AC300 Series Vector Control Inverter Manual Function Parameter Specifications
54
Notes:
1. PG refers to the speed encoder, used as PG vector control, generally with photoelectric encoder or rotary
transformer, need to select the corresponding PG card according to PG type and parameters, see function
code [F05.30];
2. When selecting the vector control mode, before the first run, first input the motor parameters correctly
and perform automatic motor parameter tuning to obtain the correct motor parameters. For details, please
refer to the detailed description of the "F05" motor parameter group.
3. The parameters of the vector control parameter group should be correctly set to ensure good steady state
and dynamic control performance. For the parameter setting and adjustment of the vector control
parameter group, please refer to the detailed description of the "F06" parameter group.
4. When selecting the vector control mode, it should be noted that the inverter can only drive one motor at
the same time; and the inverter capacity and the motor capacity level cannot be too different, the inverter
can be two or smaller than the motor power level. Failure to do so may result in reduced control
performance or the drive system may not function properly.
F00.01 Reserved
F00.02 Run command channel
Setting range: 0~3
Default: 0
Uses for selecting inverter running, stop and running direction command input channel.
0: keypad control
Running and stop of inverter control by forward running key PRG , stop key STOP/RESET of operator keypad. When
[F04.07] parameter set to 1, REV/JOG is defined for JOG running.
1: terminal control
Running, stop and rotation direction of inverter control by terminal . See [F02.00~F02.09] for details. See [F02.23] for
the terminal operation control mode and [F02.24] for the terminal startup protection.
2: RS485 communications port control
The running command is given by the host computer through communication. For communication parameter settings,
please refer to the F13 communication control parameter group.
When the peer-to-peer broadcast communication, the slave selects the run command transmitted by the host as the
run command, please refer to [F13.09] for instructions.
When Modbus RS485 communication is valid, the running command is set and modified by address 0x3001/0x2001.
See Appendix 2: Modbus Communication Protocol for details.
When the Profibus-DP communication is valid, the running command is set and modified by the corresponding
address, see the Profibus-DP card instruction manual of the optional card.
3: Option card
The operation and stop of the inverter are controlled by the external optional card communication. For the installation
method and parameter setting of the optional card, please refer to the instruction manual of the same box with the
optional card.
Note:
1. STOP/RESET of keypad, reset command from control terminal or RS485 communication are all enabled
AC300 Series Vector Control Inverter Manual Function Parameter Specifications
55
when fault reset.
Tips:
2. The function of the STOP/RESET button of the keyboard can be selected. When external terminal control
or communication control, it can be defined as the function of stop button, please refer to parameter
[F04.08]; when using external terminal for running control, if using STOP of keyboard When the /RESET
key is stopped, the inverter will stop and block the external terminal running command. At this time, the
external terminal stop command must be input to unlock, and the external terminal running command is
valid again. The communication control is the same.
F00.03 Frequency given source channel A Setting range: 0~11 Default: 0
F00.04 Frequency given source channel B Setting range: 0~11 Default: 2
Select the given source of the inverter set frequency in [F00.03], [F00.04]; [F00.06] sets the relationship between
channel A and channel B.
0: Keyboard number given
The set frequency is given by the parameter [F00.08] keyboard digital setting frequency; the current setting value of
the parameter [F00.08] can be quickly modified by selecting the [F04.09] LED single digit selection keyboard up/down
keys; Value power-down storage and up/down key action limit selection can be found in parameter [F04.09].
1: Reserved
2: Voltage/Current analog AI1 given
3: Voltage/Current analog AI2 given
The set frequency is given and modified by the input analog quantity AI1, AI2. By linearizing the input analog quantity
value, the calibration 100% corresponds to the maximum frequency. For details, see “F03” parameter group analog
quantity processing.
4: Reserved
5: Terminal pulse PUL given
The set frequency is given and modified by the control terminal (PUL) input pulse signal; by linearizing the input
pulse signal, the calibration is 100% corresponding to the maximum frequency, see parameter [F02.27~F02.33] for
details.
6: RS485 communication given
The set frequency is given by the communication method. For the communication parameter setting, please refer to
the F13 communication control parameter group.
When the peer-to-peer broadcast communication, the slave selects the host to transmit the given frequency or output
frequency as the set frequency, please refer to [F13.09] for instructions. When Modbus RS485 communication is valid,
the set frequency can be set and modified by address 0x3000/0x2000. See Appendix 2: Modbus Communication
Protocol.
When the Profibus-DP communication is valid, the set frequency is set and modified by the corresponding address.
See the Profibus-DP card instruction manual of the optional card.
When the CAN-RS485 communication is valid, the set frequency is set and modified by the corresponding address.
See the instruction manual of the optional CAN-RS485 card.