When the outside temperature is below -5°C (23°F), recovery of heat in HRV units
creates frost in the core. For ERV units, when the outside temperature is below
-10°C (14°F), recovery of energy creates frost in the core.
To maintain its proper operation, the unit is programmed to defrost the recovery
core. The defrost frequency varies according to the outside temperature.
During the defrost cycle, the unit shifts to maximum speed and the dampers close.
After defrosting, the unit returns to the operating mode selected by the user.
4
2.1 Booting Sequence
1.
Defrosting Mode
2.
Controls
BOOTING SEQUENCE (CONSTRUCTO 1.5V AND NOVOFIT 1.0 ONLY)
The unit booting sequence is similar to a personal computer booting sequence.
Each time the unit is plugged after being unplugged, or after a power failure, the
unit will perform a 30-second booting sequence before starting to operate. During
the booting sequence, the integrated control LED will light GREEN (unit set in
normal defrost) or AMBER (unit set in extended defrost) for 5 seconds, and then
will shut off for 2 seconds. After that, the LED will light RED for the rest of the
booting sequence. During this RED light phase, the unit is checking and resetting
the motorized damper position. Once the motorized damper position completely
set, the RED light turns off and the booting sequence is done.
NOTE: No command will be taken until the unit is fully booted.
BOOTING SEQUENCE (HRV EKO 1.5 AND ERV EKO 1.5 ONLY)
The unit booting sequence is similar to a personal computer booting sequence.
Each time the unit is plugged after being unplugged, or after a power failure, the
unit will perform a 30-second booting sequence before starting to operate. During the
booting sequence, the integrated control LED will light AMBER for 10 seconds.
After that, the LED will light RED for the rest of the booting sequence. During this
RED light phase, the unit is checking and resetting the motorized damper
position. Once the motorized damper position completely set, the RED light turns
off and the booting sequence is done.
NOTE: No command will be taken until the unit is fully booted.