Venmar 600 cfm, 1200 cfm, 700 cfm User Manual

Light Commercial
Heat Recovery Ventilators
Installation, Operation and Service Instructions
VB0002
VB0003
600 cfm 700 cfm
VB0001
1200 cfm
Contents
1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Installation
2.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Mounting Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.3 Mounting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.4 Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.5 Internal Grilles and Diffusers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.6 Exterior Hoods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.7 Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.8 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.3 Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.4 Remote Wall Control (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Airflow Measurement and Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.1 Flow Station Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.2 Balancing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Maintenance and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.1 Bi-Monthly Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.2 Annual Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Appendix A - Mounting Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Appendix B - Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Appendix C - Flow Station Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Appendix D - Drain Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Appendix E - Terminal Control Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Appendix F - Electrical Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Appendix G - Make-up Heat Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Appendix H - Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Appendix I - Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Page 2
1 Safety Considerations
2.3 Mounting Options
Hazards may exist within this equipment because it contains electrical and powerful moving components. Only qualified service personnel should install or service this equipment. Untrained personnel can perform basic maintenance such as maintaining filters. Observe precautions marked in literature and on labels attached to unit. Follow all safety codes.
WARNING
Disconnect main power switches to unit before performing service or maintenance. Electric shock can cause personal injury or death.
2 Installation
2.1 Inspection
Inspect the exterior of the unit for shipping damage by ensuring that there is no damage to the door, door latches, door hinges, damper, duct collars, cabinet, etc. Inspect the interior of the unit for damage by ensuring that the fan motors and housings, heat exchange cores, insulation, dampers, actuators and drain pans are all intact.
If transportation damage is found, file a claim immediately with the transportation agency. Remove all packaging, tape, etc. from the cabinet.
2.2 Mounting Location Requirements
When determining an installation location, the unit must be mounted in a heated area to prevent condensate drain lines from freezing. The mounting location should be away from occupied areas to provide quiet operation. The area should also be easily accessible for maintenance.
There are several options for hanging or floor
mounting the unit.
NOTE:
In all cases, the unit must be level. Consult local building code for restrictions in your area regarding installation.
Hang the unit with the reinforced rubber straps provided as shown in Appendix A. Check with local building codes regarding the use of rubber straps in commercial buildings. Attach the straps to the unit with two #8 screws provided. Then attach the other end of the strap to the ceiling joists, trusses, custom frame, etc.
The unit can also be hung with 3/8" (10mm) threaded rod and U channels or angles (not supplied) as shown in Appendix A.
When installing the unit, keep in mind that access to the control panel may be required. Supply and exhaust ducts to outside may have 1" to 2" (25 to 51mm) of insulation on them. Rubber vibration isolation may be required and is recommended for quiet operation.
The unit can also be mounted on a metal or wooden curb (not supplied) bolted to the floor as shown in Appendix A. Space must be left under the unit to allow connection of drain lines. A gradual slope is required for the condensate water to drain by gravity (minimum 1/4"/foot) (6mm/305mm). If this is not possible, a pump should be used. If attachment of the unit to the curb is required, ensure that screws, bolts and mounting hardware do not interfere with moving parts or that the integrity of the cabinet insulation is not affected.
2.4 Ductwork
NOTE:
These Heat Recovery Ventilators have minimum clearance requirements when mounting. See Appendix B for specific clearance requirements. Mounting options must allow 6" (152mm) clearance in front of control cover for access.
A mounting location close to an exterior partition will minimize the length of insulated duct. The unit should be close to a drain and 120 volt, 60 Hz power supply. The unit should be mounted away from hot chimneys, electrical panels and other hazards. The area should also be easily accessible for maintenance.
The supply and exhaust duct connections on the
unit are as follows:
UNIT DUCT SIZE
600 cfm/700 cfm 14" x 8" (356 x 203mm)
1200 cfm 20" x 8" (508 x 203mm)
NOTE:
Duct sizes are for connection purposes only. Ducts should be sized to keep noise and pressure drop to a minimum.
Page 3
The supply and exhaust ducts connected to outside, as well as any ducts passing through an unconditioned space, must have a minimum insulation value of R5. In addition, a continuous integral vapor barrier over the duct insulation must be used.
Air balancing dampers are recommended for both supply and exhaust ducts to allow for adjustment of airflow. Also, flexible canvas connectors should be installed close to the unit in the supply duct to the building and the exhaust duct from the building to reduce noise transmission from the unit to the building, see Appendix C.
All ports on the 600 cfm and 1200 cfm units have 1" (25mm) flanges to facilitate the installation of the ductwork. Please note that the "Fresh Air from Outside" port has a defrost damper incorporated with it. Ensure that any mechanical fasteners used to connect the duct do not interfere with the operation of the damper. Screws can be installed on the side of the
cabinet rather than the flange for this port only.
For port locations see Appendix B.
All ports on the 700 cfm unit have 2" (51mm) flanges to facilitate the installation of the ductwork. Please note the "Fresh Air From Outside" connection is factory set to be the left side upper port. It is possible to reverse the operation of the defrost damper in order to use the port on top of the cabinet for "Fresh Air From Outside" connection.
To change the "Fresh Air From Outside" from the side to the top use the following directions. For port locations see Appendix B.
The duct system should be designed according to the high speed flow rate of the unit. In order to keep the noise and pressure drop to a minimum, a maximum air velocity of 1100 ft/min (5.6 m/sec) should be used in calculations in duct design. The duct runs should be kept as short as possible with the minimum amount of elbows and transitions.
The manufacturer recommends the use of smooth radius elbows or square elbows with turning vanes to achieve maximum performance.
2.6 Exterior Hoods
It is important that the fresh air intake hood be positioned well away from any source of contamination. The exterior supply and exhaust hoods must be separated enough to prevent cross-contamination and at an elevation that will prevent blockage by snow, dirt and leaves.
NOTE:
Consult local building code for restrictions in your area.
A rodent screen with 1/4" (6mm) mesh must be installed to prevent the intake of large debris and animals. A backdraft damper may need to be installed in the exhaust duct to prevent cold air entering the building if the unit is to be shut off for a long period of time.
To maintain optimum airflow performance, exterior hood selection must be such that the minimum free area of opening is as follows: 140 inches
2
(0.09m2).
Remove the cover of the damper motor with a flat screwdriver. Reverse the Orange and Red wires by moving the Orange from terminal #2 to terminal #3 and moving the Red wire from terminal #3 to terminal #2. The end result in order to have the "Fresh Air From Outside" connection to the top port will be: #1 - White, #2 - Red, #3 - Orange.
2.5 Internal Grilles and Diffusers
Locate exhaust grilles and supply diffusers to provide effective ventilation and avoid short circuiting of airflows. Adjustable dampers should be provided at every grille and diffuser location to make balancing of the system possible.
A proper selection of style and size of grilles and diffusers is required to minimize pressure drop. The velocity of the airflow should not exceed 400 ft/min (2 m/sec) for normal applications.
Page 4
2.7 Drains
The drain fittings provided with the unit will accept a 3/4" (19mm) NPT coupler (supplied by others). The drain line for the unit must be fabricated on-site and connected to the building main. A loop in the hose or trap in the copper or plastic pipe must be provided to prevent sewer gases from entering the unit when connecting to a drain as illustrated in Appendix D.
NOTE:
Consult local building code for plumbing requirements in your area. If copper pipe is to be used, ensure not to solder to the 3/4" (19mm) coupler while it is attached to the plastic drain fitting as deformation may occur. Ensure adequate slope is present to allow good drainage (minimum 1/4" per foot or 6mm per 305mm).
2.8 Electrical Connections
Power
A terminal block and strain relief bushing or a junction box is provided for line voltage to make the necessary power connections.
The electrical requirements are as follows:
600 cfm 700 cfm 1200 cfm
The 700 cfm unit is two speed. Low speed can be initiated by creating a closure across LOW - COM or high speed can be initiated by creating a closure across HIGH - COM.
Unit Check points:
___ Power connected, no ventilation call - Both fans
are off, defrost damper (if equipped) closes off fresh air from outside.
VOLTAGE 115V 115V 115V MCA 8.65 6.63 13.4 MOP 12.5 9.13 20
Control Box Access For Low Speed Setting (600 cfm/1200 cfm only)
Disconnect power to the unit. Remove the four screws securing the cover plate as shown in Appendix F. Lift off the control cover plate and switch the red wire as shown in Appendix F.
3 Controls
3.1 General Information
Fan Interlock Relay Output (FF)
External fan control can be achieved by connecting an external 24 volts fan control through dry contacts (FF). These contacts are closed on a call for ventilation or defrost. See wiring diagram shown in Appendix E-5.
___ Power connected, low speed call - Both fans on
low speed internal defrost damper (if equipped) opens fresh air from outside. If equipped with recirculation module, the internal defrost damper closes recirculation opening.
___ Power connected, high speed call - Both fans on
high speed, defrost damper opens fresh air from outside. If equipped with recirculation module, the internal defrost damper closes recirculation opening.
___ Power connected, occupied timer/sensor connection
open (unoccupied mode) - Both fans are off, defrost damper closes fresh air from outside. If equipped with recirculation module, the internal defrost damper opens recirculation opening.
___ Power connected, FF control contacts close
during unit ventilation or defrost cycle.
3.3 Defrost
Speed Selection (600 cfm/1200 cfm only)
There are three speed settings available with the controls, only two of which can be functional at any one time. The units are factory set to use the low and high speed taps on the blower motors. If necessary, the medium speed tap can be used instead of the low speed tap. See Appendix E-2 for instructions on how to make this change. Units without the remote wall control option can be shut off by opening the contact between LOW - COM or HIGH - COM as shown in Appendix E-2.
3.2 Sequence of Operation
Before start-up, check the unit for obstructive packaging, objects near or in blowers, dampers, heat exchangers, etc. Once installation is complete, check all modes of operation to ensure that the unit is working properly. Close the doors and check for operation on LOW, COM and HIGH. Use a wall control or the dry contact switching to run fan speeds as shown in Appendix E-2.
The unit functions are controlled by integrated controls in the unit which may include Exhaust Only Defrost or Recirculation Defrost (via the recirculation module - 600 cfm and 1200 cfm units only). In cold temperatures, defrost cycles will remove frost from the heat exchanger to maintain good operation.
Exhaust Only Defrost (Optional)
Frost removal occurs when the supply blower de-energizes, the supply air damper and the core damper close and the exhaust fan continues to circulate only warm inside air through the heat recovery core to maintain ventilation. This process prevents the build up of ice in the core. Defrost is temperature initiated at 23°F to -22°F (-5°C to -30°C) and time based.
WARNING
A negative building pressure may develop during the defrost cycle with possible backdrafting fumes from combustion equipment.
Page 5
Recirculation Defrost Module (Optional - Factory Installed)
The Recirculation Defrost Module is only available with the 600 cfm and 1200 cfm units. The defrost cycle is electronically controlled in response to the outside temperature 23°F to -22°F (-5°C to -30°C). On a call for defrost, the supply air damper in the recirculation module closes, exhaust fan is de-energized and the supply fan continues to recirculate warm air through the heat recovery core. It is possible to extend the defrost times during very cold weather by removing the jumper JU1-F on the circuit board as shown in Appendix F. For dimension and weight changes to the 600 cfm and 1200 cfm models with recirculation defrost, see Appendix B-2 and B-4.
3.4 Remote Wall Control (Optional)
Remote mounted wall control options can be used to control the ventilators from a location remote to the installed unit location. The connection from the ventilator to the control is low voltage and requires a 4 conductor (24 ga. minimum) LVT cable. Models are available with either a dehumidistat control or gas sensor. The following four options are available.
Slide Switch Type
Dehumidistat to engage high speed exchange. Slide switch operation supporting continuous low exchange and continuous high exchange.
Push Button Electronic Type
Dehumidistat to engage high speed exchange. Push-button operation supporting: intermittent (stand-by) ventilation, continuous low exchange, continuous high exchange, maintenance indicator light and exchange indicator light.
Pool Electronic Type
Ideal for pool dehumidification. Dehumidistat to engage high speed exchange. Push-button operation supporting: intermittent (stand-by) ventilation, continuous low exchange, continuous high exchange, maintenance indicator light and exchange indicator light.
Pollutant Detector Type
Pollutant monitor to engage low/high exchange. Push-button operation supporting: intermittent (stand-by) ventilation, continuous low exchange, continuous high exchange, maintenance indicator light and exchange indicator light.
4 Airflow Measurement
and Balancing
Once installation is complete, the supply and exhaust airflows should be balanced. This will ensure proper operation and a good quality installation.
A well designed duct system with properly sized duct runs and equal static pressure losses of both the supply and exhaust will aid in balancing the unit. However, it will be necessary to take flow measurements with the proper equipment to ensure a balanced system.
Magnehelic gauges and Flow Measuring Stations (FMS) are available for 14" x 8" (356 x 203mm) or 20" x 8" (508 x 203mm) rectangular duct and a range of round duct sizes. Please ask your supplier for more information.
4.1 Flow Station Positions
Whether flow stations are permanently installed or used temporarily, the position they are placed in is very important to ensure accuracy as shown in Appendix C. The best locations for mounting the FMS is in the long straight sections of ducting where airflow has stabilized across the area of the duct. This position will provide the most accurate measurements.
The next best location for the FMS is immediately before or after a 90 degree elbow and 12" (305mm) from any damper. In straight sections of pipe, the FMS should be installed at least 30" (762mm) from any fan outlet. This applies to the "Supply Air Opening" connection on the heat recovery ventilator and the "Exhaust Air Opening" connection.
With airflow measuring stations permanently installed, balancing is done by measuring airflow on one side of the heat recovery ventilator and then the other. Adjustments can then be made to the damper to equalize airflows.
When using the temporary method, an FMS is installed in one air duct of the heat recovery ventilator and the flow recorded. The FMS is then relocated to the other air duct and the airflow is recorded again. Dampers can then be adjusted to equalize airflow. This procedure should be repeated to ensure that the unit is balanced properly.
Page 6
4.2 Balancing Procedure
Before proceeding with balancing, all windows, overhead doors and walk-in doors should be closed and exhaust systems should be turned off.
The connections between the flow stations and the ducts must be sealed with tape. Mount the magnehelic gauge in a convenient location where it is level and will not vibrate or be bumped. Zero the gauge. Measure the exhaust air first as it is often the lowest due to a longer duct system.
With the fan speed at maximum, connect the hoses from the FMS to the magnehelic gauge. If the needle falls below zero, reverse the hose connections. Ensure that the damper is wide open. Take a reading from the magnehelic gauge and record it. Remove the FMS and place it in the supply duct. This process is not necessary if the FMS is to be permanently mounted.
Repeat the procedure. If the reading is higher in the supply duct, adjust the damper until the reading is the same. If the reading is lower, return the FMS to the exhaust duct and adjust the damper to obtain the same reading as the supply duct.
5 Maintenance and Service
5.1 Bi-Monthly Maintenance
WARNING
Disconnect power before maintaining unit.
1
1
2
VL0001
600 cfm and 1200 cfm
1. Washable foam filter
2. MEF filter - optional
1 or 2
1
VL0002A
700 cfm
Drain Pans and Interior of Unit
With the filters removed from the unit, the foil faced insulation surfaces and the drain pans should be wiped clean with a soft cloth and mild cleaning solution. Also ensure that the drain fittings are free from dirt and are draining freely.
5.2 Annual Maintenance
Bi-monthly maintenance should include:
Air Filters
The standard foam filters are washable. Under normal conditions it is recommended that they be cleaned every two months. More frequent cleaning may be required under extremely dirty operating conditions. Use a vacuum cleaner to remove the heaviest portion of accumulated dirt, then wash with warm water.
A medium efficiency filter for the supply air stream is available from your supplier. This filter is disposable and should be replaced when it becomes dirty.
WARNING
Disconnect power before maintaining unit.
Annual service should include:
Air Filters
Vacuum and wash standard foam filters. Replace
medium efficiency filter if present.
Drain Pans and Interior of Unit
Wash the foil faced insulation surfaces and wipe the drain pans with a soft cloth and mild cleaning solution. Check the drain fittings to ensure they are draining freely.
Heat Recovery Core
The heat recovery core must be handled with care. It is recommended that it be washed once a year following the season of most intense use, in order to ensure maximum efficiency of the partitions.
Page 7
Allow the heat recovery core to soak for three hours in warm water and mild soap. Rinse under a heavy stream of water.
WARNING
Hot water and a strong cleaning agent could damage the polypropylene core. Ensure the core is returned to the unit in the correct orientation. Use the sticker as a guide.
Fans
Blower wheels and fan housing should be checked for dirt build-up. If they appear dirty, it may be necessary to remove the blower assembly and then vacuum the dust out through the fan mouth. See the following page for instructions on removing the blower assembly.
System Operation Check
Verification of all control modes should be checked to ensure proper operation. Refer to the Controls Section, Sequence of Operation.
Testing and Replacement of the Damper Actuator
Check damper operation by switching between LOW - COM or HIGH - COM on the dry contact terminal or by switching through the modes on the optional remote wall control. If the damper does not respond in one or both directions, check all connections.
Motor and Blower Removal and Installation
Disconnect power from the unit. To determine if the fan motor is burned out, disconnect the four-wire service connector between the motor and cabinet. Connect the motor directly to a 115 volt power source with an electrical cable, as follows:
RED + WHITE Low speed
BLUE + WHITE Medium speed
BLACK + WHITE High speed
If the motor functions normally, there is a problem with the wiring connections or the main circuit board. Check all wiring and replace main circuit board if necessary.
If the blower does not run, it must be replaced. To replace the motor, remove the heat recovery core from the unit. Disconnect the four-wire service connector from the unit. Remove the fasteners holding the motor assembly in place. Lift the assembly up and out, using one hand under the motor and one hand to steady it. Remove the assembly carefully from the unit to avoid damage to the insulation, shelf, etc. Install the repaired motor assembly by following these instructions in reverse.
REMOVE THESE 2 SCREWS
LOCKING PLATE
CAPACITOR
700 cfm ONLY: Check for 24 volt output between the White/Red and the White/Orange wires at the damper motor. If 24 volts can be measured at the damper motor, the problem is either in the connections, the defrost relay or the main circuit board.
600/1200 cfm ONLY: (CAUTION: 120VAC) Check for 120 volt output across the White/Black wires. If 120 volt can be measured at the motor, replace the motor. If 120 volt cannot be measured at the motor, check pins J1-9 at the printed circuit board.
Main Circuit Board Replacement
The main circuit board must be replaced if an electronic problem arises. For example, the unit suddenly stops, the unit stays in defrost all of the time or if control functions are not working properly.
Ensure that power is reaching the board. Test the blower motors and damper actuators for operation when directly connected to the appropriate power voltage. If the motor and damper actuators function normally, replace the main circuit board.
VD0004A
600 cfm and 1200 cfm
THUMBSCREW
SERVICE CONNECTOR
VD0001A
700 cfm
Page 8
Loading...
+ 16 hidden pages