Hazards may exist within this equipment because it
contains electrical and powerful moving components.
Only qualified service personnel should install or
service this equipment. Untrained personnel can perform
basic maintenance such as maintaining filters.
Observe precautions marked in literature and on
labels attached to unit. Follow all safety codes.
WARNING
Disconnect main power switches to unit before
performing service or maintenance. Electric shock
can cause personal injury or death.
2 Installation
2.1 Inspection
Inspect the exterior of the unit for shipping
damage by ensuring that there is no damage to the
door, door latches, door hinges, damper, duct collars,
cabinet, etc. Inspect the interior of the unit for damage
by ensuring that the fan motors and housings, heat
exchange cores, insulation, dampers, actuators and
drain pans are all intact.
If transportation damage is found, file a claim
immediately with the transportation agency. Remove
all packaging, tape, etc. from the cabinet.
2.2 Mounting Location Requirements
When determining an installation location, the
unit must be mounted in a heated area to prevent
condensate drain lines from freezing. The mounting
location should be away from occupied areas to provide
quiet operation. The area should also be easily accessible
for maintenance.
There are several options for hanging or floor
mounting the unit.
NOTE:
In all cases, the unit must be level. Consult
local building code for restrictions in your area
regarding installation.
Hang the unit with the reinforced rubber straps
provided as shown in Appendix A. Check with local
building codes regarding the use of rubber straps in
commercial buildings. Attach the straps to the unit
with two #8 screws provided. Then attach the other
end of the strap to the ceiling joists, trusses, custom
frame, etc.
The unit can also be hung with 3/8" (10mm)
threaded rod and U channels or angles (not supplied)
as shown in Appendix A.
When installing the unit, keep in mind that access to
the control panel may be required. Supply and exhaust
ducts to outside may have 1" to 2" (25 to 51mm) of
insulation on them. Rubber vibration isolation may
be required and is recommended for quiet operation.
The unit can also be mounted on a metal or wooden
curb (not supplied) bolted to the floor as shown in
Appendix A. Space must be left under the unit to
allow connection of drain lines. A gradual slope is
required for the condensate water to drain by gravity
(minimum 1/4"/foot) (6mm/305mm). If this is not
possible, a pump should be used. If attachment of the
unit to the curb is required, ensure that screws, bolts
and mounting hardware do not interfere with moving
parts or that the integrity of the cabinet insulation is
not affected.
2.4 Ductwork
NOTE:
These Heat Recovery Ventilators have minimum
clearance requirements when mounting. See Appendix B
for specific clearance requirements. Mounting options
must allow 6" (152mm) clearance in front of control
cover for access.
A mounting location close to an exterior partition
will minimize the length of insulated duct. The unit
should be close to a drain and 120 volt, 60 Hz power
supply. The unit should be mounted away from hot
chimneys, electrical panels and other hazards. The
area should also be easily accessible for maintenance.
The supply and exhaust duct connections on the
unit are as follows:
UNITDUCT SIZE
600 cfm/700 cfm14" x 8" (356 x 203mm)
1200 cfm20" x 8" (508 x 203mm)
NOTE:
Duct sizes are for connection purposes only.
Ducts should be sized to keep noise and pressure drop
to a minimum.
Page 3
Page 4
The supply and exhaust ducts connected to
outside, as well as any ducts passing through an
unconditioned space, must have a minimum insulation
value of R5. In addition, a continuous integral vapor
barrier over the duct insulation must be used.
Air balancing dampers are recommended for both
supply and exhaust ducts to allow for adjustment of
airflow. Also, flexible canvas connectors should be
installed close to the unit in the supply duct to the
building and the exhaust duct from the building to
reduce noise transmission from the unit to the
building, see Appendix C.
All ports on the 600 cfm and 1200 cfm units have
1" (25mm) flanges to facilitate the installation of the
ductwork. Please note that the "Fresh Air from
Outside" port has a defrost damper incorporated with it.
Ensure that any mechanical fasteners used to connect
the duct do not interfere with the operation of the
damper. Screws can be installed on the side of the
cabinet rather than the flange for this port only.
For port locations see Appendix B.
All ports on the 700 cfm unit have 2" (51mm)
flanges to facilitate the installation of the ductwork.
Please note the "Fresh Air From Outside" connection
is factory set to be the left side upper port. It is
possible to reverse the operation of the defrost
damper in order to use the port on top of the
cabinet for "Fresh Air From Outside" connection.
To change the "Fresh Air From Outside" from the
side to the top use the following directions. For port
locations see Appendix B.
The duct system should be designed according to
the high speed flow rate of the unit. In order to keep
the noise and pressure drop to a minimum, a maximum
air velocity of 1100 ft/min (5.6 m/sec) should be used
in calculations in duct design. The duct runs should
be kept as short as possible with the minimum
amount of elbows and transitions.
The manufacturer recommends the use of smooth
radius elbows or square elbows with turning vanes to
achieve maximum performance.
2.6 Exterior Hoods
It is important that the fresh air intake hood be
positioned well away from any source of contamination.
The exterior supply and exhaust hoods must be
separated enough to prevent cross-contamination
and at an elevation that will prevent blockage by
snow, dirt and leaves.
NOTE:
Consult local building code for restrictions in
your area.
A rodent screen with 1/4" (6mm) mesh must be
installed to prevent the intake of large debris and
animals. A backdraft damper may need to be
installed in the exhaust duct to prevent cold air entering
the building if the unit is to be shut off for a long
period of time.
To maintain optimum airflow performance,
exterior hood selection must be such that the
minimum free area of opening is as follows:
140 inches
2
(0.09m2).
Remove the cover of the damper motor with a flat
screwdriver. Reverse the Orange and Red wires by
moving the Orange from terminal #2 to terminal #3 and
moving the Red wire from terminal #3 to terminal #2.
The end result in order to have the "Fresh Air From
Outside" connection to the top port will be:
#1 - White, #2 - Red, #3 - Orange.
2.5 Internal Grilles and Diffusers
Locate exhaust grilles and supply diffusers to provide
effective ventilation and avoid short circuiting of airflows.
Adjustable dampers should be provided at every
grille and diffuser location to make balancing of the
system possible.
A proper selection of style and size of grilles and
diffusers is required to minimize pressure drop. The
velocity of the airflow should not exceed 400 ft/min
(2 m/sec) for normal applications.
Page 4
2.7 Drains
The drain fittings provided with the unit will
accept a 3/4" (19mm) NPT coupler (supplied by others).
The drain line for the unit must be fabricated
on-site and connected to the building main. A loop in
the hose or trap in the copper or plastic pipe must be
provided to prevent sewer gases from entering the
unit when connecting to a drain as illustrated in
Appendix D.
NOTE:
Consult local building code for plumbing requirements
in your area. If copper pipe is to be used, ensure not
to solder to the 3/4" (19mm) coupler while it is
attached to the plastic drain fitting as deformation may
occur. Ensure adequate slope is present to allow good
drainage (minimum 1/4" per foot or 6mm per 305mm).
Page 5
2.8 Electrical Connections
Power
A terminal block and strain relief bushing or a
junction box is provided for line voltage to make the
necessary power connections.
The electrical requirements are as follows:
600 cfm700 cfm1200 cfm
The 700 cfm unit is two speed. Low speed can be
initiated by creating a closure across LOW - COM or
high speed can be initiated by creating a closure
across HIGH - COM.
Unit Check points:
___ Power connected, no ventilation call - Both fans
are off, defrost damper (if equipped) closes off
fresh air from outside.
VOLTAGE115V115V115V
MCA8.656.6313.4
MOP12.59.1320
Control Box Access For Low Speed Setting
(600 cfm/1200 cfm only)
Disconnect power to the unit. Remove the four
screws securing the cover plate as shown in
Appendix F. Lift off the control cover plate and
switch the red wire as shown in Appendix F.
3 Controls
3.1 General Information
Fan Interlock Relay Output (FF)
External fan control can be achieved by connecting an
external 24 volts fan control through dry contacts (FF).
These contacts are closed on a call for ventilation or
defrost. See wiring diagram shown in Appendix E-5.
___ Power connected, low speed call - Both fans on
low speed internal defrost damper (if equipped)
opens fresh air from outside. If equipped with
recirculation module, the internal defrost
damper closes recirculation opening.
___ Power connected, high speed call - Both fans on
high speed, defrost damper opens fresh air from
outside. If equipped with recirculation module,
the internal defrost damper closes recirculation
opening.
___ Power connected, occupied timer/sensor connection
open (unoccupied mode) - Both fans are off, defrost
damper closes fresh air from outside. If equipped
with recirculation module, the internal defrost
damper opens recirculation opening.
___ Power connected, FF control contacts close
during unit ventilation or defrost cycle.
3.3 Defrost
Speed Selection (600 cfm/1200 cfm only)
There are three speed settings available with the
controls, only two of which can be functional at any one
time. The units are factory set to use the low and high
speed taps on the blower motors. If necessary, the
medium speed tap can be used instead of the low
speed tap. See Appendix E-2 for instructions on how to
make this change. Units without the remote wall control
option can be shut off by opening the contact
between LOW - COM or HIGH - COM as shown in
Appendix E-2.
3.2 Sequence of Operation
Before start-up, check the unit for obstructive
packaging, objects near or in blowers, dampers, heat
exchangers, etc. Once installation is complete, check all
modes of operation to ensure that the unit is working
properly. Close the doors and check for operation on
LOW, COM and HIGH. Use a wall control or the dry
contact switching to run fan speeds as shown in
Appendix E-2.
The unit functions are controlled by integrated
controls in the unit which may include Exhaust Only
Defrost or Recirculation Defrost (via the recirculation
module - 600 cfm and 1200 cfm units only). In cold
temperatures, defrost cycles will remove frost from
the heat exchanger to maintain good operation.
Exhaust Only Defrost (Optional)
Frost removal occurs when the supply blower
de-energizes, the supply air damper and the core
damper close and the exhaust fan continues to circulate
only warm inside air through the heat recovery core
to maintain ventilation. This process prevents the build
up of ice in the core. Defrost is temperature initiated
at 23°F to -22°F (-5°C to -30°C) and time based.
WARNING
A negative building pressure may develop during
the defrost cycle with possible backdrafting fumes
from combustion equipment.
The Recirculation Defrost Module is only available
with the 600 cfm and 1200 cfm units. The defrost
cycle is electronically controlled in response to the
outside temperature 23°F to -22°F (-5°C to -30°C).
On a call for defrost, the supply air damper in the
recirculation module closes, exhaust fan is de-energized
and the supply fan continues to recirculate warm air
through the heat recovery core. It is possible to extend
the defrost times during very cold weather by removing
the jumper JU1-F on the circuit board as shown in
Appendix F. For dimension and weight changes to
the 600 cfm and 1200 cfm models with recirculation
defrost, see Appendix B-2 and B-4.
3.4 Remote Wall Control (Optional)
Remote mounted wall control options can be used
to control the ventilators from a location remote to
the installed unit location. The connection from the
ventilator to the control is low voltage and requires a
4 conductor (24 ga. minimum) LVT cable. Models
are available with either a dehumidistat control or
gas sensor. The following four options are available.
Slide Switch Type
Dehumidistat to engage high speed exchange.
Slide switch operation supporting continuous low
exchange and continuous high exchange.
Push Button Electronic Type
Dehumidistat to engage high speed exchange.
Push-button operation supporting: intermittent
(stand-by) ventilation, continuous low exchange,
continuous high exchange, maintenance indicator
light and exchange indicator light.
Pool Electronic Type
Ideal for pool dehumidification. Dehumidistat to
engage high speed exchange. Push-button operation
supporting: intermittent (stand-by) ventilation, continuous
low exchange, continuous high exchange, maintenance
indicator light and exchange indicator light.
Pollutant Detector Type
Pollutant monitor to engage low/high exchange.
Push-button operation supporting: intermittent
(stand-by) ventilation, continuous low exchange,
continuous high exchange, maintenance indicator
light and exchange indicator light.
4 Airflow Measurement
and Balancing
Once installation is complete, the supply and
exhaust airflows should be balanced. This will
ensure proper operation and a good quality installation.
A well designed duct system with properly sized
duct runs and equal static pressure losses of both the
supply and exhaust will aid in balancing the unit.
However, it will be necessary to take flow
measurements with the proper equipment to ensure a
balanced system.
Magnehelic gauges and Flow Measuring Stations
(FMS) are available for 14" x 8" (356 x 203mm) or
20" x 8" (508 x 203mm) rectangular duct and a range
of round duct sizes. Please ask your supplier for
more information.
4.1 Flow Station Positions
Whether flow stations are permanently installed or
used temporarily, the position they are placed in is very
important to ensure accuracy as shown in Appendix C.
The best locations for mounting the FMS is in the
long straight sections of ducting where airflow has
stabilized across the area of the duct. This position
will provide the most accurate measurements.
The next best location for the FMS is immediately
before or after a 90 degree elbow and 12" (305mm)
from any damper. In straight sections of pipe,
the FMS should be installed at least 30" (762mm)
from any fan outlet. This applies to the "Supply Air
Opening" connection on the heat recovery ventilator
and the "Exhaust Air Opening" connection.
With airflow measuring stations permanently
installed, balancing is done by measuring airflow on
one side of the heat recovery ventilator and then the
other. Adjustments can then be made to the damper
to equalize airflows.
When using the temporary method, an FMS is
installed in one air duct of the heat recovery
ventilator and the flow recorded. The FMS is then
relocated to the other air duct and the airflow is
recorded again. Dampers can then be adjusted to
equalize airflow. This procedure should be repeated
to ensure that the unit is balanced properly.
Page 6
Page 7
4.2 Balancing Procedure
Before proceeding with balancing, all windows,
overhead doors and walk-in doors should be closed
and exhaust systems should be turned off.
The connections between the flow stations and the
ducts must be sealed with tape. Mount the magnehelic
gauge in a convenient location where it is level and
will not vibrate or be bumped. Zero the gauge.
Measure the exhaust air first as it is often the lowest
due to a longer duct system.
With the fan speed at maximum, connect the hoses
from the FMS to the magnehelic gauge. If the needle falls
below zero, reverse the hose connections. Ensure that
the damper is wide open. Take a reading from the
magnehelic gauge and record it. Remove the FMS
and place it in the supply duct. This process is not
necessary if the FMS is to be permanently mounted.
Repeat the procedure. If the reading is higher in
the supply duct, adjust the damper until the reading
is the same. If the reading is lower, return the FMS
to the exhaust duct and adjust the damper to obtain
the same reading as the supply duct.
5 Maintenance and Service
5.1 Bi-Monthly Maintenance
WARNING
Disconnect power before maintaining unit.
1
1
2
VL0001
600 cfm and 1200 cfm
1. Washable foam filter
2. MEF filter - optional
1 or 2
1
VL0002A
700 cfm
Drain Pans and Interior of Unit
With the filters removed from the unit, the foil
faced insulation surfaces and the drain pans should
be wiped clean with a soft cloth and mild cleaning
solution. Also ensure that the drain fittings are free
from dirt and are draining freely.
5.2 Annual Maintenance
Bi-monthly maintenance should include:
Air Filters
The standard foam filters are washable. Under
normal conditions it is recommended that they be
cleaned every two months. More frequent cleaning
may be required under extremely dirty operating
conditions. Use a vacuum cleaner to remove the
heaviest portion of accumulated dirt, then wash with
warm water.
A medium efficiency filter for the supply air
stream is available from your supplier. This filter
is disposable and should be replaced when it
becomes dirty.
WARNING
Disconnect power before maintaining unit.
Annual service should include:
Air Filters
Vacuum and wash standard foam filters. Replace
medium efficiency filter if present.
Drain Pans and Interior of Unit
Wash the foil faced insulation surfaces and wipe
the drain pans with a soft cloth and mild cleaning
solution. Check the drain fittings to ensure they are
draining freely.
Heat Recovery Core
The heat recovery core must be handled with care.
It is recommended that it be washed once a year
following the season of most intense use, in order to
ensure maximum efficiency of the partitions.
Page 7
Page 8
Allow the heat recovery core to soak for three
hours in warm water and mild soap. Rinse under a
heavy stream of water.
WARNING
Hot water and a strong cleaning agent could
damage the polypropylene core. Ensure the core is
returned to the unit in the correct orientation. Use
the sticker as a guide.
Fans
Blower wheels and fan housing should be checked
for dirt build-up. If they appear dirty, it may be
necessary to remove the blower assembly and then
vacuum the dust out through the fan mouth. See the
following page for instructions on removing the
blower assembly.
System Operation Check
Verification of all control modes should be
checked to ensure proper operation. Refer to the
Controls Section, Sequence of Operation.
Testing and Replacement of the Damper Actuator
Check damper operation by switching between
LOW - COM or HIGH - COM on the dry contact
terminal or by switching through the modes on the
optional remote wall control. If the damper does not
respond in one or both directions, check all connections.
Motor and Blower Removal and Installation
Disconnect power from the unit. To determine if
the fan motor is burned out, disconnect the four-wire
service connector between the motor and cabinet.
Connect the motor directly to a 115 volt power
source with an electrical cable, as follows:
RED + WHITELow speed
BLUE + WHITEMedium speed
BLACK + WHITEHigh speed
If the motor functions normally, there is a problem
with the wiring connections or the main circuit
board. Check all wiring and replace main circuit
board if necessary.
If the blower does not run, it must be replaced. To
replace the motor, remove the heat recovery core
from the unit. Disconnect the four-wire service connector
from the unit. Remove the fasteners holding the
motor assembly in place. Lift the assembly up and
out, using one hand under the motor and one hand to
steady it. Remove the assembly carefully from the
unit to avoid damage to the insulation, shelf, etc.
Install the repaired motor assembly by following
these instructions in reverse.
REMOVE THESE
2 SCREWS
LOCKING PLATE
CAPACITOR
700 cfm ONLY: Check for 24 volt output between the
White/Red and the White/Orange wires at the damper
motor. If 24 volts can be measured at the damper
motor, the problem is either in the connections, the
defrost relay or the main circuit board.
600/1200 cfm ONLY: (CAUTION: 120VAC) Check
for 120 volt output across the White/Black wires. If
120 volt can be measured at the motor, replace the
motor. If 120 volt cannot be measured at the motor,
check pins J1-9 at the printed circuit board.
Main Circuit Board Replacement
The main circuit board must be replaced if an
electronic problem arises. For example, the unit
suddenly stops, the unit stays in defrost all of the
time or if control functions are not working properly.
Ensure that power is reaching the board. Test the
blower motors and damper actuators for operation
when directly connected to the appropriate power
voltage. If the motor and damper actuators function
normally, replace the main circuit board.
VD0004A
600 cfm and 1200 cfm
THUMBSCREW
SERVICE CONNECTOR
VD0001A
700 cfm
Page 8
Page 9
Space must be left to allow connection
of drain lines with adequate slope for drainage
Wooden Curb (Supplied by others)
Bolt to Floor
Rubber Vibration Isolator
(Supplied by others)
U Channel
(Supplied by others)
3/8" (10mm)
Threaded Rod
(Supplied by others)
NOTE:
Diagrams show standard unit configuration.
For units with the reversed door option, the
door will be located here.
Reinforced
Rubber Strap
VD0002A
Mounting Diagrams
600 cfm and 1200 cfm
Recirculation Module
(Factory Installed)
Recirculation Module
(Factory Installed)
Appendix A
Recirculation Module
(Factory Installed)
Dry Contacts
VD0003A
3/8" (10mm)
Threaded Rod
(Supplied by others)
Cabinet Mounted
U Channel
Rubber Vibration
Isolater
700 cfm
Dry Contacts
Page 9
Bolt to Floor
Wooden Curb
(Supplied by others)
Space must be left to allow
connection of drain lines with
adequate slope for drainage
Page 10
Appendix B
Unit Dimensions
B-1: 600 cfm (without recirculation module)
Kg
20.00
13.00
26.72
17.30
LBS
44.21
28.67
58.92
38.21
A
B
C
D
PTS
HRV600i ALUMINUM CORE
Kg
11.32
17.45
23.26
15.08
LBS
38.49
24.96
51.29
33.26
Direction of airflow
Center of gravity
Dimensions in [ ] are in millimeters
NOTES:
HRV600i POLY CORE
PTS
A
B
C
D
B
77.11
170.00
TOTAL
67.13
148.00
TOTAL
3/4" NPT
CONNECTION SIZES
CONNECTION TABLE
14 Gauge wire nut
Condensate drain fitting (2x)
A
B
D
6.500"
[597]
14.000"
23.500"
LOCATION
STRAP MOUNTING
[165]
[356]
[70]
2.750"
[203]
8.000"
OPENING
OUTDOOR AIR
[622]
24.500"
OUTDOOR AIR
[203]
8.000"
OPENING
RETURN AIR
[102]
4.000"
RETURN AIR
[358]
14.103"
[196]
7.705"
[130]
5.125"
RIGHT SIDE
DRAIN LINE FITTING
A
[305]
12.005"
[864]
TOP
[340]
13.375"
C
34.000"
A
[149]
5.859"
[711]
28.005"
4.000"
LINE POWER
[102]
4.028"
[356]
14.000"
[102]
EXHAUST AIR
EXHAUST AIR
[203]
8.000"
OPENING
[102]
4.000"
SUPPLY AIR
LOW VOLTAGE
TERMINAL STRIPS
SUPPLY AIR
[203]
8.000"
OPENING
[488]
19.207"
NOTE: FOR UNITS WITH THE REVERSED DOOR OPTION,
INTERIOR COMPONENTS WILL APPEAR AS A MIRROR
IMAGE OF THE ABOVE DIAGRAM.
CONTROL BOX
ACCESS
[254]
10.005"
B
[90]
3.535"
OPTION
REVERSE DOOR
FRONT
LEFT SIDE
A MINIMUM OF 15.000" [381] CLEARANCE FROM ANY OBSTRUCTION IS REQUIRED FOR
REMOVAL OF HEAT RECOVERY CORES, FANS, ETC.
THE ACCESS DOOR CAN BE REMOVED FROM CABINET WITH ONLY 2.000" [51] OF CLEARANCE.
ACCESS DOOR
A MINIMUM OF 12.000" [305] CLEARANCE FROM ANY OBSTRUCTION
IS REQUIRED FOR REMOVAL OF CONTROL BOX.
NOTE: THIS MODEL HAS A DAMPER LOCATED ON THE OUTDOOR INTAKE CONNECTION. THIS DAMPER WILL CLOSE DURING A DEFROST CYCLE OR WHEN THE UNIT IS PLACED IN THE 'OFF' POSITION WITH POWER MAINTAINED TO THE UNIT.
THIS DAMPER IS NOT DESIGNED AS A BACKDRAFT DAMPER AND WILL REMAIN OPEN IF POWER IS DISCONNECTED FROM THE UNIT FOR ANY REASON.
HEAT RECOVERY CORE
CONTROL PLATE
REVERSED DOOR OPTION
[381]
15.000"
[305]
12.000"
VK0001A
Page 10
Page 11
Appendix B Continued
Unit Dimensions
B-2: 600 cfm with recirculation module (factory installed)
Kg
231105
LBS
[180]
7.10"
with recirculation module
PTS
HRV 600i ALUMINUM CORE
TOTAL
Kg
90
[356]
14.00"
197
LBS
HRV 600i POLY CORE
PTS
with recirculation module
NOTE: Dimensions in [ ] are millimetres.
TOTAL
Location
Strap Mounting
[203]
8.00"
Fresh Air
From Outside
4.00"
[102]
8.00"
Exhaust Air
[203]
From Building
[44]
1.75"
[358]
14.10"
Access Door
Drain Fitting
Reversed Door Option
[381]
15.00"
49.550" [1259]
2.75" [70]
28.12" [714]
14.00" [356]
Line Power
Dry Contacts
To Outside
Exhaust Air
Fresh Air
To Building
A minimum of 15.00" [381] clearance from any obstruction is required for removal
of heat recovery cores, fans, etc.
5.125" [130]
19.207" [488]
NOTE:
For units with the reversed door option, interior components will appear
as a mirror image of the above diagram.
Control Box
Reverse Door Option
The access door can be removed from cabinet with only 2.00" [51] of clearance.
A minimum of 6.00" [152] clearance from any obstruction
is required for removal of control box.
Access Door
Heat Recovery Core
[305]
12.00"
1.75" [44]
4.00" [102]
8.00"
[203]
4.00"
[102]
[622]
24.50"
8.00"
[203]
3.53"
[90]
Page 11
Control Plate
VK0004A
Page 12
Kg
27.40
19.77
27.40
LBS
60.41
43.59
60.41
A
B
C
PTS
HRV1200i ALUMINUM CORE
Kg
24.50
17.68
24.50
LBS
54.02
38.98
54.02
Direction of airflow
Center of gravity
NOTES:
Dimensions in [ ] are in millimeters
HRV1200i POLY CORE
PTS
A
B
C
19.77
43.59
D
17.68
38.98
D
94.34
208.00
TOTAL
84.36
186.00
TOTAL
Appendix B Continued
Unit Dimensions
B-3: 1200 cfm (without recirculation module)
[622]
24.500"
[203]
8.000"
EXHAUST AIR
FROM BUILDING
[102]
4.000"
[508]
20.000"
DRAIN FITTING
ACCESS DOOR
RIGHT SIDE
3/4" mpt
CONNECTION SIZES
CONNECTION TABLE
14 GAUGE WIRE NUT
CONDENSATE DRAIN FITTING (2X)
A
B
[251]
9.878"
[508]
20.000"
[279]
11.000"
STRAP MOUNT
LOCATION
[203]
8.000"
FRESH AIR
FROM OUTSIDE
[70]
2.750"
REVERSED DOOR OPTION
[381]
15.000"
[102]
RETURN AIR
SUPPLY AIR
LOW VOLTAGE
TERMINAL STRIPS
[130]
5.125"
[488]
19.207"
NOTE: FOR UNITS WITH THE REVERSED DOOR OPTION,
INTERIOR COMPONENTS WILL APPEAR AS A MIRROR
IMAGE OF THE ABOVE DIAGRAM.
CONTROL BOX
ACCESS
[288]
11.325"
FRONT VIEW
A MINIMUM OF 15.000" [381] CLEARANCE FROM ANY OBSTRUCTION IS REQUIRED FOR REMOVAL
OF HEAT RECOVERY CORES, FANS, ETC.
THE ACCESS DOOR CAN BE REMOVED FROM CABINET WITH ONLY 2.000" [51] OF CLEARANCE.
ACCESS DOOR
A MINIMUM OF 12.000" [305] CLEARANCE FROM ANY OBSTRUCTION
IS REQUIRED FOR REMOVAL OF CONTROL BOX.
HEAT RECOVERY CORE
[305]
12.000"
OUTDOOR AIR
B
A
[524]
20.620"
D
[864]
34.000"
TOP
[362]
14.250"
C
EXHAUST AIR
LINE POWER
A
[145]
5.715"
4.028"
[1047]
41.206"
[1024]
40.326"
[508]
20.000"
[254]
10.000"
TO OUTSIDE
EXHAUST AIR
[203]
8.000"
Page 12
FRESH AIR
[102]
4.000"
TO BUILDING
B
LEFT SIDE
OPTION
REVERSE DOOR
NOTE: THIS MODEL HAS A DAMPER LOCATED ON THE OUTDOOR INTAKE CONNECTION. THIS DAMPER WILL CLOSE DURING A DEFROST CYCLE OR WHEN THE UNIT IS PLACED IN THE 'OFF' POSITION WITH POWER MAINTAINED TO THE UNIT.
THIS DAMPER IS NOT DESIGNED AS A BACKDRAFT DAMPER AND WILL REMAIN OPEN IF POWER IS DISCONNECTED FROM THE UNIT FOR ANY REASON.
CONTROL COVER
VK0034A
Page 13
Appendix B Continued
Unit Dimensions
B-4: 1200 cfm with recirculation module (factory installed)
Kg
10.000"
269122
LBS
avec module recirc.
VRC 1200i NOYAU ALU
PTS
TOTAL
20.000"
Kg
112
247
LBS
avec module recirc.
PTS
VRC 1200i NOYAU POLY
TOTAL
[254]
[508]
[203]
8.00"
d’air frais
Aspiration
4.00"
[102]
[203]
8.00"
d’air vicié
Évacuation
NOTE: Les dimensions entre [ ] sont en millimètres.
Localisation de la
courroie de fixation
[44]
1.75"
[508]
20.000"
Porte d’accès
5.125" [130]
Raccord de drain
Option de porte inversée
[381]
15.00"
Un dégagement minimum de 15.00" [381] est requis pour retirer les noyaux de
récupération, les ventilateurs, etc.
La porte d’accès peut être retirée du cabinet avec seulement 2.00" [51 ]de dégagement.
Noyau de
de chaleur
récupération
49.550" [1259]
2.75" [70]
[508]
20.00"
41.24" [1047]
[254]
10.00"
Borniers
Alimentation
électrique
vicié
Sortie d’air
Entrée
d’air frais
[488]
19.207"
NOTE:
Pour les appareils munis de l’option de porte inversée, les pièces
intérieures apparaîtront à l’inverse du dessin ci-dessus (image miroir).
Boîtier
électronique
Option de porte inversée
Porte d’accès
[305]
12.00"
Un dégagement minimum de 12.00" [305] est requis pour
retirer le boîtier électronique.
boîtier
Couvercle du
VK0003F
1.75"
[44]
8.00"
[203]
[102]
4.00"
24.50"
[622]
8.00"
[203]
3.53"
[90]
Page 13
Page 14
3/4" mpt
CONNECTION SIZES
Appendix B Continued
Unit Dimensions
B-5: 700 cfm
[48]
[203]
1.875"
8.000"
[273]
10.750"
7.500"
8.000" [203]
[191]
[527]
CONNECTION TABLE
LBSKg
32.7414.85
68.4631.05
35.2015.97
A
PTS
10.000"
B
[254]
C
73.6033.38
210.00
D
TOTAL95.25
22.500"
14 gauge wire nut
A
[572]
HRV700i
Center of gravity
Direction of airflow
Dimensions in [ ] are in millimeters
NOTES:
TOP
AB
CD
20.750"
Condensate drain fitting (2x)
B
2.000"
[1194]
47.000"
DEFROST AIR
OPENING
[203]
8.000"
[51]
A
OPENING
EXHAUST AIR
EXHAUST
AIR
2.157"
Line Voltage In
[940]
37.000"
[55]
SUPPLY AIR
SUPPLY
OPENING
12.104"
AIR
[307]
[269]
10.605"
Low Voltage
Terminal Strips
[628]
24.736"
RIGHT SIDEFRONT
A minimum of 12.00" [305] clearance from any
obstruction is required for power hook-up, low
voltage remote connection, and control panel access.
[533]
21.000"
A minimum of 21.00" [533] clearance from any obstruction
is required for removal of heat recovery cores, fans, etc.
The access door can be removed from cabinet with only 2.00" [51] of clearance.
[789]
31.080"
[1295]
51.000"
HEAT RECOVERY CORE
ACCESS DOOR
[356]
14.000"
[92]
3.625"
[51]
2.000"
[48]
1.875"
[95]
3.750"
2.000"
OUTDOOR AIR
OPENING
OUTDOOR AIR
[203]
8.000"
12.250"
Page 14
[51]
[311]
40.500"
RETURN AIR
8.000"
[1029]
RETURN AIR
OPENING
[203]
B
15.250"
CONDENSATE DRAIN
[387]
LEFT SIDE
VK0002A
Page 15
Appendix C
Flow Station Positions
600 cfm and 1200 cfm
VP0001A
Min. 12"
(305mm)
Balancing Damper
Flow Measuring Station (FMS)
Min. 30"
(762mm)
Canvas Vibration Isolator
Reverse Door Option
Min. 8" (203mm)
(Optional) Canvas Vibration Isolator
Fresh Air
From Outside
Exhaust Air
From Building
Min. 12"
(305mm)
VP0002A
Min.12"
(304mm)
Flow Measuring
Station (FMS)
Canvas Vibration Isolator
700 cfm
Dry Contacts
Min. 30"
(762mm)
Balancing Damper
(not supplied)
Min. 12"
(304mm)
Page 15
Page 16
Appendix D
Drain Connections
600 cfm and 1200 cfm
Note:
All hose, pipe &
couplers to be
supplied by others
3/4"NPT
Coupler
Plastic Hose
Water Trap
700 cfm
Plastic Drain Fittings
To Drain
Copper or
Plastic Pipe
To Drain
3/4" NPT
Coupler
Plastic Hose
Water Trap
Plastic Drain Fitting
Note:
All hose, pipe,
and couplers to be
supplied by others.
To Drain
Copper or
Plastic Pipe
Page 16
Page 17
Appendix E
Terminal Control Diagrams
E-1: Terminal Label
A low voltage remote control wiring interface is
provided on the unit. The connections for the low
voltage remote wiring are located on two terminals
adjacent to the exhaust fan outlet (or adjacent to the
supply fan outlet on the 700 cfm unit). All field
installed wiring must be low voltage class II.
Remote Wall Control
Optional wall control requires a 4 wire LVT-24
gauge (or equivalent). This remote wall control runs
on 12 VDC.
Low Voltage Controls
All other terminals are dry contacts.
Low Voltage terminal control consists of the following:
Wall Control
4 wire LVT 24 gauge minimum
Occupied (Night set back) Timer/Sensor
24 VAC, needs dry contact
E-2: Wall Control Connection
Four types of remote wall controls are available:
1. Slide Switch Wall Control with fan switch and
dehumidistat control
2. Push Button Electronic Wall Control with fan
mode selection, dehumidistat control and
maintenance indicator
3. Pollutant Wall Control with fan mode selection
and air pollutant sensor/control
4. Pool Wall Control with fan mode selection,
dehumidistat control and high speed
recirculation mode.
The remote wall controls work with the microprocessor electronic control within the unit to
control ventilation sequences. Each wall control has
different features and require 4-wire connection to
the unit as shown below. Without the wall control,
fans can be operated with a remote fan switch as
shown in Appendix E-4.
LOW - COM - HIGH
Remote fan switching requires a single pole, double
throw switch (SPDT)
Fan Interlock Relay Output (FF)
Dry contact closes on ventilation or defrost. Used
to control external fan.
VE0002A
WALL CONTROL
Black
Red
OCCUPIED
TIMER/
SENSOR
F
F
CLASS 2 VOLTAGE
NOTE:
Connections are all dry
contacts except wall control
and 24VAC power supply.
Use of 24VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
Green
Yellow
LOW
COMMON
HIGH
NOTE:
An occupied timer or sensor device cannot be used
with the push button pool or pollutant wall controls.
JUMPER
VE0006A
WALL CONTROL
Black
Red
OCCUPIED
TIMER/
SENSOR
F
F
CLASS 2 VOLTAGE
NOTE:
Connections are all dry
contacts except wall control
and 24VAC power supply.
Use of 24VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
Green
Yellow
LOW
COMMON
HIGH
Wall
Control
Page 17
Page 18
Appendix E Continued
Terminal Control Diagrams
E-3: Occupied Timer/Sensor Connection
Occupancy control is achieved by connection to
the terminal interface shown below. These terminals
require a dry contact which could be provided by a
number of types of controls such as a timer, light
sensor, occupancy sensor, building management
system, or other. The unit will not operate unless
these contacts are closed!!
The illustration below shows a factory installed
jumper and programmable timer option.
NOTE:
An occupied timer or sensor device cannot be used
with the push button or pollutant wall controls.
OCC. CONTROL
(field installed)
WALL CONTROL
Black
Red
OCCUPIED
TIMER/
SENSOR
F
F
CLASS 2 VOLTAGE
NOTE:
Connections are all dry
contacts except wall control
and 24VAC power supply.
Use of 24VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
Green
Yellow
LOW
COMMON
HIGH
(factory installed)
Black
Red
JUMPER
NOTE:
Connections are all dry
contacts except wall control
and 24VAC power supply.
Use of 24VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
VE0003A
JUMPER
WALL CONTROL
OCCUPIED
TIMER/
SENSOR
F
F
CLASS 2 VOLTAGE
LOW
COMMON
HIGH
Green
Yellow
NSB Timer
Venmar PN 1604128
1M2345
24 (-) VAC
24 (+) VAC
E-4: Remote Fan Control
Remote fan control can be achieved by connecting
dry contact controls to the terminal interface at
terminals labeled: LOW - COM - HIGH. These
controls could be the following: SPDT switch,
dehumidistat, CO
sensor, light sensor, timer,
2
building management system, etc. The illustration
below represents a switch connected to the unit.
JUMPER
VE0005A
WALL CONTROL
Black
Red
OCCUPIED
TIMER/
SENSOR
F
F
CLASS 2 VOLTAGE
NOTE:
Connections are all dry
contacts except wall control
and 24VAC power supply.
Use of 24VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
LOW
COMMON
HIGH
Green
Yellow
FAN
REMOTE
SWITCH
LOWHIGH
FOUR
WIRES
TWO WIRES
heating only
FURNACE
24-VOLT
TERMINAL BLOCK
VE0010A
W
R
G
C
Y
W R G
Y
THERMOSTAT
TERMINALS
TWO WIRES
E-5: Fan Interlock Wiring Diagrams
W
W
R
R
G
C
Y
Y
*FURNACE INTERLOCK RELAY, PART # 12658
HR V CONTROL CONNECTOR
J3
I OC OL Y R G BF F
COOLING SYSTEM
987654321
Page 18
4 WIRES
2 WIRES
heating only
FURNACE
24-VOLT
TERMINAL BLOCK
VE0009A
Unit Control Module
THERMOSTAT
G
R
Y
TERMINAL
wiring
nuts
RED
GREEN
BLUE
*FURNACE INTERLOCK
2 WIRES
J1
GRAYBROWN
NCNO
COM
RELAY
COOLING SYSTEM
9-PIN AMP PLUG
7
124
7
568
93
Page 19
VE0001A
Appendix F
Electrical Connection Diagrams
Control Box Assembly 600 cfm and 1200 cfm
Remote control access plate
Remote wiring terminal block
Control box
HRV Cabinet
Control cover plate
Low Speed Setting Wire Connections 600 cfm and 1200 cfm
12 pin
2 pin
LOW SPEED SETTING
To change the minimum speed setting from
Low To Medium, move the fork connector:
from here
OL
OC
FF1 YRGB
to here
J3
7
9
Low Speed (Red)
Med Speed (Blue)
Remove power
before installing
or removing
JU1-F Extended
Defrost Jumper
VE0004A
ed
R
ABCDEFG
JU1
1J2J4
4
321
6
Page 19
Page 20
Appendix G
Make-up Heat Requirements
600 cfm and 700 cfm
1200 cfm
and Cp = .24 Btu/lbm°F
and Cp = 1.0 KJ/Kg°C
3
3
Desired Air TemperatureDesired Air TemperatureDesired Air TemperatureDesired Air TemperatureDesired Air Temperature
13.35 lb/ft
standard air at: 1.2 Kg/m
The data does not reflect a reduction in effectiveness due to frosting. Based on the
Although the 600 cfm, 700 cfm and 1200 cfm models have good efficiencies, the supply air could be colder than the ambient room air. It is possible to eliminate the
discomfort associated with this temperature difference by installing an electric duct heater. This will temper the air before it is distributed throughout the building.
NOTE:
The table below gives the heating requirements at different temperatures and airflows.
OUTDOOR AIR -40°F (- 40°C)OUTDOOR AIR -22°F (-30°C)OUTDOOR AIR -4°F (-20°C)OUTDOOR AIR +14°F (-10°C)OUTDOOR AIR +32°F (0°C)