversal,
eliminating the need to be concerned with CT load orientation...fast, trouble-free installation
Real-time power monitoring via local display or through control/data
acquisition systems
Large, easy-to-read display
Multiple values displayed at the same time on an anti-glare display
featuring a green back-light
SPECIFICATIONS
Inputs:
Control Power 100 to 415 ± 10%VAC, 5VA, 45-60 Hz DC 125 to 250VDC ± 20%VDC, 3W * Voltage Input UL: 600VAC; CE: 300VAC (L-N) Current Input CT Scaling Primary: Adjustable f rom 5A to 32,767A Measurement Input Range 1V RMS full scale (+20% over-range)
Accuracy:
Current and Voltage 0.5% Power ANSI C12.16, 1% Measurement - True RMS True RMS up to 15th harmonic, 3-phase AC System
Outputs:
Pulse Output #1 (kWH ) N.O. Static Output (240VAC or 300VDC, 100mA max. @ 25˚C, derate 0.56mA per˚C above 25˚C) 2.41kV RMS isolation Pulse Output #2 (H8463V/VB/ VBS) (Phase Loss or kVARh) N.C. Static Out put(240VAC or 300VDC, 100mA max. @ 25˚C, derate 0.56mA per˚C above 25˚C) 2.41kV RMS isolation
Mechanical:
Weigh t H84xxV: 0.8 lbs; H8 4xxVB: 6.35 lbs; H84xxVBS: 9.15 lbs Protection Class V: IP40 front, IP30 back; VB: NEMA 1, IP40
Environmental:
Operating Temperature Range Meter: 0° to 60 °C (32° to 140°F); Display: -10° to 50°C (14° to 122°F) Storage Temperature Range Meter and Display: -40°C to 85°C (-40° to 185°F) Humidity Range 0-95% noncondensing Agency Approvals UL508; ANSI C22.2, Cat. III, Pollution Degree 2, for distribution systems up to 347VAC (L-N)/600VAC (L-L); CE per IEC61010, Cat. III, Pollution Degree 2, f or distribution systems up to 300VAC (L-N)/480VAC (L-L)
*For control voltages >415VAC to 600VAC order H84xxVBS
Year
5
Warranty
800.354.8556
+1 503.598.4564
www.veris.com
HQ0001713.B 01131
800.354.8556
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWINGS
+0.8
3.6"
–0.0
H84xxV
+0.8
3.6"
–0.0
(92 mm)
H84xxVB(S)
(92 mm)
2"
(50 mm)
(19 mm)
8.3"
(210 mm)
H8400 SERIES
0.8"
3.9"
(96 mm)
3.9"
(96 mm)
4.1"
(104 mm)
9.1"
(242 mm)
DATAOUTPUTS
H8436: Full Data Set (FDS) kWh, Consumption kW, Real Power kVAR, Reactive power kVA, Apparent power Power fac tor Voltage, line to line Voltage, line to neutral Amps, Average cur rent kW, Real power ØA kW, Real power ØB kW, Real power ØC Power factor ØA Power factor ØB Power factor ØC Voltage, ØA to ØB Voltage, ØB to ØC Voltage, ØA to ØC Voltage, ØA to Neutral Voltage, ØB to Neutral Voltage, ØC to Neutr al Amps, Current ØA Amps, Current ØB Amps, Current ØC
H8437: Extended Data Set (EDS) (FDS Plus): Amps, Current Neutral Frequency kVAh, Consumption kVARh, Consumption Minimum Real power Maximum Real power KVA, Apparent Power, Per Phase KVAR, Reactive Power, Per Phase KW, Total Real Power Present Demand KVA, Total Apparent Power Present Demand KVAR, Total Reactive Power Present Demand KW, Total Real Power Max Demand KVA, Total Apparent Power Ma x Demand KVAR, Total Reactive Power Max Demand THD, Voltage A-N, B-N, C-N THD, Voltage A-B, B-C, A-C THD, Current, Per Phase Usage Hours Usage Minutes Tot al Hour s Total Minutes
ORDERING INFORMATION
MODEL DESCRIPTION DATA OUTPUT DISPLAY SCREENS
PANEL MOUNT - 120-4 80V
(For Control Voltages > 415VAC to 600VAC order H84x xVBS)
H84 63V* Panel Moun t, 1V, CT Input , FDS
H8453V * Panel Moun t, 1V, CT Input , FDS
H8436V Panel Moun t, 1V, C T Input, FDS
H8437 V Panel Mount, 1V, CT Input, ED S
WALL MOUNT - 120-4 80V
(For Control Voltages > 415VAC to 600VAC order H84x xVBS)
H84 63VB* Wall Mount , 1V, C T Input, FDS
H8453V B* Wall Mount, 1V, CT Inp ut, FDS
H8436VB Wall M ount, 1V, CT Input, FDS
H8437 VB Wall Mount , 1V, C T Input, EDS
WALL MOUNT - 240- 600V Pulse Modbus FDS EDS
H8463VBS* Wa ll Mount, 1V, CT Input, FDS, 240 -600V
H8453VBS* Wall Mo unt, 1V, CT Input, FDS, 240- 600V
H8436VBS Wall Mou nt, 1V, CT Inpu t, FDS, 240-600V
H8437 VBS Wall Mount, 1V, CT Inp ut, FDS, 240-60 0V
The H8453 has two normally open solid-state outputs: one kWh and one eld selectable for phase loss or kVARh. The H8463 has one normally open output (kWh) and one normally closed output (eld selectable for phase loss or kVAR).
Pulse Modbus FDS EDS
n n
n n
n n
n n
Pulse Modbus FDS EDS
n n
n n
n n
n n
n n
n n
n n
n n
COMPANION CURRENT TRANSFORMERS
(Model/Amps)
H681
Small:
0-1 00 = 10 0A 0-2 00 = 200A 0-30 0 = 300A
Medium:
1-40 0 = 400A 1-60 0 = 600A 1-80 0 = 800A
Large:
2-80 0 = 800A 2-16 00 = 1600A 2-2000 = 2000A 2-24 00 = 2400A
(Output Type)
-
1V
= 0 -1VAC
Example:
H681 2-800 – 1V
ACCESSORIES
Fuse Kits (AH02, AH03, AH04) DIN Rail Mounting Kit (AH23) Modbus-to-BACnet Converter (E8950) Modbus TCP Gateway (U013- 0012)
AH04
E8950
U013-0012
AH23
power/energy monitoring
HQ0001713.B 01131