VF-71E Filter Housing Installation Instructions
Hydraulic & Fuel Filtration Division
VF-71E Filter Housing
Installation Instructions
DESCRIPTION
 e VF-71E Filter Housing is designed for use in industrial applications with a variety of oils and other liquids.  e housing is shipped with no cartridge installed. Cartridges must be ordered separately.
CONNECTIONS SIZE: 3/4" NPT
HOUSING PRESSURE RATING: 150 psi
NOTE: FOR LIQUID SERVICE ONLY. Do not use or leak test this  lter vessel with compressed air or
other gasses.
INSTALLATION
1. Install the housing in an area that provides access to the inlet, outlet, and drain  ttings. Allow at least 18 inches of clearance above the band clamp for cartridge removal.
2. Make inlet and outlet connections to the appropriately labeled  ttings. DO NOT  ow backwards through the housing.
3. Installation of pressure gauges is recommended to monitor di erential pressure across the housing and to allow accurate determination of when the  lter cartridge should be changed.  e auxiliary tap in the vessel lid can be used to install a gauge for measuring the pressure upstream. If the backpressure is expected to vary, it is recom­mended that gauges be installed upstream and downstream.
4. On systems where pressure can exceed 75 psi, a pressure bypass around the pump should be installed to protect the cartridge and the system from a high pressure shock of sudden cartridge seal-o due to a slug of water.
5. Installation of shut-o valves on the inlet and outlet lines may be required to isolate the housing during cartridge change-out.
6. Install the cartridge as outlined in the cartridge change-out section.
7. Write the proper cartridge model number on the enclosed replacement cartridge label, fasten it to the housing shell just below the VF-71E label, then cover the cartridge label with the enclosed clear plastic sticker.
OPERATION
1. Check that all unused  ttings on the vessel are plugged.
2. Open the top air vent and check that the bottom housing drain is closed.
3. Start the pump and verify that air is venting from the housing. IF NOT, TURN THE UNIT OFF; check all lines for obstructions.
4. Allow all air to vent from the housing. Close the top air vent when  uid begins to bleed out.
5.  e vent should be opened periodically to expel any entrapped air. A large accumulation of air will reduce the  ltering area of the cartridge.
6. Check all  ttings and lid for leakage. Additional tightening may be required.
7. Note the pressure gauge reading. For most oils it will be below 5 psi with a clean cartridge.
-1-
Parker Hanni n Corporation
Hydraulic & Fuel Filtration Division
1210 Garden of the Gods Road
VEL1658R12 0316 PN09-881 www.velcon.com
VF-71E Filter Housing Installation Instructions
CARTRIDGE CHANGE-OUT
1. When the pressure has risen by 20-25 psi over the initial clean pressure, or when di erential pressure reaches 25 psid, the cartridge must be changed.
2. Turn the unit o .
3. Vent the housing at the cover, and drain all liquid through the bottom drain. MAKE CERTAIN THE HOUSING IS COMPLETELY DRAINED BEFORE REMOVING THE LID.
4. Loosen the band clamp and remove the lid.
5. Remove the old cartridge and install a new one. See the accompanying  gure for proper assembly of parts. Use a new rubber washer included with each cartridge, and tighten the thumb screw until the rubber washer curls slightly.
6. Clean the cover o-ring and o-ring groove. Lightly lubricate the O-ring with the fuel or oil it will be used in, and position it on the groove (or head).
7. Replace the cover and fasten the band clamp.
8. Close the bottom drain and restart  ow. Close the top air vent when the housing has  lled.
9. Check all  ttings and cover for leaks.
Hydraulic & Fuel Filtration Division
REPLACEMENT PARTS
Description of Part Velcon Part Number
Band Clamp Assembly 025X903
Air Vent 550X002
Top Seal Plate 12-02M
Rubber Gasket G-0305
Flat Washer 402X046
Lock Washer 402X082
 umb Screw 404X101
*Std. Buna-N Lid Gasket G-1016
*Optional Viton A Lid Gasket G-1016A
*NOTE: Lid gaskets can be obtained at most O-ring suppliers. Specify size 2-442.