the user will be required to correct the interference at his own expense.
POWER MONITORING
H84xx
Power Meters For Use With 1V CTs
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
INSTALLATION GUIDE
Installer’s Specifications
Electrical Characteristics:
Type of measurement True RMS up to the 15th harmonic. On three-phas e AC system
Measurement A ccuracy:
Current & Voltage ANSI C12.16, 0.5%
Power ANSI C12.16, 1%
Frequency ±-0.01 Hz from 45 to 65 Hz
Data Update Rate 1 sec
Input Voltage Characteristics:
Measured Voltage Max. UL to 600VAC (L-L); CE to 300VAC (L-N)
Metering Over-Range +20%
Impedance 2 MΩ (L-L)/ 1MΩ (L-N)
Frequency Range 45 to 65 Hz
Input Current Characteristics:
CT Scaling Primary: Adjustable from 5A to 32,767A
Measurement Input Range 0 to 1.0VAC (+20% over-range)
Impedance 100 k Ω
Control Power * AC: 100 to 415 ±10%VAC, 5VA; DC: 125 to 250 ±20%VDC, 3W
(see * for 600V option)
Control Power Ride Through Time 100 mS at 120VAC
Output:
Pulse Output #1 H8453V/VB, H84 63V/VB (kWh) N.O., static output
(240 VAC or 300VDC, 100mA max. at 25°C,
derate 0.56mA per °C above 25°C) 2.41kV RMS isolation
Pulse Output #2 H8453V/VB (Phase Detec t or kVARh) N.O., static output
(240 VAC or 300VDC, 100mA max. at 25°C,
derate 0.56mA per °C above 25°C) 2.41kV RMS isolation
Pulse Output #2 H8463V/VB (Phas e Detect or kVARh) N.C., static output
(240VAC or 300VDC, 100mA max. at 25°C,
derate 0.56mA per °C above 25°C) 2.41kV RMS isolation
RS485 Por t; H8436V/VB; H8437V/VB 2-wire, 2400 to 19200 baud, Modbus RTU
Mechanical Characteristics:
Weight H8400V=0.81lb; H8400VB=6.35lb; H8400VBS=9.15lb
IP Degree of Protection (IEC 60529) IP40 front display, meter body IP30 for VB
Display Charac teristics Back-lit green LCD (6 lines total, 4 concurrent values)
Environmental Conditions:
Operating Temperature Meter: 0° to 60 °C; Display: -10° to 50°C
Storage Temperature Meter and Display: -40° to 85°C
Humidity Range 5 to 95% RH at 50°C (non-condensing)
Metering Category:
North America CAT III; for distribu tion systems up to 347V L-N/600VAC L-L
CE CAT III; for distribution systems up to 300V L-N/480VAC L-L
Dielectric Withs tand Per UL 508, EN61010
Conducted and Radiated Emissions FCC part 15 Class B, EN55011
Safety:
North America UL508/C22.2
Europe CE per IEC 61010
*For control voltages >415VAC order H84xxVBS
Modifications to this product without the express authorization of
Veris Industries nullify this statement.
QUICK INSTALL
1. Mount the device in a re/electrical enclosure. Use the retaining clips for the
H84xx-V. Use appropriate wall-mounting screws for the H84xx-VB(S).
2. Wire the device. See the Wiring Diagrams section for options.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
INSTALLATION GUIDE
SAFETY
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only qualied electrical workers should install this equipment. Read
entire instructions before performing this work.
• Before performing visual inspections, tests, or maintenance on this
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized, tested,
and tagged. Pay particular attention to the design of the power system.
Consider all sources of power, including the possibility of backfeeding.
• Turn o all power supplying the power meter and the equipment in which
it is installed before working on it.
• Always use a properly rated voltage sensing device to conrm that all
power is o.
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. In the USA, see NFPA 70E.
• Qualied persons performing diagnostics or troubleshooting that require
electrical conductors to be energized must comply with NFPA 70 E Standard for Electrical Safety Requirements for Employee Workplaces and
OSHA Standards - 29 CFR Part 1910 Subpart S - Electrical.
• Before closing all covers and doors, carefully inspect the work area for
tools and objects that may have been left inside the equipment.
• Use caution while removing or installing panels so that they do not
extend into the energized bus; avoid handling the panels, which could
cause personal injury.
• NEVER bypass external fusing.
• NEVER short the secondary of a potential transformer.
• Before performing Dielectric (Hi-Pot) or Megger testing on any
equipment in which the power meter is installed, disconnect all input
and output wires to the power meter. High voltage testing may damage
electronic components contained in the power meter.
• Install the power meter in a suitable electrical and re enclosure.
Failure to follow these instructions may result in death or serious
injury.
DIMENSIONS
+0.8
3.6"
–0.0
(92 mm)
(210 mm)
H8400 SERIES
8.3"
H84xxV
+0.8
3.6"
–0.0
(92 mm)
2"
(50 mm)
H84xxVB(S)
0.8"
(19 mm)
3.9"
(96 mm)
3.9"
(96 mm)
4.1"
(104 mm)
Always observe all National and Local Codes during installation
of this product.
9.1"
(242 mm)
Mount the box on a solid surface:
1. For use in a pollution degree 2 or better environment only.
3. Disconnect devices: in Europe, provide a switch or circuit breaker rated for a
maximum of 20 amps to disconnect the H84xx from the supply source. Place the
switch or circuit breaker in close proximity to the equipment and within easy
reach of the operator, and mark it as the disconnecting device. The disconnecting
device shall meet the relevant requirements of IEC 60947-I and IEC 60947-3 and
be suitable for the application. In the US and Canada, disconnecting fuse holders
can be used.
NOTE: Recommended distance from left sid e of box to another object is 1.8” (45 mm) to allow
meter door to open.
4. Provide overcurrent protection for supply conductors with approved current
limiting devices suitable for protecting the wiring but not exceeding 20 Amps.
5. Wiring can be up to 12 AWG (2mm) and rated min. 600V.
6. After installation, close the box and secure with the provided plastic cable tie or
securing screw. A lockout device may also be used for this purpose.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
INSTALLATION GUIDE
PRODUCT DIAGRAMS
H84xxV
1
1
2 3 4 5 6
+
1 10-415V 5 V A
50/60 Hz / 125-250V 3W
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
T urn o f f all power supplying this device and the equipment in which it is installed before
working on it.
Failure to follow these instructions will result in death or serious injur y.
RIESGO DE DESCARG A ELÉCTRICA, EXPLOSIÓN O DESTELLO DE ARCO
Apague la alimentación del dispositivo y del equipo en el que está instalado antes de
efectuar cualquier trabajo.
El incumplimiento de estas precauciones podrá causar la muerte o lesiones serias.
Z104144-0C
RISQUE D'ÉLECTROCUTION, D'EXPLOSION OU D'ARC ELECTRIQUE
Coupez l'alimentation de cet appareil et de l'équipement dans lequel il est installé avant travaille r .
240V
Si ces précautions ne sont pas respectés, cela entraÎnera la mort ou des blessures graves.
100mA max
KWH PHASE or
KVARH
7 8 9 10
1
VO LT AGE INPUTS / ENTRADAS DE TENSIÓ N
ENTRÉES DE TENSION
"CURRENT" INPUTS / ENTRADAS DE CORRIENTE
ENTRÉES DE COURANT 1V NOM. / 1.2V MAX.
2
4
Red
1. Control Power
2. Voltage Inputs
3. 1 Volt ‘‘Current” Inputs
4. Pulse Outputs for H8453V, H8463V or RS-485 Output for H8436V, H8437V
H84xxVB(S)
2
V
V
1
I I
1+ 3+ 2- 2+
14 15 16 17 18 19
White White White
2
600V L-L 50/60Hz
R
480V L-L 50/60Hz
1-
Black
V
3
I I I
Yellow
V
N
I
3-
3
INSTALLATION
H84xxV Mounting
1. Insert the power meter through a 3.6” x 3.6” (92mm x 92mm) cut-out.
2. Attach the two retainer clips to the
power meter using the retainer slots
at position A or position B.
There are two sets of retainer slots
on the left, right, top and bottom of
the power meter. The rst set is for
installation locations thinner than
3 mm (1/8 in.). The second set is for
installation locations 3 to 6 mm (1/8 in.
to 1/4 in.).
NOTE: For use on a at surface of a protective enclosure (for example, in the USA, use
a NEMA Type 1 rated enclosure or better).
Removing the Connectors:
1. Insert the at end of a screwdriver into the groove between the
power meter and the connector, as shown in the image.
2. Pull down the screwdriver to remove the connector.
B
A
A
B
1
2
9
V
V
V
V
2
1
3
+
1 10-415V 5 V A
50/60 Hz / 125-250V 3W
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLAS H
T urn o f f all power supplying this device and the equipment in which it is installed before
working on it.
Failure to follow these instructions will result in death or se rious injury .
RIESGO DE DESCARG A ELÉCTRICA, EXPLOSIÓN O DESTELLO DE
Apague la alimentación del dispositivo y del equipo en el que e stá instalado antes de
efectuar cualquier trabajo.
El incumplimiento de estas precauciones podrá causar la muerte o lesiones serias.
Z104389-0A
RISQUE D'ÉLECTROCUTION, D'EXPLOSION OU D'ARC ELECTRIQU E
Coupez l'alimentation de cet appareil et de l'équipement dans l equel il est installé avant travailler .
240V
Si ces précautions ne sont pas respectés, cela entraÎnera la mo rt ou des blessures graves.
2. RS-485 Input (H8436VB/S, H8437VB/S) or Pulse Contacts (H8453VB/S, H8463VB/S)
3. 1 Volt “Current” Inputs
4. Voltage Inputs
5. Control Power Input
6. Control Power Fuse — 1/2 Amp, 600VAC
7. Self-Power Connections
H84xxVB(S) Mounting
Mount the meter box at an appropriate
height allowing for easy viewing of the
display.
Allow a clearance of 1.8” (45mm) of open
space on the left side of the meter to allow
the meter door to open.
0.5"
13 mm
7.5"
190 mm
1.5"
38 mm
6.5"
165 mm
8. 600VAC Connections for H84xxVBS or jumper on H84xxVB
9. Studs for 600V transformer — H84xxVBS only
* NOTE: If this unit is the last unit in a daisy chain, the n this switch should be in the “on” position.
Otherwise, this switch should remai n in the “o” position.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
WIRING DIAGRAM
H84xxVB(S)
J6
J5
A
N
H84xx
NOTE: Voltage inputs and control power for distributio n systems up to 347V L-N and 600 V L-L
comply with metering category III. Also, terminal wiring should have a minimum temperature
rating of 80°C.
INSTALLATION GUIDE
The following symbols are used in the diagrams:
SymbolDescription
Voltage disconnect switch
J7
B
Fuse
Earth ground
N
L
"CONTROL POWER INPUT"
CONTROL POWER may be taken from the voltage inputs by selecting appropriate
jumper connections.* CONTROL POWER must be below 415V L-L and a maximum of
300V from either line to ground. For operation up to 600VAC, use the X050 DJU 600V
to 300 dropping transformer provided in H84xx-XBS products.
In this product, the jumpers connect to J6 and J8 with 480 or 600V Delta power
systems.
* Set jumpers for N & A . If product will be used on a 480V or higher Delta install ation, provide a
separate control power source or use the optiona l X050 DJU 600V to 300 dropping transformer.
S1
Current transformer
S2
Potential transformer
Protection containing a voltage disconnect switch with a fuse or
disconnect circuit breaker (the protection device must be rated
for the available short-circuit current at the connection point).
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
SUPPORTED SYSTEM TYPES
Voltages Less Than or Equal to 347VAC L-N/600VAC L-L, Direct Connect, No PTs
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
L1 L2
N
H84X XV WIR ING DIAGR AM S
H84xx
INSTALLATION GUIDE
NL1
1-Phase Line-to-Neutral 2- Wire System 1 CT
USE SYSTEM TYPE 101
S1
S2
1-Phase Direct Voltage Connection 2 CT
USE SYSTEM TYPE 12USE SYSTEM TYPE 31
14
15
16
17
18
19
1-Phase Line-to-Line 2-Wire System 1 CT
L1 L2
3
V1
4
V2
5
V3
6
VN
I1+
I1–
I2+
S1
S2
I2–
I3+
I3–
USE SYSTEM TYPE 11
3
V1
4
V2
5
V3
6
VN
I1+
14
I1–
15
I2+
16
I2–
17
I3+
18
I3–
19
3-Phase 3-Wire 3 CT no PT
L2 L3L1
3
V1
4
V2
5
V3
6
VN
3
V1
4
V2
5
V3
6
VN
S1
S2
S1
S2
14
15
16
17
18
19
I1+
I1–
I2+
I2–
I3+
I3–
Balanced 3-Phase 3-Wire Direct Voltage Input Connection 1 CT
L2 L3L1
S1
S2
USE SYSTEM TYPE 32
3
4
5
6
14
15
16
17
18
19
V1
V2
V3
VN
I1+
I1–
I2+
I2–
I3+
I3–
S1
S2
S1
S1
S2
S2
14
15
16
17
18
19
I1+
I1–
I2+
I2–
I3+
I3–
3-Phase 4-Wire Wye Direct Voltage Input Connection 3 CT
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Control Power
H84xx
TM
INSTALLATION GUIDE
Direct Connect Control Power C (Phase to Phase)
L1 L2 L3
• Phase to Phase only when voltage <415 +10%VAC max.
• See Table below.
Direct Connect Control Power (DC Control Power)
12
12
Direct Connect Control Power (Phase to Neutral)
L1 L2 L3N
12
• Phase to Neutral only when voltage <415+10% VAC max.
• See Table below.
Control Power Transformer (CPT) Connection
L1 L2 L3
12
• DC Control Power 100 VDC<V<300VDC
• See Table below.
Fuse Recommendation
1. To avoid distortion, use parallel wires for control power and voltage inputs. Keep
the fuse close to the power source.
2. Use with 480Y/277V and 208Y/120V systems.
3. For an open delta PT connection with 120V L-L secondaries, use system type 31.
• Control Power Transformer 120 or 240VAC. Secondary 50VA max.
• See Table below.
Control Power
Source
CPTVs < 125VFNM or MDL250
CPT125 < Vs < 240VFNQ or FNQ-R250
CPT240 < Vs < 305VFNQ or FNQ-R250
Line VoltageVs < 240VFNQ-R250
Line VoltageVs > 240VFNQ-R250
DCVs < 300VLP- CC500
NOTES:
Place over-current protection as close to the device as possible.
For selecting fuses and circuit breakers other than those listed above, use the following criteria:
• Rate over-current protection as listed above.
• Select current interrupt capacit y based on the installation category and fault current capability.
• Select over-current protection with a time delay.
• Base the voltage rating on the input voltage applied.
• If a 0.25A fuse is not available with the required fault current capability, use a fuse rated at a maximum of 0.5A.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
≤ 100 mA
TM
PULSE OUTPUT CAPABILITIES
Solid-state Pulse Output
The H8453 has two normally open solid-state KY outputs. The H8463 has one
normally open KY output and one normally closed KZ solid-state output. One is
dedicated to kWh, and the other is eld-selectable for Phase Detect or kVARh. See the
Setup section for conguration information.
Over-current Protective Device
(not supplied)
Digital Output/Pulse Ou tput is a solid state
pulse output rated for 240VAC/DC max.
Maximum load curren t is 100mA at 25°C.
Derate 0.56mA per °C above 25°C.
LOAD
~
=
INSTALLATION GUIDE
Power So urce
3-240VDC
6-24 0VAC
78910
The over-current protective device
must be rated for the short circuit
current at the connection point.
*The power source should not be a safety e xtra low voltage (SELV) circui t. Pulse outputs are not SELV rated.
V1
3
4
V2
V3
5
kWhOPTION
kVARh
or
PHASE
H8453
(on H8463, the optional output is normally closed)
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
COMMUNICATIONS
Communications Capabilities
RS-485 Communications Distances:
Baud RateMaximum Communication Distances
FeetMeters
960080002438
1920060001829
Note: Use distances as a guide only; they are not guaranteed. Refer to the master
device’s documentation for any additional distance limitations.
Daisy-chaining Devices to the Power Meter
The RS-485 slave port allows the power meter to be connec ted in a daisy chain with
up to 31 2-wire devices.
Belden 1120A or equivalent
INSTALLATION GUIDE
120 Ω terminator on the
last device of the daisy chain*
–
+
Not used
• If the power meter is the rst device on the daisy chain, connect it to the
host device using a RS-232 to RS-485 converter.
• If the power meter is the last device on the daisy chain, terminate it with
the terminator provided.
• The rst device on the chain should also have a 120 Ω terminator between
+ and -.
• The terminal’s voltage and current ratings are compliant with the
requirements of the EIA RS-485 communications standard
* A 120 Ω resistor is included on the circuit board inside the H8436VB/S and H8437VB/S units.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
OPERATION
Operating the Display
The power meter is equipped with a large, back-lit LCD display. It can display up to
ve lines of information plus a sixth row of menu options.
INSTALLATION GUIDE
AB
L
K
J
Button Symbols
-------
1;
------
C
I
1
2
3
N
1;DMD
View more menu items on the current level.
Return to the previous menu level.
Indicates the menu item is selected and there are no menu levels below
the current level.
Change values or scroll through the available options. When the end of a
range is reached, press + again to return to the rst value or option.
Select the next number of a series.
Move to the next editable eld or save the changes and exit the screen if
the last editable eld is selected.
MAX DEMAND
265
275
268
PHASE
I
Navigation
Change Values
2.4
H
! &
{{{{{}}}}}}
10 50 100
A
{{{{{}}}}}}
10 50 100
A
{{{{{}}}}}}
10 50 100
A
%
A
G
<-
Power Meter Display
A. Type of measurement
B. Screen Title
C. Maintenance icon
D
E
F
D. Bar Chart (%)
E. Units
F. Display more menu items
G. Menu item
H. Selected menu indicator
I. Button
J. Return to previous menu
K. Values
L. Phase
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
SETUP
Set Up the Power Meter
1. Press -----> until you see SETUP.
H84xx
INSTALLATION GUIDE
2. Press SETUP. Enter your password (Default password is 00000).
3. Press + to change a digit, <----- to select the next digit.
4. Press OK.
Set Up CTs
1. Press CT. ----->
2. Enter the PRIM CT (primary CT) number (1 to 32767, using the + and <----but tons).
3. Press OK.
Set Up PTs
1. Press PT. The default is NO PT. Single Phase System types (10, 11, 12) do not allow
PTs.
2. Press +
3. Select the SCALE value: x1, x10, x100, NO PT (for direct connect).
4. Press OK.
5. Enter the PRIM (primary) value.
6. Press OK.
7. Enter the SEC. (secondary) value.
8. Press OK.
Set Up the System Frequency
1. Press -----> until HZ is visible.
2. Press HZ.
3. Press + to select the frequency: 50 Hz or 60 Hz (default is 60Hz).
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Set Up the Meter System Type
H84xx
TM
INSTALLATION GUIDE
1. Press -----> until SYS is visible.
2. Press SYS.
3. Press + to select the SYS (system type): 10, 11, 12, 30, 31, 32, 40, 42, 44. NOTE: See
Wiring section for a description of the system types.
4. Press OK.
Set Up the Passwords
NOTE: The default passwords are 00000.
1. Press -----> until PASSW (password) is visible.
2. Press PASSW.
3. Press + to change a digit in the SETUP password, <----- to select the next digit.
NOTE: This sets the password to enter the Setup Menu or change SETUP via
Modbus.
3-PHASE SYSTEM
4
3
3
40
1;+OK
<-
PASSWORD SETUP
00000
00000
00000
&
Wire
CT
PT
SYS
&
DIAG.
SETUP
RESET
4. Press OK.
5. Enter the RESET (password to reset the power meter) password. NOTE: This sets
the password required to reset stored values such as kWh via the local RESET
menu or remotely via Modbus (if so equipped.)
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
Set Up Demand
1. Press -----> until DEMND (demand) is visible. (H8437V/ VB/S only)
2. Press DEMND.
3. Enter the MIN (interval in minutes): 0 to 60. Press + to change a digit, <----- to
select the next digit.
4. Press OK. Enter the SUB-I (number of subintervals): 1 to 60. Press + to change a
digit, <----- to select the next digit.
I
INSTALLATION GUIDE
DEMAND SETUP
100
15
1
&
MSEC
MIN
SUB-i
5. Press OK.
NOTE: The calculation method used for SUB-I is as follows:
• 0 = sliding block
• 1 = block
• >1 = rolling block (The SUB-I value must divide evenly into the MIN
value. For example, if MIN is 15, SUB-I can be 3, 5, or 15. If you selected 3,
you would have 3 subintervals at 5 minutes each.)
Set Up Communications (H8436V/VB, H8437V/VB)
1. Press -----> until COM is visible.
2. Press COM.
3. Enter the ADDR (meter address): 1 to 247. Press + to change a digit, <----- to
select the next digit.
4. Press OK.
5. Press + to select the BAUD (baud rate): 2400, 4800, 9600 or 19200.
6. Press OK.
7. Press + to select the parity: EVEN, ODD, NONE.
8. Press OK to return to the SETUP MODE screen.
0.1
1;+OK
<-
COMMS SETUP
001
9600
nOnE
1;+OK
<-
KVARH
ADDR
bauD
Par
mbus
Set Up Pulse Options (H8453V/VB, H8463V/VB)
1. Press -----> until PULSE is visible.
2. Press PULSE.
3. Press + to select the MSEC (kWh pulse duration in milliseconds): 100, 300, 500, or
1000.
4. Press OK.
5. Press + to select the kWh/P (pulse weight): 0.1, 1, 10, 100, 1000, or 10000.
6. Press OK.
0.1
&
MSEC
KWH/P
MSEC
KVARH
7. Select the MSEC (kVARh pulse
duration in milliseconds): PHASE, 100,
300, 500, or 1000.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
NOTE: Selecting PHASE changes the output operation from kVARh to PHASE DETECT.
If phase is selected, the H8453V/VB will close the contacts on the PHASE kVARh
output when all three phase voltages are within 25% of each other and no phase
is less than 82.5 volts Line to Neutral. The H8463V/VB will open the contacts on
the Phase kVARh output when all three phase voltages are within 25% of each
other and no phase is less than 82.5 volts line to neutral.
8. Press OK.
9. Select the kVARh (pulse weight):
0.1, 1, 10, 100, 1000, or 10000. This
is unavailable if PHASE is selected
above.
10. Press OK to return to the SETUP
MODE screen.
PULSE SETUP
100
0.1
_ _
<-
1;+OK
&
MSEC
KWH/P
PHASE
DIAGNOSTICS
H84xx
TM
INSTALLATION GUIDE
View the Meter Information
1. From the SUMMARY screen, DIAGN (diagnostics)
2. Press METER (meter info).
3. View the meter information (model number, rmware operating system version,
rmware reset system version, and power meter serial number).
Check the Health Status
1. Press HELTH
2. View the health status. If there are no
problems, OK is displayed on the lower
right (see right).
HEALTH STATUS
1;HELTHMAINT
&
OK
METER
^
Reset Energy Accumulators: kWh, kVAh, and kVARh, (Ph, Qh, Sh), (H8453V,
H8463V, H8436V)
1. From the SUMMARY screen, RESET is visible.
2. Press RESET.
3. Enter the RESET password (00000 is the default).
4. Press OK.
5. Press YES to RESET, NO to cancel. The RESET value displayed is a lifetime count of
the number of times the energy accumulators have been reset. This is a security
feature to detect tampering.
Reset Menu, (H8437V) (see below)
1. From the SUMMARY screen, RESET is visible.
METER INFO
H
8400U
10
4
25000193
1;HELTH
The wrench icon is displayed on all
screens when a health problem is
detected (see right). Problems are
shown on the right of the screen with
the location in the center.
Problem:
PLOSS: Phase Loss. F indicates unable to
establish frequency lock on Phase A. In
3 phase systems, A, B, and or C indicates
that the Phase voltage is 25% lower
than the other phases or if the voltage has dropped below 82 volts Line to Neutral.
VCLIP: Voltage Clipping. Indicates the voltage input is too high for the meter to
measure.
ICLIP: Current Clipping. Indicates the current input is too high for the meter to
measure.
&
MODEL
0.5.
R.S.
S.N.
METER
^
2. Press RESET.
3. Enter the RESET password (00000 is the default).
4. Press OK.
5. Press -----> until the parameter you want to reset is displayed.
6. Press the parameter to
cancel.
7. Press YES to reset.
8. Menu Options:
METER - Performs all the resets
below.
ENERG - Resets energy
accumulations (the only reset on the H8436V, H8453V and H8463)
DEMND - Resets Demand calculations and maximum values.
MINMX- All stored minimum and maximum values.
TIMER - Resets usage and elapsed timers.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
MENU TREES
Definitions
BDS – Basic Data Stream. Only the Real Energy and Power data points are output.
FDS – Full Data Stream. 26 data points minimum as on the Enercept H8036.
EDS – Extended Data Stream. In addition to the FDS, includes Frequency (phase A),
Current THD, Voltage and THD on each phase.
Syste m Typ es
Support system types 10, 11, 12, 31, 32, 40, 42, & 44.
Modbus Point Map
The Basic Data Stream (BDS) matches the Veris H8035 Enercept meter. The Full Data
Stream (FDS) matches the H8036 Enercept. The Extended Data Stream (EDS) is unique
to the H84xx Series and adds parameters such as Frequency, Demand, and THD. The
conguration of the H84xx is also unique to this device. Integer registers begin at 001
(0x001). Floating point registers begin at 257 (0x101). Conguration registers begin
at 129 (0x081).
H8436/H8453/H8463 FDS Menu Tree (Full Data Stream)
INSTALLATION GUIDE
AMPS VOLTS POWER
I U-V PQS
I
AMPS PER PHASE
---
V VOLTS LINE-LINE
U ---
3-PHASE SUMMARY
------
P
POWER SUMMARY PQS
V
V L-L V L-NU V
V VOLTS LINE-NEUT
V ---
P
SUMM PHASEPQS PHASE
Blue = IEEE
Red = IEC
Black = Same for both IEEE & IEC
P W INSTANT
P
DISPLAY MODE
3-PHASE SUMMARY
ENERG PF
E PF
E ACCUM Wh
----
/ Power Factor
PF
NOTE: Accumulated VAh and
VARh are displayed on Pulse
Models.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
H8436/H8453/H8463 FDS Menu Tree (Full Data Stream), continued
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
H8437 EDS Menu Tree (Enhanced Data Stream), continued
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
H8437 EDS Menu Tree (Enhanced Data Stream), continued
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
H8437 EDS Menu Tree (Enhanced Data Stream), continued
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
INSTALLATION GUIDE
MODBUS POINT MAP
H8400
R/W NVFormatUnits
REG.
H8436-FDS
H8437-EDS
3-Phase Summary
--- BDS ---
•• 001RNV
•• 002RNVkWhE0-0xFFFFReal Energy Consumption (MSW)
•• 003RUIntkWW0-32767Total Instantaneous Real Power (3 Phase Total)
--- FDS ---
•• 004RUIntkVAW0-32767Total Instantaneous Apparent Power (3 Phase Total)
•• 005RUIntkVARW0-32767Total Instantaneous Reactive Power (3 Phase Total)
•• 006RUIntRatio0.00010-10000Total Power Factor (Total kW / Total kVA)
•• 007RUIntVoltV0-32767Voltage, L-L, Average of 3 Phases
•• 008RUIntVoltV0-32767Voltage, L-N, Average of 3 Phases
•• 009RUIntAmpI0-32767Current, Average of 3 Phases
Per Phase
•• 010RUIntkWW0-32767Real Power, Phase A
•• 011RUIntkWW0-32767Real Power, Phase B
•• 012RUIntkWW0-32767Real Power, Phase C
•• 013RUIntRatio0.00010-10000Power Factor, Phase A
•• 014RUIntRatio0.00010-10000Power Factor, Phase B
•• 015RUIntRatio0.00010-10000Power Factor, Phase C
•• 016RUIntVoltV0-32767Voltage, Phase A-B
•• 017RUIntVoltV0-32767Voltage, Phase B-C
•• 018RUIntVoltV0-32767Voltage, Phase A-C
•• 019RUIntVoltV0-32767Voltage, Phase A-N
•• 020RUIntVoltV0-32767Voltage, Phase B-N
•• 021RUIntVoltV0-32767Voltage, Phase C-N
•• 022RUIntAmpI0-32767Current, Instantaneous, Phase A
•• 023RUIntAmpI0-32767Current, Instantaneous, Phase B
•• 024RUIntAmpI0-32767Current, Instantaneous, Phase C
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
INSTALLATION GUIDE
H8400
R/W NVFormatUnits
REG.
H8436-FDS
H8437-EDS
Demand
• 039RUIntkWW0-32767Total Real Power Present Demand
• 040RUIntk VAW0-32767Total Apparent Power Present Demand
• 041RUIntkVARW0-32767Total Reactive Power Present Demand
• 042RNVUIntkWW0-32767Total Real Power Max Demand
• 043RNVUIntkVAW0-32767Total Apparent Power Max Demand
• 044RNVUIntkVARW0-32767Total Reactive Power Max Demand
Usage Time
• 045RNVUIntHours10-32767Usage Hours
• 046RNVUIntMinutes10-59Usage Minutes
• 047RNVUIntHours10-32767Total Hours
• 048RNVUIntMinutes10-59Total Minutes
• 049RNVUInt%.010-10000Percent UsagePercent Usage = Usage Time / Total Time .
THD
• 050RUInt%0.10-10000THD, Voltage A-N
• 051RUInt%0.10-10000THD, Voltage B-N
• 052RUInt%0.10-10000THD, Voltage C-N
• 053RUInt%0.10-10000THD, Voltage A-B
• 054RUInt%0.10-10000THD, Voltage B-C
• 055RUInt%0.10-10000THD, Voltage A-C
• 056RUInt%0.10-10000THD, Current Phase A
• 057RUInt%0.10-10000THD, Current, Phase B
• 058RUInt%0.10-10000THD, Current, Phase C
Conguration
--- BDS ---
--- FDS ---
•• 129R/WUIntN/A
•• 130R/WUInt
•• 131R/WUInt1-32767CT Ratio – Primary
5A 5A 132R/WUInt1 or 5 ACT Ratio – Secondary (H8400A Only, unused on H8400V)
•• 133R/WUInt1-32767PT Ratio – Primary
•• 134R/WUInt0,1,10,100PT Ratio – Scale (0 = No PT)
•• 135R/WUInt100,110,115, 120 PT Ratio – Secondary
•• 136R/WUIntHz50 or 60
•• 137R/WUInt0.1
Scale
Factor/
Mult.
RangeDescription
This combination timer counts the total time for
which the absolute current on at least one phase
is >0.1 Amp.
This timer counts the total time since the usage
timer was reset.
Reset:
- Write 30078 to clear all Energy Accumulators to 0 (All).
- Write 14255 to reset all Power Min/Max to Present Values
(H8400 EDS Only).
- Write 21212 to reset Peak Demand values to Present Demand Values
(H8400 EDS Only).
- Write 10001 to clear the Usage Timers to 0 (H8400 EDS Only).
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
INSTALLATION GUIDE
H8400
R/W NVFormatUnits
REG.
H8436-FDS
H8437-EDS
•• 138R/WSInt
•• 139R/WSIntScale Factor V (voltage) Default = -1
•• 140R/WSIntScale Factor W (power) Default = -2
•• 141R/WSIntScale Factor E (energy) Default = -2
•• 142RUIntReserved, always returns 0
•• 143RUIntReserved, always returns 0
•• 144RUIntReserved, always returns 0
•• 145RUIntReserved, always returns 0
•• 146RUInt
•• 147RNV UInt0-32767Count of Energy Accumulator resets
--- EDS ---
• 148RNVUInt0-32767Count of Usage Timer resets
• 149R/WNVUIntMinutes1-60
• 150R/WNVUInt0-60
3-Phase Summary
--- BDS ---
•• 257/258RNV FloatkWhReal Energy Consumption
•• 259/260RFloatkWTotal Instantaneous Real Power
--- FDS ---
•• 261/262RFloatkVATotal Instantaneous Apparent Power
•• 263/264RFloatkVARTotal Instantaneous Reactive Power
•• 265/266RFloatRatio0.0-1.0Total Power Factor (Total KW / Total KVA)
•• 267/268RFloatVoltVoltage, L-L, Average of 3 Phases
•• 269/270RFloatVoltVoltage, L-N, Average of 3 Phases
•• 271/272RFloatAmpCurrent, Average of 3 Phases
Scale
Factor/
Mult.
-4 0.0001
-3 0.001
-2 0.01
-1 0.1
0 1.0
1 10.0
2 100.0
3 1000.0
4 10000.0
RangeDescription
Scale Factor I (current) Default = -2
Error Bitmap:
bit0: Phase A Voltage out of range
bit1: Phase B Voltage out of range
bit2: Phase C Voltage out of range
bit3: Phase A Current out of range
bit4: Phase B Current out of range
bit5: Phase C Current out of range
bit6: Frequency out of range or insucient voltage on Phase A to determine frequency.
*range of 45-65 Hz.
bit7: Reserved for future use
bit8: Phase Loss A
bit9: Phase Loss B
bit10: Phase Loss C
bit11-15: Reserved for future use
(Power) Demand Block Interval – Used for PQS (P=Real Power KW, Q=Reactive Power KVAR,
and S=Apparent Power KVA) demand calculations.
Number of Power Demand Block Sub-Intervals - Sets the number of sub-intervals per
Demand Block Interval (above). The method of demand calculation is set as follows:
0 = Sliding Block. Like rolling block, but with a subinterval of 15 seconds is used for Demand
Intervals <= 15 minutes, or 60 seconds for intervals > 15 minutes.
1 = Block. Fixed block with no sub-intervals.
>1 = Rolling Block. The number of sub-intervals per block. This value must divide evenly
into the Block Demand Interval (above). For example, if the Demand Block Interval is 15
minutes, valid Sub-Interval values are: 3, 5, or 15. If the value of 3 is chosen, then there will
be 3 subintervals of 5 minutes each.
Floating Point Statistics
Note: These registers
contain a signed
integer, which
scales the
corresponding
parameters.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
INSTALLATION GUIDE
H8400
R/W NVFormatUnits
REG.
H8436-FDS
H8437-EDS
Per Phase
•• 273/274RFloatkWReal Power, Phase A
•• 275/276RFloatkWReal Power, Phase B
•• 277/278RFloatkWReal Power, Phase C
•• 279/280RFloatRatio0.0-1.0Power Factor, Phase A
•• 281/282RFloatRatio0.0-1.0Power Factor, Phase B
•• 283/284RFloatRatio0.0-1.0Power Factor, Phase C
•• 285/286RFloatVoltVoltage, Phase A-B
•• 287/288RFloatVoltVoltage, Phase B-C
•• 289/290RFloatVoltVoltage, Phase A-C
•• 291/292RFloatVoltVoltage, Phase A-N
•• 293/294RFloatVoltVoltage, Phase B-N
•• 295/296RFloatVoltVoltage, Phase C-N
•• 297/298RFloatAmpCurrent, Instantaneous, Phase A
•• 299/300RFloatAmpCurrent, Instantaneous, Phase B
•• 301/302RFloatAmpCurrent, Instantaneous, Phase C
--- EDS ---
• 303/304RFloatAmpCurrent, Instantaneous, Neutral
• 305/306RFloatHz45.0-65.0Frequency (derived from Phase A)
• 307/308RNV FloatkWTotal Real Power Minimum
• 309/310RNV FloatkWTotal Real Power Maximum
• 311/312RNV FloatkVA hApparent Energy Consumption
• 313/314RNV FloatkVARhReactive Energy Consumption
Per Phase Power
• 315/316RFloatkVAApparent Power, Phase A
• 317/318RFloatkVAApparent Power, Phase B
• 319/320RFloatkVAApparent Power, Phase C
• 321/322RFloatkVARReactive Power, Phase A
• 323/324RFloatkVARReactive Power, Phase B
• 325/326RFloatkVARReactive Power, Phase C
Demand
• 327/328RFloatkWTotal Real Power Present Demand
• 329/330RFloatkVATotal Apparent Power Present Demand
• 331/332RFloatkVARTotal Reactive Power Present Demand
• 333/334RNV FloatkWTotal Real Power Max Demand
• 335/336RNV FloatkVATotal Apparent Power Max Demand
• 337/338RNV FloatkVARTotal Reactive Power Max Demand
Usage Time
• 339/340RNV FloatHours>= 0.0Usage Hours
• 341/342RNV FloatMinutes0.0-59.0Usage Minutes
• 343/344RNV FloatHours>= 0.0Total Hours
• 345/346RNV FloatMinutes0.0-59.0Total Minutes
Scale
Factor/
Mult.
RangeDescription
This combination
timer counts the
total time for
which the absolute
current on at least
one phase is >0.1
Amp.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
INSTALLATION GUIDE
H8400
H8436-FDS
H8437-EDS
REG.
R/W NVFormatUnits
Scale
Factor/
Mult.
RangeDescription
THD
• 349/350RFloat%0.0-1000.0THD, Voltage A-N
• 351/352RFloat%0.0-1000.0THD, Voltage B-N
• 353/354RFloat%0.0-1000.0THD, Voltage C-N
• 355/356RFloat%0.0-1000.0THD, Voltage A-B
• 357/358RFloat%0.0-1000.0THD, Voltage B-C
• 359/360RFloat%0.0-1000.0THD, Voltage A-C
• 361/362RFloat%0.0-1000.0THD, Current, Phase A
• 363/364RFloat%0.0-1000.0THD, Current, Phase B
• 365/366RFloat%0.0-1000.0THD, Current, Phase C
Modbus Conguration (Downloadable rmware support only)
•• 7000RNVUInt0-32767Firmware Version, Reset System (Boot Down Loader)
•• 7001RNVUIntFirmware Version, Operating System (Application)
•• 7002/03RNV ULongSerial Number (date/time of manufacture in UTC)
•• 7004RNVUInt15166Device ID
•• 7005RNVUInt1-247Modbus Address
•• 7006RNVUInt
2400,4800,
9600,19200
Baud rate
•• 7007RNVUIntPassword (always returns 0). Used only for download.
•• 7008RUIntSelf test (always returns 0)
•• 7009RUInt0,65535
PLOS. Returns the one’s complement of software’s safe vectors ag. Indicates if the
Application (OS) or Boot (Downloader/Reset System) is running.
•• 7010RUIntReserved, always returns 0
•• 7011RUIntReserved, always returns 0
•• 7012RUIntReserved, always returns 0
•• 7013RUIntReserved, always returns 0
•• 7014RUIntReserved, always returns 0
Command Interface (Downloadable rmware support only)
•• 7015R/WUIntCommand
•• 7016-031R/WUIntParameters
•• 7032R/WUIntStatus
•• 7033R/WUIntResult
•• 7034R/WUIntI/O Data
•• 7035-162R/WUIntData Area
Note 1: Calculate demand using sliding, xed, or rolling block intervals. See registers 4117-4119 for settings.
Note 2: DOWNLOADABLE FIRMWARE. When the Operating System is erased, only registers 7000-7162 are available. Register 7001 (Firmware Version, Operating System) reads
as 0 in this condition. Additionally, the ID string returned from a “Report ID” query (0x11) will be “Veris Power Meter - RESET SYSTEM RUNNING”.
Note 3: THD (Total Harmonic Distortion) is calculated as the % ratio over the fundamental frequency. H
2
2
2
√ H
+ H
+ H
2
3
2
+ H
+ ... to the 15th harmonic
4
5
H
1
is the nth harmonic.
n
Note 4: Unused or unsupported Integers return 0x8000, Floats 0x7FC00000
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
Legend
R/W: R=Read only, R/W=Read/Write
NV: Value is stored in non-volatile memory
Format
UInt: Unsiged 16-bit integer, read most signicant Byte (MSB) rst.
SInt: Signed 16-bit integer, read most signicant Byte (MSB) rst.
ULong: Unsigned 32-bit integer; Upper 16-bits Most Signicant Word (MSW), in
lowest numbered register (257/258)=MSW/LSW)
Float: 32-bit oating point; encoded per IEEE Standard 754 single precision; Upper
16-bits Most Signicant Word (MSW) in lowest numbered register (257/258)=MSW/
LSW)
Scale Factor/Multiplier
Integer Registers must be multiplied by this value to be read correctly in the given
units. Scale Factors I, V, W, and E are congurable (see registers 138-141).
Defaults are: I = 0.01, V = 0.1, W = 0.01, E = 0.01
Modbus Commands Supported
DATA OUTPUTS
Full Data Set (FDS)
kWh, Consumption
kW, Real Power
kVAR, Reactive power
kVA, Apparent power
Power fac tor
Voltage, line to line
Voltage, line to neutral
Amps, Average current
kW, Real power ØA
kW, Real power ØB
kW, Real power ØC
Power factor ØA
Power factor ØB
Power factor ØC
Voltage, ØA to ØB
Voltage, ØB to ØC
Voltage, ØA to ØC
Voltage, ØA to Neutral
Voltage, ØB to Neutral
Voltage, ØC to Neutral
Amps, Current ØA
Amps, Current ØB
Amps, Current ØC
INSTALLATION GUIDE
Extended Data Set (EDS), Full Data Set (FDS)
Amps, Current Neutral
Frequency
kVAh, Consumption
kVARh, Consumption
Minimum Real power
Maximum Real power
KVA, Apparent Power, Per Phase
KVAR, Reactive Power, Per Phase
KW, Total Real Power Present Demand
KVA, Total Apparent Power Present Demand
KVAR, Total Reactive Power Present Demand
KW, Total Real Power Max Demand
KVA, Total Apparent Power Max Demand
KVAR, Total Reactive Power Max Demand
THD, Voltage A-N, B-N, C-N
THD, Voltage A-B, B-C, A-C
THD, Current, Per Phase
Usage Hours
Usage Minutes
Total Hou rs
Total Minutes
0X03: Read holding registers
0x04: Read input registers
0x06: Preset single register
0x10: Preset multiple registers
0x11: Report ID
Return string:
byte0: address
by te1: 0x 11
byte2: #bytes following w/out crc
byte3: ID byte = 250
bytes4: status = 0xFF
bytes5+: ID string = “H84__ Power Meter”
last 2 bytes: CRC
0x2B: Read Device Identication, BASIC implementation (0x00, 0x01 and 0x02 data),
Conformity Level 1.
Object Values:
0x01: Vendor Name = “Veris Industries”
0x02: Product Code = “H84__”
0x03: Major/Minor Revision = “Vxx.yyy”, where xx.yyy is the OS version
number (reformatted version of the Modbus register #7001, (Firm
ware Version, Operating System). If register #7001 == 12345, then
the 0x03 data would be “V12.345”).
When the Operating System is erased, only registers 7000-7162 are available. Register 7001 (Firmware Version, Operating System) will read as 0 in this condition.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H84xx
TM
INSTALLATION GUIDE
TROUBLESHOOTING
ProblemCauseSolution
The maintenance wrench icon
appears in the power meter
display.
The display is blank after applying
control power to the meter.
The data displayed is inaccurate.Incorrect setup valuesVerify the values entered for power meter setup
Cannot communicate with power
meter from a remote personal
computer.
There is a problem with the inputs to the power meter.Go to DIAGN>HELTH (MAINT). The error messages
describe the problem. See the Diagnostics section
(page 16) for details.
The meter is not receiving adequate power.Verify that the meter control power (terminals 1 and 2)
are receiving the necessary voltage. See the Control
Power wiring diagram (page 9).
Verify that the LED is blinking.
Check the fuse.
parameters (CT and PT ratings, system type, nominal
frequency, etc.). See the Setup section (page 13).
Incorrect voltage inputsCheck power meter voltage input terminals to verify
adequate voltage.
Power meter is wired improperly.Check all CTs and PTs to verify correct connection to the
same service, PT polarity, and adequate powering.
Check shorting terminals, if used. See the Wiring
Diagrams (pages 6-8) section for more information.
Power meter address is incorrect.Verify that the meter is correctly addressed (see Setup
section).
Power meter baud rate is incorrect.Verify that the baud rate of the meter matches that of
all other devices on its communications link (see Setup
section).
Communications lines are improperly connected.Verify the power meter communications connections
(see the Communications section).
Verify the terminating resistors are properly installed on
both ends of a chain of units. Units in the middle of a
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.