Vemer ADR Series, ADR-R, ADR-R Spot, ADR-D, ADR-D Spot User Manual

...
Analizzatore
di Rete
ADR
Manuale d’Uso
Network Analyser User’s Manual
ADR Network analyser - User’s guide
English
Index
Safety warnings Page 24
Technical specifications Page 24
Instrument description Page 25
Keys Page 26
Parameter settings Page 26
Measurement page display Page 30
Measurement / calculation methods Page 36
Serial communications Page 37
ADR-View software Page 37
Reference standards Page 38
Dimensions and connection diagrams Page 39
ADR Network analyser - User’s guide
English
During the installation and operation of the instrument, proceed in accordance with the instructions below:
1) The instrument should be installed by competent personnel
2) Follow the installation diagrams carefully
3) When connecting the instrument, always use TA x/5 A
4) The appliance should be installed in a panel from which no access can be gained to the terminals after installation
5) The terminals of the voltage and current circuits may be connected with a maximum rated voltage to earth of 300 V eff
6) The panel should be wired in accordance with the EN standards that apply
7) Do not power or connect the instrument if any part of it is damaged
NOTE:
VEMER mains analysers are designed to be used in locations with over-voltage category III and pollution level 2, in accordance with the EN 61010-1 •standard The electrical system of the building in which the instrument is to be installed should have a switch or isolator fitted in the vicinity of the instrument in a place to which the operator has easy access. A protective device against over-currents should be fitted.
ower supply: 230 V AC (-15%/+10%)
•F
•P
requency: 50/60 Hz
Maximum power consumption: 4 VA
Indications: customised, rear lit LCD display
•Voltmeter inputs: max 550 V rms, 47÷63 Hz
Ammetric inputs: max 6 A rms, 47÷63 Hz
Scales: 1 voltage scale with max reading 550 V rms
2 current scales with maximum readings of 2 A rms and 6 A rms
• Precision:
-Voltage 0.5% of the end of scale value (for measurements between
10% and 100% of the end of scale)
- Minimum signal measured 10 V
- Current 0.5% of the end of scale value (for measurements between
10% and 100% of the end of scale)
- Minimum signal measured 20 mA
-Power 1% of the end of scale value
-F
- Active energy class 2 to standard EN 62052-21
- Reactive energy class 3 to standard EN 62053-23
requency ±0.1 Hz (47÷63 Hz)
TECHNICAL SPECIFICATIONS
SAFETY WARNINGS
ADR Network analyser - User’s guide
English
• TV selected: primary 1÷9999 V, secondary 230 V
• TA selected: primary 1÷9999 A, secondary 5 A
• Serial output: insulated RS-485 with MODBUS RTU protocol (max 9600 Baud) for the ADR-R, ADR-D, ADR-R E and ADR-D E models
• Operating temperature: 0 °C ÷ +50 °C (for the ADR-DE model: 0 °C ÷ +40 °C)
• Relative humidity: 10%÷90% non-condensing
• Containers:
- Rear panel version: material in class V-0 in line with the UL 94 standard,
standardised dimensions 72x72 mm in line with the DIN 43700 standards
- Modular version: material in class V-0 in line with the UL 94 standard,
4 module DIN container, colour RAL-7035 grey
Analizzatore di Rete
Code Model Description VN561700 ADR-R Insulated network analyser with serial output, rear panel VN560900 ADR-R Spot Insulated network analyser, rear panel VN563300 ADR-D Insulated network analyser with serial output, modular VN562500 ADR-D Spot Insulated network analyser, modular VE280400 ADR-R E Uninsulated network analyser with serial output, rear panel VE279600 ADR-R E Spot Uninsulated network analyser, rear panel version VE281200 ADR-D E Uninsulated network analyser with serial output, modular VE071700 ADR-D E Spot Uninsulated network analyser, modular VN564100 ADR-view 1.00 Software for network analysers + interface
INSTRUMENT DESCRIPTION
Display and messages
- Numerical fields for the display of the values measured
-
Type of measurement taking place
-
Measurement unit
-
Phase symbols
INSTRUMENT DESCRIPTION
1
cos
APPA RENT REACTIVE ENERGY
VOLTAGE CURRENT FREQUENCY
POWER
2
GMk Wh Hz VARh
AV
3
1
2
2
3
1
3
4
pK
T
ADR
GMk Wh Hz VARh cos
AV
1
2
2
3
1
3
APPARENT REACTIVE ENERGY
VOLTAGE CURRENT FREQUENCY
POWER
ADR Network analyser - User’s guide
English
Scroll to the next page and set parameters
Scroll to the previous page and set parameters
Display of the system values
•For the ADR-D, ADR-R, ADR-D E and ADR-R E:
Display of the peak value and selection of parameters during programming
•For the ADR-D spot, ADR-R spot, ADR-D E spot and ADR-R E spot :
Parameter selection during programming
Access to the programming menus takes place when the instrument is switched on by holding down the “up” (
) and “down” ( ) keys at the same time.
The following parameters can be programmed by the user in the order shown:
Primary TV (fixed secondary 230 V)
Primary TA (fixed secondary 5 A)
Serial port configuration (3 screen displays) (not available in the spot version)
Zeroing of active energy meter
Zeroing of reactive energy meter
Rear lighting handling For a new parameter setting, the power to the instrument has to be cut off and
restored by pressing the “up” (
) and “down” ( ) keys at the same time.
PARAMETER SETTING
pK
T
KEYS
ADR Network analyser - User’s guide
English
TV setting
• Press the “up” ( ) or “down” ( ) keys to select the required value of the flashing figure
•To move to the next figure, press the “pK” key (or the (•) key in the spot version)
•To confirm the value set and move to the next window, press “T”
TA setting
• The same as the TV setting procedure.
Note: for the TV and TA primaries, any value from 0001 to 9999 can be set. If the value 0000 is set, the instrument will force this to 0001. The secondaries are set to 230 V and 5 A respectively.
Serial port configuration (not in the spot version)
Setting the serial port address: the same as the TV setting procedure.
v
VOLTAGE
T
v
VOLTAGE
pK
A
CURRENT
T
A
CURRENT
pK
T
pK
ADR Network analyser - User’s guide
English
Setting the serial port speed: press “pK” to select one of the 4 possible speeds (1200, 2400, 4800 or 9600 Baud).
•To confirm the value set and move to the next window, press “T”.
Setting the parity bit: press “pK” to select one of the
options, NONE, ODD
or EVEN, in order.
•To confirm the value set and move to the next window, press “T”.
Zeroing the active energy meter
Press “pK” (or (•) in the spot version) to select the option “Yes” or “No”.
•To confirm the value set and move to the next window, press “T”.
T
k
k
pK
k
k
T
pK
ACTIVE ENERGY
T
ACTIVE ENERGY
pK
ADR Network analyser - User’s guide
English
Zeroing the reactive energy meter
Same procedure as the zeroing of the active energy meter.
Rear lighting handling
Press “pK” (or (•) in the spot version) to select from the options “NO” (rear lighting off), “YES” (on) or “TIME” (on for approximately 60 seconds
after a key is pressed).
•To confirm the value set and terminate the parameter setting procedure, press “T”.
When “T” is pressed, all the symbols in the display will come on for approximately 3 seconds, followed by the display of the main page.
Note:
Note: for ADR-D E model it is better not to select “YES” option
(rear lighting always ON).
if the power is cut off during the programming procedure, the
instrument will memorise all the settings in place at the instant when this
occurs.
REACTIVE ENERGY
T
REACTIVE ENERGY
pK
T
pK
ADR Network analyser - User’s guide
English
When the instrument is switched on (or after the programming procedure) the main page is displayed after approximately 3 seconds when the display is fully operational. When “up” ( ) is pressed from the main page, the following are displayed: all the other measurement pages in sequence. When “up” (
) is pressed from the last page, the system returns to the main page. If V is >999 or I is >999, the relevant measurement will flash to indicate that the unit is not complete (prefix K or M missing).
1) Main page
The system voltage, current and active power are displayed.
2) Phase voltage page
The phase voltages are displayed. If the three phase system has no neutral, the voltages refer to a fictitious star delta centre.
The “T” key is used to display the system voltage page.
2a) Peak phase voltage value page (not in the spot version)
•If “pK” is pressed repeatedly from one of the two phase voltage pages, the following are displayed in order:
-the peak voltage values (phase of system), with the “V” measurement unit
flashing
DISPLAYING THE MEASUREMENT PAGE
k W
AV
V
VOLTAGE
pK
V
1
2
3
VOLTAGE
T
ADR Network analyser - User’s guide
English
- the instant when the peak occurred (time and date)
- the number of hours lapsing between the start-up of the instrument and the occurrence of the peak (expressed in hours and tenths of an hour)
•To zero the peak values, simply press “pK” and “T” at the same time
• The “up” (
) key can be pressed at any time to move to the next page
3) Concatenating voltage page
• The concatenating voltages between the phases are displayed
4) Phase current page
• The phase currents are displayed.
• The “T” key is used to display the system current.
h
VOLTAGE
pK
T
h
VOLTAGE
pK
V
1
2
3
VOLTAGE
pK
V
1
2
2
3
1
3
VOLTAGE
A
CURRENT
pK
A
1
2
3
CURRENT
T
ADR Network analyser - User’s guide
English
4a) Peak phase current value page (not in the spot version)
The same procedure as that for the display of the peak phase voltage values
5) Active phase power page
The active phase powers are displayed.
The “T” key is used to display the active system power.
5a) Peak active power value pages (not in the spot version)
The same procedure as that for the display of the peak phase voltage values
A
1
2
3
CURRENT
pK
h
CURRENT
pK
h
CURRENT
pK
T
k W
ACTIVE
POWER
pK
W
1
2
3
ACTIVE
POWER
T
h
ACTIVE
POWER
pK
k W
1
2
3
ACTIVE
POWER
pK
h
ACTIVE
POWER
pK
T
ADR Network analyser - User’s guide
English
6) Apparent phase power page
The apparent phase powers are displayed
The “T” key is used to display the apparent system power.
7) Reactive phase power page
The reactive phase powers are displayed.
The “T” key is used to display the reactive system power.
7a) Reactive power peak value pages (not in the spot version)
The same procedure as that for the display of the peak phase voltage values.
k VA
APPARENT
POWER
k VA
1
2
3
APPARENT
POWER
T
k VAR
REACTIVE
POWER
pK
VAR
1
2
3
REACTIVE
POWER
T
VAR
1
2
3
REACTIVE
POWER
pK
VAR
h
REACTIVE
POWER
pK
h
REACTIVE
POWER
pK
T
ADR Network analyser - User’s guide
English
8) Phase power factor page
The phase power factors are displayed
The “T” key is used to display the system power factor
9) Voltage-current phase shift page
The voltage-current phase shifts are displayed in sexagesimal degrees (the letter “C” indicates a capacitative phase shift, and “L” indicates an inductive phase shift)
10) Total active energy page
The total active energy is displayed
The “T” key is used to display the partial active energy of the single phases
(these energy readings are zeroed each time the total active energy is increased)
cos cos
1
2
3
T
1
2
3
Wh
1
2
3
ACTIVE ENERGY
k Wh
ACTIVE ENERGY
T
ADR Network analyser - User’s guide
English
11) Total reactive energy page
The total reactive energy is displayed
The “T” key is used to display the partial reactive energy readings for the single
phases (these energy readings are zeroed each time the total reactive energy is increased)
12) Frequency page
The V1 voltage frequency is displayed
13) Time and date page (not in the spot version)
The time and date are displayed in dd-mm-yy format
The “pK” key is used to move from the display of the time and date lapsed since
the instrument was switched on (expressed in hours and tenths of an hour)
The “up” (
) key is used to return to the starting page
k VARh
1
2
3
REACTIVE ENERGY
k VARh
REACTIVE ENERGY
T
Hz
FREQUENCY
h h
pK
ADR Network analyser - User’s guide
English
13a) Setting the time and date (not in the spot version)
When “T” is pressed from one of the time display pages, the time and date can be set
Press the “up” (
) or “down” ( ) keys to select the required value of the
flashing number
Press “pK” to move to the next number
The “T” key can be pressed at any time to return to the time display page, with the
memorisation of the modifications entered
Note: up to the entry of the first setting,the time and date will flash. The time and date will also flash in the peak value pages.
The voltage and current measurements take place in (True RMS) by means of sampling and analogue-digital conversion.
•To calculate the system values, the following formulas are used:
System voltage V =
V1+ V2+ V
3
3
System current I =
I1+ I2+ I
3
3
Active system power P = P1+P2+P
3
Reactive system power Q = Q1+Q2+Q
3
(addition)
Apparent system power A =
P
2
+
Q
2
System power factor
PF =
P
A
MEASUREMENT / CALCULATION METHOD
pK
h
T
h
T
ADR Network analyser - User’s guide
English
Total active energy E = E1+E2+E
3
Total reactive energy Er = Er1+Er2+Er
3
The instrument has an insulated RS-485 serial output The data communication system is based on the MODBUS protocol and is suitable for the connection of the following to a master device such as a PC or PLC in a common RS-485 line:
up to 31 ADR (slaves) without the use of signal amplifiers, up to a maximum distan­ce of 1000 m
up to 247 ADR (slaves) in groups of 30, separated by suitable signal amplifiers The communication takes place in half duplex and only the master (PC/PLC) is able to start up the dialogues with the slaves, of a question/answer type (one slave only addressed), or with the message addressed to all the slaves (address 0) without obtaining any reply
The features of the Modbus protocol implemented are:
•Type of coding: RTU (Remote Terminal Unit)
•Transmission speed (Baud Rate): 9600, 4800, 2400, 1200 bps
(selected by the user)
Byte format transmitted: 1 start bit, 8 data bits, 1 parity bit (can be selected): none, odd o even, 1 stop bit For the Modbus functions and the use of the registers, ask the SAT service for the relevant documentation.
When the ADR-View software is installed (not suitable for the spot versions), it is possible to monitor all the values measured by means of tables and graphs, to set up a data file and obtain the trend of the signals over time. The software is available for Windows 98 or later and is based on a simple,
“user friendly interface”.
Minimum hardware requirements:
IBM or compatible personal computer
•Pentium 200 microprocessor
32 Mb of RAM (64Mb recommended)
Minimum 30Mb space available on the hard disk
VGA graphic card with 800x600 resolution (1024x768 recommended)
Colour monitor
•1serial port dedicated to the RS-485 line connection
ADR-View software (optional)
SERIAL COMMUNICATION (not in the spot version)
ADR Network analyser - User’s guide
English
REFERENCE STANDARDS
Conformity to EC directives 2006/95/EC (LVD)
2004/108/EC (EMC) is declared with reference to the following harmonised standards:
Safety: EN 61010-1
Electromagnetic compatibility: EN 61000-6-2 and EN 61000-6-4
Metering requirements: EN 62052-21 and EN 62053-23
ADR Network analyser - User’s guide
English
DIMENSIONS
pK
T
ADR-R
GMk Wh Hz VARh cos
AV
1
2
2
3
1
3
APPARENT REACTIVE ENERGY
VOLTAGE CURRENT FREQUENCY
POWER
66
100
514
66
72
ADR Network analyser - User’s guide
English
CONNECTION DIAGRAMS
ADR-R
ADR-R E
ADR-R
ADR-R E
ADR-R
ADR-R E
AC
Single phase
AC
Three phase+N
L1N
2
3
0
V
~
5
0
-
6
0
H
z
~
RS-485
+
I1
+
N
L
3
6
5 4
2
1
10
13
12 11
9
8 7
14
N
L
L1L2L3N
2
3
0
V
~
5
0
-
6
0
H
z
~
RS-485
+
I2 I1I3
+ + +
L3
L2
L1
N
3
6
5 4
2
1
10
13
12 11
9
8 7
14
L3
L2
L1
P2
S2 S1
P1
I
N
L1L2L3N
2
3
0
V
~
5
0
-
6
0
H
z
~
RS-485
+
I2 I1I3
+ + +
L3
L2
L1
3
6
5 4
2
1
10
13
12 11
9
8 7
14
L3
L2
L1
AC
Three phase
Attention: the secondary circuits of the CT can be
earthed for the ADR-R model only
ADR Network analyser - User’s guide
English
ADR-R spot
ADR-R E spot
ADR-R spot
ADR-R E spot
ADR-R spot
ADR-R E spot
AC
Single phase
AC
Three phase+N
L1N
2
3
0
V
~
5
0
-
6
0
H
z
~
I1
+
N
L
3
6
5 4
2
1
10
13
12 11
9
8 7
14
N
L
L1L2L3N
2
3
0
V
~
5
0
-
6
0
H
z
~
I2 I1I3
+ + +
L3
L2
L1
N
3
6
5 4
2
1
10
13
12 11
9
8 7
14
L3
L2
L1
N
L1L2L3N
2
3
0
V
~
5
0
-
6
0
H
z
~
I2 I1I3
+ + +
L3
L2
L1
3
6
5 4
2
1
10
13
12 11
9
8 7
14
L3
L2
L1
AC
Three phase
P2
S2 S1
P1
I
Attention: the secondary circuits of the CT can be
earthed for the ADR-R spot model only
CONNECTION DIAGRAMS
ADR Network analyser - User’s guide
English
DIMENSIONS
10
11
12
13
14
15
16
17
18
1
2
3
4
5
6
7
8
9
pK
T
ADR
GMk Wh Hz VARh cos
AV
1
2
2
3
1
3
APPARENT REACTIVE ENERGY
VOLTAGE CURRENT FREQUENCY
POWER
87
70
45
60
65
ADR Network analyser - User’s guide
English
CONNECTION DIAGRAMS
ADR-D
ADR-D E
AC
Single
phase
AC
Three phase
Three phase+N
RS-485
+
N L
2
3
0
V
~
5
0
-
6
0
H
z
~
I1
+
N
5
2
3 4
6
7 81
L
14
11
12 13
15
16 1710
N
L
S1/k
9
18
RS-485
+
N L
2
3
0
V
~
5
0
-
6
0
H
z
~
I2 I3I1
+ + +
N
5
2
3 4
6
7 81
L1
14
11
12 13
15
16 1710
N
L3
9
18
L2
L1
L2 L3
RS-485
+
N L
2
3
0
V
~
5
0
-
6
0
H
z
~
I2 I3I1
+ + +
5
2
3 4
6
7 81
L1
14
11
12 13
15
16 1710
L3
9
18
L2
L1
L2 L3
AC
ADR-D
ADR-D E
ADR-D
ADR-D E
P2
S2 S1
P1
I
Attention: the secondary circuits of the CT can be
earthed for the ADR-D model only
ADR Network analyser - User’s guide
English
CONNECTION DIAGRAMS
ADR-D spot
ADR-D E spot
AC
Single phase
AC
Three phase+N
N L
2
3
0
V
~
5
0
-
6
0
H
z
~
I1
+
N
5
2
3 4
6
7 81
L
14
11
12 13
15
16 1710
N
L
9
18
N L
2
3
0
V
~
5
0
-
6
0
H
z
~
I2 I3I1
+ + +
N
5
2
3 4
6
7 81
L1
14
11
12 13
15
16 1710
N
L3
9
18
L2
L1
L2 L3
N L
2
3
0
V
~
5
0
-
6
0
H
z
~
I1 I2 I3
+ + +
5
2
3 4
6
7 81
L1
14
11
12 13
15
16 1710
L3
9
18
L2
L1
L2 L3
AC
Three phase
P2
S2 S1
P1
I
ADR-D spot
ADR-D E spot
ADR-D spot
ADR-D E spot
Attention: the secondary circuits of the CT can be
earthed for the ADR-D spot model only
V3IS00498-010-072013
Vemer S.p.A.
I - 32032 Feltre (BL) Via Camp Lonc, 16 Tel +39 0439 80638 Fax +39 0439 80619
e-mail: info@vemer.it - web site: www.vemer.it
Loading...