Verilink 1042 Installation Guide

1042 Dual Power Supply
Configuration Guide
Front Panel
45-00122
2.0
1042 POWER SUPPLY
1
2 43 6 7
Front Panel Description
P/S A
ALARM
CUTOFF
ALARM
P/S B
5
TRANSPORT
Index Function
1 Mounting Bracket: Rack mounting ears are available for installation into standard 19- and 23-inch racks. 2 Panel Screw: These two screws are used to mount the front panel to the 1042 housing. 3 Power Indicator: This green indicator ligh ts whe n the 1042 power shelf has 110 VAC applied to it and operation is normal. 4 Power Supply: Power supplies PS A and PS B are inserted into these two opening. 5 ACO: This yellow LED lights if the Alarm Cutof f switch is placed in the upper ON position, ind ic ating that the alarm relay contac ts
are disabled.
6 Alarm: This red LED lights if any fuse opens or if one of the two power supplies fails (this is cleared by removing the supply). 7 Alarm Cutoff: This switch controls the alarm relay con tacts. If it is placed in the upper ON position, the alarm relay circuitry i s
deactivated.
Installation
The Verilink 1042 Dual Power Supply Shel f is de­signed to hold either one or two power supplies con­forming to industry-standard Type-400 mechanics (such as the Verilink model number 9 -1000 -4 8V-
2). The shelf provides wiring from the power supply connectors to an AC power input. Fused DC output terminals are located on the rear of the shelf.
Rack mounting brackets are available for installation into standard 19 - and 23 -inc h racks. To install the brackets onto the 104 2, use the two tapped screw holes on each side of the 104 2. To install the 1042 into a rack, in sert two screws through b oth the left and right mounting brackets.
The 1042 shelf has two slots accessible from the front in which the power supplies are inserted. To in­stall the power supplies, first remove t he front panel by removing the two screws. Then insert each supply through one of the t wo slots until t he card is firmly seated to the rear con nector.
AC power is applied to the unit by inserting the pow­er cord into a 110 V outlet. DC power is the n ob­tained from the unit by c onnec tion to the r ear-panel terminal strips.
WARNING: Use caution when installing or removing the power supplies. 110 volts AC is present on the inside rear circuitry.
When installing a power supply with A C po wer con­nected, the A LARM LED ligh ts for about ten s ec­onds while the unit stabilizes (undergoes a soft start). The green power indicator then lights if the unit is operating normally.
WARNING: When replacing one of the power supplies while in service, wait at least 10 minutes after rem oving the supply before replacing the new one. This prevents contact arcing of the edge connector.
Specifications
Input Voltage: 115 VAC (±20 V) Output Voltage: 48 VDC (±2 V) Output Current: 2 A maximum, 50 mA minimum
per power supply Power Input: 113 W maximum Heat Generation: 390 BTU Efficiency: 80 % Alarm Contact Ratings: 1.0 A at 220 VDC
1.0 A at 250 VAC
Mechanical: 16.5″ W, 1.625 H, 6″ D
4.5 lbs without power supplies
7 lbs with power supplies
Ordering Numbers
F-1042-000--110:The part number of the 1042 shelf (dual 400 plug-in shelf) without any power supplies
9-1000-48V-2: The part number for the 48 VDC power supply
Industry Listings
FCC Compliance: Part 15 Class A
Subpart B
U.S. Safety: UL 1459 Canadian Safety: CSA C22.2 No. 225-M90
1042 Power Shelf Rear Panel
FUSE RATING
115 VAC
2.0A 60Hz
3.0A 125V
B
F1
+
PSB
48VDC
2A
ALARM
CONTACTS
NOCNC
ELECTRIC SHOCK AND ENERGY HAZARDS, TO
COMPLETELY DEENERGIZE REQUIRES THE
DISCONNECTION OF THE AC AND DC SOURCE
REPLACE WITH SAME TYPE/RATING FUSE
2 31 4 5
Rear Panel Description
Index Function
1 AC Power Cord: This cord can be connected to any available 110-V outlet. 2 Fuse F1: This fuse protects power supply B (PS B) with a rating of 3 amperes. 3 PS B: The three screw terminals on th e l eft are used to connect a 48-VDC load to the main feeds.
Alarm Contacts: The three isolated contacts on the right permit connection to a remote indicating device. The contacts may be
4
5 Fuse F2: This fuse protects power supply A (PS A) with a rating of 3 amperes. 6 PS A: Th ese t hree screw terminals are used to connect a 48-VDC load to the main feeds.
configured as normally closed (NC) or normally open (NO). NO and NC refer to the contact’s relationship to the common (C) contact under a no alarms condition.
+
PSA
48VDC
2A
FUSE RATING
3.0A 125V
A
F2
6
Simplified Schematic
PS A
-48 V F2
3 A
PS B
-48 V F1
3 A
ALARM CONTACTS
+
+
NO
C
NC
TERMINAL STRIP A
TERMINAL STRIP B
145 Baytech Drive
San Jose, Califo rnia 95134
127 Jetplex Circ le
Madison, Alab ama 35758
(800) 837-4546
www.verilink.com
FAX-On-Demand
(800) 957-5465