Veris H8186-CB Installation Instructions

TM
the user will be required to correct the interference at his own expense.
Power MoNITorING
INSTALLATIoN GUIDe
H8186 - CB
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of Veris Industries nullify this statement.
Product identification
H8186-CB BACnet Communications Board for H81xx Energy Meter
H8186 - CB
BACnet Communication Board
for the H81xx Energy Meter
Installer’s Specifications
Output Type BACnet Connection 2-wire Baud Rate 9600, 19200, 38400 Address Range 1-63
quick install
H81xxCB Series interfaces are sold as open devices. Observe handling precautions for static sensitive devices to avoid damage to the circuitry which would not be covered under the factory warranty.
1. Turn o all power to the energy meter and the equipment in which it is installed.
2. Discharge static.
3. Slide the H8186-CB into the channels on either side of the energy meter until the male connection on the meter clicks into place.
4. Insert the communication terminal onto the RS-485 communication terminals.
5. If the demand subinterval feature is used, wire it into the end of the demand subinterval terminal.
6. Replace the voltage terminal into the energy meter.
table of contents
Operation 2
Data Output Specications 2
Product Diagram 2
Conguration 3
RS-485 Communications Setup 3
Wiring 4
Installing the H8186-CB in the Energy Meter 5
Troubleshooting 5
BACnet MAC Address Setup 6
BACnet Descriptions 7
BACnet Protocol 8
Z204062-0F PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 02122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
ON
123 456
ON
123 456
1 2
TX RX
3RX4
TX
5
6
7
8
9
ALIVE
LITHIUM BATTERY
H8186-CB
INSTALLATIoN GUIDe
oPeration
H8186-CB energy meter communication board is an optional eld-installable plug­and-play accessory board for the H81xx energy meter that allows networking the H81xx to an existing BACnet MS/TP control/data acquisition system. It features eld selectable baud rate (9600, 19200, 38400).
data outPut sPecifications
kWh, Consumption kW, Real power kVAR, Reactive power kVA, Apparent power Power fac tor Voltage, line to line Voltage, line to neutral Amps, Average current kW, Real power ØA kW, Real power ØB kW, Real power ØC Power factor ØA Power factor ØB Power factor ØC Voltage, ØA to ØB Voltage, ØB to ØC Voltage, ØA to ØC Voltage, ØA to Neutral Voltage, ØB to Neutral Voltage, ØC to Neutral Amps, Current ØA Amps, Current ØB Amps, Current ØC
Product diagram
1. RS-485 LED (TX): Red LED; blinks to indicate that the H8186-CB is transmitting data to the master.
2. RS-485 LED (RX): Red LED; blinks to indicate that the H8186-CB is receiving data from the master.
3. LED from Main Board (RX): Green LED; blinks to indicate that the H8186-CB is receiving data from the main board.
4. LED from Main Board (TX): Green LED; blinks to indicate that the H8186-CB is transmitting data to the main board.
5. “ALIVE” LED: Green LED; should blink once per second to indicate normal operation of the H8186-CB.
6. Network Address DIP Switches: Use these DIP switches to set the network address for the H8186-CB.
7. Connection to Energy Meter: Install the H8186-CB in the energy meter by inserting this connector into the connection slot at the top of the energy meter.
8. Communication DIP Switches: Use these DIP switches to set the H8186-CB baud rate.
9. RS-485 Communication Terminals: Insert the RS-485 connector into these terminals. See the Wiring Diagram section of this guide for instructions on wiring the connector for 2-wire communications.
CAUTION! Danger of explosion if battery is incorrectly replaced. Replace only with the same or equivalent type recommended by the manufacturer. Dispose of used bat­teries according to the manufacturer’s instructions.
Z204062-0F PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 02122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
8 + 32 = 40
Wiring Baud Parity
Power MoNITorING
INSTALLATIoN GUIDe
configuration
This section describes the communications settings you must make to the H8186-CB. When daisy-chaining devices, follow these guidelines:
• Connect up to 63 H8186-CB devices on a single daisy chain.
• Each H8186-CB device on the daisy chain must have a unique address.
Before connecting the H8186-CB to the RS-485 communication wires, set the address according to directions in “Selecting the Network Address DIP Switches” on this page. If you assign the same address to two devices, neither device will communicate.
• Set the baud rate according to directions in “Selecting Baud Rate — Communication DIP Switches.” The settings for each H8186-CB must match the other devices on its daisy chain.
• For RS-485 cables, use shielded, twisted-pair wire (Belden Cable 1120A or equivalent).
• If the H8186-CB is the last device, terminate it per the RS-485 standard (120 Ω nominal impedence).
Selecting The Network Address DIP Switches
Use the Network Address DIP switches to select the network address. Each H8186-CB on a daisy chain must have a unique network address (from 0 to 63). Devices with the same address will be unable to communicate.
Always set the address before you install the H8186-CB in the energy meter and before you connect the energy meter to the daisy chain.
Each of the six DIP switches has a unique address value, page 6 lists DIP switch positions for specic addresses.
Network Address DIP Switch Values
Switch Value
1 1
2 2
3 4
4 8
5 16
6 32
In this example, the network address for the device is 40. Switch 4 and 6 oer the only combination of values that total 40.
This gure illustrates how to set the switches. Up is ON; down is OFF.
Selecting Baud Rate – Communication DIP Switches
Use the communication DIP switches (pictured below) to set the H8186-CB baud rate.
The gures below list the baud rate switch settings and the location of these switches.
Wiring and Baud Rate Settings
Parameter Switch Number and Setting
1 2 3 4 5 6
Wire Type 2-wire ON
9600 OFF OFF
Baud Rate
Parity Not applicable to this model. OFF OFF
19200 ON OFF
38400 OFF ON
38400 ON ON
Switches 1, 5, and 6 are unused. Always leave
them in the OFF position.
This example illustrates the default switch
settings for a 2-wire device that uses 9600 baud rate.
Parity function is not applicable to this model;
leave these switches in the OFF position.
rs-485 communications setuP
Daisy Chain Maximum Distances
The maximum number of devices capable of being supported on a single daisy chain is determined based on the combination of baud rate, the length of the daisy chain, and the types of RS-485 devices on the daisy chain. The RS-485 interface will support daisy chains that fall within the specications shown below.
2-Wire Daisy Chain Maximum Distances
Baud Rate Maximum Distances
1-8 Devices 9-16 Devices
9600 10000 ft. (3048 m) 4000 ft. (1219 m)
19200 5000 ft. (1,524 m) 2500 ft. (762 m)
38400 2500 ft. (762 m) 1200 ft. (380 m)
Wiring the Connector
Remove the connector from the RS-485 communication terminals of the H8186-CB (see Wiring Diagram section). To wire RS-485 communications, follow these steps:
1. Wire the communications connector for 2-wire communication (see Wiring Diagram section). The Wire Type setting in the communication DIP switch must match this wiring type (set Switch 2 to the ON position; see Selecting Baud Rate section).
2. Use a small, at-blade screwdriver to tighten the connector screws.
3. Replace the connector on the RS-485 communication terminals of the H8186-CB.
4. If the H8186-CB is the last device on the daisy chain, terminate it to ensure reliable communication per the RS-485 standard (120 Ω nominal impedence).
Z204062-0F PAGE 3 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 02122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Loading...
+ 5 hidden pages