Installation, Operating and Service Instructions for
Residential
Condensing
High Efficiency
Direct Vent
Gas-Fired
Combi Boilers
9700609
As an ENERGY STAR® Partner, Velocity Boiler Works
has determined that the PHANTOM™ Combi boilers meet
the ENERGY STAR® guidelines for energy efficiency
established by the United States Environmental Protection
Agency (EPA).
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property
damage, injury, or loss of life. For assistance or additional information, consult a qualified installer,
service agency or the gas supplier. This boiler requires a special venting system. Read these instructions
carefully before installing.
108095-02- 4/18
1
Page 2
IMPORTANT INFORMATION - READ CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations enforced in the area
where the installation is to be made. These regulations shall be carefully followed in all cases. Authorities
having jurisdiction shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or
local regulations.
All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or
local regulations.
The City of New York requires a Licensed Master Plumber supervise the installation of this product.
The Commonwealth of Massachusetts requires this product to be installed by a Licensed Plumber or Gas Fitter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various
risk levels, or to important information concerning product life.
DANGER
Indicates an imminently
hazardous situation which, if not avoided, will
result in death, serious injury or substantial
property damage.
WARNING
Indicates a potentially
hazardous situation which, if not avoided,
could result in death, serious injury or
substantial property damage.
DANGER
Explosion Hazard. DO NOT store or use gasoline or other flammable vapors or liquids
in the vicinity of this or any other appliance.
If you smell gas vapors, DO NOT try to operate any appliance - DO NOT touch any electrical switch or use
any phone in the building. Immediately, call the gas supplier from a remotely located phone. Follow the
gas supplier’s instructions or if the supplier is unavailable, contact the fire department.
WARNING
This boiler must only be serviced and repaired by skilled and experienced service
technicians.
•
If any controls are replaced, they must be replaced with identical models.
•
Read, understand and follow all the instructions and warnings contained in all the sections of this manual.
•
If any electrical wires are disconnected during service, clearly label the wires and assure that the wires
are reconnected properly.
•
Never jump out or bypass any safety or operating control or component of this boiler.
•
Assure that all safety and operating controls and components are operating properly before placing the
boiler back in service.
•
Annually inspect all vent gaskets and replace any exhibiting damage or deterioration.
CAUTION
Indicates a potentially
hazardous situation which, if not avoided, may
result in moderate or minor injury or property
damage.
NOTICE Indicates special instructions on
installation, operation, or maintenance which
are important but not related to personal injury
hazards.
2
108095-02 - 4/18
Page 3
WARNING
Asphyxiation Hazard. Fire Hazard. Explosion Hazard. This boiler requires regular
maintenance and service to operate safely. Follow the instructions contained in this manual.
WARNING
Asphyxiation Hazard. Fire Hazard. Explosion Hazard. This boiler requires regular
maintenance and service to operate safely. Follow the instructions contained in this manual.
•
Improper installation, adjustment, alteration, service or maintenance can cause property damage,
personal injury or loss of life. Read and understand the entire manual before attempting installation,
start-up operation, or service. Installation and service must be performed only by an experienced, skilled,
and knowledgeable installer or service agency.
•
This boiler must be properly vented.
•
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air.
•
Asphyxiation Hazard. The interior of the venting system must be inspected and cleaned before the
start of the heating season and should be inspected periodically throughout the heating season for any
obstructions. A clean and unobstructed venting system is necessary to allow noxious fumes that could
cause injury or loss of life to vent safely and will contribute toward maintaining the boiler’s efficiency.
•
Installation is not complete unless a safety relief valve is installed in the supply piping. - See the System
Piping Section of this manual for details.
•
This boiler is supplied with safety devices which may cause the boiler to shut down and not re-start
without service. If damage due to frozen pipes is a possibility, the heating system should not be left
unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating
system to prevent damage if the boiler is inoperative.
•
Burn Hazard. This boiler contains very hot water under high pressure. Do not unscrew any pipe fittings
nor attempt to disconnect any components of this boiler without positively assuring the water is cool and
has no pressure. Always wear protective clothing and equipment when installing, starting up or servicing
this boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the
temperature and pressure of the boiler. This boiler contains components which become very hot when
the boiler is operating. Do not touch any components unless they are cool.
•
Respiratory Hazard. Boiler materials of construction, products of combustion and the fuel contain
alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful
substances which can cause death or serious injury and which are known to the state of California to
cause cancer, birth defects and other reproductive harm. Always use proper safety clothing, respirators
and equipment when servicing or working nearby the appliance.
•
Failure to follow all instructions in the proper order can cause personal injury or death. Read all
instructions, including all those contained in component manufacturers manuals which are provided with
the boiler before installing, starting up, operating, maintaining or servicing.
•
All cover plates, enclosures and guards must be in place at all times.
gas, high voltage electricity, moving parts, and very hot water under high pressure. Assure that all
gas and electric power supplies are off and that the water temperature is cool before attempting any
disassembly or service.
Do not attempt any service work if gas is present in the air in the vicinity of the boiler. Never modify,
remove or tamper with any control device.
108095-02- 4/18
3
Page 4
WARNINGS FOR THE HOMEOWNER
FOLLOW ALL INSTRUCTIONS and warnings
printed in this manual and posted on the boiler.
INSPECT THE BOILER ANNUALLY. To keep
your boiler safe and efficient, have a service
technician follow the Service checklist near the
end of this manual.
IF YOU ARE NOT QUALIFIED to install or service
boilers, do not install or service this one.
THE BOILER MAY LEAK WATER at the end of its
useful life. Be sure to protect walls, carpets, and
valuables from water that could leak from the
boiler.
PROTECT YOUR HOME IN FREEZING
WEATHER. A power outage, safety lockout, or
component failure will prevent your boiler from
lighting. In winter, your pipes may freeze and
cause extensive property damage. Do not leave
the heating system unattended during cold
weather unless alarms or other safeguards are in
place to prevent such damage
DO NOT BLOCK AIR FLOW into or around the
boiler. Insufficient air may cause the boiler to
produce carbon monoxide or start a fire.
KEEP FLAMMABLE LIQUIDS AWAY from the
boiler, including paint, solvents, and gasoline.
The boiler may ignite the vapors from the liquids
causing explosion or fire.
KEEP CHILDREN AND PETS away from hot
surfaces of the boiler, boiler piping, vent piping
and vent terminals.
CARBON MONOXIDE (CO) is an odorless,
deadly gas that may be introduced into your
home by any malfunctioning fuel-burning
product or vent system failure. Consider
installing CO alarms near bedrooms in all levels
of the building to warn you and your family of
potential CO exposure.
DANGER
• Water temperature over 125°F (52°C)
can cause severe burns instantly or
death from scalds.
• Children, disabled and elderly are at
highest risk of being scalded.
• Feel water before bathing or showering.
• Installation of an ASSE 1017 or ASSE
1070 certied tempering valve is
REQUIRED as part of this boiler’s
installation. Consult Sections X and
XIII for details on valve installation and
temperature adjustment.
4
108095-02 - 4/18
Page 5
WARNINGS FOR THE INSTALLER
READ THIS ENTIRE MANUAL before attempting
installation, start-up, or service. Improper
installation, adjustment, alteration, service,
or maintenance may cause serious property
damage, personal injury, or death.
DO NOT DISCONNECT PIPE FITTINGS on
the boiler or in the heating system without first
verifying that the system is cool and free of
pressure and that your clothing will protect you
from a release of hot water or steam. Do not rely
solely on the boiler’s temperature and pressure
gage when making this judgment.
USE PROPER PERSONAL PROTECTION
EQUIPMENT when servicing or working near the
boiler. Materials of construction, flue products,
and fuel contain alumina, silica, heavy metals,
carbon monoxide, nitrogen oxides, and/or
other toxic or harmful substances that can are
hazardous to health and life and that are known
to the State of California to cause cancer, birth
defects, and other reproductive harm.
INSTALL ALL GUARDS, cover plates, and
enclosures before operating the boiler.
SIZE THE BOILER PROPERLY relative to the
design heat load or, if using domestic hot water
priority, the peak hot water load, whichever
is larger. A grossly oversized boiler will cycle
excessively and this will lead to premature failure
of the boiler and its components. Our warranty
does not apply to damage from excessive
cycling.
ADHERE TO ALL LOCAL CODE
REQUIREMENTS. Contact your local code
inspector prior to installation. In the absence of
a local code, adhere to the National Fuel Gas
Code ANSI Z223.1/NFPA 54 or CAN/CSA B149.1,
Natural Gas and Propane Installation Code.
ALL WIRING must comply with the National
Electrical Code ANSI/NFPA 70 (in the USA) or
the Canadian Electrical Code CSA C22.1 (in
Canada) and any local regulations.
Appendix A: Instructions for High Altitude Installation Above 2,000 ft. . 154
Appendix B: Special Requirements For Side-Wall Vented Appliances
In The Commonwealth of Massachusetts . . . . . . . . . . . . . 157
6
108095-02 - 4/18
Page 7
I. Product Description
This boiler is a stainless steel gas fired condensing boiler designed for use in forced hot water heating systems
requiring supply water temperatures of 180°F or less. In addition to providing water for space heat, this boiler
also generates domestic hot water (DHW). This boiler may be vented vertically or horizontally with combustion
air supplied from outdoors. It is not designed for use in gravity hot water systems or systems containing
significant amounts of dissolved oxygen.
II. Specifications
SEE TABLE 2.4
17
OUTSIDE
OF WALL
"A"
INSIDE
OF WALL
VENT
CONNECTION
RELIEF
VALVE
AIR INTAKE
CONNECTION
ACCESS
30
TEMPERATURE/
PRESSURE GAUGE
(INSIDE CABINET)
BOILER SUPPLY WATER
CONNECTION
BOILER RETURN WATER
CONNECTION
DOMESTIC HOT WATER OUTLETDOMESTIC COLD WATER INLET
CONDENSATE
CONNECTION
GAS CONNECTION
DOOR
CONDENSATE TRAP
CLEANOUT
108095-02- 4/18
Figure 2.1: General Configuration
7
Page 8
Model
Size
Fig 2.1 Dim
“A”, (in)
Connection Size (NPT Male)
Boiler Water
Content,
(Gal.)
Net Weight,
(lbs.)
Supply/Re-
turnHot/ColdGas
1351513/41/20.53109
1501913/41/20.79126
1801913/41/20.79126
II. Specifications (continued)
Model
Size
Nominal
Vent/Intake
Size (in.)
Min. Vent
Length (in.)
Max Vent
Length (ft.)
Approx. Derate
at Max Vent (%)
1353121357
1503521357
1803521359
Table 2.2: Performance Specifications
Space Heating RatingsDomestic Hot Water (DHW) Ratings
Hot Water Draw Limits, GPM
3
Input, MBH
Model Number
MinMaxMinMax
PHNTM135CB121201129795.0121353.33.02.60.5
PHNTM150CB1515014212395.0151503.93.73.10.5
PHNTM180CB1818016914795.0181804.54.13.50.5
Notes:
1. DHW ratings are not AHRI certified.
2. The Net AHRI Water Ratings shown are based on a piping and pickup allowance of 1.15. The manufacturer should be consulted before selecting a boiler for
installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
3. Maximum draw rates shown are at sea level and minimum vent length. Under other conditions draw rates will be reduced proportionally to the reduction in input. See Table 2.4
and Appendix A for input de-rate information.
4. Minimum flow rate shown is that required through the boiler to initiate a call for DHW. A higher flow rate may be required through the fixture due to mixing at the
tempering valve and fixture itself.
Heating
Capacity,
MBH
2
Net AHRI
Water,
MBH
AFUE, %
Input, MBH
70°F77°F90°F
RiseRiseRise
Max.
Table 2.3: Physical Specifications
1
4
Min.
Table 2.4: Vent Lengths
III. Before Installing
1. Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict
accordance with this manual and the requirements of the authority having jurisdiction.
• In the absence of an authority having jurisdiction, installation must be in accordance with this manual
and the National Fuel Gas Code, ANSI Z223.1. In Canada, installation must be in accordance with the
B149.1 Installation Code.
• Where required by the authority having jurisdiction, this installation must conform to the Standard for
Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1).
2. Read Section VII to verify that the maximum combustion air and exhaust pipe lengths will not be exceeded
in the planned installation. Also verify that the vent terminal can be located in accordance with Section VII.
3. Make sure that the boiler is correctly sized:
• For heating systems employing convection radiation (baseboard or radiators), use an industry
8
accepted sizing method such as the I=B=R Guide RHH published by the Air-Conditioning, Heating and
Refrigeration Institute (AHRI).
108095-02 - 4/18
Page 9
III. Before Installing (continued)
• For new radiant heating systems, refer to the radiant tubing manufacturer’s boiler sizing guidelines.
• For system which includes an indirect water heater, make sure the boiler has the output called for by the
indirect water heater manufacturer’s instructions.
4. All boilers are shipped from the factory configured for use with natural gas. They may be converted for use
with LP gas (“propane”) using a proper conversion kit per Table 3.1. Use a combustion analyzer and follow all
instructions supplied with conversion kit.
Table 3.1: LP Conversion Kit
Model SizeLP Conversion Kit PN
135, 150107874-01
180107875-01
WARNING
Do not attempt to operate this boiler on LP gas without converting it using the proper
conversion kit.
• Do not attempt to convert this boiler to LP gas without the use of a combustion analyzer.
•
Failure to follow the conversion instructions will result in operation of the boiler at unsafe Carbon
Monoxide (CO) levels and may result in personal injury or loss of life. Improper conversion may also
result in unreliable operation, resulting in property damage.
• Before attempting to operate this boiler at altitudes above 2000 ft., follow instructions shown in Appendix
A of this manual.
NOTICE This product must be installed by a licensed plumber or gas fitter when installed within the
Commonwealth of Massachusetts. See Appendix C for additional important information about installing
this product within the Commonwealth of Massachusetts.
IV. Locating the Boiler
1. Observe the minimum clearances shown in Figure 4.1. These clearances apply to combustible construction
as well as non-combustible walls, floors, ceilings and doors.
2. Note the recommended service clearances in Figure 4.1. These service clearances are recommended, but
may be reduced to the combustible clearances provided:
a. Access to the front of the boiler is provided through a door.
b. Access is provided to the condensate trap located beneath the boiler.
Note that servicing the boiler will become increasingly difficult as these service clearances are reduced.
3. Observe the following clearances from piping to combustible construction:
Non-concentric vent (exhaust): ¼”
Air intake piping: 0”
Hot water piping: ¼”
4. The relief valve must be installed in the location shown in Figure 2.1 and must be in the same space as the
boiler.
5. The boiler should be located so as to minimize the length of the vent system.
6. The combustion air piping must terminate where outdoor air is available for combustion and away from areas
that will contaminate combustion air. Avoid areas near chemical products containing chlorine, chloride
based salts, chloro/fluoro carbons, paint removers, cleaning solvents and detergents.
108095-02- 4/18
9
Page 10
IV. Locating the Boiler (continued)
10
Figure 4.1: Minimum Clearances To Combustible Construction
108095-02 - 4/18
Page 11
V. Mounting The Boiler
A. Wall Mounting
CAUTION
This boiler weighs as much as 126 pounds:
• Two people are required to safely lift this boiler onto the wall mounting hook.
• Make sure that wall mounting hook is anchored to a structure capable of supporting the
weight of the boiler and attached piping when filled with water. Jurisdictions in areas
subject to earthquakes may have special requirements for supporting this boiler. These
local requirements take precedence over the requirements shown below.
1. If the boiler is installed on a framed wall, minimum acceptable framing is 2 x 4 studs on 16” centers. The
boiler mounting holes are on 16” centers for installation between two studs at the standard spacing. In
cases where the boiler cannot be centered between the studs, or where the studs are spaced closer than
16” apart, the boiler may be anchored to ¾” plywood or horizontal 2 x 4’s anchored to the studs.
2. 5/16” x 2” lag screws and washers are provided for mounting this boiler. These lag screws are intended
for mounting the boiler directly onto studs covered with ½” sheathing. When the boiler is attached to other
types of construction, such as masonry, use fasteners capable of supporting the weight of the boiler and
attached piping in accordance with good construction practice and applicable local codes.
3. Make sure that the surface to which the boiler is mounted is plumb.
4. Before mounting the boiler, make sure that wall selected does not have any framing or other construction
that will interfere with the vent pipe penetration.
5. Once a suitable location has been selected for the boiler, and any needed modifications have been made
to the wall, use Figure 5.1 to locate holes “A” and “B”. Make sure that the horizontal center line of these
holes is level. Holes “C” and “D” may also be drilled at this time or after the boiler is hung on the wall. If the
5/16” x 2” lag screws are used, drill 3/16” pilot holes.
6. The wall mounting hook is used to secure the boiler to the shipping pallet. Remove this hook from the
pallet and secure to the wall using the 5/16” x 2” lag screws and washers, or other suitable anchors as
appropriate (Figure 5.2). Make sure the hook is level.
7. Hang the boiler on the wall hook as shown in Figure 5.2.
8. If not already done in Step (5) locate and drill holes “C” and “D” using the ob-round slots in the bottom
mounting flange. Secure the bottom flange to the wall using the 5/16”x 2” lag screws, or other fasteners as
appropriate (Figure 5.2).
9. Verify that the front of the boiler is plumb. If it is not, install washers at holes “C” and “D” between the
bottom mounting flange and the wall to adjust.
Outdoor combustion air must be piped to the air intake. Never pipe combustion air from
areas containing contaminates such as swimming pools and laundry room exhaust vents. Contaminated
combustion air will damage the boiler and may cause property damage, personal injury or loss of life.
Air for combustion must always be obtained directly from outdoors (see Section VII for intake piping). Although
combustion air must always be obtained directly from outdoors, ventilation openings may still be required to
prevent overheating of boiler components if the boiler is installed in a small space, such as a closet.
• If the recommended service clearances shown in Figure 4.1 can be maintained (with all doors to the
room closed), no ventilation openings are required for this boiler.
• If the above service clearances cannot be maintained, provide two openings into the room, one near
the floor and one near the ceiling. The top edge of the upper opening must be within 12” of the ceiling
and the bottom edge of the lower opening within 12” of the floor. Each of these openings must have a
free area of at least 100 square inches. The “free area” takes into account the blocking effect of mesh
grilles and louvers. Where screens are used they must be no finer than ¼” (4 x 4) mesh.
• If this boiler is installed in a room with other appliances, provide adequate air for combustion and/or
ventilation in accordance with the other appliance manufacturer’s installation manual or applicable
code. In cases where such provisions require two openings in excess of 100 square inches, no
additional opening area is required for this boiler.
14
108095-02 - 4/18
Page 15
VII. Venting
WARNING
Asphyxiation Hazard. Failure to vent this boiler in accordance with these instructions
could cause products of combustion to enter the building resulting in severe property damage, personal
injury or death.
•
Do not interchange vent systems or materials unless otherwise specified. Read, understand and follow all
the instructions and warnings contained in all the sections of this manual.
•
The use of thermal insulation covering vent pipe and fittings is prohibited.
•
Do not use a barometric damper, draft hood or vent damper with this boiler.
•
Any CPVC vent materials supplied with this boiler do not comply with B149.1.S1-07 and are not approved
for use in Canadian jurisdictions that require vent systems be listed to ULC S636-2008. In these
jurisdictions, vent this boiler using a listed ULC S636 Class IIB venting system.Annually inspect all vent
gaskets and replace any exhibiting damage or deterioration.
•
Do not locate vent termination where exposed to prevailing winds. Moisture and ice may form on surface
around vent termination. To prevent deterioration, surface must be in good repair (sealed, painted, etc.).
•
Do not locate air intake vent termination where chlorine, chlorofluorocarbons (CFC’s), petroleum
distillates, detergents, volatile vapors or other chemicals are present. Severe boiler corrosion and failure
will result.
•
The use of cellular core PVC (ASTM F891), cellular core CPVC or Radel (polyphenolsulfone) is prohibited.
•
Do not locate vent termination under a deck.
•
Do not reduce specified diameters of vent and combustion air piping.
•
When installing vent pipe through chimney, as a chase, no other appliance can be vented into the
chimney.
A. Vent System Design
There are three basic ways to vent this boiler:
• Horizontal (“Side Wall”) Twin Pipe Venting (Figure 7.0a) - Vent system exits the building through an outside wall. Combustion air and flue gas are routed between the boiler and the terminal(s) using separate pipes for
at least part of the way. A summary of Horizontal Twin Pipe venting options is shown in Table 7.5.
• Vertical Twin Pipe Venting (Figure 7.0b) - Vent system exits the building through a roof. Combustion air and flue gas are routed between the boiler and the terminal(s) using separate pipes for at least part of the
way. A summary of Vertical Twin Pipe venting options is shown in Table 7.13
• Split Venting (Figure 7.0c) - Exhaust system exits the building through a roof, and combustion air is drawn
from a terminal mounted on the side wall. A summary of split venting options is shown in Table 7.21
All of these systems are considered “direct vent” because the air for combustion is drawn directly from the outdoors
into the boiler. One of the vent option columns in Tables 7.5, 7.13, 7.21 must match the planned vent and air intake
system exactly.
Design details applying to all vent systems are shown in this section. Observe all design requirements in this
section, as well as those unique to the type of system being installed:
• B - Design Requirements Unique to Horizontal Twin Pipe Vent Systems
• C - Design Requirements Unique to Vertical Twin Pipe Vent Systems
• D - Design Requirements Unique to Split Vent Systems
1. Approved Vent Systems and Materials – The following materials and vent systems may be used to vent this
boiler:
• CPVC – Use only CPVC listed to ASTM F441. In Canada, this pipe must also be listed to ULC S636.
• PVC – PVC may be used only as permitted in this manual. All PVC must be listed to ASTM D2665. At least
30” of CPVC pipe, and at least one CPVC elbow, must be installed between the boiler’s vent connection and
the PVC pipe. Use of foam core PVC is not permitted for venting. PVC vent pipe may not be used to vent this
boiler in Canada.
108095-02- 4/18
15
Page 16
VII. Venting A. Vent System Design (continued)
Figure 7.0a: Horizontal Twin Pipe
16
Figure 7.0b: Vertical Twin Pipe
Figure 7.0c: Split Venting
BOILER
108095-02 - 4/18
Page 17
VII. Venting A. Vent System Design (continued)
• DuraVent PolyPro - ULC S636 listed Polypropylene special gas vent system.
• Selkirk Polyflue - ULC S636 listed Polypropylene special gas vent system.
• Centrotherm InnoFlue SW - ULC S636 listed Polypropylene special gas vent system.
• DuraVent FasNSeal Flex - UL 1738 listed Stainless Steel special gas vent system.
Use PVC and/or CPVC for the air intake system. PVC may be used for all air intake piping between the intake
terminal and the boiler.
When CPVC and/or PVC pipe is used, it must be joined using primer and cement that is listed for use with the
pipe material being joined (PVC, CPVC, or CPVC to PVC).
2. Vent Kit Available for Use with this Boiler - The following vent kit is available for CPVC/PVC vent systems installed
with this boiler in the USA:
• 107039-02 - 3” CPVC/PVC Vent Kit
These kit include the following:
(1) 30” CPVC Straight Pipe
(1) 90 degree short bend CPVC Elbow
(1) Straight PVC Coupling (for exhaust terminal)
(1) 90 degree PVC Elbow (for intake termination)
(2) Rodent screens
The CPVC Pipe and elbow supplied with these kits are not listed to ULC S636 and may not be used in Canada.
3. Maximum Vent and Air Intake Lengths - The maximum length of the vent air intake piping depends upon the vent
option selected and the boiler size. See Tables 7.5, 7.13 or 7.21for the maximum vent lengths. These maximum
lengths apply to both the vent and intake piping (e.g. Option 1 may have up to 135ft of intake and 135ft of vent
piping). For all vent systems, the lengths shown in Tables 7.5, 7.13 and 7.21 are in addition to the first 90° elbow.
If more elbows are desired, the maximum allowable vent length must be reduced by the amount shown in Table
7.1 for each additional elbow used. Termination fittings are never counted.
It is recommended that all field supplied PVC or CPVC elbows be “1/4 Bend” (Sanitary 90° Elbow) or “Long
Sweep 1/4 Bend” type elbows (Figure 7.2). In this manual “sanitary” and “long sweep” elbows are treated as
having the same equivalent length.
Example:
A 3” twin pipe horizontal CPVC/PVC vent system is planned for a horizontally vented 135 MBH model which has
the following components in the vent system:
• 1 ft CPVC Straight Pipe
• 90 CPVC Elbow (short bend)
• 1-1/2 ft CPVC Straight Pipe
• Coupling
• 10 ft PVC Straight Pipe
• 90 PVC Elbow (Sanitary Elbow Design)
• 15 ft PVC Straight Pipe
• PVC Coupling Terminal
The Vent Option #1 column in Table 7.5 describes a horizontal direct vent system using 3” CPVC and PVC pipe.
From this column, we see that the boiler may have a vent length of up to 135ft. The first CPVC 90 degree elbow
is not considered. From Table 7.1, we see that the equivalent length of the 90 PVC elbow is 4ft and that the
equivalent length of the coupling is 0ft. The total equivalent length of the planned venting system is therefore:
Since Table 7.1 shows a maximum allowable vent length of 135ft, the planned vent system length is acceptable.
The flex venting used on some of the Vertical Twin Pipe and Split Vent Options also reduces the maximum
allowable vent length. See Sections VII-C or VII-D for details.
108095-02- 4/18
17
Page 18
VII. Venting A. Vent System Design (continued)
NOTICE Do not exceed maximum vent/combustion air system length. Refer to Tables 7.1B, 7.5, 7.13, and
7.21 in this section for maximum vent/combustion air system length.
Use only vent and combustion air terminals and terminal locations shown in Tables 7.1B, 7.5, 7.13 and 7.21.
4. Vent Side Noise Attenuator - This boiler comes with a vent side noise attenuator. If equivalent vent length is less
than 70 equivalent ft., install noise attenuator as described below. Attenuator is not required on size 135 at
altitudes above 2000ft. Refer to Figure 7.1A.
a. To properly install attenuator, insert approximately a 9” length CPVC pipe in vent adaptor.
b. Fit a 3” CPVC coupling on length of pipe. Glue coupling to pipe using a field supplied cement and
primer that is listed for use with materials being joined (CPVC and/or PVC).
c. Insert attenuator in length of pipe. Ensure attenuator tube is pointing down and sits inside 3” CPVC
coupling.
d. Install remaining venting as described in this manual. If using one of the polypropylene or stainless
steel vent systems listed described in this manual, use a listed adapter to adapt from CPVC to be the
other vent system.
Figure 7.1A: Installation of Vent Side Attenuator
NOTICE Indicates special instructions on installation, operation, or maintenance which are important but
not related to personal injury hazards.
18
108095-02 - 4/18
Page 19
VII. Venting A. Vent System Design (continued)
NOTICE Do not exceed maximum vent/combustion air system length. Refer to Tables 7.1B, 7.5, 7.13, and
7.21 in this section for maximum vent/combustion air system length.
Use only vent and combustion air terminals and terminal locations shown in Tables 7.5, 7.13 and 7.21.
5. Minimum Vent and Air Intake Lengths - Observe the minimum vent lengths shown in Tables 7.5, 7.13 and 7.21.
6. Clearances to Combustibles - Maintain the following clearances from the vent system to combustible
construction:
• Vent - 1/4” (also observe clearances through both combustible and non-combustible walls - see 9)
• Air Intake - 0”
• Concentric Portion of ConcentricTerminals - 0”
7. Pitch of Horizontal Vent Piping - Pitch all horizontal vent piping so that any condensate which forms in the piping
will run towards the boiler.
• Pitch CPVC/PVC vent piping 1/4” per foot.
• Pitch Polypropylene vent piping 5/8” per foot.
Table 7.1B: Vent/ Air Intake Fitting Equivalent Length
CPVC/PVC Fitting
3” 90° Elbow (“Sanitary Bend”)4.03” 90° Elbow8.7
3” 45° Elbow2.03” 45° Elbow4.6
3” 90° Elbow (“Short Bend”)10.0
3” Coupling0.0
Equivalent
Length (ft)
PolyPro, Polyflue
or InnoFlue
Vent Fitting
Equivalent
Length (ft)
FasNSeal Vent Fitting
3” 90° Elbow4.0
3” 45° Elbow2.0
3” Straight Tee18.0
3” Boot Tee8.0
Equivalent
Length (ft)
108095-02- 4/18
Figure 7.2: CPVC and PVC Elbows
19
Page 20
VII. Venting A. Vent System Design (continued)
8. Supporting Pipe - Vertical and horizontal sections of pipe must be properly supported. Maximum support
spacing is as follows:
• Support CPVC/PVC horizontally and vertically every 4 feet.
• Support DuraVent PolyPro horizontally near the female end of each straight section of pipe and vertically
every 10 feet.
• Support Centrotherm InnoFlue horizontally every 39 inches with additional supports at elbows and vertically
every 78”.
• Support 3” Polyflue horizontally every 39”. Support vertical runs of 3” Polyflue every 16 ft.
• Support DuraVent FasNSeal horizontally every 6ft or less. Support vertical runs at the base and every 12ft or
less.
Les instructions d´installation du système d´évacuation doivent préciser que les sections horizontales
doivent être
supportées pour prévenir le fléchissement. Les méthodes et les intervalles de support doivent être
spécifiés. Les
instructions divent aussi indiquer les renseignements suivants:
• les chaudières de catégories II et IV doivent être installées de façon à empêcher l´accumulation de
condensat: et
• si nécessaire, les chaudières de catégories II et IV doivent être pourvues de dispositifs d´évacuation du
condensat.
9. Allowing for Thermal Expansion -
• For CPVC/PVC pipe design, the vent system shall allow 3/8” of thermal expansion for every 10ft of CPVC/
PVC pipe. The boiler will always act as an anchor to one end of the vent system. If at all possible, select and
install hangers and wall thimbles so that the vent system can expand towards the terminal. When a straight
run of pipe exceeds 20ft and must be restrained at both ends, an offset or expansion loop must be provided
(Figures 7.3a, 7.3b). When a straight horizontal run of pipe exceeds 20ft and is restrained at one end with
an elbow at the other, avoid putting a hanger or guide less than “Y” inches from the elbow in the adjoining
straight section (Figure 7.3c). Thermal expansion fittings are not permitted.
• When properly assembled, expansion of PolyPro, Polyflue and InnoFlue vent systems is accommodated at
the joints. See Section VII - F, G & H of this manual for details.
• Stainless steel vent systems must be free to expand and contract in accordance with manufacturer’s
installation instructions.
10. Running PVC Vent Pipe Inside Enclosures and Through Walls - PVC vent pipe must be installed in a manner that
permits adequate air circulation around the outside of the pipe:
• Do not enclose PVC venting - Use CPVC in enclosed spaces, even if PVC is installed upstream.
• PVC venting may not be used to penetrate combustible or non-combustible walls unless all of the following
conditions are met:
a. The wall penetration is at least 66 inches from the boiler as measured along the vent.
b. The wall is 12” thick or less
c. An airspace of at least that shown in Figure 7.4 is maintained around the OD of the vent.
If any of these conditions cannot be met, use CPVC for the wall penetration.
11. Vent Manufacturer’s Instructions – The vent system manufacturer may have additional vent system design
requirements. Read and follow the vent manufacturer’s instructions in addition to those shown here. Where a
conflict arises between the two sets of instructions, the more restrictive requirements shall govern.
20
108095-02 - 4/18
Page 21
VII. Venting A. Vent System Design (continued)
Figure 7.3a
Figure 7.3c
Figure 7.3b
Figure 7.3: Expansion Loops for CPVC/PVC Pipe
Figure 7.4: Wall Penetration Clearances for PVC Vent Pipe
108095-02- 4/18
21
Page 22
VII. Venting B. Design Requirements Unique to Horizontal Twin Pipe Venting Systems (continued)
B. Design Requirements Unique to Horizontal Twin Pipe Venting Systems
Table 7.5 summarizes all horizontal twin pipe vent options. Illustrations of horizontal twin pipe vent systems
are shown in Figures 7.6 – 7.10. In addition to the requirements in Section VII - A, observe the following design
requirements:
1. Permitted Terminals for Horizontal Venting:
Terminal Option A: Fittings (Acceptable for Vent Options 1-4) – Vent terminates in a plain end (coupling for PVC,
bell end for PolyPro, Polyflue and plain end pipe for InnoFlue). Intake terminates in a PVC 90 sweep elbow
pointing down. Outer edge of both terminals must be within 10” of the wall surface (Figures 7.6, 7.9). The section
of DuraVent PolyPro, Centrotherm InnoFlue or Selkirk Polyflue exposed to the outdoors must be UV resistant.
Use of rodent screens (not supplied) is generally recommended for both terminations. These can be fabricated
from 2 x 2 (1/2” mesh) stainless steel screen. Rodent screens and are installed as shown in Figure 7.28. Rodent
screens (“bird guards”) for PolyPro, InnoFlue and Polyflue are as follows:
If necessary to achieve required clearance above grade, CPVC or CPVC/PVC vent systems may be terminated
using fittings on snorkels as shown in Figure 7.12. When this is done, the equivalent length of all pipe on the
exterior of the building, except for the terminal fittings themselves, must be counted when calculating the
equivalent length. The maximum vertical run of the snorkel is 7 feet. Brace both the vent and inlet piping if
required. PolyPro, InnoFlue and Polyflue may not be snorkeled.
Terminal Option B: Ipex Low Profile Terminal (Acceptable for Vent Option 1) – This terminal is shown in Figure
7.7. If the terminal is oriented vertically (alternate orientation shown in Fig 7.7) the exhaust opening must be
on the top as shown. See Section VII - E of this manual and the Ipex instructions provided with the terminal, for
installation details.
Terminal Option C: DiversiTech “Low Profile” Terminal (Acceptable for Vent Option 1) – This terminal is shown in
Figure 7.7. If the terminal is oriented vertically (alternate orientation shown in Fig 7.7) the exhaust opening must
be on the top as shown. See Section VII - E of this manual and the DiversiTech instructions provided with the
terminal, for installation details.
Terminal Option D: Ipex FGV Concentric Terminal (Acceptable for Vent Option 1) - This terminal is shown in
Figure 7.8 and may be used with CPVC/PVC vent systems. This terminal is available in various lengths and in
both PVC and CPVC. Terminals acceptable for use with these vent options are as follows:
Ipex PN FGV Concentric Terminal Description
196006 3 x 20” PVC
196106 3 x 32” PVC
196116 3 x 44” PVC
197107 3 x 32” CPVC
197117 3 x 44” CPVC
See Section VII - E of this manual and the Ipex instructions provided with the terminal, for installation details.
Terminal Option E: DiversiTech Concentric Terminal (Acceptable for Vent Option 1) - This terminal is shown in
Figure 7.8 and may be used with CPVC/PVC vent systems. See Section VII - E of this manual and the DiversiTech
instructions provided with the terminal, for installation details.
Terminal Option F: DuraVent PolyPro Concentric Terminal (Acceptable for Vent Option 2) - This terminal is shown
in Figure 7.10 and may be used with DuraVent 3” PolyPro vent systems. See Section VII - F of this manual and
the DuraVent instructions provided with the terminal, for installation details.
22
108095-02 - 4/18
Page 23
VII. Venting B. Design Requirements Unique to Horizontal Twin Pipe Venting Systems (continued)
Table 7.5: Summary of Horizontal Twin Pipe Venting Options
Vent Option1234
Illustrated in Figure7.6, 7.7, 7.87.9, 7.107. 97. 9
Pipe
1. Max vent lengths shown also apply to the intake. For example, Vent Option #1 may have up to 135ft of vent pipe and also up
to 135 ft of intake pipe.
2. First 30” of vent and vent Elbow connected to boiler must be CPVC. Downstream vent pipe can be PVC except as noted in
text.
3. PVC Terminal coupling and inlet elbow may be offset on snorkels as shown in Figure 7.12.
108095-02- 4/18
23
Page 24
VII. Venting B. Design Requirements Unique to Horizontal Twin Pipe Venting Systems (continued)
PITCH INTAKE AWAY FROM
BOILER IF POSSIBLE
BOILER ROOM
TRIM
COLLAR
BUILDING EXTERIOR
2. Horizontal Vent and Air Intake Terminal Location - Observe the following limitations on the vent terminal location
(also see Figure 7.11). When locating a concentric terminal, observe the limitations outlined below for “vent
terminals”.
• Vent terminal must be at least 1 foot from any door, window, or gravity inlet into the building.
• When Terminal Option A (fittings) are used, maintain the correct clearance and orientation between
the intake and exhaust terminals. If possible, locate vent and combustion air terminals on the same
wall to prevent nuisance shutdowns. If not, boiler may be installed with roof vent terminal and sidewall
combustion air terminal (see Section D). When installed on the same wall, locate exhaust vent terminal at
same height or higher than combustion air intake terminal. Horizontal separation: Recommended: 36”,
Minimum: 12”, Maximum: none. Minimum horizontal separation of 12” is required regardless of vertical
separation.
• The bottom of all terminals must be at least 12” above the normal snow line. In no case should they be less
than 12” above grade level.
• The bottom of the vent terminal must be at least 7 feet above a public walkway.
• Do not install the vent terminal directly over windows or doors.
• The bottom of the vent terminal must be at least 3 feet above any forced air inlet located within 10 feet.
• USA Only: A clearance of at least 4 feet horizontally must be maintained between the vent terminal
and gas meters, electric meters, regulators, and relief equipment. Do not install vent terminal over this
equipment. In Canada, refer to B149.1 Installation Code for clearance to meters, regulators and relief
equipment.
• Do not locate the vent terminal under decks or similar structures.
• Top of terminal must be at least 24” below ventilated eves, soffits and other overhangs. In no case may the
overhang depth exceed 48”. Where permitted by the authority having jurisdiction and local experience,
the terminal may be located closer to unventilated soffits. For the minimum vertical separation, which
depends upon the depth of the soffit, see Figure 7.11.
• Vent terminal must be at least 6 feet from an inside corner.
• Under certain conditions, water in the flue gas may condense, and possibly freeze, on objects around
the vent terminal including on the structure itself. If these objects are subject to damage by flue gas
condensate, they should be moved or protected.
• Install the vent and air intake terminals on a wall away from the prevailing wind. Reliable operation of this
boiler cannot be guaranteed if these terminals are subjected to winds in excess of 40 mph.
• Air intake terminal must not terminate in areas that might contain combustion air contaminates, such as
near swimming pools. See WARNING on page 14.
Figure 7.10: Duravent PolyPro Horizontal Venting with Concentric Terminal,
26
BUILDING EXTERIOR
(Vent Option #2, Terminal Option F)
108095-02 - 4/18
Page 27
VII. Venting B. Design Requirements Unique to Horizontal Twin Pipe Venting Systems (continued)
108095-02- 4/18
Terminal (Shown) Two-Pipe System Air Intake Terminal (Not Shown)
Note: Air intake termination not shown.
Figure 7.11: Location of Vent Terminal Relative to Windows, Doors, Grades, Overhangs, Meters and Forced Air Inlets - Two-Pipe System Vent
27
Page 28
VII. Venting C. Design Requirements Unique to Vertical Venting Systems (continued)
Figure 7.12: Snorkel Terminal Configuration (CPVC/PVC Vent Systems Only)
C. Design Requirements Unique to Vertical Venting Systems
Table 7.13a summarizes all vertical twin pipe vent options. Table 7.13.b summarizes vent options in which an
abandoned B-vent chimney is used both as a chase for the vent pipe and as a conduit for combustion air.
In addition to the requirements in Section VII - A, observe the following design requirements:
1. Permitted Terminals for Vertical Venting
Terminal Option H: Fittings (Acceptable for Vent Options 5-8) – Vent terminates in a plain end (coupling for PVC,
bell end for PolyPro, Polyflue and plain end pipe for InnoFlue). Intake terminates in a PVC 180 elbow pointing
down (two sweep 90’s may be substituted). Observe the clearances from the roof, and normal snow line on the
roof, shown in Figures 7.15 and 7.17. The section of PolyPro, Polyflue or InnoFlue exposed to the outdoors must
be UV resistant.
Use of rodent screens (not supplied) is generally recommended for both terminations. These can be fabricated
from 2 x 2 (1/2” mesh) stainless steel screen. Rodent screens and are installed as shown in Figure 7.29. Rodent
screens (“bird guards”) for PolyPro, InnoFlue and Polyflue are as follows:
Terminal Option I: Ipex FGV Concentric Terminal (Acceptable for Vent Option 5) - This terminal is shown in
Figure 7.16 and may be used with CPVC/PVC vent systems. Use a compatible roof flashing and storm collar in
accordance with the Ipex instructions for this terminal. This terminal is available in various lengths and in both
PVC and CPVC. Terminals acceptable for use with these vent options are as follows:
1. Max vent lengths shown also apply to the intake. For example, Vent Option #1 may have up to 135ft of vent pipe and also
up to 135 ft of intake pipe.
2. First 30” of vent and vent Elbow connected to boiler must be CPVC. Downstream vent pipe can be PVC except as noted in
text.
3. Ipex FGV Concentric Terminal available in various lengths and also CPVC (see text).
CVENT-3 Not Permitted
Not
Permitted
3PPS-VKNot Permitted
All vertical terminals require compatible roof flashing and storm collars.
108095-02- 4/18
29
Page 30
VII. Venting C. Design Requirements Unique to Vertical Venting Systems (continued)
Table 7.13b: Summary of Vertical “B-Vent Air Chase” Vent Options
(B-Vent Chase MUST Be Sealed)
Option910
Illustrated in Figure7. 1 97.20
Pipe Penetration
Through Structure
Material
Nominal Diameter
Min Equivalent Vent Length:
Models
Max Equivalent Vent Length (Note 1):
Models
Vent Manufacturer’s PN for Flex
Termination/Components Required
VentRoofRoof
IntakeRoofRoof
Vent
IntakeB Vent/PVCB Vent/PVC
Vent3”3”
Intake3”3”
Min B Vent ID6”6”
13536”36”
15052”52”
18052”52”
135135ft135ft
150135ft135ft
180135ft135ft
DuraVent
PolyPro
(Rigid/Flex)
3PPS-VFT
3PPS-BV*
3PPS-FLEX**
Centrotherm
InnoFlue
SW/Flex
IFBK03****
IAWP03B
* Specify size of B vent (e.g. 3PPS-BV6 is for use with 6” B vent)
** Specify length in feet.
**** Specify Flex length and B-vent diameter (e.g. IFBK032506 includes 25ft of flex and used with 6” B
vent)
Note 1: Max vent lengths shown also apply to the intake. Flex vent reduces the maximum allowable
vent length. See equivalent lengths for flex vent shown in Table 7.14 and sizing example on next
page.
NOTICE Vertical venting and combustion air roof penetrations (where applicable) require the use of roof
flashing and storm collar, which are not supplied with the boiler, to prevent moisture from entering the
structure.
30
108095-02 - 4/18
Page 31
VII. Venting C. Design Requirements Unique to Vertical Venting Systems (continued)
Terminal Option J: DiversiTech Concentric Terminal (Acceptable for Vent Option 5) - This terminal is shown
in Figure 7.16 and may be used with CPVC/PVC vent systems. See Section VII - E of this manual and the
DiversiTech instructions provided with the terminal, for installation details.
Terminal Option K: DuraVent PolyPro Concentric Terminal (Acceptable for Vent Option 6) - This terminal is shown
in Figure 7.18 and may be used with DuraVent 3” PolyPro vent systems. Use a compatible DuraVent roof flashing
and storm collar in accordance with the DuraVent instructions for this terminal See Section VII - F of this manual
and the DuraVent instructions provided with the terminal, for installation details.
2. Vertical Vent and Air Intake Location – Observe the following clearances from roof mounted terminals:
• Bottom of air intake opening must be at least 12” above the normal snow line anticipated on the roof.
• Exhaust opening must be at least 2ft above any portion of the roof or structure located within horizontally
within 10ft.
• For terminal option H, maintain at least 12” of vertical separation between the exhaust and intake opening as
shown in Figure 7.15 and 7.17.
3. Requirements for B-Vent Air Chase Options – Observe the following additional requirements when using an
abandoned B-vent chimney as an air chase as described in Options # 9 & 10. Also refer to Figures 7.19 & 7.20.
• B vent must be clean and in good condition.
• Use of flex Polypropylene outside of B-vent chimney is not permitted.
• All joints and seams in the B-vent must be sealed with RTV. If these seams are not accessible, vent options
9 - 10 cannot be used while complying with the National Fuel Gas Code (as an alternative, the B-vent chimney can be used as a chase for the vent pipe while combustion air is piped from an outside wall - see
Section VII - D for additional details).
• All venting is Polypropylene supplied by the vent manufacturer shown in Table 7.13b. The portion of this
venting within the B–vent is flexible.
• All flex pipe must be installed vertically. Up to two offsets (four bends) may be made in the vertical run of flex
pipe. Bends used to make these offsets may not exceed 45 degrees.
• Because the flex pipe is corrugated, it has a higher pressure drop than the rigid pipe used elsewhere in the
vent system. Equivalent lengths for flex venting are shown in Table 7.14. Reduce the maximum allowable
vent length shown in Table 7.13b by this equivalent length for each foot of flex pipe used, as well as for each
elbow in addition to the first. The termination is not counted. If offsets (described above) are present, the
equivalent length of the bends in these offsets can also be ignored.
Example: A 135MBH model is to be installed as using Vent Option 9 as shown in Figure 7.19. The following
components are used:
Intake:
3” PVC – 6ft
3” PVC Sweep 90 – 3
Turn in B vent Tee
Straight B-vent (6” or larger) containing flex vent – 20ft
DuraVent 3PPS-VFT Terminal (intake side)
Vent Equivalent length – First elbow is ignored. The terminal is also ignored. From Table 7.14, the equivalent
length of 3” DuraVent Poly-Pro Flex is 2.0ft. From Table 7.1 the equivalent length of the second 90 elbow is 8.7ft.
The equivalent length of the vent system is therefore:
4 + 8.7 + (20 x 2.0) = 52.7ft.
Since Vent Option 9 shows a max vent length of 135ft, the planned vent length of OK.
Intake Equivalent length - First elbow and the turn in the B vent tee are ignored, leaving two sweep 90 elbows
that must be counted. From Table 7.1, the equivalent length of each of these elbows is 4.0ft. From Table 7.14 the
equivalent length of the vent containing flex is 1.0ft. Equivalent length of the intake system is therefore:
(2 x 4.0) +6 +(20 x 1.0) = 34.0ft.
Since this is less than 135ft, the planned intake length is OK.
108095-02- 4/18
31
Page 32
VII. Venting C. Design Requirements Unique to Vertical Venting Systems (continued)
Table 7.14: Equivalent Length of Flex Pipe
Equivalent Length (ft)
Flex Vent (1 ft):
3” DuraVent PolyPro Flex2.0 ft
3” Centrotherm InnoFlue Flex2.3 ft
3” Selkirk Polyflue2.3 ft
3” Duravent FasNSeal Flex1.0 ft
B-Vent Air Chase (1ft):
3” Flex Vent in 6” (or larger) B-Vent1.0 ft
Note: Up to four 45 degree bends may be made in flex pipe or air chase.
These bends are not counted when figuring equivalent length.
32
108095-02 - 4/18
Page 33
VII. Venting C. Design Requirements Unique to Vertical Venting Systems (continued)
Figure 7.16: Vertical CPVC/PVC Venting with IPEX Concentric Vent Terminal
(Vent Option 5, Terminal Option I, J)
108095-02- 4/18
33
Page 34
VII. Venting C. Design Requirements Unique to Vertical Venting Systems (continued)
Figure 7.17: Duravent PolyPro, Selkirk Polyflue or Centrotherm InnoFlue Vertical Single Wall PP Venting
(Vent Options #6-8, Terminal Option H)
Figure 7.18: Duravent PolyPro Vertical Venting with Concentric Terminal
34
(Vent Option #6, Terminal Option K)
108095-02 - 4/18
Page 35
VII. Venting C. Design Requirements Unique to Vertical Venting Systems (continued)
3
Figure 7.19: Duravent PolyPro B-Vent Air Chase System (Vent Option #9)
Figure 7.20: Centrotherm InnoFlue B-Vent Air Chase System (Vent Option #10)
108095-02- 4/18
35
Page 36
VII. Venting D. Design Requirements Unique to Split Vent Systems (continued)
D. Design Requirements Unique to Split Vent Systems
Table 7.21 summarizes all split vent options. Illustrations of split vent systems are shown in Figures 7.22, 7.23,
7.24a and 7.25a. In addition to the requirements in Section VII - A, observe the following design requirements:
1. Permitted Terminals for Split Venting:
Rigid Vent Systems (Vent Options 11-14) – Vent terminates in a plain end (coupling for PVC, bell end for PolyPro,
Polyflue, and plain end pipe for InnoFlue). Intake terminates in a PVC 90 sweep elbow pointing down. The
section of PolyPro, Polyflue or InnoFlue exposed to the outdoors must be UV resistant.
Use of rodent screens (not supplied) is generally recommended for both terminations. These can be
fabricated from 2 x 2 (1/2” mesh) stainless steel screen. Rodent screens and are installed as shown in Figure
7.28. Rodent screens are installed as shown in Figure 7.28. Rodent screens (“bird guards”) for PolyPro, Polyflue
and InnoFlue are as follows:
Flex Vent Terminals (Options 15-18) – The flex vent kits shown for options 15-18 include vent terminals that must
be installed in accordance with the vent manufacturer’s instructions. In some cases, different terminals are used
for Masonry and B-vent chimney chases.
Air Intake Terminals (Vent Options 11-18) - All split venting options shown in Tables 7.21 terminate in a
PVC 90 sweep elbow pointing down. Use of rodent screens (not supplied) is generally recommended for both terminations. These can be fabricated from 2 x 2 (1/2” mesh) stainless steel screen. Rodent screens and
are installed as shown in Figure 7.28.
2. Vent Terminal Location – Observe the following clearances from roof mounted vent terminals (also see Figures
7.22, 7.23, 7.24a or 7.25a):
• Bottom of terminal must be at least 12” above the normal snow line anticipated on the roof.
• Exhaust opening must be at least 2ft above any portion of the roof or structure located within horizontally
within 10ft.
3. Horizontal Air Intake Terminal Location - Observe the following limitations on the intake terminal location (also
see Figures 7.22, 7.23,7.24a, and 7.25a):
• The bottom of all terminals must be at least 12” above the normal snow line. In no case should they be less
than 12” above grade level.
• If possible, install the intake terminal on a wall away from the prevailing wind. Reliable operation of this boiler
cannot be guaranteed if the intake terminal is subjected to winds in excess of 40 mph.
• Air intake terminal must not terminate in areas that might contain combustion air contaminates, such as near
swimming pools. See WARNING on page 13.
4. Use of abandoned chimneys as a Vent Chase for flexible Polypropylene Venting (Options 15-17) – Vent options
15-17 permit flexible Polypropylene venting to be routed to the roof using an abandoned masonry or B- vent
chimney. In these applications combustion air is drawn horizontally from a wall terminal. See Figure 7.23 or
7.24a. When using one of these vent options, observe the following requirements:
• When a masonry chimney containing multiple flues is used as a chase, ALL flues must be abandoned
(Figure 7.24b).
• Masonry or B vent chimney used as a chase must be structurally sound and in good repair.
• Use of flex Polypropylene outside of a masonry or B-vent chimney is not permitted unless allowed by the
vent manufacturer and permitted by local codes.
• All venting is Polypropylene supplied by the vent manufacturer shown in Table 7.21. The portion of this
venting within the masonry or B–vent chimney is flexible.
• All flex pipe must be installed vertically. Up to two offsets (four bends) may be made in the vertical run of flex
pipe. Bends used to make these offsets may not exceed 45 degrees (Figure 7.24b).
• Because the flex pipe is corrugated, it has a higher pressure drop than the rigid pipe used elsewhere in the
vent system. Equivalent lengths for flex venting are shown in Table 7.14. Reduce the maximum allowable
vent length shown in Table 7.21 by this equivalent length for each foot of flex pipe used, as well as for each
elbow in addition to the first. The first elbow and termination are not counted. If offsets (described above)
are present, the equivalent length of the bends in these offsets can also be ignored.
36
108095-02 - 4/18
Page 37
VII. Venting D. Design Requirements Unique to Split Vent Systems (continued)
5. Use of abandoned chimney as vent chase for flexible Stainless Steel venting (option 18) - Vent option 18 permits
flexible Stainless Steel venting to be routed to the roof using an abandoned masonry type chimney. In this application, combustion air is drawn horizontally from a wall terminal. See Figure 7.25a. When using one of these
options, observe the following requirements:
• When a masonry chimney containing multiple flues is used as a chase, the flexible stainless vent installation
is permitted through an adjacent UNUSED flue providing local authority having jurisdiction approves such
installation. (Figure 25b)
• Masonry chimney used as a chase must be structurally sound and in good repair.
• All venting is stainless steel supplied by the vent manufacturer shown in Table 7.21. The portion of this
venting within the masonry or B-vent chimney is flexible.
• When flexible stainless steel is used for combustion product venting, it must be installed at vertical or near
vertical plane. This will insure proper condensate flow back to the boiler. (Figure 25a)
Example: A 135MBH model is to be installed as using Vent Option 15 in a masonry chimney as shown in Figure
7.24a. The following components are used:
Vent:
3” DuraVent Poly-Pro (Rigid) – 4ft
3” DuraVent Poly-Pro Flex – 30ft
Poly-Pro elbows – 2 (one at base of chimney and one above boiler)
DuraVent 3PPS-FK Terminal
Intake:
3” PVC – 6ft
3” PVC Sweep 90 – 2 (one above the boiler and one as an intake terminal)
Vent Equivalent length – First elbow is ignored. The terminal is also ignored. From Table 7.14, the equivalent
length of 3” DuraVent Poly-Pro Flex is 2.0ft. From Table 7.1 the equivalent length of the second 90 elbow is 8.7ft.
The equivalent length of the vent system is therefore:
4 + 8.7 + (30 x 2.0) = 72.7ft.
Since Vent Option 15 shows a max vent length of 135ft, the planned vent length of OK.
Intake Equivalent length - First elbow and termination elbow are ignored, leaving just the straight pipe.
Equivalent length of the intake system is therefore 6ft. Since this is less than 135ft, the planned intake length is
OK.
WARNING
Asphyxiation Hazard. Flexible polypropylene vent must be installed only in an UNUSED
chimney. A chimney flue is considered UNUSED when it is not being used for any appliance venting. If
chimney is a multiple flue type where one of the multiple flues is being used for an appliance venting, the
flexible vent installation is not permitted through any of the adjacent flues.
Asphyxiation Hazard. Flexible stainless steel vent must be installed only in an UNUSED chimney flue. A
chimney flue is considered UNUSED when it is not being used for any appliance venting. If chimney is
a multiple flue type where one of the multiple flues is being used for an appliance venting, the flexible
stainless vent installation is permitted through an adjacent, unused flue providing a local authority having
jurisdiction approves such installation.
108095-02- 4/18
37
Page 38
VII. Venting D. Design Requirements Unique to Split Vent Systems (continued)
Table 7.21: Summary of Split Vent System Options
Option #111213141516
Illustrated in Figure7.227.227.227.227.23, 7.247.23, 7.24
* Specify size of B vent (e.g. 3PPS-BV6 is for use with 6” B vent).
** Specify length in feet.
Note 1: Max vent lengths shown also apply to the intake. Flex vent reduces the maximum allowable vent length in some
applications. See equivalent lengths for flex vent shown in Table 7.14 and sizing example on page 32.
Note 2: First 30” plus first exhaust elbow are CPVC.
Note 3: See Polyflue installation manual for gaskets, spacers and other required vent components.
All vertical terminals require compatible roof flashing and storm collars.
38
108095-02 - 4/18
Page 39
VII. Venting D. Design Requirements Unique to Split Vent Systems (continued)
Table 7.21: Summary of Split Vent System Options (cont.)
** Specify length in feet.
**** Specify Flex length and B vent diameter (e.g. IFBK032506 includes 25ft of flex and used with 6” B vent).
Note 1: Max vent lengths shown also apply to the intake. Flex vent reduces the maximum allowable vent length in
some applications. See equivalent lengths for flex vent shown in Table 7.14 and sizing example on page 32.
VentIFCK03**
Intake
VentIFBK03****2SVFLXR03
Intake
90 Elbow
w/Screen
90 Elbow
w/Screen
2SVSCKIT03**
2SVFLXCN03**
90 Elbow
w/Screen
90 Elbow
w/Screen
All vertical terminals require compatible roof flashing and storm collars.
108095-02- 4/18
39
Page 40
VII. Venting D. Design Requirements Unique to Split Vent Systems (continued)
FIRE STOP LISTED FOR
USE WITH VENT SYSTEM
PITCH 1/4" PER FT TOWARDS TRAP
PVC AIR
INTAKE PIPE
Figure 7.22: Split Rigid Vent System (Vent Options 11-14)
PVC AIR INTAKE PIPE
Figure 7.23: Split Vent System (Flex in B-Vent Chase) Vent Options 15-17)
40
108095-02 - 4/18
Page 41
VII. Venting D. Design Requirements Unique to Split Vent Systems (continued)
EXHAUST
NOTE: DURAVENT POLYPRO FLEX
COMPONENTS SHOWN.
PPs FLEX
CLEAN, TIGHT
UNUSED CHIMNEY
BASE SUPPORT
AND ELBOW FOR
PPs FLEX PIPE
EXTERIOR
WALL PLATE
DURAVENT POLYPRO
VENT PIPE
PVC AIR
INTAKE PIPE
BOILER
OUTSIDE WALL
PVC ELBOW
WITH RODENT
SCREEN
12" MIN
NORMAL SNOW
LINE ABOVE
GROUND LEVEL
10" OR LESS
Figure 7.24a: Split Vent System (PP Flex in Abandoned Masonry Chimney) (Vent Options 15-17)
108095-02- 4/18
41
Page 42
VII. Venting D. Design Requirements Unique to Split Vent Systems (continued)
VII. Venting D. Design Requirements Unique to Split Vent Systems (continued)
RIGID SINGLE WALL VENT
RIGID TEE
FOR SS FLEX PIPE W/
CONDENSATE DRAIN CAP
CLEAN, UNUSED,
MASONRY CHIMNEY FLUE
STAINLESS STEEL, DOUBLE LAYER, FLEXIBLE
LINER
EXTERIOR WALL PLATE
BOILER
FEMALE FLEX ADAPTER
MALE FLEX ADAPTER
RIGID ELBOW FOR SS FLEX PIPE
ALTERNATE VENT PIPING
RIGID TEE WITH CONDENSATE
DRAIN CAP
12" MIN.
10" OR LESS
NORMAL SNOW
LINE ABOVE
GROUND LEVEL
PVC ELBOW
WITH RODENT
SCREEN
PVC AIR
INTAKE PIPE
OUTSIDE WALL
RAIN CAP
Figure 7.25a: Split Vent Systems (SS Flex in Abandoned Masonry Chimney) (Vent Option 18)
Figure 7.25b: Flexible SS Masonry Chimney Chase Requirements
108095-02- 4/18
43
Page 44
VII. Venting E. Assembly of CPVC/PVC Vent Systems (continued)
E. Assembly of CPVC/PVC Vent Systems
WARNING
Asphyxiation Hazard. Failure to follow these instructions could cause products of
combustion to enter the building, resulting in severe property damage, personal injury or death.
•
Use all CPVC vent components for near-boiler vent piping before transitioning to Schedule 40 PVC pipe
(ASTM 2665) components for remainder of vent system.
•
Use CPVC vent components within any interior space where air cannot circulate freely, including through
vertical or horizontal chase ways, inside a stud wall, in closets and through wall penetrations.
•
The use of cellular core PVC (ASTM F891), cellular core CPVC or Radel (polyphenolsulfone is prohibited.
•
All condensate that forms in the vent must be able to drain back to the boiler.
•
Never leave the boiler in operation without the gas sample cap in place (Figure 7.27).
1. Assemble the vent system, starting at the boiler:
a. If 3” PVC is to be used for venting, a 3” CPVC elbow and the 30” straight section of CPVC must be used
before transitioning to PVC. If necessary the 30” straight section of CPVC may be cut at any location and a
CPVC elbow can be inserted between the two resulting segments.
b. When cutting CPVC or PVC pipe, use a miter saw or a saw designed to cut PVC pipe. Use a miter box or
other method to cut pipe squarely. De-burr both the inside and outside of the cut end.
c. Dry fit all vent components before assembly.
d. The vent adaptor has three different inside diameters. The larger (upper) inside diameter accepts 3” CPVC
pipe and is used in this application (the middle inside diameter accepts 3” nominal PolyPro, Polyflue or
InnoFlue, and the smaller, lower inside diameter accepts 3” stainless steel). A locking band clamp in the
adaptor prevents the vent pipe from coming out of the adaptor once it is installed and tightened. Lubricate the
upper gasket in the vent adaptor with water and insert the first piece of 3” CPVC into the vent adaptor until it
bottoms out. Tighten locking band clamp to secure vent pipe.
e. Assemble a 3” CPVC elbow and remainder of 30” CPVC piping before transitioning to PVC. If 3” PVC is
used, the first piece of PVC will either be connected to the CPVC elbow or the end of a section of CPVC vent
pipe. In the latter case, a PVC coupling may be used to connect the first piece of PVC to the last piece of
CPVC.
f. Clean all CPVC and PVC components with the appropriate primer before cementing. Cement the vent system
together, starting at the boiler and following the instructions provided on the cans of cement and primer. Use
a field supplied cement and primer that is listed for use with the materials being joined (CPVC and/or PVC).
The following, or its equivalent, may be used to join CPVC to PVC:
Always use primer on both the pipe and fitting before applying the cement. Assemble the pipe in
accordance with the instructions on the cans of primer and cement.
g. Assemble the rest of the vent system, being sure to pitch horizontal sections back towards the boiler 1/4”/ft.
Support the vent at intervals not exceeding 4ft.
h. Maintain the clearances from the vent pipe outlined in Section VII - A of this manual. If exiting the exterior wall
using PVC pipe, use half of an appropriately sized wall thimble (or a sheet metal plate) on the exterior of the
building, to provide a weather tight seal while maintaining the proper clearance in the wall penetration. Seal
the joint between the pipe and the wall plate using RTV applied on the exterior side of the wall. This sealant
must not restrain the expansion of the vent pipe.
2. Installation of Air Intake System - Start assembly of the PVC air intake system at the boiler. Assembly of the air
intake system is done in the same manner as the vent system except as follows:
a. Drill a 7/32” clearance hole into the front side of the air intake adapter. Insert the first piece of PVC air
intake pipe into the air intake connection and drill a 1/8” tap hole into the PVC which lines up with the
7/32” clearance hole and secure them together with a #10 x 1” sheet metal screw. Seal the joint
between the intake pipe and the adaptor with RTV.
b. All intake piping may be PVC.
c. There is a 0” minimum clearance between the air intake piping and all types of construction.
d. To the extent possible, pitch horizontal air intake piping towards the outdoors.
44
108095-02 - 4/18
Page 45
VII. Venting E. Assembly of CPVC/PVC Vent Systems (continued)
Figure 7.27: Vent Connections and Flue Gas Sample Cap Location
3. Installation of Horizontal Fitting Terminals (Terminal Option A):
a. See Figure 7.28 for proper orientation of twin pipe horizontal terminals. Outer edge of both terminals must be
within 10” from wall surface. (Figure 7.6)
b. If desired, the terminals can be attached to the end of the vent and/or intake pipes with field supplied
stainless steel screws so that they can be later removed for cleaning and inspection. If this is done, drill a
clearance hole in the coupling or elbow and a tap hole in the end of the vent/intake pipes to accept these
screws.
c. If these terminals are installed on snorkels, assemble the snorkels as shown in Figure 7.12. Brace the vertical
run of piping on the building exterior as required.
4. Installation of Vertical Fitting Terminals (Terminal Option H):
a. See Figure 7.29for the proper orientation of twin pipe vertical terminals.
b. The coupling is used to secure the rodent screen to the end of the vent pipe.
c. A 180° bend (or two 90° elbows) are installed on the top of the air intake pipe. If two 90° elbows are used, a
rodent screen can be installed between them (Figure 7.29). If a 180° bend is used, install a rodent screen in
the open side of the bend, using a ring made of PVC pipe. If desired, the termination fittings can be attached
to the end of the vent and/or intake pipes with field supplied stainless steel screws so that they can be later
removed for cleaning and inspection. If this is done, drill a clearance hole in these fittings and a tap hole in
the end of the vent/intake pipes to accept these screws.
d. Use roof flashings and storm collars to prevent moisture from entering the building. Seal the roof flashing to
the roof using generally accepted practice for the type of roof on the installation. Apply RTV to seal the storm
collars to the vent and intake pipes.
5. Installation of IPEX low profile vent terminal (Terminal Option B) - See Figure 7.30:
a. Cut two holes in wall to accommodate the size PVC pipe being used. The distance between hole centers is
5.6”.
b. Slide both vent and intake air pipes through the holes, and cement them to the base of the vent termination kit
using a primer and cement listed for use with PVC.
c. Fasten the vent base to the wall using the supplied screws and anchors. The anchors require the drilling of a
3/16” hole x 1-3/16” deep. Locate the holes using the vent base as a template.
d. Screw the vent cap to the vent base using the supplied screws.
108095-02- 4/18
45
Page 46
VII. Venting E. Assembly of CPVC/PVC Vent Systems (continued)
Figure 7.28: Installation of Standard Horizontal Terminals
Figure 7.29: Installation of Standard Vertical Terminals
46
108095-02 - 4/18
Page 47
VII. Venting E. Assembly of CPVC/PVC Vent Systems (continued)
e. Once the vent termination and pipes are secure seal the wall penetrations from the interior using a weather
resistant RTV sealant.
6. Installation of DiversiTech Low Profile Terminal (Terminal Option C) – See Figure 7.31:
a. Use vent plate as a guide to locate the openings for the vent and air intake pipes, as well as to locate the
holes for the mounting screws.
b. Drill two 3-1/8 holes through the wall for the vent and intake pipes.
c. Drill four 3/16 holes for the mounting screws.
d. Install the vent and intake pipe sections passing through the wall. Cut the pipes so that they protrude the
following distances from the surface on which the vent plate will be mounted:
• Vent: Between 1-3/4 and 2-1/4”
• Intake: Between ¼ and 1”
e. Seal pipe penetrations in wall with RTV (silicone sealant).
f. Mount the vent plate using the #8 x 2” screws and anchors provided with this kit.
g. Seal the vent plate to the wall with RTV.
h. Apply a bead of RTV around the OD of the vent pipe near its end.
i. Slide the vent cap over the vent pipe and secure to the wall plate with the #8 x 2” screws provided.
7. Installation of IPEX FGV or DiversiTech CVENT Concentric Vent Terminal (Terminal Options D,E,I & J) - This
terminal may be used for either horizontal or vertical venting. See Figure 7.33 for horizontal installation or Figure
7.34 for vertical installation. When PVC is used for venting, a 30” CPVC straight section and CPVC elbow must
be used prior to connection of the vent system to this terminal. If the vent system is too short to permit this, use
the IPEX FGV CPVC terminal:
a. For horizontal installations at the planned location cut a round hole in the exterior wall 1/2” larger than the “C’
dimension indicated on Figure 7.32 for the size terminal being used. (See Section VII - B of this manual for
permitted terminal locations).
b. For vertical installations, cut a hole in the roof large enough to clear the concentric terminal at the location of
the terminal (see Section VII - C of this manual for permitted terminal locations).
c. If desired, the terminal can be shortened. See Figure 7.32 for specific information on making the terminal kit
shorter based on the kit size being used. Cut the pipe squarely and de-burr both the OD and ID of the cut
edges.
d. Cement the inner pipe section of PVC pipe supplied with this kit to the Wye fitting using a primer and cement
listed for use with PVC.
e. Cement the outer pipe to the Wye, being careful, to keep the inner and outer pipes concentric.
f. Slip the partially assembled terminal through the wall or ceiling from the inside and for horizontal installations
orient so that the side outlet on the Wye is on or above the horizontal plane.
g. For horizontal installations, seal the gap between the OD of the “outer pipe” and the exterior side of the wall
with RTV sealant.
h. Cement the rain cap onto the inner pipe. If desired, the rain cap can be attached to the inner pipe with the
supplied stainless steel screw and nut so that it can be later removed for cleaning and inspection. If this is
done, drill a 3/16”clearance hole in the rain cap and inner pipe in the location shown on Figure 7.32 for the
size terminal kit being used and affix screw and nut. Do not overtighten. A field supplied rodent screen may
also be installed on the end of the rain cap.
WARNING
Asphyxiation Hazard. CPVC/PVC vent piping and fittings rely on glued joints for proper
sealing. Follow all manufacturer instructions and warnings when preparing pipe ends for joining and
using the primer and the cement.
•
When PVC is used with the concentric vent kit, a 30” CPVC straight section and elbow must be used prior
to connection of the vent system to this terminal. If the vent system is too short to permit this, use an FGV
CPVC terminal.
•
Do not operate boiler without the rain cap in place.
•
Method of securing and sealing terminals to the outside wall must not restrain the expansion of vent
pipe.
108095-02- 4/18
47
Page 48
VII. Venting E. Assembly of CPVC/PVC Vent Systems (continued)
Figure 7.30: Installation of IPEX Low Profile Terminal Through Sidewall
Figure 7.31: Installation of DiversiTech Low Profile Terminal Through Sidewall
48
108095-02 - 4/18
Page 49
VII. Venting E. Assembly of CPVC/PVC Vent Systems (continued)
Figure 7.32: Cutting IPEX and DiversiTech Concentric Vent Terminals
Figure 7.33: Installation of IPEX and DiversiTech Concentric Terminal through Sidewall
108095-02- 4/18
49
Page 50
VII. Venting E. Assembly of CPVC/PVC Vent Systems (continued)
Figure 7.34: Installation of IPEX and DiversiTech Concentric Terminal Through Roof
i. For vertical installations, use a roof flashing and storm collar to prevent moisture from entering the building.
Seal the roof flashing to the roof using generally accepted practice for the type of roof on the installation.
Install the storm collar after verifying that the bottom of the rain cap will be at least 12” above the normal snow
line. Apply RTV to seal the storm collars to the terminal.
50
108095-02 - 4/18
Page 51
VII. Venting F. Assembly of DuraVent PolyPro Vent Systems (continued)
F. Assembly of DuraVent PolyPro Vent Systems
1. This boiler has been approved for use with the DuraVent PolyPro single wall Polypropylene vent system to be
provided by the installer.
WARNING
Asphyxiation Hazard. Follow these instructions and the installation instructions included
by the original Polypropylene venting component manufacturers, M&G/DuraVent. Failure to do so could
cause products of combustion to enter the building, resulting in severe property damage, personal injury
or death. Where a conflict arises between M&G/DuraVent instructions and these instructions, the more
restrictive instructions shall govern. If any controls are replaced, they must be replaced with identical
models.
Do not mix vent components or joining methods for listed manufacturers.
Examine all components for possible shipping damage prior to installation.
All condensate that forms in the vent must be able to drain back to the boiler.
2. Assemble the vent system, starting at the boiler:
a. The vent adaptor has three different inside diameters. The middle inside diameter accepts 3” nominal PolyPro
(Figure 7.27). A locking band clamp in the adaptor prevents the vent pipe from coming out of the adaptor
once it is installed and tightened. Lubricate the upper gasket in the vent adaptor with soapy water and insert
the first piece of 3” PolyPro into the adaptor until it bottoms out. Tighten locking band clamp to secure vent
pipe.
b. Assemble the next piece of 3” PolyPro.
c. For each joint, verify that the gasket is evenly seated in the bell (female) end of the pipe. Lubricate this gasket
with water. Slide a locking band over the male end of the pipe to be joined as shown in Figure 7.35. Push the
male end of the next section of pipe into the bell until it bottoms out, then back out 1/4-5/8” to provide room
for thermal expansion. Push barb on locking band over the bell end of the first section of pipe as shown in
Figure 7.35.
d. Assemble the rest of the vent system per the manufacturer’s installation instructions, being sure to pitch
horizontal sections back towards the boiler 5/8” per ft.
e. Support each horizontal pipe section with a minimum of one wall strap each and at intervals not exceeding
4ft.
Figure 7.35: PolyPro Locking Band Installation
108095-02- 4/18
51
Page 52
VII. Venting F. Assembly of DuraVent PolyPro Vent Systems (continued)
3. Installation of Air Intake System - Start assembly of the PVC air intake system at the boiler. Assembly of the air
intake system is done in the same manner as the vent system except as follows:
a. Drill a 7/32” clearance hole into the front side of the air intake adapter. Insert the first piece of PVC air
intake pipe into the air intake connection and drill a 1/8” tap hole into the PVC which lines up with the 7/32”
clearance hole and secure them together with a #10 x 1” sheet metal screw. Seal the joint between the intake
pipe and the adaptor with RTV.
b. All intake piping may be PVC.
c. There is a 0” minimum clearance between the air intake piping and all types of construction.
d. To the extent possible, pitch horizontal air intake piping towards the outside.
WARNING
Asphyxiation Hazard. Vent systems made by M&G/DuraVent rely on gaskets for proper
sealing. When these vent systems are used, take the following precautions:
• Make sure that gasket is in position and undamaged in the female end of the pipe.
• Make sure that both the male and female pipes are free of damage prior to assembly.
• Only cut vent pipe as permitted by the vent manufacturer in accordance with their instructions. When
pipe is cut, the cut end must be square and carefully de-burred prior to assembly.
• Use locking band clamps at all vent pipe joints.
• Do not use anything other than soapy water to lubricate gaskets.
NOTICE The venting system must be free to expand and contract and supported in accordance with the
installation instructions included by the original Polypropylene venting component manufacturer, M&G/
DuraVent. Polypropylene pipe sections must be disengaged 1/4 to 5/8 in. (6 mm to 16 mm) per joint to
allow for thermal expansion.
4. Installation of Horizontal Fitting Terminals (Terminal Option A):
a. See Figure 7.36 for proper orientation of twin pipe horizontal terminals. Outer edge of exhaust coupling must
be 10” or less from the wall surface. (Figure 7.9)
b. Remove the gasket from the end of the integral exhaust coupling and insert DuraVent Bird Guard #3PPS-BG
in it’s place.
c. Add PVC intake per instructions from Section VII - F.
5. Installation of Vertical Fitting Terminals (Terminal Option H):
a. See Figure 7.37for the proper orientation of twin pipe vertical terminals.
b. Remove the gasket from the end of the integral exhaust coupling and insert the installer supplied rodent
screen in it’s place.
c. A 180° bend (or two 90° elbows) are installed on the top of the air intake pipe. If two 90° elbows are used,
a rodent screen can be installed between them (Figure 7.37). If a 180° bend is used, a the rodent screen in
the open side of the bend, using a ring made of PVC pipe. If desired, the termination fittings can be attached
to the end of the intake pipes with field supplied stainless steel screws so that they can be later removed for
cleaning and inspection. If this is done, drill a clearance hole in these fittings and a tap hole in the end of the
intake pipes to accept these screws.
d. Use roof flashings and storm collars to prevent moisture from entering the building. Seal the roof flashing to
the roof using generally accepted practice for the type of roof on the installation. Apply RTV to seal the storm
collars to the vent and intake pipes.
52
108095-02 - 4/18
Page 53
VII. Venting F. Assembly of DuraVent PolyPro Vent Systems (continued)
Figure 7.36: Installation of Duravent PolyPro UV Resistant Single Wall Horizontal Terminal
Figure 7.37: Installation of Duravent PolyPro UV Resistant Single Wall Vertical Terminal
108095-02- 4/18
53
Page 54
VII. Venting F. Assembly of DuraVent PolyPro Vent Systems (continued)
a. At the planned location cut a 5-1/8” round hole for the 3” terminal in the exterior wall. (See Section VII - A of
this manual for permitted terminal locations).
b. If desired, the terminal can be shortened. Mark the desired location of the cut on the outer pipe no closer than
2” from the edge of the tab on the interior wall plate. Prior to cutting outer pipe measure dimension ‘A’ of the
inner pipe as shown in Figure 7.38 and maintain this dimension after cutting the outer pipe. All cuts must be
square and de-burred.
c. Attach the exterior wall plate and seal all around with weather resistant RTV.
d. Slide the cap through the exterior wall plate and hole from the outside of the building and orient the
termination so the air intake slots face down. The cap must be installed level or sloped 1/8” per foot away
from the appliance.
e. Seal the termination to the exterior wall plate with weather resistant RTV.
f. Slide the interior wall plate over the termination and attach to the wall from inside the room.
g. Attach the interior wall plate to the termination with the provided hardware.
h. Install gaskets into co-linear adapter.
i. Attach co-linear adapter to horizontal termination and orient so that the side outlet on the adapter is on or
a. Cut a hole in the roof large enough to clear the concentric terminal at the location of the terminal (see Section
VII - A of this manual for permitted terminal locations).
b. Use a roof flashing and storm collar to prevent moisture from entering the building. See Figure 7.40 for the
model number of the flashing to be used depending on the type of roof. Seal the roof flashing to the roof
using generally accepted practice for the type of roof on the installation.
c. Slide the vertical termination into the flashing from above until seated on the flashing.
d. Plumb the termination and mount the support bracket to the structure.
e. Install gaskets into co-linear adapter.
f. Attach co-linear adapter to vertical termination.
VII. Venting F. Assembly of DuraVent PolyPro Vent Systems (continued)
Figure 7.39: Installation of Duravent PolyPro Concentric Vent Terminal Through Sidewall
Figure 7.40: Installation of Duravent PolyPro Concentric Terminal Through Roof
108095-02- 4/18
55
Page 56
VII. Venting F. Assy of DuraVent PolyPro & G. Selkirk Polyflue Vent Systems (continued)
8. Installations using PolyPro-flex (Vent Options 9 & 15):
WARNING
Asphyxiation Hazard. When using PolyPro flex, observe the following precautions:
• PolyPro flex may be damaged by handling at low temperatures. Do not bend, uncoil, or attempt to install
if it has been stored at a temperature below 42°F without allowing it to warm to a higher temperature
first.
• Do not bend PolyPro flex more than 45°.
• Instructions below reference the DuraVent PolyPro Flex instruction manual. Not all vent
configurations shown in the DuraVent manual are approved for use with this boiler.
Refer to DuraVent PolyPro flex Instructions for assembly of all flex components including the chimney cap and the adaptor to rigid PolyPro at the base of the masonry or B vent chimney. In addition, observe the following
requirements:
a. Refer to the appropriate Vent option in Tables 7.13b or 7.21 for a list of the principle flex components
required. Rigid vent pipe by the same manufacturer will also be required for the run from the boiler to the
base of chimney.
b. Masonry chimneys cannot be used for an air chase
c. B vent chimneys can only be used for an air chase (Vent option 9) if the B vent has the minimum size shown
in Table 7.13b and is fully accessible for sealing of all joints and seams.
d. When Vent Option 9 is used, install a Tee on the base of the B-vent that is the same size as the B- Vent
chimney. Install the PolyPro Lower B–Vent adaptor in the base of this Tee as described in the DuraVent
PolyPro Flex instructions.
Connection of the PVC air intake pipe to the side outlet of the tee is made using a cap and a PVC socket x
male thread adaptor. Cut a clearance hole in the cap for the male threads. Secure the adaptor to the cap
using a 3” electrical conduit lock nut. Seal all joints with RTV.
G. Assembly of Selkirk Polyflue Vent Systems
1. This boiler has been approved for use with the Selkirk Polyflue single wall Polypropylene vent system to be
provided by the installer.
2. Assemble the vent system, starting at the boiler:
a. The vent adaptor has three different inside diameters. The middle inside diameter accepts 3” nominal Polyflue
(Figure 7.27). A locking band clamp in the adaptor prevents the vent pipe from coming out of the adaptor
once it is installed and tightened. Lubricate the gaskets in the vent adaptor with mild soapy water and insert
the first piece of 3” Polyflue into the adaptor until it bottoms out. Tighten locking band clamp to secure vent
pipe.
b. Assemble the next piece of 3” Polyflue.
c. For each joint, verify that the gasket is evenly seated in the bell (female) end of the pipe. Lubricate this gasket
with mild soapy water. Slide a Pipe Locking Band over the male end of the pipe to be joined as shown in
Figure 7.41. Push the male end of the next section of pipe into the bell until it bottoms out, then back out 1/8—
1/4” to provide room for thermal expansion. Slide pipe locking band over the female end of the connections
and tighten both hose clamps.
d. Assemble the rest of the vent system per the manufacturer’s installation instructions, being sure to pitch
horizontal sections back towards the boiler 5/8” per ft.
56
108095-02 - 4/18
Page 57
VII. Venting G. Assembly of Selkirk Polyflue Vent Systems (continued)
3. Installation of Air Intake System - Start assembly of the PVC air intake system at the boiler. Assembly of the air
intake system is done in the same manner as the vent system except as follows:
a. Drill a 7/32” clearance hole into the front side of the air intake adapter. Insert the first piece of PVC air
intake pipe into the air intake connection and drill a 1/8” tap hole into the PVC which lines up with the 7/32”
clearance hole and secure them together with a #10 x 1” sheet metal screw. Seal the joint between the intake
pipe and the adaptor with RTV.
b. All intake piping may be PVC. There is a 0” minimum clearance between the air intake piping and all types of
construction.
c. To the extent possible, pitch horizontal air intake piping towards the outside.
4. Installation of Horizontal Fitting Terminals (Terminal Option A):
a. See Figure 7.42 for proper orientation of twin pipe horizontal terminals. Outer edge of exhaust coupling must
be 10” or less from the wall surface. (Figure 7.9)
b. Remove the gasket from the end of the integral exhaust coupling and insert Selkirk #3PFHVST in its place.
c. Add PVC intake per instructions from Section VII - F.
5. Installation of Vertical Fitting Terminals (Terminal Option H):
a. See Figure 7.43 for the proper orientation of twin pipe vertical terminals.
b. Remove the gasket from the end of the integral exhaust coupling and insert Selkirk #3PFHVST in its place.
c. A 180° bend (or two 90° elbows) are installed on the top of the air intake pipe. If two 90° elbows are used, a
rodent screen can be installed between them (Figure 7.43). If a 180° bend is used, install a rodent screen in
the open side of the bend, using a ring made of PVC pipe. If desired, the termination fittings can be attached
to the end of the intake pipes with field supplied stainless steel screws so that they can be later removed for
cleaning and inspection. If this is done, drill a clearance hole in these fittings and a tap hole in the end of the
intake pipes to accept these screws.
d. Use roof flashings and storm collars to prevent moisture from entering the building. Seal the roof flashing to
the roof using generally accepted practice for the type of roof on the installation. Apply RTV to seal the storm
collars to the vent and intake pipes.
WARNING
Asphyxiation Hazard. Selkirk Polyflue vent systems rely on gaskets for proper sealing.
When this vent system is used, take the following precautions:
• Make sure that gasket is in position and undamaged in the female end of the pipe.
• Make sure that both the male and female pipes are free of damage prior to assembly.
• Only cut vent pipe as permitted by the vent manufacturer in accordance with their Instructions. When
pipe is cut, the cut end must be square and carefully de-burred prior to assembly.
• Use pipe locking bands at all vent pipe joints.
NOTICE The venting system must be free to expand and contract and supported in accordance with the
installation instructions included by the original Polypropylene venting component manufacturer, Selkirk.
Polypropylene pipe sections must be disengaged 1/8 to 1/4 in. (3mm to 6mm) per joint to allow for thermal
expansion.
108095-02- 4/18
57
Page 58
VII. Venting G. Assembly of Selkirk Polyflue Vent Systems (continued)
6. Installations using flexible Polyflue (Vent Option 16):
WARNING
Asphyxiation Hazard. When using Polyflue flex, observe the following precautions:
• Polyflue flex may be damaged by handling at low temperatures. Do not bend, uncoil or attempt to
install if it has been stored at a temperature below 42°F without allowing it to warm to a higher
temperature first.
• Do not bend Polyflue flex more than 45°.
• Instructions below reference the Selkirk Polyflue instruction manual. Not all vent configurations shown
in the Selkirk vent manual are approved for use with this boiler.
Refer to Selkirk Polyflue Instructions for assembly of all flex components including the chimney cap and the
adaptor to rigid Polyflue at the base of the masonry or B vent chimney. In addition, observe the following
requirements:
a. Refer to the appropriate Vent option in Table 7.21 for a list of the principle flex components required. Rigid
vent pipe by the same manufacturer will also be required for the run from the boiler to the base of the
chimney.
b. Polyflue may not be used in air chase applications.
Figure 7.41: Polyflue Pipe Locking Band Installation
58
108095-02 - 4/18
Page 59
VII. Venting G. Assembly of Selkirk Polyflue Vent Systems (continued)
Figure 7.42: Installation of Selkirk Polyflue UV Resistant Single Wall Horizontal Terminal
Figure 7.43: Installation of Selkirk Polyflue UV Resistant Single Wall Vertical Terminal
108095-02- 4/18
59
Page 60
VII. Venting H. Assembly of Centrotherm InnoFlue Vent Systems
H. Assembly of Centrotherm InnoFlue Vent Systems
1.This boiler has been approved for use with the Centrotherm InnoFlue single wall Polypropylene vent system to
be provided by the installer.
WARNING
Asphyxiation Hazard. Follow these instructions and the installation instructions included
by the original Polypropylene venting component manufacturers, Centrotherm. Failure to do so could
cause products of combustion to enter the building, resulting in severe property damage, personal injury
or death. Where a conflict arises between Centrotherm instructions and these instructions, the more
restrictive instructions shall govern.
Do not mix vent components or joining methods for listed manufacturers.
Read, understand and follow all the instructions and warnings contained in all the sections of this manual.
If any electrical wires are disconnected during service, clearly label the wires and assure that the wires
are reconnected properly.
Never jump out or bypass any safety or operating control or component of this boiler.
Assure that all safety and operating controls and components are operating properly before placing the
boiler back in service.
Annually inspect all vent gaskets and replace any exhibiting damage or deterioration.
2. Assemble the vent system, starting at the boiler:
a. The vent adaptor has three different inside diameters. The middle inside diameter accepts 3” nominal
InnoFlue (Figure 7.27). A locking band clamp in the adaptor prevents the vent pipe from coming out of the
adaptor once it is installed and tightened. Lubricate the upper gasket in the vent adaptor with water and
insert the first piece of 3” InnoFlue into the adaptor until it bottoms out. Tighten locking band clamp to secure
vent pipe.
b. Assemble the next piece of 3” InnoFlue.
c. For each joint, verify that the gasket is evenly seated in the bell (female) end of the pipe. Lubricate this gasket
with Centrocerin # IACE50. Slide a connector ring over the male end of the pipe to be joined as shown in
Figure 7.44. Push the male end of the next section of pipe into the bell until it bottoms out, then back out 1/4”
to provide room for thermal expansion. Push hook on connecting ring over the bell end of the first section of
pipe as shown in Figure 7.44.
d. Assemble the rest of the vent system per the manufacturer’s installation instructions, being sure to pitch
horizontal sections back towards the boiler 5/8”/ft.
e. Support each horizontal pipe section with a minimum of one wall strap each and at intervals not exceeding
39in.
Figure 7.44: InnoFlue Connector Ring Installation
60
108095-02 - 4/18
Page 61
VII. Venting H. Assembly of Centrotherm InnoFlue Vent Systems
3. Installation of Air Intake System - Start assembly of the PVC air intake system at the boiler. Assembly of the air
intake system is done in the same manner as the vent system except as follows:
a. Drill a 7/32” clearance hole into the front side of the air intake adapter. Insert the first piece of PVC air
intake pipe into the air intake connection and drill a 1/8” tap hole into the PVC which lines up with the 7/32”
clearance hole and secure them together with a #10 x 1” sheet metal screw. Seal the joint between the intake
pipe and the adaptor with RTV.
b. All intake piping may be PVC.
c. There is a 0” minimum clearance between the air intake piping and all types of construction.
d. To the extent possible, pitch horizontal air intake piping towards the outside.
WARNING
Asphyxiation Hazard. Vent systems made by Centrotherm rely on gaskets for proper
sealing. When this vent system is used, take the following precautions:
• Make sure that gasket is in position and undamaged in the female end of the pipe.
• Make sure that both the male and female pipes are free of damage prior to assembly.
• Only cut vent pipe as permitted by the vent manufacturer in accordance with their instructions. When
pipe is cut, the cut end must be square and carefully de-burred prior to assembly.
• Use connector rings at all vent pipe joints.
NOTICE The venting system must be free to expand and contract and supported in accordance with
the installation instructions included by the original Polypropylene venting component manufacturer,
Centrotherm. Polypropylene pipe sections must be disengaged 1/4 in. (6mm) per joint to allow for thermal
expansion.
4. Installation of Horizontal Fitting Terminals (Terminal Option A):
a. See Figure 7.45 for proper orientation of twin pipe horizontal terminals. Outer edge of end pipe must be 10”
or less from the wall surface. (Figure 7.5)
b. Use plain end UV stabilized Centrotherm 3” pipe # ISEP03 or ISEP0339 and insert Centrotherm Bird Screen
#IASPP03 in the end of the pipe.
c. Add PVC intake per instructions from Section VII - F.
5. Installation of Vertical Fitting Terminals (Terminal Option H):
a. See Figure 7.46for the proper orientation of twin pipe vertical terminals.
b. Use plain end UV stabilized Centrotherm 3” pipe # ISEP03 or ISEP0339 and insert Centrotherm Bird Screen
#IASPP03 in the end of the pipe.
c. A 180° bend (or two 90° elbows) are installed on the top of the air intake pipe. If two 90° elbows are used, a
rodent screen can be installed between them (Figure 7.46). If a 180° bend is used, install a rodent screen in
the open side of the bend, using a ring made of PVC pipe. If desired, the termination fittings can be attached
to the end of the intake pipes with field supplied stainless steel screws so that they can be later removed for
cleaning and inspection. If this is done, drill a clearance hole in these fittings and a tap hole in the end of the
intake pipes to accept these screws.
d. Use roof flashings and storm collars to prevent moisture from entering the building. Seal the roof flashing to
the roof using generally accepted practice for the type of roof on the installation. Apply RTV to seal the storm
collars to the vent and intake pipes.
108095-02- 4/18
61
Page 62
VII. Venting H. Assembly of Centrotherm InnoFlue Vent Systems
Figure 7.45: Installation of Centrotherm InnoFlue UV Stabilized Single Wall Horizontal Terminal
Figure 7.46: Installation of Centrotherm InnoFlue UV Stabilized Single Wall Vertical Terminal
62
108095-02 - 4/18
Page 63
VII. Venting H. Assembly of Centrotherm InnoFlue Vent Systems
6. Installations using InnoFlue Flex (Vent Options 10 & 17):
WARNING
Asphyxiation Hazard. When using InnoFlue Flex, observe the following precautions:
• InnoFlue Flex may be damaged by handling at low temperatures. Do not bend, uncoil or attempt to
install if it has been stored at a temperature below 42°F without allowing it to warm to a higher
temperature first.
• Do not bend InnoFlue Flex more than 45°.
• Instructions below reference the Centrotherm InnoFlue instruction manual. Not all vent configurations
shown in the Centrotherm manual are approved for use with this boiler.
Refer to Centrotherm InnoFlue Instructions for assembly of all flex components including the chimney cap and
the adaptor to rigid InnoFlue at the base of the masonry or B vent chimney. In addition, observe the following
requirements:
a. Refer to the appropriate Vent option in Tables 7.13b or 7.21 for a list of the principle flex components required.
Rigid vent pipe by the same manufacturer will also be required for the run from the boiler to the base of
chimney.
b. Masonry chimneys cannot be used for an air chase
c. B vent chimneys can only be used for an air chase (Vent option 10) if the B vent has the minimum size shown
in Table 7.13b and is fully accessible for sealing of all joints and seams.
d. When Vent Option 10 is used, install a Tee of the same size at the base of the vent. Route the smooth section
of InnoFlue Flex (3”) through a cap in the base of this Tee. Use a Centrotherm IAWP03B wall plate and RTV to
seal this penetration. Install the Base Support using the Base support bracket as described in the InnoFlue
installation manual.
Connection of the PVC air intake pipe to the side outlet of the tee is made using a cap and a PVC socket x
male thread adaptor. Cut a clearance hole in the cap for the male threads. Secure the adaptor to the cap
using a 3” electrical conduit lock nut. Seal all joints with RTV.
108095-02- 4/18
63
Page 64
VII. Venting I. Assembly of Stainless Steel Vent Systems
I. Assembly of Stainless Steel Vent Systems
1. This boiler has been approved for use with Duravent FasNSeal Flex Stainless Steel vent systems to be provided by the installer.
WARNING
Asphyxiation Hazard. Follow these instructions and the installation instructions
included by the original stainless steel venting component manufacturer, DuraVent. Failure to do so
could cause products of combustion to enter the building, resulting in severe property damage, personal
injury or death. Where a conflict arises between DuraVent instructions and these instructions, the more
restrictive instructions shall govern.
Do not mix vent components from listed manufacturers.
Examine all components from listed manufacturers.
All condensate that forms in the vent must be able to drain back to the boiler.
2. The vent adaptor has three different inside diameters. The smaller, lower diameter accepts 3” Stainless steel
(Figure 7.27). A locking band clamp in the adaptor prevents the vent pipe from coming out of the adaptor
once it is installed and tightened. Lubricate the upper gaskets in the vent adaptor with water and insert the
first piece of 3” stainless into the adaptor until it bottoms out. Tighten locking band clamp to secure vent
pipe.
3. Installation of Air Intake System - Start assembly of the PVC air intake system at the boiler. Assembly of the
air intake system is done in the same manner as the vent system except as follows:
a. Drill a 7/32” clearance hole into the front side of the air intake adaptor. Insert the first piece of PVC air
intake pipe into the air intake connection and drill a 1/8” tap hole into the PVC which lines up with the 7/32”
clearance hole and secure them together with a #10 x 1” sheet metal screw. Seal the joint between the intake
pipe and the adaptor with RTV.
b. All intake piping may be PVC.
c. There is a 0” minimum clearance between the air intake piping and all types of construction.
d. To the extent possible, pitch horizontal air intake piping towards the outside.
WARNING
sealing. When these vents systems are used, take the following precautions:
• Make sure that gasket is in position and undamaged in the female end of the pipe
• Make sure that both male and female pipes are free of damage prior to assembly.
• Only cut vent pipe as permitted by the vent manufacturer in accordance with their instructions.
When pipe is cut, the cut end must be square and carefully de-burred prior to assembly.
4. Installation using DuraVent FasNSeal Flex (Vent Option 18)
Refer to manufacturer’s instructions for assembly of all flex components including the chimney cap and
adaptor to rigid pipe at base of masonry or B Vent Chimney (DuraVent FasNSeal Flex only permitted in
a. Refer to the appropriate Vent option in table 7.21 for a list of the principle flex components required. Rigid
b. Masonry chimneys cannot be used for an air chase.
c. Flexible stainless steel vent shall be installed in an UNUSED masonry chimney/chase and supplying
masonry type chimneys). In addition, observe the following requirements:
vent pipe by the same manufacturer will also be required for the run from the boiler to the base of chimney.
combustion air through a separate wall or roof combustion air terminal. The unused chimney flue must
be structurally sound and in good repair. A chimney is considered UNUSED when it is not being used for
any appliance venting. If chimney is a multiple flue type where one of the multiple flues is being used for
an appliance venting, the flexible stainless vent installation is permitted through an adjacent, unused flue
providing a local authority having jurisdiction approves such installation. (Figure 7.25b)
Asphyxiation Hazard. Vent systems made by Duravent rely on gaskets for proper
64
108095-02 - 4/18
Page 65
VII. Venting I. Assembly of Stainless Steel Vent Systems (continued)
d. When flexible stainless steel pipe is used for combustion product venting, it must be installed at vertical or
near vertical orientation. This will insure proper condensate flow back towards the boiler.
e. Follow flexible stainless steel pipe manufacturer specific instructions regarding application/listing, permits,
minimum clearances to combustibles, installation details (proper joint assembly, pipe support and routing,
gasket and fitting installation, optional tooling availability/usage, routing through masonry combination of
combustion product venting and combustion air supply).
f. When there is a conflict between flexible stainless steel pipe manufacturer installation instructions and boiler
installation, Operating and Service Instructions, the more restrictive instructions shall govern.
108095-02- 4/18
65
Page 66
VII. Venting J. Condensate Trap and Drain Line (continued)
J. Condensate Trap and Drain Line
All condensate which forms in the boiler or vent system passes through the heat exchanger and out of a bottom
drain port which is connected to the condensate trap with a hose. This trap allows condensate to drain from the heat
exchanger while retaining flue gases in the boiler. This trap is an integral part of the boiler but must be connected to
a drain pipe as shown in Figure 7.47. A length of corrugated tubing is supplied with the boiler and is connected to
the trap as shown in Figure 7.47. Note the following when disposing of the condensate:
1. If the corrugated condensate drain line must be extended, construct the extension from PVC or CPVC pipe.
Insert the hoseprovided with the boiler into the end of the extension as shown in Figure 7.47.
2. Condensate is slightly acidic. Do not use metallic pipe or fittings in the condensate drain line. Do not route the
drain line through areas that could be damaged by leaking condensate.
3. Some jurisdictions may require that the condensate be neutralized before being disposed of. Dispose of
condensate in accordance with local codes.
4. Do not route, or terminate, the condensate drain line in areas subjected to freezing temperatures.
5. If the point of condensate disposal is above the trap, it will be necessary to use a condensate pump to move
the condensate to the drain. In such cases, select a condensate pump that is approved for use with condensing
boilers. If overflow from this pump would result in property damage, select a pump with an overflow switch and
use this switch to shut down the boiler. Alternatively, if heat is a necessity, use the overflow switch to trigger an
alarm.
6. Do not attempt to move the trap from the location shown in Figure 7.47. Do not attempt to substitute another trap
for the one provided with the boiler.
7. The trap vent is connected to a barbed fitting attached to the right side panel with rubber tubing and must be left
open for the trap to work properly.
WARNING
Asphyxiation Hazard. Failure to install the condensate drain in accordance with the
above instructions could cause flue gas to enter the building, resulting in personal injury or death.
NOTICE Indicates special instructions on installation, operation, or maintenance which are important but
not related to personal injury hazards.
Figure 7.47: Condensate Piping Arrangement
66
108095-02 - 4/18
Page 67
VII. Venting K. Removing an Existing Boiler From a Common Chimney (continued)
K. Removing an Existing Boiler From a Common Chimney
This section only applies if this boiler is replacing an existing boiler that is being removed from a common chimney.
In some cases, when an existing boiler is removed from a common chimney, the common venting system may be too
large for the remaining appliances. At the time of removal of an existing boiler, the following steps shall be followed
with each appliance remaining connected to the common venting system placed in operation, while the other
appliances remaining connected to the common venting system are not in operation.
(a) Seal any unused openings in the common venting system.
(b) Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
(c) Insofar as practical, close all building doors and windows and all doors between the space in which all the
appliances remaining connected to the common venting system are located and other spaces of the building.
Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
(d) Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so the
appliance will operate continuously.
(e) Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a
match or candle, or smoke from a cigarette, cigar, or pipe.
(f) After it has been determined that each appliance remaining connected to the common venting system properly
vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gasburning appliances to their previous condition of use.
(g) Any improper operation of the common venting system should be corrected so the installation conforms with the
National Fuel Gas Code, ANSI Z223.1. When re-sizing any portion of the common venting system, the common
venting system should be re sized to approach the minimum size as determined using the appropriate tables in
Part 11 of the National Fuel Gas Code, ANSI Z223.1.
WARNING
Never common vent this boiler with other appliances.
Au moment du retrait d’une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil
toujours raccordé au système d’evacuation commun et qui fonctionne alors que d’autres appareils toujours
raccordés au système d’évacuation ne fonctionnent pas:
(a) Sceller toutes les ouvertures non utilisées du système d’évacuation.
(b) Inspecter de façon visuelle le système d’évcuation pour déterminer la grosseur et l’inclinaison horizontale qui
conviennent et s’assurer que le système est exempt d’obstruction, d’étranglement, de fuite, de corrosion et
autres défaillances qui pourraient présenter des risques.
(c) Dans la mesure du possible, fermer toutes les portes et les fenêtres du bâtiment et toutes les portes entre
l’espace où les appareils toujours raccordés au système d’évacuation sont installés et les autres espaces du
bâtiment. Mettre en marche les sécheuses, tous les appareils non raccordés au système d’évacuation commun
et tous les ventilateurs d’extraction comme les hottes de cuisinière et les ventilateurs des salles de bain. S’assurer que ces ventilateurs fonctionnent à la vitesse maximale. Ne pas faire fonctionner les ventilateurs d’été.
Fermer les registres des cheminées.
(d) Mettre l’appareil inspecté en marche. Suivre les instructions d’allumage. Régler le thermostat de façon que
l’appareil fonctionne de façon continue.
(e) Faire fonctionner le brùleur principal pendant 5 min ensuite, déterminer si le coupe-tirage déborde à l’ouverture
de décharge. Utiliser la flamme d’une allumette ou d’une chandelle ou la fumée d’une cigarette, d’un cigare ou
d’une pipe.
(f) Une fois qu’il a été déterminé, selon la méthode indiquée ci-dessus, que chaque appareil raccordé au système
d’évacuation est mis à l’air libre de façon adéquate. Remettre les portes et les fenêtres, les ventilateurs, les
registres de cheminées et les appareils au gaz à leur position originale.
(g) Tout mauvais fonctionnement du système d’évacuation commun devrat être corrigé de façon que l’installation
soit conforme au National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes d’installation CAN/ CSA-B149.1. Si la grosseur d’une section du système d’évacuation doit être modifiée, le système devrait être
modifié pour respecter les valeurs minimales des tableaux pertinents de l’appendice F du National Fuel Gas
Code, ANSI Z223.1/NFPA 54 et (ou) des codes d’installation CAN/CSA-B149.1.
108095-02- 4/18
67
Page 68
VIII. Gas Piping
WARNING
Explosion Hazard. Failure to properly pipe gas supply to boiler may result in improper
operation or leaks of flammable gas.
•
Gas supply to boiler and system must be absolutely shut off prior to installing or servicing boiler gas
piping.
•
Always assure gas piping is absolutely leak free and of the proper size and type for the connected load.
•
Use a thread compound compatible with liquefied petroleum gas. Failure to use proper thread
compounds on all gas connectors may result in leaks of flammable gas.
If inlet pressure is above 1/2 psig (3.4 kPa) an additional gas pressure regulator is required. Consult gas
•
supplier.
•
Size corrugated stainless steel tubing (CSST) to ensure proper capacity and minimize flow restrictions.
Gas piping to the boiler must be sized to deliver adequate gas for the boiler to fire at the nameplate
input at an inlet pressure between the minimum and maximum values shown in Table 8.2. When sizing,
also consider other existing and expected future gas utilization equipment (i.e. water heater, cooking
equipment). For more information on gas line sizing, consult the utility or the National Fuel Gas Code,
NFPA54/ANSI Z223.1, and/or CAN/CSA B149.1 Natural Gas and Propane Installation Code.
Figure 8.1 shows typical gas piping connection to the boiler. A sediment trap must be installed upstream of
all gas controls. Install a manual shut-off valve (provided by installer) outside the jacket with a ground joint
union as shown. All above ground gas piping upstream from manual shut-off valve must be electrically
continuous and bonded to a grounding electrode. Refer to National Electrical Code, NFPA 70.
The boiler and its gas connection must be leak tested before placing the boiler in operation. When doing
this, the boiler and its individual shut-off must be disconnected from the rest of the system during any
pressure testing of that system at pressures in excess of 1/2 psi (3.5kPa). When pressure testing the gas
system at pressures of 1/2 psi (3.5kPa) or less, isolate the boiler from the gas supply system by closing
its individual manual shut-off valve. Locate leaks using approved combustible gas non-corrosive leak
detector solution.
DANGER
Explosion Hazard. Do not use matches, candles, open flames or other ignition source to
check for leaks.
WARNING
If gas pressure in the building is above ½ psig (3.4 kPa), an additional gas pressure
regulator is required. Using one additional regulator for multiple gas appliances may result in unsafe
boiler operation. The additional regulator must be able to properly regulate gas pressure at the input of
the smallest appliance. If the regulator can not do this, two or more additional regulators are required.
Consult regulator manufacturer and/or local gas supplier for instructions and equipment ratings.
68
108095-02 - 4/18
Page 69
VIII. Gas Piping (continued)
CAUTION
Support the weight of the gas line piping independently from the boiler gas connection
fitting located on the bottom of the boiler.
If an additional regulator is used to reduce boiler inlet pressure below 1/2 psig (3.4 kPa) it must be at least
6 to 10 ft. upstream of the boiler.
It is very important that the gas line is properly purged by the gas supplier or utility company.
NOTICE Install 1/2” ground joint union (nut side down) as shown in Figure 8.1. Failure to do so will make it
difficult or impossible to remove burner for servicing.
Table 8.2: Minimum and Maximum Inlet Pressures
ModelMax. (Natural & LP)Min. (Natural)Min. (LP)
135-18014.0”2.5”11.0”
108095-02- 4/18
Figure 8.1: Gas Connection to Boiler
69
Page 70
IX. System Piping
A. General System Piping Precautions
WARNING
Failure to properly pipe boiler may result in improper operation and damage to boiler or
structure.
•
Install boiler so that the gas ignition system components are protected from water (dripping, spraying,
rain, etc.) during boiler operation and service (circulator replacement, etc.).
•
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components and can
lead to boiler failure. Warranty does not cover problems caused by oxygen contamination of boiler water
or scale (lime) build-up caused by frequent addition of water.
CAUTION
1. The heat transfer-medium must be water or other nontoxic fluid having a toxicity
rating or Class of 1, as listed in Clinical Toxicology of Commercial Products, 5th edition.
2. The pressure of the heat transfer medium must be limited to a maximum of 30 PSIG by an approved
safety or relief valve.
WATER QUALITY AND BOILER WATER ADDITIVES
IMPORTANT NOTE
The heat exchanger used in this boiler is made from stainless steel coils having relatively narrow waterways.
Once filled with system water, it will be subjected to the effects of corrosion, as well as fouling from any debris
introduced from the system. Take the following precautions to minimize the chance of severe heat exchanger
damage caused by corrosion and/or overheating:
1. Flush the system before connecting the boiler - In a replacement installation, flushing the system will
remove impurities, such as sediment, solder flux, metal shavings, and traces of old boiler additives. Even if
the system is new, do not omit this step – new systems will contain flux and may even contain some of the
other impurities listed above. Flush the system completely and repeat if necessary to completely remove
these contaminants. If necessary, a cleaning agent may be used to assist in system cleaning. See Section
XII (“Start-up and Check-out”) for recommended cleaners.
2. Make sure that the system is tight - This is the single most important guideline. Tap water contains dissolved
oxygen which causes corrosion. In a tight system, this oxygen comes out of solution and is quickly removed
from the system through the automatic air vent. The system then remains essentially free of oxygen. If the
system is not tight, however, frequent additions of make-up water can expose the heat exchanger to oxygen
on a continuous basis. In addition, frequent additions of hard make-up water can cause calcium deposits to
collect in the heat exchanger, causing severe damage. To minimize additions of make-up water:
• Inspect the system thoroughly for leaks before placing it in service.
• If the system includes underground piping, or other piping in which a leak might go undetected,
consider isolating the boiler from the system with a heat exchanger.
• Make sure that the expansion tank is properly sized and in good condition. If it is not, the relief valve
may open frequently, resulting in regular additions of make-up water.
• If an automatic fill valve is installed, installation of a water meter in the fill line is strongly recommended
so that routine additions of make-up water can be detected and their cause corrected.
3. Non-Metallic Tubing - Even if the system is tight, oxygen can be introduced into the system through some
types of non-metallic tubing used in radiant or snow melt systems. Other nonmetallic tubing is equipped
with an oxygen barrier to prevent migration of oxygen into the water. If the boiler is to be installed in a
system containing non-metallic tubing without an oxygen barrier, it must be isolated from the boiler with a
heat exchanger as shown in Figure 9.8.
4. Water Chemistry, Antifreeze, and Boiler Water Additives – Improper boiler water chemistry can cause the
heat exchanger damage described above, as well as deterioration of seals. Observe the water chemistry
requirements shown in Section XII (“Start-up and Check-out”).
70
108095-02 - 4/18
Page 71
IX. System Piping (continued)
B. Standard Piping Installation Requirements
Observe the following requirements when installing the boiler piping:
1. Relief Valve (Required) – The relief valve is shipped loose and must be installed in the location shown
in Figure 9.0. Pipe the outlet of the relief valve to a location where water or stream will not create a hazard or cause property damage if the valve opens. The end of the discharge pipe must
terminate in unthreaded pipe. If the relief valve discharge is not piped to a drain, it must terminate
at least 6” above the floor. Do not run the discharge piping through an area that is prone to freezing. The
termination of the relief valve must be in an area where it is not likely to become plugged by debris.
The relief valve supplied with the boiler is set to open at 30 psi. If it is replaced, the replacement must
have a setting less than or equal to the maximum allowable working pressure (MAWP) shown on the
ASME data plate located on the left side of the heat exchanger.
DANGER
Explosion Scald Hazard. Pipe relief discharge to a location where the potential of severe
burns is eliminated.
•
Do not install a relief valve having a setting greater than the MAWP shown on the rating plate.
•
Do not install a valve in the relief valve discharge line.
•
Do not install a relief valve in a location other than that specified by the factory.
•
Do not plug the relief valve discharge.
2. Circulator (required) – The boiler loop circulator is factory installed inside the boiler cabinet. Usually at
least one addition circulator (not supplied) will be required for the system to work properly. See the
following section for more information.
3. Expansion Tank (required) – If this boiler is replacing an existing boiler with no other changes in the
system, the old expansion tank can generally be reused. If the expansion tank must be replaced,
consult the expansion tank manufacturer’s literature for proper sizing. If using antifreeze, account for additional expansion of glycol solution when sizing an expansion tank. In a typical residential heating
system, a glycol mixture has an expansion rate about 1.2 times that of water alone, therefore a tank for
an anti-freeze system should be at least 1.2 times greater in size.
4. Fill Valve (required) – Either a manual or automatic fill valve may be used, but a manual valve is preferred
because it eliminates unmonitored additions of make-up water to the system. The ideal location for the
fill valve is at the expansion tank. If using antifreeze with automatic fill valve, it is recommended to install
a water meter to monitor makeup water. Antifreeze concentration will decrease as makeup water is
added. If using antifreeze, local codes often require a backflow preventer or disconnect from city water.
5. Automatic Air Vent (required) – At least one automatic air vent is required. Manual air vents will usually
be required in other parts of the system to remove air during initial fill.
6. Manual Reset High Limit (required by some codes) - This control is required by ASME CSD-1 and some
other codes. Install the high limit in the boiler supply piping just above the boiler with no intervening
valves. Set the manual reset high limit to 200°F. Wire the limit per Figure 11.3 in the Wiring section.
7. Isolation Valves (recommended) - Isolation valves are useful when the boiler must be drained, as they
will eliminate having to drain and refill the entire system.
8. Strainer (recommended) – Install a Y Strainer, or other suitable strainer, to prevent any system debris
from entering the boiler and fouling the water passages. Note that some strainers have a significant
pressure drop, which may impact the ability of the boiler pump to obtain the required flow. See Part C of
this section for additional information.
108095-02- 4/18
71
Page 72
IX. System Piping (continued)
9. Drain Valve (required) – Install the drain valve (provided by the installer) as shown in Figure 9.2.
10. Low Water Cut-off (may be required by local jurisdiction) – Protection of this boiler against low water
and/or inadequate flow is provided by the UL353 certified flow switch built into the boiler. This is a water
tube boiler and this flow switch is therefore the only effective way to provide such protection. Section
HG614(c ) of the 2015 ASME boiler and Pressure Vessel Code recognizes the use of a listed flow switch
in lieu of a low water cut-off on water tube boilers.
In the event that a local jurisdiction insists upon the installation of a low water cut-off with this boiler,
refer to Part XI and the low-water cut-off manufacturer’s instructions for proper wiring. Install the low water cut-off in the supply piping at the point prescribed the local jurisdiction (generally at a point
above the boiler).
If a probe type low water cut-off is used, be certain that it is located at a point in the piping from which
air can escape to an automatic air vent. Generally, this means that there should be no down-turns in the
piping between the low water cut-off and the point where the automatic air vent is installed. Failure to do
this may result in nuisance boiler shut-downs due to small amounts of air trapped around the probe.
Figure 9.0: Factory Supplied Piping and Trim Installation
72
108095-02 - 4/18
Page 73
IX. System Piping (continued)
C. Near Boiler Piping Design
Proper operation of this boiler requires that the water flow rate through it remain within the limits shown in
Table 9.1 any time the boiler is firing. At flow rates below the minimum shown, the boiler’s flow switch and/or
temperature rise limit function may prevent the boiler from firing. Flow rates through the boiler in excess of the
maximum shown in Table 9.1 can result in excessive noise or erosion damage to piping
There are two basic methods that can be used to pipe this boiler into the system. Method #1 (primary-secondary
piping) is always preferred. Additional information on hydronic system design can be found in the I=B=R Guide
RHH published by the Air-Conditioning, Heating and Refrigeration Institute (AHRI).
This method is shown in Figure 9.2. In this system, the flow rate through the boiler (“secondary loop”) is
completely independent of the flow rate through the system (“primary loop”). Use the following guidelines to
ensure that the boiler will have the required flow shown in Table 9.1 regardless of the flow in the heating system.
MinimumMaximum
Flow (GPM)
1. System Loop Piping - Size the system circulator and piping to obtain the design flow rate through the heating
system as you would on any other heating system. All piping between the expansion tank and secondary
connection tees must be at least 1”. In order to keep the flow rates in the system and boiler loops independent of each other, provide at least 8 diameters of straight pipe upstream of the first tee and 4
diameters downstream of the second tee. Keep the distance between the expansion tank and the first secondary tee as short as practical.
2. Boiler Loop Piping – All boilers are supplied with a built in circulator which will deliver the flow required by
Table 9.1 provided both of the following conditions are met:
• All piping in the boiler loop has a nominal size of at least 1”
• The equivalent length of all piping in the boiler loop is 60 ft or less.
To verify that the 60 ft, equivalent length is not exceeded, do the following:
a. Count all fittings in the planned boiler loop (the shaded piping in Figure 9.5).
b. Using Table 9.3, find the equivalent lengths of all fittings in the secondary loop. Total these equivalent
lengths and add them to the total length of planned straight pipe in the secondary loop.
c. The result is the total equivalent length of the planned boiler loop. If the equivalent length calculated
in (b) is under the limit shown in Table 9.4, the boiler pump will achieve a flow rate and temperature rise
approximately equal to that shown in this table. Otherwise, the equivalent length must be reduced.
108095-02- 4/18
73
Page 74
IX. System Piping (continued)
74
Figure 9.2: Piping Method #1 - Near Boiler Piping - Heating Only
108095-02 - 4/18
Page 75
IX. System Piping (continued)
Example – A 135MBH model is to be connected to a heating system as shown in Figure 9.5. A total of 20 ft of
straight pipe will be installed between the boiler and the system loop.
Count all fittings in the boiler loop (shaded in Figure 9.5):
4 90° Elbows
2 Turn in Tee
2 Isolation Valves
Note: Unions, Secondary Connection Tees, and factory supplied fittings are ignored.
Calculate total equivalent length from Table 9.3:
20 ft Straight Pipe + 4 Elbows x 2.8 + 2 Turn in Tee x 5.5 + 2 Valves x 0.7 = 43.6 Equivalent Feet
Since the total equivalent length is less than 60 ft, flow through boiler loop meets requirements in Table 9.1.
3. Hydraulic Separators – Hydraulic separators serve the same purpose as the closely spaced tees connecting
the boiler and system loops in Figure 9.2. They also generally provide effective connection points for automatic air elimination devices and an expansion tank. These separators are available from several sources and may be used in place of the closely spaced tees shown in Figure 9.2. When a hydraulic separator is used in place of the tees, the 60 ft equivalent length limitation still applies. Select a hydraulic
separator having 1” or larger boiler connections that is designed for the boiler flow rates shown in Table 9.1.
Table 9.3: Equivalent Lengths for Selected Valves and Fittings
(May Be Used for Copper or Threaded Fittings)
FittingPipe SizeEquivalent Length (ft)
90° Elbow1”2.8
45° Elbow1”1. 4
90° Turn in Tee1”5.5
Run of Tee1”1. 8
Gate Valve (Open)1”0.7
Full Port Ball Valve1”0.7
Y-Strainer*1”7. 0
* Based on Cv of 20. Pressure drop through strainers varies widely. 7 ft equivalent length
may be assumed for strainers having a published Cv greater than 20.
Table 9.4a: Flow Available with Boiler Loop
Equivalent Length of 30 ft or Less
Method 2: Direct Connection to Heating System (Generally NOT Recommended)
In some relatively rare cases it may be possible to connect this boiler directly to the heating system as is done
with conventional boilers (Figure 9.6). If this is done, the flow rate through the boiler will equal the flow rate
through the system. The flow rate through the system must therefore always remain within the limits shown in
Table 9.1. For this reason, the pressure drop through the entire system must be known.
This method is generally not recommended because it is often very difficult to accurately calculate the pressure
drop through the system. In replacement installations, it may be impossible to get an accurate measurement of
the amount of piping and number of fittings in the system. In addition, if the system is zoned, the system flow
may drop well below the minimum required when only one zone is calling for heat.
The one advantage to this method is its installation simplicity. It may make sense to use this method when the
boiler is to be installed with a new single zone system having a low-pressure drop.
Figure 9.7 shows the performance curve for the pump in each boiler model, taking into account the pressure
drop through the boiler’s heat exchanger and internal piping. These curves therefore show the flow that can be
achieved through the boiler as a function of the pressure drop through the connected piping. Calculation of the
system pressure drop must be performed by someone having familiarity with pressure drop calculations, such
as an HVAC engineer.
NOTICE Where it is not possible to install a separate boiler loop, the system circulator must be sized to
ensure that the flow through the boiler stays within the defined parameters to prevent overheating when
the boiler is fired at it’s full rated input. Install a flow meter to measure the flow, or fire the boiler at full
rate and ensure the boiler delta T does not exceed 35°F (19°C).
Figure 9.6: Piping Method #2 - Direct Connection of Boiler to Heating System
108095-02- 4/18
77
Page 78
0246810
AvailableHead(ft
IX. System Piping (continued)
Note: These curves show the flow that can be achieved through the boiler as a function of the
pressure drop through the connected piping.
35
30
25
20
15
10
5
0
Flow(GPM)
Figure 9.7a: 135 Net Circulator Performance Curve (Taco 0011)
40
35
30
25
20
15
AvailableHead(ft
10
5
78
0
02468101214
Figure 9.7b: 150/180 Net Circulator Curve (Taco 0013)
Flow(GPM)
108095-02 - 4/18
Page 79
IX. System Piping (continued)
D. Piping for Special Situations
1. System containing oxygen - Many hydronic systems contain enough dissolved oxygen to cause severe
corrosion damage to a boiler. Some examples include:
• Radiant systems that employ tubing without an oxygen barrier.
• Systems with routine additions of fresh water.
• Systems which are open to the atmosphere.
If the boiler is to be used in such a system, it must be separated from the oxygenated water being heated
with a heat exchanger as shown in Figure 9.8. Consult the heat exchanger manufacturer for proper heat
exchanger sizing as well as flow and temperature requirements. All components on the oxygenated side of
the heat exchanger, such as the pump and expansion tank, must be designed for use in oxygenated water.
2. Piping with a Chiller - If the boiler is used in conjunction with a chiller, pipe the boiler and chiller in parallel.
Use isolation valves to prevent chilled water from entering the boiler.
3. Air Handlers - Where the boiler is connected to air handlers through which refrigerated air passes, use flow
control valves in the boiler piping or other automatic means to prevent gravity circulation during the cooling
cycle.
Figure 9.8: Isolation of the Boiler from Oxygenated Water with a Plate Heat Exchanger
108095-02- 4/18
79
Page 80
X. Domestic Hot Water Piping
DANGER
Scald Hazard. Under certain conditions this boiler can deliver domestic hot water
(DHW) at temperatures in excess of the DHW set point on the boiler control. An installer-supplied, ASSE
1017 or ASSE 1070 certified tempering valve is therefore REQUIRED as part of this boiler’s installation.
• Select and install tempering valve in accordance with the valve manufacturer’s instructions and
applicable local codes. In the absence of such codes follow the Uniform Plumbing Code (IAPMO/UPC-1).
Also note that additional tempering valves may be required at the fixtures themselves.
NOTICE
•
DHW feature on this boiler is designed to only to heat potable water (i.e. water from a well or water utility
that is suitable for drinking) having the following characteristics:
a. Hardness less than 200PPM
b. PH between 6 and 8
c. Chloride level less than 80PPM.
Use of water not having these characteristics could result in premature failure of the DHW handling
components in this boiler.
• Internal components near the Hot and Cold connections can be damaged by excessive heat during
soldering. If copper adaptors are mounted directly on the combi, solder adjacent piping to these
adaptors before installing them on the boiler. Failure to do so may cause internal leaks and/or other
damage to the boiler.
Install the domestic hot water piping as shown in Figure 10.1. Combi connections are ¾” NPT male thread. The
components in this system, and their functions are as follows:
1. ASSE 1070 or ASSE 1017 Listed Tempering Valve (Required) – This boiler is equipped with a control system
that attempts to regulate the DHW outlet temperature to a DHW set point (default set point is 120F – see
Section XIII for more information). As with all water heaters there are inherent limitations on the ability of the
control system to accurately regulate water temperature to this set point under all conditions. Extremely
low draw rates and transitions from heating to DHW are two examples of conditions that can cause the
temperature of water leaving the boiler to significantly exceed the DHW set point. To minimize “spikes” in
DHW temperature, a tempering valve is therefore required. Select and install in accordance with the valve
manufacturer’s instructions and applicable codes. Note that some codes require additional tempering
devices at some of the fixtures as well.
2. Flow Restrictor (Optional) - If domestic hot water is drawn from at a rate in excess of the rating in Table 2.2,
the temperature of the hot water may be too low to be of use. The use of a flow restrictor will help prevent this
problem by limiting the rate at which water can pass through the DHW heat exchanger. If a restrictor is used,
select one having a rating in GPM approximately equal to that shown in Table 2.2 at the desired temperature
rise.
3. Pressure Relief Valve (Required) - Limits the pressure in the domestic hot water piping. Use a valve designed
for DHW service, such as the Watts #3L or #53L. Note that this is a pressure relief valve, not a T&P valve.
Select a valve with a pressure setting less than or equal to 145 psi. Pipe the discharge to a safe location
using piping the same size as the discharge connection on the valve.
4. Hose Bib Valves (Recommended) - These valves permit the DHW plate heat exchanger be periodically
“back flushed” to remove sediment.
5. Globe or Ball Valve (Recommended) - Used to aid in back flushing the heat exchanger and to isolate the
DHW piping if it must be serviced. In addition, the upstream valve may be used to limit the DHW flow if
necessary.
6. Thermal Expansion Tank (Required if a backflow preventer is installed) – If a back flow preventer or check
valve is installed upstream of the cold connection, a thermal expansion tank will prevent the build-up of
pressure in the DHW piping. Use a thermal expansion tank designed for use in potable water service.
7. Unions – Improve serviceability of DHW piping.
80
108095-02 - 4/18
Page 81
X. Domestic Hot Water Piping (continued)
108095-02- 4/18
Figure 10.1: Domestic Hot Water Piping
81
Page 82
XI. Wiring
DANGER
Electrical Shock Hazard. Positively assure all electrical connections are unpowered
before attempting installation or service of electrical components or connections of the boiler or building.
Lock out all electrical boxes with padlock once power is turned off.
WARNING
All wiring and grounding must be done in accordance with the authority having
jurisdiction or, in the absence of such requirements, with the National Electrical Code /NFPA 70). In
Canada, all wiring and grounding must be done in accordance with the Canadian Electrical
Code, Part 1 (CSA C22.1 - latest edition).
Failure to properly wire electrical connections to the boiler may result in serious physical harm.
Electrical power may be suppled from more than one circuit. Make sure all power is off before attempting
any electrical work.
Each boiler must be protected with a properly sized over-current device.
Never jump out or make inoperative any safety or operating controls.
The wiring diagrams contained in this manual are for reference purposes only. Each boiler is shipped
with a wiring diagram attached to the front door. Refer to this diagram and the wiring diagram of any
controls used with the boiler. Read, understand and follow all wiring instructions supplied with the
controls.
NOTICE This boiler is equipped with a listed high water temperature limit function. This limit provides
boiler shutdown in the event the boiler water temperature exceeds the set point of the limit control.
Certain Local Codes require an additional water temperature limit. If necessary, install an additional water
temperature limit such as a Honeywell L4006 Aquastat. Wire as indicated in Figure 11.3.
Figure 11.1 shows the locations for making both high voltage and low voltage field connections.
1. Line Voltage (120 VAC) Field Connections – Leads for the line voltage connections are located in the
junction box as shown in Figure 11.1. Provide a dedicated circuit for the boiler of 15A or greater. A service
switch is recommended and is required by many local codes. Locate this switch in accordance with local
codes or, in the absence of any, in a location where it can be safely accessed in an emergency involving the
boiler. All 120VAC connections to the boiler itself are wire nut connections, except for the ground, which is a
screw. The leads are color coded as follows:
• 120VAC Hot - Black
• 120VAC Neutral - White
• System Pump Hot - Yellow
See Figure 11.2 for line voltage field connection wiring.
Note that the system circulator is field supplied and is the pump that, in most cases, actually circulates water
through the radiation. The system pump is always on when the boiler is responding to a call for space heat.
Maximum recommended current draw for the system pump is 2.0A.
82
108095-02 - 4/18
Page 83
XI. Wiring (continued)
2. Low Voltage Connections – Commonly used low voltage field connections are located on the low voltage
PCB and are shown in Figure 11.3 and listed from left to right:
1 Heat T’Stat - 24VAC heating thermostat
2 Heat T’Stat - 24VAC heating thermostat
3 DHW Stat - No field connection
4 DHW Stat - No field connection
5 External Limit - Field supplied low voltage safety limit contacts (1)
6 External Limit - Field supplied low voltage safety limit contacts (2)
7 Outdoor Sensor - Tasseron TSA00AA Outdoor Temperature Sensor (1)
8 Outdoor Sensor - Tasseron TSA00AA Outdoor Temperature Sensor (2)
External power must not be applied to any of the low voltage terminals - doing so may damage the boiler control.
Also note the following:
a. External Limit - The external limit terminals are intended for use with a field supplied safety device,
such as a manual reset high limit or low-water cut-off. When an external limit is used, the jumper
between these two terminals must be removed. Failure to remove this jumper will render the external
safety devices ineffective.
b. Outdoor Sensor - Use only the Tasseron TSA00AA outdoor sensor supplied with the boiler. When
this sensor is connected and enabled, the boiler will adjust the target supply water temperature
downwards as the outdoor air temperature increases. This sensor should be located on the outside of the structure in an area where it will sense the average air temperature around the house. Avoid placing this sensor in areas where it may be covered with ice or snow. In general,
locations where the sensor will pick up direct radiation from the sun should also be avoided. Avoid
placing the sensor near potential sources of electrical noise such as transformers, power lines, and
fluorescent lighting. Wire the sensor to the boiler using 22 gauge or larger wire. As with the sensor
itself, the sensor wiring should be routed away from sources of electrical noise. Where it is impossible to avoid such noise sources, wire the sensor using a 2 conductor, UL Type CM, AWM
Style 2092 shielded cable. Connect one end of the shielding on this cable to ground. See Section XIII of this manual for information on enabling the outdoor reset sensor.
Figure 11.1: Location of High and Low Voltage Field Electrical Connections
108095-02- 4/18
83
Page 84
XI. Wiring (continued)
Figure 11.2: Line Voltage Field Connections
Figure 11.3: Low Voltage PCB Terminal Connections
84
108095-02 - 4/18
Page 85
XI. Wiring (continued)
c. Low water cut-off wiring – Although not necessary to protect this boiler (see Part IX), some jurisdictions may insist that a low water cut-off (LWCO) be installed with this boiler. There are two ways to wire a LWCO into this boiler:
• A 120V LWCO may be wired to break 120V power to the boiler (Figure 11.4a)
• A 24V LWCO may be wired so that its contacts are wired to the external limit connections on the boiler. When this is done either:
• A separate transformer must be supplied by the installer to power the LWCO’s sensing circuit. This transformer must be completely isolated from the boiler wiring (Figure 11.4b).
OR
• Power may be taken from EnviraCOM connections, if not otherwise in use (Figure 11.4c)
d. 4-20 mA Energy Management System (EMS) - A 4-20 mA EMS may be wired to the Sage controller (Figure
11.5). Manufacturer part numbers for contacts (field supplied) required to install wire leads in JST housing
are:
• SRSF-61T-250A (Recommended for size 16 AWG wire)
• ASRSFSRSF16K51B (2" lead between contacts)
• ASRSFSRSF16K152B (6" lead between contacts)
• ASRSFSRSF16K305B (12" lead between contacts)
• SRSF-21T-250A (Recommended for size 20 AWG wire)
• ASRSFSRSF20K51B (2" lead between contacts)
• ASRSFSRSF20K152B (6" lead between contacts)
• ASRSFSRSF20K305B (12" lead between contacts)
3. Data Connections – Modbus and EnviraCOM connections are located in the green control connector shared
with the display connections (Figure 11.6). These connections have the following uses:
a. EnviraCOM - Used to connect EnviraCOM thermostat or other EnviraCOM device listed by the boiler manufacturer for use with this boiler.
b. MODBUS - Boiler-To-Boiler communication network is used for multiple boiler (“Lead-Lag”) installations.
Note that combi boilers may only be used as slaves in such a system.
CAUTION
When making low voltage connections, make sure that no external power source is
present in the thermostat or limit circuits. If such a power source is present, it could destroy the boiler’s
control. One example of an external power source that could be inadvertently connected to the low
voltage connections is a transformer in the old thermostat wiring.
Do not attempt to use EnviraCOM connections for any purpose not explicitly permitted by the boiler
manufacturer. Attempting to do so may result in unreliable operation and/or damage to controls.
USE WIRE CODE ON CONNECTIONS DIAGRAM TO DETERMINE COLOR.
WIRE MARKING
WIRE NO. IN
FIG 11.8
36a VISPL VI-1/ -RD
36b VISPL VI-1/ -SD
37 BLJ3-3/ 5V+
38 PIJ3-6/ 5V-
WIRE MARKING
108095-02- 4/18
91
Page 92
XI. Wiring (continued)
Figure 11.9: TACO SR504 or Equivalent Zone Panel Wiring Connection Diagram
92
108095-02 - 4/18
Page 93
XI. Wiring (continued)
Figure 11.10: Sage Zone Control Circulator Panel Wiring Connection Diagram
108095-02- 4/18
93
Page 94
XII. Start-Up and Checkout
WARNING
Completely read, understand and follow all instructions in this manual before
attempting start-up.
NOTICE Safe lighting and other performance criteria were met with the gas train assembly provided on the
boiler when the boiler underwent the tests specified in Z21.13.
Use the following procedure for initial start-up of the boiler:
1. Verify that the venting, water piping, gas piping and electrical system are installed properly.
2. Confirm all electrical, water and gas supplies are turned off at the source and that vent is clear of
obstructions.
3. Confirm that all manual shut-off gas valves between the boiler and gas source are closed.
4. If not already done, flush the system to remove sediment, flux, and traces of boiler additives.
5. Fill the boiler and hydronic system with water meeting the following requirements below (also see
the note on the next page):
• pH between 6.5 and 9.5
• Hardness less than 7 grains/gallon
• Chlorides less than 200 ppm
• Pressurize the system to at least 12 psi at the boiler
WARNING
Burn Hazard. The maximum operating pressure of this boiler is 30 psig (210 kPa) or
50 psig (340 kPa), depending on the model and safety relief valve option selected. Never exceed the
maximum allowable working pressure on the heat exchanger ASME plate.
6. Bleed air from the heat exchanger using the manual air vent in the top left side of the heat exchanger (Figure 12.1). To do this install a piece of ¼” ID clear tubing over the hose barb and route
the tubing to a location where water will not damage controls or nearby construction. Turn vent counter clockwise and allow heat exchanger to vent until a steady stream of water is observed.
Close vent and remove hose.
7. Check all gas piping for leaks and purge piping sections that are filled with air. Refer to the National
Fuel Gas Code for additional information on testing and purging gas lines.
DANGER
Explosion Hazard. Do not use matches, candles, open flames or other ignition source to
check for leaks.
Make sure that the area around the boiler is clear and free from combustible materials, gasoline and other
flammable vapors and liquids.
8. Confirm vent system is complete and free of obstructions before attempting to fire boiler.
9. Inspect all wiring for loose, uninsulated or miswired connections.
10. If the boiler is to be converted to propane, convert as described in conversion kit instructions. If
boiler is operating at elevations above 2000ft, see Appendix A of this manual for setup instructions.
94
108095-02 - 4/18
Page 95
XII. Start-Up and Checkout (continued)
DANGER
Asphyxiation Hazard. Failure to properly convert this boiler for use on LP gas can cause
unreliable operation at elevated carbon monoxide (CO) levels, resulting in personal injury or death.
NOTICE To minimize the risk of premature heat exchanger failure, observe the following water chemistry
requirements:
1. Minimize the introduction of make-up water, dissolved oxygen, and contaminants into the boiler by
following the installation guidelines shown in the “Water Quality and Boiler Water Additives Note” on
Page 70.
2. Make sure the system is filled with water meeting the following criteria:
• pH between 6.5 and 9.5 (for systems containing aluminum components, between 6.5 and 8.5)
• Chloride level less than 200 PPM. If fill water is drawn from a system containing a water softener, test a
sample of the fill water to confirm that this criteria is met.
• Hardness less than 7 grains/gallon.
3. Avoid the use of petroleum based boiler additives and ester-based oils/lubricants.
These can attack seals in both the boiler and system.
4. If freeze protection is required, use the following or its equivalent:
Refer to the antifreeze manufacturer’s instructions for required dosage. In general these products are a
blend of glycol (for freeze protection) and inhibitors (to protect the glycol from attacking metallic system
components). Do not add any more antifreeze than is necessary to protect the system from freeze damage.
Many of these products require annual testing of the system water to ensure that the inhibitors are still
active; consult the manufacturer’s instructions for maintenance requirements. Allowance must be made for
the additional expansion of the glycol solution.
5. Test antifreeze and inhibitor concentration annually.
• Inhibitor concentration test kit for Fernox Protector F1, 25 tests per kit. Part Number: 101148-01
6. For system cleaning, use the following or its equivalent:
• Fernox Cleaner F3
• Sentinel® X300 System cleaner (for New Heating systems)
• Sentinel® X 400 System Restorer (For old Closed Loop Hydronic Heating Systems)
Refer to the instructions supplied with the cleaner for proper dosage and use.
Fernox products are available from Alent PLC Consumer Products Division, 4100 6th Avenue, Altoona
PA, (972) 547-6002 (fernox_usa@alent.com)
Sentinel® Products are available from Douglas Products and Packaging, 1550 E. Old 210 Highway,
Liberty, MO 64068, Tel: (877) 567-2560 (Toll Free) and /or selected HVAC distributors.
WARNING
Poison Hazard. Use only inhibited propylene glycol solutions specifically formulated for
hydronic systems. Do not use ethylene glycol, which is toxic and can attack gaskets and seals used in
hydronic systems. Use of ethylene glycol could result in property damage, personal injury or death.
108095-02- 4/18
95
Page 96
XII. Start-Up and Checkout (continued)
ATTACH 1/4" ID CLEAR
TUBING TO HOSE BARB
AND ROUTE TO SAFE PLACE
AWAY FROM CONTROLS
BEFORE OPENING VENT.
MANUAL AIR VENT
FLAME ROD
Figure 12.1: Location of Manual Air Vent
11. Start the boiler using the lighting instructions on page 100. With the boiler powered up, and with no
call for heat, the display should look like Figure 12.2a. Once a call for heat is present, it will look like
Figure 12.2b.
12. The boiler should attempt to fire approximately 30 seconds after a call for heat appears. With the
front door open, this try for ignition will appear as an audible spark (lasting approximately 4 seconds) and an audible click from the gas valve. Upon initial start-up, the gas train will be filled
with air. Even if the gas line has been completely purged of air, it may take several tries for ignition
before a flame is established. If the boiler does not light after six tries for ignition, it will enter a “soft
lockout” and will wait for one hour before attempting another ignition sequence. This soft lockout can
be reset by interrupting power to the boiler for a few seconds. Once a flame has been established
for the first time, subsequent calls for burner operation should result in a flame on the first try.
13. If there is a problem that appears before the first try for ignition, or if the boiler fails to light after six
tries for ignition, the blinking “HELP” button is highlighted on the Home screen (Figure 12.2c). Touching this “HELP” button will take the user to the Diagnostics menu where the cause of the problem can usually be found by pressing the flashing button on each successive screen.
14. Inspect the flame visible through the window. On high fire the flame should be stable and mostly
blue (Figure 12.3). No yellow tipping should be present; however, intermittent flecks of yellow and
orange in the flame are normal.
15. Check the inlet gas pressure. Verify that the inlet gas pressure is between the upper and lower
limits shown on the rating plate with all gas appliances on and off.
96
108095-02 - 4/18
Page 97
XII. Start-Up and Checkout (continued)
i
Boiler /Combi
i
Boiler /Combi
i
Boiler /Combi
Status
Detail
Help
Adjust
Figure 12.2a: Home Screen at Power-Up (No Call for Heat)
Status
Detail
Help
Adjust
Figure 12.2b: Home Screen on Heat Demand
Status
Detail
Help
Adjust
180 F
Standby
Energy Save On
High Efficiency On
180 F
Central Heat
Energy Save On
High Efficiency On
180 F
Standby
Energy Save On
High Efficiency On
0
80
0
kbtu
hr
kbtu
hr
kbtu
hr
Figure 12.2c: Home Screen with Active Fault
Figure 12.3: Burner Flame
108095-02- 4/18
97
Page 98
XII. Start-Up and Checkout (continued)
Figure 12.4: Gas Valve Detail
WARNING
Do not attempt to operate this boiler on LP gas without converting it using the proper
conversion kit.
Do not attempt to convert this boiler to LP gas without the use of a combustion analyzer.
Failure to follow the conversion instructions will result in operation of the boiler at unsafe Carbon
Monoxide (CO) levels and may result in personal injury or loss of life. Improper conversion may also
result in unreliable operation, resulting in property damage.
Before attempting to operate this boiler at altitudes above 2000 ft., follow instructions shown in Appendix
A of this manual.
16. Perform a combustion test. Boilers are equipped with a screw cap in the vent adapter. Be sure to
replace this cap when combustion testing is complete. Check CO2 (or O2) and CO at both high
and low fire. Ensure the door panel is sealed before combustion readings are taken. The boiler may
be temporarily locked into high or low fire as follows:
a. Fire the boiler through any call for heat.
b. From the Home Screen, press “ADJUST” to enter the adjust menu.
c. Press “ADJUST”.
d. Press “LOGIN”.
e. Press “000”.
f. Enter the password “086”
g. Press return arrow to close the keypad.
h. Press “SAVE”.
i. Press “ADJUST”
j. Press “MANUAL CONTROL”.
k. Press “HIGH” or “LOW” as appropriate.
98
108095-02 - 4/18
Page 99
XII. Start-Up and Checkout (continued)
To return the boiler to automatic modulation, press AUTO FIRE. Note: If the Auto Fire button is not pressed,
boiler will remain in manual fire for around 10 minutes. After 10 minutes boiler automatically returns to
automatic modulation.
At both high and low fire, CO readings should be less than 200 PPM air free. Typical CO
are shown in Table 12.5A. Final readings should be taken with all doors and covers in place. If adjustments
are needed, make them as follows:
a. With burner at high fire, adjust gas valve throttle (Fig 12.4) as needed to obtain CO2 (or O2)
setting shown in Table 12.5A.
• To reduce the CO
• To increase the CO
(increase the O2), turn throttle clockwise.
2
(reduce the O2), turn throttle counter-clockwise.
2
Make adjustments in increments of 1/8 to 1/4 turns and allow the boiler at least a minute to respond
before making another adjustment.
b. With the burner at low fire, adjust gas valve offset regulator (Fig 12.4) as needed to obtain
CO
(or O2) setting shown in Table 12.5A.
2
• To reduce the CO2 (increase the O2), turn offset regulator counter-clockwise.
• To increase the CO2 (reduce the O2), turn offset regulator clockwise.
Make adjustments in increments of no more than 1/8 turns and allow the boiler at least a minute to
respond before making another adjustment.
WARNING
Improper gas valve adjustments can result in unreliable operation, substantial property
damage, personal injury or loss of life due to carbon monoxide (CO) poisoning. Observe the following
precautions:
•
Do not attempt to adjust gas valve without a combustion analyzer.
•
Each boiler is tested at the factory and adjustments to the gas valve are normally not necessary when
operating on natural gas at sea level. Before making any adjustments, make sure that the analyzer is
calibrated and that combustion readings have stabilized.
•
Regulator (“offset”) screw used for low fire adjustment is very sensitive. Adjust no more than 1/8 turn
before checking combustion with analyzer. Maximum total regulator adjustment is ± 1 turn from factory
setting.
and O2 readings
2
17. Perform a check of the ignition safety shut-off device. With the burner firing, carefully unplug the
orange flame rod wire at the flame rod using a pair of insulated pliers (Figure 12.1). The burner
should shut off immediately.
18. Test any external limits or other controls in accordance with the manufacturer’s instructions.
19. Refer to the Operation Manual to set-up the control for the system in which the boiler is installed. Some common set-up tasks include:
• Setting the CH temperature set-point.
• Defining the system pump operation.
20. Adjust the heating thermostat to its final set point.
108095-02- 4/18
99
Page 100
XII. Start-Up and Checkout (continued)
NOTICE In some cases, such as when the gas valve is replaced, the throttle may be far enough out of
adjustment that it is not possible to fire the boiler while “dialing in” the CO
analyzer. In such a case, do the following:
1. Turn the throttle screw clockwise until it stops turning.
2. For natural gas applications, turn the throttle screw counter-clockwise by the number of turns shown
in Figure 12.5B.
3. For LP gas applications set the preliminary throttle setting per conversion kit instructions.
4. Start the boiler using the lighting instructions on Page 100.
5. Once the boiler is firing, use a combustion analyzer to adjust the CO2 (or O2) to its final value as
described above.
Table 12.5A: Typical Natural Gas Combustion Readings (Sea Level Only)
(or O2) using a combustion
2
Boiler Size
Measured High Fire %CO
RangeTarget
*
2
Maximum CO Air-Free
135
8.7-9.29.1200ppm150
180
* Low Fire Range and Target values are the same as High Fire above. Ensure low fire CO
than or equal to high fire CO2 reading.
Boiler Size
Measured High Fire %O
RangeTarget
**
2
Maximum CO Air-Free
135
4.7-5.64.9200ppm150
180
** Low Fire Range and Target values are the same as High Fire above. Ensure low fire O
than or equal to high fire O2 reading.
Table 12.5B: Starting Number of Throttle Turns for Natural Gas
Model
# Counter-clockwise Turns (From Fully
Closed)
13512-1/4
15010
18015
reading is less
2
reading is greater
2
NOTICE This boiler has a limited warranty, a copy of which is included with this boiler. It is the
responsibility of the installing contractor to see that all controls are correctly installed and are operating
properly when the installation is complete.
100
108095-02 - 4/18
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.