Ventamatic VX25 series Installation Manual

INSTALLATION INSTRUCTIONS
A leader in the ventilation industry for over 60 years, Ventamatic, Ltd. oers a complete line of air movement products for commercial, industrial, agricultural, and residential use sold under these ne names:
®
®
VENTAMATIC, LTD. P.O. BOX 728, MINERAL WELLS, TX 76068-0728 • PHONE 800-433-1626 FAX 940-325-9311 • WWW.BVC.COM • E-MAIL: BVC@BVC.COM
®
PLEASE READ AND SAVE THESE INSTRUCTIONS
Use this unit only in the manner intended by the manufacturer. If you have any questions, please contact the manufacturer.
When cutting or drilling into a wall or ceiling do not damage electrical wiring or other hidden utilities.
VX25 SERIES
The VX25 Series Static Ventilator provides 144 square inches of Net Free Area, which will ventilate a 500 sq ft attic. For larger attics, use two or more ventilators. Attic ventilators operate most efficiently when air intakes are located around the eaves. At least 600 square inches of air intake ventilation is required per unit.
VX25 SERIES STATIC ATTIC VENTILATORS
INSTALLATION INSTRUCTIONS
1. Position unit on top of shingles, as close to the center of the roof (between the ends of the house) and about 8" down from the ridgeline. The "low profile" housing should be visible on only one side of the roof (Figure 1). Measure the distance from the ridgeline to the center of the unit (this measurement will be used in Step 2).
2. From the attic side of the roof, place a mark on the roof that is a) the same distance from the ridgeline to the center of the unit established in Step 1 and b) located halfway between two roof rafters. Drill a hole on this mark, drilling from the attic through the roof. This hole will be used as a “center” for the following steps.
3. Draw a reference square 25
3/8” x 25 3/8” on the roof using the drilled hole as a center.
4. Within the reference square draw a circle with a 17 3/8” diameter. Remove shingles, nails and felt from this circle.
5. Draw another circle that is 14
7/8” in diameter, using the same centerpoint that you
used to draw the larger circle in Step 4. Cut a hole through the roof decking on this smaller circle.
6. With the unit parallel to the ridgeline, slide the top flange of the unit up under the shingles (some roofing nails may need to be removed). Position the unit on the reference square. With the unit so located, apply a generous amount of roofing compound between the flange and the shingles, approximately 1” in from the perimeter of the flange. Secure the flange to the roof using galvanized roofing nails following the nailing pattern in Figure 2. Nail through the shingles and flange to the roof decking. Apply a small amount of roof cement over nails.
7. Check the installation for any water leakage by pouring water on the roof (or by using a garden hose) around the flange. DO NOT POUR/SPRAY WATER DIRECTLY INTO THE VENTILATOR OPENING.
1. Position unit on the roof about 8" down from ridgeline. If using only one unit, position
the unit in the center of the roof (between the ends of the house). For two or more units, space evenly. Be sure that the ventilator(s) are located between the roof rafters. The "low profile" housing should be visible on only one side of the roof (Figure 1).
2. Drill a hole to mark the center of the unit(s).
3. Using the drilled hole as a centerpoint, draw a circle that is 14
7/8” in diameter. Cut a
hole through the roof decking on this circle.
4. Mount the unit in the circular hole and secure the flange into place with galvanized
roofing nails using the nailing pattern in Figure 2.
5 Install roofing felt and shingles. Leave the bottom part of the flange exposed as shown
in Figure 3.
INSTALLATION IN NEW CONSTRUCTION
INSTALLATION IN EXISTING CONSTRUCTION
Loading...
+ 2 hidden pages