POWER MONITORING
the user will be required to correct the interference at his own expense.
TM
H8238
Multi-Circuit Meter
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• SECONDARY LEADS/TERMINALS OF CURRENT OUTPUT (e.g. 5A) CTs MUST BE SHORTED,
OR CONNECTED TO THE BURDEN AT ALL TIMES.
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
NOTICE
INSTALLATION GUIDE
SPECIFICATIONS
Electrical Services Eight 3Ø circuits sharing a common line voltage source
Sample Rate 1280 Hz
Operating Temperature Range 0° to 60°C (32° to 140°F) (<95% RH, non-condensing)
Storage Temperature Range -40°C to 70°C (-40° to 158°F)
Altitude of Operation 3 km
Systems Accuracy +/- 1% (target, exclusive of user-supplied CTs)*
Variable Update Rate 200 msec for voltages, 1.6 sec for all others
Measured Voltage Inputs:
Number of Channels Three (phase A, B, C, plus neutral). Average of phases used
for L-N values if no neutral present
Maximum Voltage 277VAC L-N +10%; 480VAC L-L +10%
Frequency 50/60 H z
Terminal Block 4-position Euro style pluggable connec tor (max. wire size 12 gauge);
torque 5.7 in•b (0.64 N•m)
Measured Current Inputs:
Number of Channels 24 (8 meters x 3 phases/meter)
CT Input Type 5 Amp (customer-supplied)
CT Range Each of 8 meter s independently adjustable from 1A:5A to 9999A:5A
Terminal Block 6-position Euro style c age clamp connector (max. wire size 14 gauge);
torque 4.4 in•lb (0.50 N•m)
Operating Power Inputs:
Power Source Dedicated 120VAC L-N (H8238) or 240VAC L-N (H8238E); fused 40 mA
Power Voltage Tolerance +10/-25%
Frequency 50/60 Hz
Terminal Block 2-position Euro style pluggable connector (max. wire size 12 gauge)
Network Connections:
Type Modbus RTU
Connection DIP switch-selectable 2-wire or 4-wire
Address DIP switch-selectable base address (1 to 233 in steps of 8)
Baud Rate DIP switch-selectable 2400, 4800, 9600, 19200**
Parity DIP switch-selectable NONE, ODD, EVEN
Communication Format 8-data-bits, 1-star t-bit, 1-stop-bit
Terminal Block 5-position Euro style pluggable connec tor (max. wire size 12 gauge);
nominal torque 4.0 in•l b (0.45 N•m); maximum torque 5.0 in•lb (0.56 N•m)
Installation Categor y Cat III, pollution degree 2
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of
Veris Industries nullify this statement.
* Accuracy specication valid only whe n amperages are greater than 10% of maximum CT range.
** Baud rates for H8238EL are 1200, 2400, 4800, and 9600.
QUICK INSTALL
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Connect the current inputs.
2. Connect the voltage leads.
3. Congure the communication switches.
4. Select a network address.
5. Connect the RS-485 connection to the communications wiring.
PRODUCT IDENTIFICATION
6. Connect the circuit power.
MODEL DESCRIPTION
H8238 Multi-Circuit Monitor, 90-130 VAC supply voltage
H8238E Multi-Circuit Monitor, 240 VAC supply voltage
H8238EL Multi-Circuit Monitor, 240 VAC supply voltage, low baud rate version
Z202837- 0H PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 11124
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H8238
1
2
3
3
4
5
6
7
8
9
101
11
12
13
14
TM
INSTALLATION GUIDE
PRODUCT OVERVIEW
The H8238 multi-circuit meter provides a means of monitoring multiple loads
originating from the same electrical service. The multi-circuit meter can monitor
up to eight 3-phase, 3-wire loads or six 3-phase, 4-wire loads with neutral current
monitoring. With one RS-485 connection, the H8238 provides a Modbus RTU
communications output and 72 alarms for situations such as over/under voltage,
over/under current, and phase loss. Up to 30 devices can be addressed on the same
Modbus network.
DIMENSIONS
Top View
Side View
main circuit board
mounting bracket
3
A B
C
D
F
E
PRODUCT DIAGRAM
1. Board Connection Ribbon Cable: Connects the transducer and CT circuit
boards.
2. Configuration Table: Easy reference communications conguration chart, silk-
screened on the circuit board.
3. ALIVE LED: Flashes once per second to indicate correc t operation. If steadily lit,
indicates internal communications diagnostic event.
4. Sensed Voltage Connection: Sensed line voltage, common for all meter
channels. 0-480 VAC.
5. Baud Rate & Parity Selection Switches: Field selectable parity, baud rate, and
2 or 4 wire communications parameters.
WIDTH:
A 5.3”/135mm (board)
B 8.9”/226mm (mounting bracket base)
LENGTH:
C 6.0”/153mm
D 12.8”/325mm
6. Modbus Address DIP Switches: Set these switches must be set to assign an
individual Modbus address before connecting the device (see page 7) .
7. TX LED: Indicates successful transmission of information over the Modbus
network.
8. Optical Isolation: An optical isolation barrier separates high voltage from the
HEIGHT:
E 2.9”/74mm
F 4.0”/101mm
communications network.
9. RS-485 2 or 4-wire Connection: Daisy chain multiple H8238s using a 2 or
4-wire Modbus network.
10. RX LED: Indicates successful reception of information over the Modbus network.
11. Power Transformers: Linear power supply for reliability and low noise.
12. 250 VAC 40mA Slow Blow Fuse: Fused power connection for circuit protection.
13. 120 or 240 VAC Power Connection*: Easy 2-wire 120 or 240 VAC line to neutral
50/60 Hz.
14. 5A CT Input Terminals: Current Transformer (CT) terminals accept any 5 A CT
signal. Two wire, not polarity sensitive.
* For 240 VAC power connection version, use the H8238E or H8238EL.
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
Z202837- 0H PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 11124
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H8238
*
A
B
C
N
JP1 JP2
METER 1
JP3
A B C
TM
INSTALLATION GUIDE
INSTALLATION
Disconnect and lock out power to the device.
Current Configuration
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
1. Connect the current inputs. The multi-circuit meter is capable of monitoring up to
eight 3Ø 3-wire circuits or six 3Ø circuits plus neutral current. Choose either 8 or 6
meter conguration and proceed to either step 2 or 3, as appropriate.
2. Eight 3Ø 3-Wire Circuit Monitoring Mode: Connect 5 Amp CTs to terminal blocks
JP1 through JP24. The JP terminal blocks are two position, not polarity sensitive,
and compatible with standard 2-wire 5 Amp CT outputs. Connect each monitored
service to the JP terminals within a meter set. For example meter #1 CT inputs are
labeled JP1 (PhA), JP2(PhB), & JP3(PhC). Connect the CT monitoring phase A for
metered service to the rst JP in its set.
3. Six 3Ø 4-Wire Circuit Monitoring Mode: Connect 5 Amp CTs to terminal blocks
JP1 through JP24. The JP terminal blocks are two position, not polarity sensitive,
and compatible with standard 2-wire 5 Amp CT outputs. Connect each monitored
service to the JP terminals within a meter set. For example meter #1 CT inputs are
labeled JP1 (PhA), JP2 (PhB), & JP3 (PhC). Connect the CT monitoring phase A for
metered service to the rst JP in its set. The terminal blocks referenced by meter 7
and meter 8 are used to monitor neutral currents. Wire the CT monitoring neutral
current for the service monitored by METER 1 to JP19. Wire the CT monitoring
neutral current for the service monitored by METER 2 to JP20. Wire the CT
monitoring neutral current for the service monitored by METER 3 to JP21 and so
on through JP24.
4. Connect the voltage leads to the phase conductors as shown in the wiring
examples on this page. The monitored voltage must be common to all services
monitored by the CTs installed previously.
A
B
C
HOT
HOT
3-Phase 3-Wire Installation
1-Phase 3-Wire Installation
N
†
*
Neutral current
monitoring optional
3-Phase 4-Wire Installation
1-Phase 2-Wire Installation†
120V
HOT
Z202837- 0H PAGE 3 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 11124
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Neutral current
monitoring optional
N
† Phase loss, Under Current & Under Voltage alarms are ac tive when
monitoring single phase lo ads.
*
Neutral current
monitoring optional