Verine Orbis Installation And Manintenance Instructions

Orbis
INSET LIVE FUEL-EFFECT GAS FIRES
Installation and Maintenance Instructions
Hand these instructions to the owner following installation
Model No’s NVICC**MN, NVICC**SN & NVICC**RN are only for use on Natural Gas (G20) at a supply pressure of 20 mbar in G.B. / I.E.
Model No’s NVICC**MP is only for use on Propane Gas (G31) at a supply pressure of 37 mbar in G.B. / I.E.
** denotes trim and fret variant fitted to product
CONTENTS
Section 1 Information and Requirements PAGE
1
.0 Appliance Information 3-4
1.1 Conditions of Installation 5
1.2 Flue and chimney suitability 5 1
.3 Fireplace / surround suitability 6
1.4 Shelf position 6
1.5 Chimney inspection 6
1.6 Fire place opening / catchment space 7-8
1.7 Fitting to Metal Flue Boxes 9
1.8 Hearths 9
1.9 Spillage Monitoring System 9
Section 2 Installation of Fire
2.1 Unpacking the fire 10
2.2 Installing the fire box 10-18
2.3 Gas tightness and inlet pressure (MC models) 19
2.4 Gas tightness and inlet pressure (SC models) 19
2.5 Gas tightness and inlet pressure (RC models) 20
Section 3 Assembling Fuel Bed and Commissioning
3.1 Assembling the ceramics and fuel bed 21-24
3.2 Fixing the Infra-red Eye in position 24-25
3.3 Connecting the battery pack 26
3.4 Fitting the trim (all models) 26
3.5 Fitting the fender (all models) 26
3.6 Lighting the appliance (Manual control models) 27
3.7 Lighting the appliance (Slide control models) 28
3.8 Lighting the appliance (Remote control models) 29
3.9 Checking for clearance of combustion products 30
Section 4 Maintenance
4.1 Removal of the Burner Assembly (Manual control models) 31
4.2 Removal of the Piezo Igniter 31
4.3 Removal of the Control Tap 32
4.4 Removal of the Pilot Assembly 32
4.5 Removal of the Burner Assembly (Slide control models) 32-33
4.6 Removal of the Battery Ignitor 33
4.7 Repacing the Battery 33-34
4.8 Removing the Oxy-Pilot Assembly 34
4.9 Replacing the Control Cable 34-35
4.10 Removal of the Burner Assembly (Remote control models) 36
4.11 Removal of the Valve 36
4.12 Removal of the Oxy-Pilot Assembly 37
4.13 Replacing the Battery 37
This appliance is manufactured by:-
BFM Europe Ltd, Trentham Lakes, Stoke-on-Trent, ST4 4TJ
2
SECTION 1
INFORMATION AND REQUIREMENTS
1.0 APPLIANCE INFORMATION
Model NVICC**MN (MC) NVICC**MP (MC)
NVICC**SN (SC) NVICC**RN (RC)
Gas Type G20 G31
Main injectors (2 off) Size 260 Size 85
Pilot Type Copreci 21100 / 141 (MC NG)
Copreci 21100 / 162 (SC & RC NG) Copreci 21100 / 264 (MC LPG)
Maximum Gross Heat Input : 6.9 kW 6.9 kW
Minimum Gross Heat Input : 4.2 kW 4.2 kW
Cold Pressure : 20.0 mbar +/- 1.0mbar (All NG models)
37.0 mbar +/- 1.0mbar (All LPG models)
Ignition : Push Button Piezo (MC models)
1.5V Battery Generator (SC models) 9V Battery Generator (RC models)
Electrode Spark Gap 4.5mm Nominal
Weight (with fender) 18.5 Kg Orbis MC
19.0 Kg Orbis SC
19.5 Kg Orbis RC
Important Note
: This manual is only suitable for Verine Orbis models that are to be installed in GB / IE. If in the future the product is to be installled in any other country detailed as appropriate for the gas type and supply pressure on the rating plate then the manufacturer (BFM Europe Ltd.) must be contacted to obtain a set of instructions that are translated into the language of the country of destination, and reflect the dif­fering legislative installation criteria for that country.
3
Fire box Dimensions (All Models)
Width : (with trim, no spacer) 503mm Height : (with trim, no spacer) 590mm Depth : (overall-without fender) 250mm
Gas Connection 8mm Compression (Supplied with fire)
Efficiency Declaration
The efficiency of this appliance has been measured as specified in BS 7977-1 : 2002 and the result is 58%. The gross calorific value of the fuel has been used for this efficiency calculation. The test data from which it has been calculated has been certified by Advantica. The efficiency value may be used in the UK Governments Standard Assessment Procedure (SAP) for energy rating of dwellings.
4
INSTALLATION REQUIREMENTS
1.1 CONDITIONS OF INSTALLATION
It is the law that all gas appliances are installed only by a Registered Installer, in accordance with these installation instructions and the Gas Safety (Installation and Use) Regulations 1998 as amended. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to comply with the law.
The installation must also be in accordance with all relevant parts of the Local and National Building Regulations where appropriate, the Building Regulations (Scotland Consolidation) issued by the Scottish Development Department, and all applicable requirements of the following British Standard Code of Practice.
1. BS 5871 Part 2 Installation of Inset Live Fuel Effect Gas Fires
2. BS 6891 Installation of Gas Pipework
3. BS 5440 Parts 1 & 2 Installation of Flues and Ventilation
4. BS 1251 Open fire place components
5. BS 715 / BS EN 1856-2 Metal flue pipes for gas appliances
6. BS 6461 Part 1 Installation of Chimneys and flues
7. IS 813 : 1996 Domestic Gas Installation (Republic of Ireland)
No purpose made additional ventilation is normally required for this appliance, when installed in G.B. When Installing in I.E. please consult document I.S. 813 : 1996 Domestic Gas Installation, which is issued by the National Standards Authority of Ireland. If installing in Northern Ireland, please consult local building regulations. Any purpose made ventilation must be checked periodically to ensure that it is free from obstruction.
1.2 FLUE AND CHIMNEY SUITABILITY
This appliance is designed for use with conventional brick built or lined chimneys and fabricated flues and metal flue boxes conforming to BS 715 / BS EN 1856-2. All flues must conform to the following minimum dimensions.
Minimum diameter of circular flues 125 mm (Without Flue
Restrictor Fitted)
Minimum effective height of all flue types 3 metres
When fitting to conventional chimneys or 175mm flues it may be desirable to fit the flue restrictor baffle (supplied) to reduce the flue flow and increase the efficiency of the fire. Safe clearance of products must always be checked by carrying out a smoke match test as described.
5
1.3 FIREPLACE / SURROUND SUITABILITY
The fire must only be installed on a hearth it must not be installed directly onto carpet or other combustible floor materials.
The fire is suitable for fitting to non-combustible fire place surrounds and
proprietary fire place surrounds with a temperature rating of at least 150oc.
If a heating appliance is fitted directly against a wall without the use of a fire surround or fire place all combustible material must be removed from behind the trim. Soft wall coverings such as blown vinyl, wall paper etc. could be affected by the rising hot air and scorching and/or discoloration may result. Due consideration should be made to this when installing or decorating.
1.4 SHELF POSITION
The fire may be fitted below a combustible shelf providing there is a minimum distance of 200mm above the top of the fire and the shelf does not project more than 150mm. If the shelf overhangs more than 150mm the distance between the fire and the shelf must be increased by 15mm for every 25mm of additional overhang over 150mm.
1.5 FLUE / CHIMNEY INSPECTION
Before commencing installation, a flue or chimney should be inspected to ensure that all the following conditions are satisfied.
1. Check that the chimney / flue only serves one fire place and is clear of any
obstruction. Any dampers or register plates must be removed or locked in the open position.
2. Brick/stone built chimneys or any chimney or flue which has been used for
an appliance burning fuel other than gas must be thoroughly swept. The base of the chimney / flue must also be thoroughly cleared of debris etc.
3. Any under-floor air supply to the fire place must be completely sealed off.
4. Ensure that the inside of the chimney / flue is in good condition along it’s
length and check that there is no leakage of smoke through the structure of the chimney during and after the smoke pellet test.
5. Using a smoke pellet, check that there is an up-draught in the
chimney / flue and that the smoke can be seen issuing from the terminal / chimney pot outside. There must be no leakage of smoke through the structure of the chimney during or after the smoke pellet test and it is important to check inside upstairs rooms adjacent to the chimney / flue.
6
Check the chimney pot / terminal and general condition of the brickwork or masonry. If the chimney or flue is in poor condition or if there is no up-draught do not proceed with the installation. If there is a history of down-draught conditions with the chimney / flue, a tested and certificated flue terminal or cowl suitable for the relevant flue type should be considered.
6. A spillage test must always be carried out during commissioning of
the appliance.
1.6 FIRE PLACE OPENING AND CHIMNEY CATCHMENT SPACE
The front opening of the fire place must be between 400 and 450 mm wide, and between 550 and 570mm high. If the opening exceeds these dimensions then a surround must be constructed from suitable non-combustible material to produce a correct size opening. Any surround must be suitably sealed to the fire place to prevent leakage. See below in fig.1
When installing into a brick built chimney, you must ensure that there is sufficient depth to accomodate any debris which may fall from the chimney. This depth must be sufficient to accomodate 12 litres of volumetric space.
Fire Opening
400mm Minimum 450mm Maximum
580mm Minimum
470mm Minimum
Fig. 1
550mm Minimum 570mm Maximum
Minimum Flat Sealing Area
7
Table A - Installation Depth Requirements for a Verine Orbis being installed into a brick built chimney, requiring 12.0 litres of debris collection volume (fig. 2)
Opening Width (mm) Minimum Depth Required (mm)
400 (minimum opening width) 298 410 392 420 285 430 280 440 273 450 (maximum opening width) 269
For example, if the appliance was to be fitted into a 400mm wide opening, the depth required would be 298mm. See fig. 2 below for explanatory diagram.
Fig. 2
8
Opening Width ( e.g. 400mm)
Depth Required
(e.g. 298mm
minimum)
1.7 FITTING TO PRE-FABRICATED TWIN WALL METAL FLUE BOXES
The appliance may be fitted to twin wall metal flue boxes conforming to the constructional requirements of BS 715 / BS EN 1856-2, (for example the Selkirk LFE 175 box). The box must have a minimum flue diameter of 175mm internal and minimum internal dimensions of 300mm deep by 580mm high by 400mm wide. There are no maximum dimensional requirements for the box. The top face of the box must be insulated with a minimum thickness of 50mm of non-combustible mineral wool insulation or similar material. The flue box must stand on a non-combustible base of minimum thickness 12mm.
1.8 HEARTHS
This appliance must only be installed on to a concrete or non-combustible hearth. The hearth material must be a minimum thickness of 13mm with the top surface at least 50mm above the floor. The hearth must be fitted symmetrically about the fire opening and have a minimum width of 760mm and a minimum projection of 300mm forwards from the fire opening.
1.9 SPILLAGE MONITORING SYSTEM
This appliance is fitted with an atmosphere sensing spillage monitoring system in the form of an oxygen sensing pilot. This is designed to shut the fire off in the event of a partial or complete blockage of the flue causing a build up of combustion products in the room in which the fire is operated. The following are important warnings relating to this spillage monitoring system :-
1) The spillage monitoring system must not be adjusted by the installer.
2) The spillage monitoring system must not be put out of operation.
3) When the spillage monitoring system is exchanged only a complete original manufacturers part may be fitted. It is not possible to replace individual parts on the pilot system on this appliance, only a complete pilot assembly (including the thermocouple) may be fitted.
9
SECTION 2
INSTALLATION OF FIRE
2.1 UNPACKING THE FIRE
Carefully lift the fire out of the carton. Remove the loose item packaging carefully from the front of the appliance. Check the contents as listed :-
Packing Check List
1 off Fire box / burner assembly 1 off Boxed ceramic base, front ceramic rail and 20 coals (9 large square, 9
large random and 2 small square) coals 1 off Remote control handset (RC models only) 1 off Loose items bag 1 off each User instruction book and Installation book 1 off Battery Pack (RC models only)
2.2 INSTALLING THE FIRE BOX
Establish which type of flue you are intending to install the fire in to :-
225 x 225mm (9 inch x 9 inch) brick built chimneys 175mm (7 inch) diameter lined brick or stone flue, insulated pre-fabricated metal flue box to BS 715 / BS EN 1856-2
When installing into 125mm (5 inch) diameter lined brick or stone flue, or insulated pre-fabricated metal flue box to BS 715 / BS EN 1856-2. the restrictor baffle must not be fitted.
A spillage test must always be carried out to check satisfactory clearance of flue products, regardless of the type of flue the appliance is being fitted to.
10
For manual control Orbis models proceed as follows :-
a) Remove the trim / fret. Remove the burner heat shield from the front of
the fire box to allow access to the burner. See fig. 3 below.
Fig. 3
b) Ensure that the hearth is protected from damage and carefully lift the
fire box into the fire opening, then slide it back into position. Check that
the fire box fits flush to the sealing face of the fire surround or
wall with no gaps present.
c) Remove the four retaining screws securing the burner to the firebox.
The base of the burner unit can now be pulled forward, allowing the
burner to be removed from the fire box. See fig. 4 below.
Fig. 4
11
For slide control Orbis models proceed as follows:
d) Remove the trim / fret. Remove the burner heat shield from the front of
the fire box to allow access to the burner. See fig. 5 below.
Fig. 5
e) Ensure that the hearth is protected from damage and carefully lift the
fire box into the fire opening, then slide it back into position. Check that
the fire box flange fits flush to the sealing face of the fire surround or
wall with no gaps present.
f) Remove the burner. To allow burner removal, the control lever operat
ing cable must be removed. The control lever operating cable can be
seen running across the base of the fire, below the burner. To release
the cable, unscrew the cable securing screw located in the centre of the
aluminium operating arm and pull the cable out from its fixing hole.
Release the other end of the cable by pushing the cable forwards to the
right, i.e. into the operating arm so as to release the tension. Pull the
cable nipple out of the retaining hole and remove the cable through the
slot in the operating arm. See fig. 6 overpage
12
Loading...
+ 26 hidden pages