Vent-Axia HR205, HR204 User, Installation & Servicing Instructions

Page 1
Whole House Ventilation System
with Heat Recov ery and Cooker Hood(HR205)
User, Installation & Servicing Instructions
Please leave these instructions with the user
Page 2
Contents
Section
2.0 General Layout
3.0 Technical Data
4.0 Appliance Operation
5.0 Installation Requirements
6.0 Installation
7.0 Wiring Diagrams
8.0 Commissioning
9.0 Maintenance
10.0 Changing Components
11.0 Fault Finding
12.0 Short Parts List
Page
3
6
8
10
11
14
18
22
24
26
30
35
2
Page 3
1.0 User Information
The HR204 (Fig. 1) and HR205 (Fig. 2) are whole house ventilation units.
This appliance must be installed in accordance with the manufacturers’ instructions and the regulations in force.
Duct systems must be installed in accordance with CIBSE guides and BRE Digest 398.
Read the instructions fully before installing or using the appliance.
Warning : The ventilation for any open flued appliance must always be considered before siting the extract and inlet vents, the vents must also be sited away from other flue terminals, ventilators etc. on the outside of the dwelling. In addition there shall be adequate ventilation of the room when the cooker hood is used at the same time as appliances burning gas or other fuel. The exhaust air duct must not be discharged into a flue which is used for exhausting fumes from appliances burning gas or other fuels. Refer to the relevant current British Standard Codes of Practice, Part J of the Building Regulations England and Wales and Part F of the Building Standards (Scotland) Regulations.
3
Page 4
1.0 User Information
• HR204
Important:The HR204 is not suitable for installation above any cooking appliance.
The HR204 is a mechanical ventilation with heat recovery (MVHR) unit. The unit provides continuous extraction of stale air from the dwelling typically from the bathroom and from the kitchen. The stale air passes through the heat exchanger before being ducted to outside.
Fresh air from the outside is continuously drawn into the unit and passed through a filter and then into the heat exchanger. In the heat exchanger the fresh air is pre­warmed and ducted into the dwelling typically to living rooms/ bedrooms.
• HR205
The HR205 is a mechanical ventilation with heat recovery (MVHR) unit, designed solely to operate with the Vent-Axia telescopic cooker hood. The unit provides continuous extraction of stale air from the dwelling typically from the bathroom and the kitchen. The stale air passes through the heat exchanger before being ducted to outside.
Fresh air from the outside is continuously drawn into the unit, passed through a filter and then into the heat exchanger. In the heat exchanger the fresh air is pre­warmed and ducted into the dwelling typically to living rooms/ bedrooms.
When the telescopic hood is extended the MVHR unit switches automatically to boost. The hood draws steam and fumes from cooking through metal filters and direct to outside.
Important: The cooker hood must always be fully opened when the cooker /hob is in use.
Warning: Do not flambé under the cooker hood
4
Page 5
1.0 User Information
Cleaning the Unit
Warning: Disconnect from mains electrical supply before cleaning any components.
Note: It is important that any door or cupboard front covering the MVHR unit is easily removab le by the user as access for regular cleaning of the air filters and heat exchanger is required.
Warning: Failure to clean the cooker hood and its filters as described below will lead to a fire risk.
Release hand fastners
Air inlet filter pull out, brush & vacuum clean
Warning
Pull forward & remove the outer case
UP
FRONT
UP
FRONT
Use strap to pull out heat exchanger.
WiringService
WHC0006A
The cooker hood and filters should be checked and cleaned every 3 months.
Fig. 3
1.1 Heat Exchanger - HR204 & HR205
1. Lift off the front door panel by releasing the two hand screws and lifting upwards.
2. Note how the heat exchanger is fitted and by using the plastic strap pull forwards to remove.
3. If necessary the heat exchanger can be washed in warm water using a mild detergent. Take care not to damage the fins. Re-assemble in reverse order after thoroughly drying.
1.2 Air Inlet Filter - HR204 & HR205
Fig. 4
1. Lift off the front door panel by releasing the two hand screws and lifting upwards.
2. Remove the air inlet filter by pulling forwards.
3. Carefully brush and vacuum the filter in a well ventilated area.
HR205
Remove the cooker hood filters for cleaning
View from below the unit
Fig. 4
Fig. 5
4. Re-assemble in reverse order.
1.3 Cooker Hood Filters - HR205
Fig. 5
1. Rear Filter - To remove the rear filter grip and pull inwards the grey handles at either side and slide the filter forwards and downw ards.
2. Front Filter - To remove the front filter grip and pull inwards the grey handles at either side and drop the filter downwards.
3. The filters can be washed in a dishwasher or in warm soapy water. Thoroughly dry the filters and re-assemble in reverse order.
Note: For spare parts see Section 12.
5
Page 6
2.0 General Layout
HR205
Cover Panels removed for clarity.
1. Heat Exchanger (Lexan)
2. Fan (Fresh Air In)
3. Fan Capacitor (RH)
4. Electrical Control/Transformer
5. Fuse (3.15amp fast blow)
6. Terminal Block
7. Overheat Sensor
8. Lower Fixing Hole
Fig. 6
6
9. Fire Damper
10. Condensate Drain (15mm)
11. Condensate T r ay
12. Alternative outlet for condensate
13. Fan (Extraction)
14. Fan Capacitor (LH)
15. Inlet Air Filter
16. Air Connections (4 off)
Page 7
2.0 General Layout
HR 204
Cover Panels removed for clarity
1. Heat Exchanger (PVC)
2. Fan (Fresh Air In)
3. Fan Capacitor (RH)
4. Electrical Control/Transformer
5. Fuse (3.15amp fast blow)
6. Terminal Block
7. Lower Fixing Hole
8. Alternative outlet for condensate (bottom)
9. Condensate Drain (15mm)
10. Condensate Tray
11. Alternative outlet for condensate (side)
12. Fan (Extraction)
13. Fan Capacitor (LH)
14. Inlet Air Filter
15. Air Connections (4 off)
Fig. 7
7
Page 8
3.0 Technical Data
HR205 HR204
Including cooker hood
Dimensions (mm) Height 458 412 Width 598 552 Depth 285 285
Min. Clear ances (mm) Both sides 1 5 Above casing 200 200 Below casing 700 100 Front f or servicing 250 250 Front in operation None None
Lift weight (kg) 20.6 16.7 V oltage tappings Po wer consumption (watts) Po wer consumption (watts)
Lights off Lights on 80 16 96 16 100 27 107 27 120 40 120 40 140 52 132 52 160 65 145 65 230 111 191 111
Duct connections All suitable for 100mm circular ducts Condensate connection Suitable for 15mm pipe
Electrical supply 230v – 50Hz appliance must be connected to an earthed supply External fuse rating 3 amps Internal fuse rating Transformer - 3.15 F
Filtration EU2
8
Page 9
The MVHR unit has five normal
fan speed
settings and
one boost
setting. The
performance
curve chart
gives the
ventilation rates
at each fan
speed setting
compared to the
pressure drop of the system.
3.0 Technical Data
Flow Rate Vs Pressure Chart
350
100Pa @
300
250
230v
200
150
Pressure / Pa
100
50
0
0 2010 30 50 7040 60 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230
160v
140v
120v
100v
80v
Flow rate / m³ / hr
100m³/Hr
WHC0022A
240
Fig. 8
Fig. 9
9
Page 10
4.0 Appliance Operation
• HR204
Optional Extras
External Controls
N
orm
al
Normal/boost
B
oost
Switch NBSW
Normal/boost
Pull Switch
PCSW
Humidity Sensor
HS6
When the electricity is switched on the external controls (humidstat or normal/boost switch) supply electricity to the fans.
On normal running the fans run at the voltage set during commissioning (80,100,120,140 or 160 volts).
Air is then moved through the unit (see Fig 8) If the fans become jammed then a thermal trip in the fan senses temperature rise and breaks the electrical supply to the motor. This can only be
reset by disconnecting from the mains supply.
If the external controls call for boost operation the fans automatically run at 230 volts and increase the air movement of both exhaust and inlet air.
• HR205
When the electricity is switched on the unit checks for continuity across the overheat thermostat.
Power ON
Normal Operation
Fans run in whole
house mode at 80, 100,
120, 140, or 160 Volts.
Cooker
Hood
Open
Boost Operation
Fans run at 230 Volts.
Cooker
Hood
Closed
Continuous extract
typically from
bathroom/kitchen.
Continuous supplying
of fresh filtered
air typically to
living room/ bedroom.
Lights on the Cooker
Hood can be used.
Increased extract rates,
also extract from
Cooker Hood.
Increased supply to
living room/bedroom.
The fans then run at the voltage set during commissioning (80,100,120,140 or 160 volts).
Air is then moved through the unit (see Fig 8) If the fans become jammed then a thermal trip in the fan senses temperature rise and breaks the electrical supply to the motor. This can only be
reset by disconnecting from the mains supply.
If the overheat thermostat senses an elevated rise in temperature from the cooker/hob it breaks the electrical supply to the fans. The overheat
thermostat can only be reset by disconnecting the mains supply to the unit.
In the event of a serious fire at the hob (e.g. chip pan fire) the in built fire damper will operate sealing the clean air side of the unit from the fire.
10
Lights on the Cooker
Hood can be used.
WHC0021A
Fig. 10
Page 11
5.0 Installation Requirements
5.1 Location
1. The cooker hood MVHR unit is only suitable for installation above a domestic cooker or domestic hob. The HR205 must be sited a minimum of 700 mm above the cooker/hob.
2. The exhaust duct must pass through an outside wall or roof and discharge to atmosphere in a suitable position .The clean air inlet duct must pass through an outside wall or roof and be suitably positioned to provide an adequate fresh air supply from atmosphere.
5.2 Site requirements
1. For the HR205 a flat vertical area 1332mm high x 600mm wide is required for installation.
For the HR204 a flat vertical area 692mm high x 562mm wide is required for installation.
Important: The HR204 is not suitable for installation above any cooking appliance or with any extraction system servicing a cooking appliance.
2. Before installation consideration must be given to the position of the ductwork connections, the electrical connection and the condensate pipe connection.
Warning: Please check the information on the data plate is compatible with local supply conditions.
3. The installation must be carried out by a competent person and be in accordance with the relevant Building regulations (Scotland) (consolidation), the Local building regulations, the current I.E.E. Wiring regulations.
Reference should also be made to the BRE digest 398 and CIBSE guidelines.
Warning: The addition of anything that may interfere with the normal operation of the appliance without the express written permission of Vent-Axia Ltd could invalidate the appliance warranty and infringe regulations.
Warning: If the unit is fitted in a room containing a bath or shower then reference should be made to the current I.E.E. Wiring Regulations and Building Regulations.
11
Page 12
5.0 Installation Requirements
5.3 General
1. The MVHR unit has five normal fan speed settings and one boost setting. The performance curve chart (Section 3, Fig. 8) gives the ventilation rates at each fan speed setting compared to the pressure drop of the system.
2. The transmission of noise along ducts should be reduced by fitting noise attenuation ducts Part No. FS100.
5. 4 Ducting
1. The outside exhaust duct and outside air intake duct should be sited a minimum of 1 metre apart to minimise the risk of contaminated air being drawn into the house.
2. The duct work system should be sized and installed to minimise the pressure loss along it.
Examples of different ducting & fittings
Outside
Wall
RD104WHRD104WH
Terminals
minimum
1m apart
NQT100
IQTB45
0.25m
NQT100
OR
NQT40
NQT100
1m
IQTB90
NQT100
or
NQT40
3. Using larger diameter pipes and keeping the number of bends and fittings used to a minimum will reduce the pressure drop and allow the unit to be set at a lower fan speed.
4. Ducting should be insulated in cold areas to minimise heat losses. All duct joints should be suitably taped to ensure an air tight seal.
RD060
RD015
1.5m
EV100
Bathroom
RD015
RD060
RD015
SV100
Living Room
Fig. 13
12
1m
IQTB45
IFD100
HR205
Fresh air in
Exhaust out
RD070
Warm air out
Hot stale air in
WHC0010A
Page 13
5.0 Installation Requirements
Warning : The ventilation for any open flued appliance must always be considered before siting the extract and inlet vents, the vents must also be sited away from other flue terminals, ventilators etc. on the outside of the dwelling. In addition there shall be adequate ventilation of the room when the cooker hood is used at the same time as appliances burning gas or other fuel. The exhaust air duct must not be discharged into a flue which is used for exhausting fumes from appliances burning gas or other fuels. Refer to the relevant current British Standard Codes of Practice, Part J of the Building Regulations England and Wales and Part F of the Building Standards (Scotland) Regulations.
5.5 System controls
1. An optional Humidistat (HS6) Part No. 370254 is available for automatic boost control.
2. An optional boost switch (NBSW) Part No. 370495 is available for manual/boost control remote from the unit. An optional pull cord boost switch (PCSW) Part No. 370278 is available for manual/boost control remote from the unit.
5.6 Electrical supply
1. External wiring must be correctly earthed , polarised and in accordance with the current I.E.E. Regulations.
2. The mains supply must be 230v ~ 50Hz fused at 3amps
Note: The method of connection to the mains supply must facilitate complete electrical isolation of the appliance. Connection may be via a fused double pole isolator with a contact separation of at least 3mm in all poles and supplying the MVHR unit and its system controls only.
5.7 Condensate drain
Fig. 14
1. The condensate pipe should have a continuous fall of 10° (1 in 6) with as much of the condensate pipe as possible run inside the property to avoid freezing. The pipe should also incorporate a trap with a minimum height of 75mm. See Fig. 17.
2. The HR205 has two alternative condensate outlet positions: - rear and left hand side HR204 has three condensate outlet positions: ­rear, bottom and left hand side.
.
The
13
Page 14
6.0 Installation
Make sure the Wall
Template is level
Mark position
of the
condensate
pipe 15 mm
(drill where
required)
Top of hob
6.1 Preparation
1. Check site requirements (Section 5) before commencing.
ir
rm A
a
t
W
u
O
le
a t St o
H
In
ir
A
ir
A
h es r
F
In
t
s
u
a
h
x
t
E
u
O
Mark position
of the
fixing holes
2 top (minimum)
& 1 lower
then drill & plug
2. Remove the fixing template from the MVHR carton.
After considering the site requirements position the template on the wall ensuring it is level.
3. Mark the positions of at least two top fixing holes, the lower fixing hole and the condensate outlet.
Measure 700mm
from hob
If required mark off the positions of the four duct connections.
4. Drill and plug the wall at the fixing points and drill the condensate hole.
5. The top two screws should now be fitted leaving enough space for the keyhole fixing slots to engage.
6. Place the MVHR unit on its back (Fig. 15). Lift
HR205
off the front door panel by releasing the two hand screws and lifting upwards.
Mark out the
position of the
unit of the
Wall Template
Part No. 372706
Exhaust
Fresh AirInHot Stale
Out
Bottom of Mounting Brackets
4 Fixing Holes
(Key Holes)
Use one
hole each side
MVHR Side
Minimum Side
Clearance
24mm
(HR205c)
Minimum Side
Clearance
5mm
(HR204)
Back Case
Condensate Hole
Side Case Knock
Out Condensate Hole
Minimum Side
Clearance 1mm
Bottom Condensate
Pipe Exit (HR204 Only)
Minimum
Top
Clearance
200mm
Wall Template HR204 &
HR205
(with cooker hood)
Whole House Ventilation System
Minimum
Side
Clearance
(MVHR)
Minimum
24
Top Clearance for servicing
200
300
Minimum
Side Clearance (MVHR)
24
Minimum
Side
Minimum
Clearance
Front
(C.Hood)
Clearance
1
for servicing
250
Clearances
HR205c
Minimum Bottom
All dimensions
Clearance from Hob
700
Bottom of
Cooker Hood
Cooker Hood
Measure Minimum
Bottom Clearance
700mm
From Hob
(HR205c Model)
Minimum
Clearance
servicing
in mm
Fixing Hole
7. Remove the bottom electrical cover by releasing the 3 screws, pulling the panel forwards and disconnecting the earth lead to the panel.
Warm Air
Air In
Out
98mm
Minimum
Side
Clearance
5
Minimum Top Clearance for servicing
280
200
Minimum
Side
Front
Clearance for
250
Clearances
HR204
Minimum Bottom
Clearance
100
Bottom
Minimum Side
5
Minimum Side
Bottom of MVHR Unit
Minimum Bottom Clearance
100mm
(HR204 Model)
Top of MVHR
Unit
MVHR
Clearance
24mm
(HR205c)
Clearance
5mm
(HR204)
Minimum Side
Clearance 1mm
Mains Cable Outlet
Side
understairs installation
WHC0013A
Stair Case
Example of a possible
HR204
Fig. 15
14
Ground Floor
Page 15
6.0 Installation
6.2 Assembly of the MVHR unit and the
cooker hood - HR205 only.
Remove
the
Cooker
Hood filters
before
fitting
Cooker
Hood to
MVHR
Unit
View from below the unit
Top View (MVHR Unit
placed on it's back)
Warning
UP
FRONT
Use a packing piece to
hold
open
the
cooker
hood
1. Unpack the cooker hood, locate the four screws and washers and the protective box for the cooker hood plug and socket.
2. Open out the telescopic hood and remove the two metal filters by releasing the grey plastic springs and sliding out.
3. Offer up the hood to the MVHR unit and carefully feed the cable and four pin cooker hood socket through the hole in the back right hand side of the MVHR unit.
4. Align the cooker hood and attach it to the MVHR unit using the four screws provided.
Note: it will be necessary to support the telescopic hood when attaching it to the MVHR unit.
5. Carefully route the cook er hood cable and socket into the MVHR unit and engage it with the plug ensuring the locating lugs align.
It is important that the cables are routed away from the cooker hood outlet and fire damper.
WHC0032A
MVHR
Unit
Connect
Cooker
Hood
Grommet
Secure Cooker Hood to MVHR
Unit with 4 screws supplied
Correct route for cooker hood cable
connection (HR205)
Connector
Clamp the
Protective Box
around the
Connector
Cable
Clips
Grommet
HR205
The cable
must be
routed clear
of the fire
damper
6. Locate the assembled plug and socket in the protective box taking care to route the cables as shown (Fig. 16). Clip the bo x together and secure using the screws provided. Locate the large cable grommet in the hole and ensure it is seated correctly.
6.3 Condensate outlet
1. If the condensate pipe is to exit the unit at the left hand side, stand the unit up on its base taking care not to damage the telescopic hood and filters.
2. Locate the semi-pierced hole and carefully remove the metal disc.
3. Swap over the grommet used on the rear exit hole and seal the rear hole with duct tape or similar.
Note: The HR204 has an extra condensate outlet on the bottom panel.
Fig. 16
15
Page 16
6.0 Installation
6.4 Fitting the MVHR unit
1. Offer the combined unit to the wall and engage the keyhole slots over the screws previously fitted.
2. Make sure the unit is level and tighten the top screws before engaging the final screw.
6.5 Making the condensate connection
1. The condensate connector is suitable for 15 mm pipe.
2. The condensate pipe should incorporate a water trap to prevent foul air being drawn into the unit. The minimum height of the trap should be 75 mm.
Note: To ensure the condensate pipe is primed, slowly pour water into the condensate tray until it discharges into the drain.
Fig. 17
16
Page 17
6.0 Installation
6.6 Making the duct connections
1. The unit has four duct connections suitable for 100mm plastic pipe.
1. Exhaust outlet to outside
2. Air inlet from outside
3. Stale air inlet from dwelling
4. Fresh air outlet to dwelling
Notes: It is essential that the duct system is connected as indicated.
It is important that the duct system does not interfere with the correct fitting of the outer door and does not prevent the correct operation of the unit.
6.7 Controls
160 140 120
100
80
L
N
Fit bottom cover panel.
Warning
HR205
WiringService
UP
FRONT
Position the white lead for the required fan speed setting, (160v fast to 80v slow available) 120v shown.
WHC0009A
Fig. 18
1. The HR204 requires external controls to enable normal/boost switching, see Page 20 ­Wiring Diagrams.
2. The HR205 can have optional external controls fitted, see Pages 18 and 19 - Wiring Diagrams.
6.8 Making the electrical connection
Warning: This appliance must be earthed
1. The normal running speed of the fans is set at 120v.
2. The unit must be set to the appropriate voltage as determined by air flow required and duct system pressure loss (see Section 5.3).
To change the voltage setting for the fans, unscrew and remove the white wire from the 120v connection on the controller.
3. Carefully insert the wire into the desired connection (80, 100, 120, 140 or 160) and secure the wire.
4. Fit the bottom cover panel.
5. Connect the flying lead to the mains supply ­see Section 5.6.
6. Check the electrical installation for; Earth continuity, short circuits, resistance to earth and correct polarity.
17
Page 18
7.0 Wiring Diagrams
HR205 MVHR Unit Wiring
Mains
In
230v
br
b
g/y
Fan
(air out)
r
b
g/y
For External Controls
br
b
g/y
r
Overheat Thermostat
1
N
2
L
3
b
4
L
N
gr
gr
Key Colors
b - Blue gr - Grey r - Red w - White
b
bk
w
br
w
b
br
To Cooker Hood
Fan
(air in)
br - Brown g/y - Green/Yellow p - Purple bk - Black
g/y
Controller
w br grgr
O
B
C
160 140
b
r
120 100
80
L
g/y
N
b
br
r
b
WHC0031A
bk
br
b
b
L
Fuse (3.15AT)
N
b
Earth for Inspection Panel
Fig. 19
b
p
br
boost speed 230v
b
br
gr
c
Micro Switch
To MVHR
gr
40 watts
bulb
br
Light Switch
HR205 Cooker Hood Wiring
p
bulb 40 watts
br
18
Page 19
7.0 Wiring Diagrams
HR205 MVHR Unit Wiring with optional Humidstat HS6
Mains
In
230v
(air out)
g/y
br
b
g/y
Fan
r
HS6 Humidistat
Common
0
Boost
2
Ordinary
1
Key Colors
b - Blue gr - Grey r - Red w - White
br - Brown g/y - Green/Yellow p - Purple bk - Black
Fan
(air in)
N
L
Remove Link
1
N
L
2 3
gr
b
gr
4
br
b
g/y
r
b
L
N
gr
br
gr
br
w
br
Overheat
b
Thermostat
bk
w
w
br
b
b
To Cooker Hood
bk
b
b
Controller
O B C
L
Fuse (3.15AT)
N
160 140 120 100
80
L
N
r
g/y
Earth for Inspection Panel
g/y
b
r
b
br
b
Mains
In
230v
(air out)
g/y
br
b
g/y
Fan
r
HR205 MVHR Unit Wiring with optional Normal/Boost Switch
Manual Normal /Boost
Switch NBSW or
Pull Switch PCSW
Common
Boost
Remove Link
Normal
1
gr
2 3
b
b
gr
4
br
b
g/y
r
b
L
N
gr
w
br
gr
w
b
br
c
w br
Overheat Thermostat
bk
br
b
bk
b
b
To Cooker Hood
Key Colors
b - Blue gr - Grey r - Red w - White
Controller
O B C
L
Fuse (3.15AT)
N
br - Brown g/y - Green/Yellow p - Purple bk - Black
160 140 120 100
80
L N
r
g/y
Earth for Inspection
Fan
(air in)
g/y
b
r
b
br
WHC0011A
b
Fig. 20
Panel
19
Page 20
7.0 Wiring Diagrams
HR204 MVHR Unit Wiring
Mains
In
230v
br
b
g/y
Fan
(air out)
r
b
g/y
For
External Controls
br
b
g/y
r
Fan
(air in)
Key Colors
b - Blue gr - Grey r - Red w - White
1
N
2
L
3
b
4
L
N
br
br
b
br - Brown g/y - Green/Yellow p - Purple bk - Black
For External Controls
br
b
b
Controller
O B C
L
Fuse (3.15AT)
N
160 140 120 100
80
L
N
g/y
g/y
b
r
b
br
r
b
WHC0033A
Earth for Inspection Panel
20
Fig. 21
Page 21
7.0 Wiring Diagrams
HR204 MVHR Unit Wiring with optional Humidstat HS6
Mains
In
230v
(air out)
g/y
br
b
g/y
Fan
r
HS6 Humidistat
Common
0
Boost
2
Ordinary
1
Key Colors
b - Blue gr - Grey r - Red w - White
br - Brown g/y - Green/Yellow p - Purple bk - Black
Fan
(air in)
N L
1
N
L
br
b
g/y
r
b
2 3
b
4
L
N
br
br
b
br
b
b
Controller
O B C
L
Fuse (3.15AT)
N
160 140 120 100
80
L N
r
g/y
Earth for Inspection Panel
g/y
b
r
b
br
b
Mains
In
230v
(air out)
g/y
br
b
g/y
Fan
r
HR204 MVHR Unit Wiring with optional Manual/Boost Switch
Key Colors
b - Blue gr - Grey r - Red w - White
Manual Normal /Boost
Switch NBSW or
Pull Switch PCSW
Normal
c
1 2 3
b
br
b
g/y
r
b
L
N
4
br
Boost
b
Common
br
br
b
b
Controller
O B C
L
Fuse (3.15AT)
N
br - Brown g/y - Green/Yellow p - Purple bk - Black
160 140 120 100
80
L N
b
br
r
b
g/y
Fan
(air in)
g/y
r
b
WHC0012A
Earth for Inspection Panel
Fig. 22
21
Page 22
8.0 Commissioning
8.1 Prepare for commissioning - HR205
1. Refit the front door panel by hooking it over the top lip of the appliance and swinging down. Tighten the two case screws.
2. Ensure the telescopic hood is retracted.
3. Turn on the electrical supply. The unit will now start running at the normal ventilation speed.
4. Pull the telescopic hood forward. The unit will now switch to boost speed.
5. Check the operation of the cooker hood lights.
8.1a Prepare for commissioning - HR204
1. Refit the front door panel by hooking it over the top lip of the appliance and swinging down. Tighten the two case screws.
2. Check the external controls are set to normal running.
3. Turn on the electrical supply. The unit will now start running at the normal ventilation speed.
4. Set the external control to boost. The unit will now switch to boost speed.
22
Page 23
8.0 Commissioning
8.2 Balancing the system
Inside View of
Supply V alve
Air direction
SV100
Adjust Ceiling Supply Valve for Living Room etc
Air Deflector
Plate
Locking Nut
to lock
the valve
in position
Air
Direction
Indictor
Note: It is important that a suitable anemometer is used to balance the system therefore giving the required ventilation rates to each room.
1. Set the appliance running on normal speed.
2. Make a preliminary adjustment of all the duct inlet and outlet louvres.
Note: The supply air terminal is directional and incorporates a deflector plate. Ensure that the deflector plate is correctly positioned so that the active part of the terminal is discharging to the room.
3. Check the flow rate and adjust if necessary the extract valve furthest from the appliance.
4. Check the flow rates and adjust if necessary the remaining extract valves.
5. Repeat the flow checks and adjust until the extract system is balanced.
6. Check the flow rate and adjust if necessary the inlet valve furthest from the appliance.
Inside View of
Extract Valve
Locking Nut
to lock
the valve
in position
WHC0029A
7. Check the flow rate and adjust if necessary the remaining inlet valves.
8. Repeat the checks and adjust until the system is correctly balanced.
Note: If the flow rates have been achieved with all the louvres nearly closed, it may be possible to reduce the fan speed and re-adjust the louvre settings.
8.3 Instruct the user
Instruct the user in the operation of the appliance. Hand over these instructions, giving advice on the necessity for regular servicing of the filters and heat exchanger.
Note: It is important that any door or cupboard front covering the MVHR unit is easily removab le by the user as access for regular cleaning of the air filter and heat exchanger is required.
EV100
Adjust Ceiling Extract Valve for Bathroom etc
Fig. 23
23
Page 24
Release handand fastners (Butterfly Bolts)
Air inlet filter pull out, brush & vacuum clean
Remove covers to inspect
Warning
LH/RH Fans & Fire Damper (clean as required)
HR205
Pull out & clean the Condensate Tray
Pull forward & remove the outer case
UP
FRONT
UP
FRONT
Use strap to pull out heat exchanger.
WiringService
Pull Cooker Hood forward
9.0 Maintenance
Important: Before servicing ensure that the appliance is isolated from the electrical supply. After isolating from the electrical supply, allow one minute for the fans to stop rotating before servicing the appliance.
1. HR205 only -Extend the telescopic hood and remove the two metal filters. The cooker hood filters can be washed in a dishwasher; alternatively a hot hand wash will suffice. Check and clean the filters if necessary. Dry the filters thoroughly before re-fitting.
2. Lift off the front door panel by releasing the two hand screws and lifting upwards.
3. Identify the air inlet filter and remove by pulling forwards.
Taking note of the offset sliders, carefully remove the heat e xchanger by gently pulling forwards.
4. Remove the bottom electrical cover by releasing the 3 screws, pulling the panel forwards and disconnecting the earth lead to the panel.
5. Loosen the two screws on each side plate and lift to remove.
6. HR205 only - Check the cooker hood inlet for debris and fat deposits. Clean as required. Check the fire damper is in satisfactory condition and unaffected by debris and fat deposits. Replace if necessary.
7. Check both fans, fan compartments and
WHC0016A
exhaust duct outlets for deposits. Clean as necessary.
8. Remove the condensate tray by pulling forwards. Check and clean if necessary.
9. Check the condition of the four heat exchanger sealing strips and front door seal. Replace all seals as necessary (Fig. 24).
Remove
the cooker
hood
filters
for cleaning
View from
below the
unit
Fig. 24
24
10. Carefully wash the heat exchanger in warm soapy water taking care not to loosen the heat exchanger fins. Thoroughly dry the heat exchanger before re-fitting.
Note: Ensure the heat exchanger is located correctly in the offset sliders.
11. Carefully vacuum the air inlet filter. Replace if necessary.
12. Re-assemble in reverse order and re-fit the outer door ensuring the door makes a good seal.
Page 25
9.0 Maintenance
13. Turn on the electrical supply to the appliance. With the hood closed the appliance will run on normal setting. Extend the hood and the appliance will switch to boost setting. With the appliance on boost check the operation of the cooker lights
14. Check the condition of the ductwork system, the soundness of all joints and repair if necessary
25
Page 26
10.0 Changing Components
Bulkhead
Controller
Controller securing screws (4 off)
160 140 120 100
80
L N
Warning
Mounting bracket to bulkhead securing screws (2 off)
Controller Mounting Bracket
Rear View of the Controller
Take note of the fan speed setting, 120v shown. When the new controller is fitted, fit the white lead to the position of the old controller for the correct fan speed.
Controller
UP
FRONT
IMPORTANT: ISOLATE FROM THE ELECTRICAL SUPPLY BEFORE STARTING ANY WORK ON THE APPLIANCE.
The fans continue to rotate for one minute after isolating from the electrical supply
10.1 Controller
1. HR205 Only - Fully extend the telescopic cooker hood and remove the two metal filters.
2. Remove the outer door by releasing the two screws and lifting the door up and forwards.
3. Remove the bottom electrical cover by releasing the 3 screws, pulling the panel forwards and disconnecting the earth lead to the panel. Make a note of the voltage setting for the fans and of the wiring arrangement for the controller.
4. Release all the wires connected to the controller.
5. Remove R.H. fan cover panel and remove the R.H. fan (see Section 10.3). Unscrew the two screws securing the controller mounting bracket to the bulkhead and remove the bracket and controller unit. Separate the bracket from controller by removing the four screws.
6. Re-assemble with the new controller in reverse order. Check the electrical installation
for; Earth continuity, short circuits, resistance to earth and correct polarity.
Overheat
Thermostat
Head
Overheat
Thermostat
Fig. 25
26
Sleeve
HR205
Cable
Overheat
Thermostat
Clip
Remove RH fan cover
panel & bottom cover panel.
Tie
Bulkhead Grommet
WHC0018A
10.2 Overheat thermostat - HR205 Only
1. Lift off the front door panel by releasing the two hand screws and lifting upwards.
2. Remove the bottom electrical cover by releasing the 3 screws, pulling the panel forwards and disconnecting the earth lead to the panel. Identify the connections for the overheat thermostat. Make a note of the routing for the overheat thermostat cable.
3. Release the overheat thermostat connections.
4. Release the sensor head by springing open the clip and pulling out the sensor head.
5. Remove the overheat thermostat taking care not to dislodge the bulkhead grommet.
6. Carefully locate the new sensor and position the lead as shown in Fig. 26. Re-assemble with the new overheat thermostat in reverse order.
Check the electrical installation for; Earth continuity, short circuits, resistance to earth and correct polarity.
Page 27
10.0 Changing Components
10.3 Extract fan and Inlet fan
Removal
of the
Lefthand
Fan
(righthand
fan similiar)
HR205
Slacken
the 2 rear
securing
screws
Fan
capacitor
Cable ties
UP
FRONT
Warning
Remove LH cover to access the LH Fan
WiringService
Push Fan
Assenbly to the left
and pull
away from
unit
Fan support
bracket
1. Lift off the front door panel by releasing the two hand screws and lifting up wards.
2. Loosen the two screws on the side plate and lift to remove.
3. Release the clip on the plastic plug and disconnect the plug.
4. Slacken the two rear fan bracket screws.
5. Remove the two front fan bracket screws and remove the fan assembly. Note the position of the fan bracket relative to the fan.
6. Remove the bracket and re-fit to the new fan.
7. Re-assemble with the new fan in reverse order ensuring the cable does not foul the fan motor. Check the electrical installation for;
Earth continuity, short circuits, resistance to earth and correct polarity.
10.4 Fan capacitor
1. Lift off the front door panel by releasing the two hand screws and lifting up wards.
2. Loosen the two screws on the side plate and lift to remove.
Spade
terminals
Release
the
electrical plug
Fan securing
screws 4 off
Fan support
bracket
Fan
capacitor
Cable ties
Remove
the 2 front
securing
screws
Fan
3. Release the clip on the plastic plug and disconnect the plug.
4. Slacken the two rear fan bracket screws.
5. Remove the two front fan bracket screws and remove the fan assembly.
6. Disconnect the two 2.5 mm spade terminals from the capacitor.
7. Cut the two cable ties and remove the capacitor.
8. Re-assemble in reverse order with the new capacitor and use the new cable ties provided. Ensure the cable does not foul the fan motor.
Check the electrical installation for; Earth continuity, short circuits, resistance to earth and correct polarity.
WHC0020A
Fig. 26
27
Page 28
10.0 Changing Components
10.5 Fire damper - HR205 Only
HR205
Fit 4 new self-adhesive sealing strips
(see positions
1 to 4 below)
Fire Damper
U
P
FR
O
N
T
4 Fixing
Screws
Re-fit new
heat
exchanger
1. Fully extend the telescopic cooker hood.
2. Remove the two metal filters.
3. Remove the outer door by releasing the two screws and lifting the door up and forwards.
4. Remove the bottom electrical cover by releasing the 3 screws, pulling the panel forwards and disconnecting the earth lead to the panel.
5. Remove the four screws that secure the fire damper and lift it away from the unit.
10.6 Heat exchanger
1. Lift off the front door panel by releasing the two hand screws and lifting up wards.
2. Gently ease the heat exchanger forwards and remove.
3. Re-assemble in reverse order taking care not to damage the heat exchanger seals.
Warning
With the Cooker Hood filters removed, pull off the old seal and clean the glue away.
HR205
2
1 3
4
10.7 Heat exchanger seals
1. Lift off the front door panel by releasing the two hand screws and lifting up wards.
2. Gently ease the heat exchanger forwards and remove.
3. Remove the four heat exchanger seals taking care to remove all the old adhesive backing.
WiringService
WHC0019A
4. Fit the new seals ensuring they make good contact with the location channel.
5. Re-assemble in reverse order taking care not to damage the heat exchanger seals.
10.8 Cooker hood seals
1. Fully extend the cooker hood.
2. Remove the metal filters.
3. Pull away the old cooker hood seal and remove any remaining glue. Use a small amount of solvent if necessary.
Adhesive Strip
Peel back adhesive strip &
fit new Cooker Hood Seal
Fig. 27
28
4. Peel back the adhesive strip and carefully fit the new seal as shown in Fig. 28.
5. Re-assemble in reverse order.
View from below the unit
Page 29
This page is intentionally blank
29
Page 30
11.0 Fault Finding
HR205 - Main Unit Fault Finding Chart
Before starting FAULT FINDING
carry out preliminary electrical systems checks
i.e. Earth Continuity, Polarity, Short Circuit
and Resistance to Earth.
START
Ensure the Cooker
Hood is closed.
Is there
mains voltage
across terminals
A1/A2?
NO
Ensure continuity
between terminals
D5 & A1
and between
D6 & A2.
Check mains
supply.
YES
Is the
fuse on the
controller
O.K.
NO
Investigate cause
and
rectify fault
Replace fuse
3.15AT
WARNING
If the Overheat sensor or Fan thermal trip has operated, check the entire system and unit for correct installation. Check all ducting outside & terminals for blockages.
IMPORTANT
When investigating overheating allow the unit to run long enough for any fault to become apparent.
Ensure all external controls are operating and are set to normal running. Ensure that a mains electrical supply is available to the unit.
YES
Is the voltage across terminals B1 &
B2 between 80v
& 160v?
NO
Disconnect wires
from terminals
F1, F2 & F3. Ensure voltage selector wire is
correctly engaged.
Check external
Is the voltage
across F1 & B2
between 80v
& 160v?
YES
control wiring. Refer to 205 wiring diagram (section 7)
Reconnect wires
NO
Replace controller
Replace
cooker hood
YES
Disconnect 4 pin
cooker hood plug.
voltage across
the blue & white
wires on the cooker hood
plug between
NO
Rectify fault on plug and lead.
YES
to terminals
F1, F2 & F3.
Is the
80v and
160v.
cooker hood
Refer to diagrams below to identify terminals on components (e.g. A1, D3 etc).
Are both fans
operating?
YES
NO
See Fan Fault Finding Chart
Note 1
Electricity supply must be isolated and Fan Motor temperature must be less than 100˚ to allow thermal trip to reset.
Note 2
Electricity supply must be isolated and Overheat temperature must be less than 80˚ to allow Overheat Thermostat to reset.
30
G
Fan
Plug
C.Hood
Plug
3 2 1
Connector
Block
1 2 3
DE
4 5 6
F
B
Controller
1
O
2
B C
3
1
L N
2
Voltage Selector Wire
Fuse
(3.15AT)
1 2
160 140 120 100
C
80
L
A
N
WHC0035A
Page 31
YES
Is there adequate airflow at the appliance
inlets and
outlets
NO
Clean filter &
heat exchanger
(section 9). Check
duct system and
terminals for blockages or
damage. Ensure
terminals are
adjusted correctly.
YES
Does the
appliance switch
to boost when the cooker
hood is opened? (Mains
voltage is present
across terminals
B1 & B2
NO
Disconnect 4 pin
cooker hood plug.
Is the
mains voltage
across the blue &
brown wires on the
cooker hood
plug.
YES
YES
Replace cooker
hood
11.0 Fault Finding
HR205 - Main Unit Fault Finding Chart
Do cooker hood
lights operate?
NO
Are the light
bulbs faulty?
NO
YES
YES
Unit operating
Replace bulbs
satisfactorily
(Max. 40 watts)
Replace bulbs
(Max. 40 watts)
NO
Ensure continuity
across cooker hood
plug and lead.
WHC0036A
31
Page 32
11.0 Fault Finding
HR204 - Main Unit Fault Finding Chart
Before starting FAULT FINDING
carry out preliminary electrical systems checks
i.e. Earth Continuity, Polarity, Short Circuit
and Resistance to Earth.
START
Is there
mains voltage
across terminals
A1/A2?
NO
Ensure continuity
between terminals
D5 & A1
and between
D6 & A2
Check mains
supply.
YES
Is the
fuse on the
controller
O.K.
NO
Investigate cause
and
rectify fault
Replace fuse
3.15AT
WARNING
If the Fan thermal trip has operated, check the entire system and unit for correct installation. Check all ducting outside & terminals for blockages.
Ensure all external controls are operating and are set to normal running. Ensure that a mains electrical supply is available to the unit.
YES
Is the voltage across terminals B1 &
B2 between 80v
& 160v?
NO
Disconnect wires
from terminals
F1, F2 & F3. Ensure voltage selector wire is
correctly engaged.
Check external
Is the voltage
across F1 & B2
between 80v
& 160v?
YES
control wiring.
Refer to 204 wiring
diagram (section 7)
Reconnect wires
to terminals
F1, F2 & F3.
NO
Replace controller
Is there mains
voltage between
F2 and B2
NO
Replace controller
Refer to diagrams below to identify terminals on components (e.g. A1, D3 etc).
YES
Are both fans
operating?
NO
See Fan Fault Finding Chart
YES YES
external controls
have a mains supply
from F2 & reduced
voltage supply
NO
Rectify fault on wiring to
external control
Do the
from F1
YES
Check
external
control,
rectify or
replace
as
necessary.
IMPORTANT
When investigating overheating allow the unit to run long enough for any fault to become apparent.
Note 1
Electricity supply must be isolated and Fan Motor temperature must be less than 100˚ to allow thermal trip to reset.
32
G
Fan
Plug
1
O
2
B
C
3
1
L
N
2
Controller
Voltage Selector Wire
Fuse
(3.15AT)
160 140 120 100
C
80
1
L
A
N
2
WHC0037A
Connector
Block
3 2 1
1 2 3
D
4 5 6
F
B
Page 33
11.0 Fault Finding
HR204 - Main Unit Fault Finding Chart
YES
Is there adequate airflow at the appliance
inlets and
outlets
NO
Clean filter &
heat exchanger
(section 9). Check
duct system and
terminals for blockages or
damage. Ensure
terminals are
adjusted correctly.
YES
Do external
controls switch
the unit to boost.
NO
WHC0038A
YES
Unit operating
Replace bulbs
satisfactorily
(Max. 40 watts)
33
Page 34
Investigate the
cause and rectify.
Fan has overheated.
YES
YES
Is the
2 µF?
approximately
capacitor reading
YES
With
the capacitor
wires at the fan
disconnected is there
between the black & blue
160 - 200 Ohms resistance
YES
G2/G3?
connector
NO
NO
Replace
capacitor
(section 10.4)
Replace fan
(section 10.3)
11.0 Fault Finding
Fan Circuit Fault Finding Chart
WHC0039A
NO
fan?
wires from the
female fan plug.
across male and
Ensure continuity
Replace fan
(section 10.3)
Note 1
Electricity supply must be
IMPORTANT
When investigating
isolated and Fan Motor
temperature must be less than
100˚ to allow thermal trip to
reset.
overheating allow the unit to
run long enough for any fault
to become apparent.
Note 2
Electricity supply must be
isolated and Overheat
temperature must be less
than 80˚ to allow Overheat
Voltage Selector Wire
Controller
123
Thermostat to reset.
C
A
L
N
80
160
140
120
100
1
2
Fuse
B
C
O
F
(3.15AT)
1
2
L
N
B
Has the fan
thermostat trip
Is the
G2 and G3 on
voltage across
YES
(see note
operated.
80v and
the fan plug between
1).
160v?
NO
Disconnect
the capacitor.
Is there between
NO
the brown & black
350 & 405 Ohms between
Rectify fault.
NO
Is there
continuity across the
For HR205 Model Only
(Ensure the overheat
overhead thermostat?
below 80˚c)
thermostat is
Replace
Overheat
Thermostat
(section 10)
1
23456
Block
Connector
DE
34
fan
YES YES
Re-align
Plug
C.Hood
YES
Start
Are fans
free to
rotate?
NO
Is the
on inlet
fan fouling
NO
Replace fan
(section 10.3)
WARNING
If the Overheat sensor or Fan
thermal trip has operated,
check the entire system and
unit for correct installation.
Check all ducting outside &
terminals for blockages.
Fan
Plug
3
2
1
ring?
G
Page 35
12.0 Short Parts List
3
4
2
1
UP
FRONT
6
7
8
5
11
10
N
orm
a
l
B
o
ost
15
WHC0023A
12
14
9
13
Key No. Spares Part No. Description
1 372730 Fan assemb ly c.w. capacitor 2 372731 Capacitor 3 372732 Controller 4 372733 Overheat thermostat 5 372734 Fire damper 6 372735 Inlet duct filter 7 372736 Heat exchanger 8 372737 Heat exchanger seals (4 off) 9 372739 Outer door assembly 10 372741 Cooker hood seal 11 372743 Cooker hood filters (set of two) 12 372748 M5 wing screw 13 372777 Light Cover
16
Fig. 28
Optional extras 14 370254 Humidity sensor HS6
15 370495 Normal/boost switch NBSW 16 370278 Normal/boost switch PCSW
35