SI23 Solar Pump Inverter Manual
4
inverter is zero when the switch is working)
6. At over 1,000 meters altitude, the inverter’s heat dissipation function worsened due to the thin air, it is necessary to use
less.
7. The inverter output voltage is pulse wave type. If using digital multi-meter measurement, deviation of the reading will be
great. And the deviation is different by using different type of digital multi-meter. Under normal circumstances, while RMS
380V, digital multi-meter reading is around 450V.
8. Solar panel can be connected in the series or parallel. For rated voltage 380V controller, we suggest working voltage
between 480V and 560V while MPPT. What means the solar panel open circuit voltage should be between 600V and
700V.
1.4 Technical Specification
Solar pump
inverter
power(KW)
Pump
Max solar
power
input
(KW)
Max DC
input
voltage V
Recommend
Voc voltage (V)
Rated
output
current
(A)
Output
frequency
(Hz)
Rated
power
(KW)
Rated
voltage
(V)
SI23-D1 series, DC60-400VDC input, 3 phase 110-230VAC output
0.75 0.75 110 1.0 400 175~380 7A 0-600
1.5 1.5 110 1.95 400 175~380 10A 0-600
SI23-D3 series,DC150V-450V input, 3 phase 220-240VAC output
0.75 0.75 220 1.0 450 360~430 4A 0-600
1.5 1.5 220 1.95 450 360~430 7A 0-600
2.2 2.2 220 2.86 450 360~430 10A 0-600
4 4 220 5.4 450 360~430 16A 0-600
SI23-D5 series,DC250V to 780VDC input, 3 phase 380-460VAC output
0.75 0.75 380 1.0 780 620~750 3.0 0-600
1.5 1.5 380 2.2 780 620~750 4.0 0-600
2.2 2.2 380 3.3 780 620~750 6.0 0-600
4 4 380 5.6 780 620~750 10 0-600
5.5 5.5 380 8 780 620~750 13 0-600
7.5 7.5 380 10 780 620~750 17 0-600
11 11 380 14.3 780 620~750 25 0-600
15 15 380 19.5 780 620~750 32 0-600
18.5 18.5 380 23.4 780 620~750 38 0-600
22 22 380 28.6 780 620~750 45 0-600
30 30 380 39 780 620~750 60 0-600
SI23-T3 series,DC350V to 780VDC input,3phase 380-440VAC output
37 37 380 48.1 780 620~750 75 0-600
45 45 380 58.5 780 620~750 90 0-600
55 55 380 71.5 780 620~750 110 0-600
75 75 380 97.5 780 620~750 150 0-600
1.5 Cautions in Disposal
When you dispose frequency inverter, please pay attention to:
1. Electrolytic capacitor: the electrolytic capacitor of main circuit or the printing plate may explode when they are burned.
2. Plastic: plastic incineration may generate toxic gases.
3. Dispose method: please dispose as industrial waste.