Veeder-Root VaporTEK Installation, Setup And Troubleshooting Manual

Installation, Setup and Troubleshooting Manual
VaporTEK
Manual No: 577014-013 Revision: E
Notice
Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication may be photocopied, modified or translated to another language without the prior written consent of Veeder-Root. Contact TLS Systems Technical Support for additional troubleshooting information at 800-323-1799.
DAMAGE CLAIMS / LOST EQUIPMENT
Thoroughly examine all components and units as soon as they are received. If any cartons are damaged or missing, write a complete and detailed description of the damage or shortage on the face of the freight bill. The carrier's agent must verify the inspection and sign the description. Refuse only the damaged product, not the entire shipment.
Veeder-Root must be notified of any damages and/or shortages within 30 days of receipt of the shipment, as stated in our Terms and Conditions.
VEEDER-ROOT’S PREFERRED CARRIER
1. Contact Veeder-Root Customer Service at 800-873-3313 with the specific part numbers and quantities that were missing or received damaged.
2. Fax signed Bill of Lading (BOL) to Veeder-Root Customer Service at 800-234-5350.
3. Veeder-Root will file the claim with the carrier and replace the damaged/missing product at no charge to the customer. Customer Service will work with production facility to have the replacement product shipped as soon as possible.
CUSTOMER’S PREFERRED CARRIER
1. It is the customer’s responsibility to file a claim with their carrier.
2. Customer may submit a replacement purchase order. Customer is responsible for all charges and freight associated with replacement order. Customer Service will work with production facility to have the replacement product shipped as soon as possible.
3. If “lost” equipment is delivered at a later date and is not needed, Veeder-Root will allow a Return to Stock without a restocking fee.
4. Veeder-Root will NOT be responsible for any compensation when a customer chooses their own carrier.
RETURN SHIPPING
For the parts return procedure, please follow the appropriate instructions in the "General Returned Goods Policy” pages in the "Policies and Literature" section of the Veeder-Root North American Environmental Products price list. Veeder-Root will not accept any return product without a Return Goods Authorization (RGA) number clearly printed on the outside of the package.
©Veeder-Root 2018. All rights reserved
.

Table of Contents

Introduction
Contractor Certification Requirements .................................................................................................2
Related Manuals .........................................................................................................................................2
Safety Precautions ....................................................................................................................................2
Safety Warnings .........................................................................................................................................3
VaporTEK Configurations ........................................................................................................................5
VaporTEK Pump Certifications & Markings .........................................................................................6
Safety Certification..........................................................................................................................6
Hazardous Area Installation Instructions ....................................................................................6
Equipment Marking .........................................................................................................................6
Material Compatibility With Constituents Of The Potentially Explosive Atmosphere ......7
TUV Certification..............................................................................................................................7
VaporTEK Kits .............................................................................................................................................7
VaporTEK Pump Kit - P/N 900612-001 ....................................................................................7
VaporTEK Controller Kit - P/N 900634-001.............................................................................8
VaporTEK Interface Kit - P/N 900635-001............................................................................ 10
VaporTEK High Voltage Relay Kit - P/N 900664-001......................................................... 10
VaporTEK Low Voltage Relay Kit - P/N 900665-001.......................................................... 10
VaporTEK Pump Characteristics ........................................................................................................ 11
VaporTEK Pump Specifications ................................................................................................ 11
VaporTEK Controller .............................................................................................................................. 12
VaporTEK Interface ................................................................................................................................ 14
VaporTEK Interface I/O ............................................................................................................... 15
VaporTEK Interface LEDs........................................................................................................... 15
VaporTEK LEDs ........................................................................................................................... 15
VaporTEK Pump Configuration ........................................................................................................... 17
Installation
VaporTEK Pump ...................................................................................................................................... 18
VaporTEK Controller and VaporTEK Interface ................................................................................. 20
Wiring Schematics
VaporTEK Wiring .................................................................................................................................... 23
Communication Setup - VaporTEK Interface
Setup with Laptop .................................................................................................................................. 32
VaporTEK Interface for Input Configuration ...................................................................................... 39
VaporTEK Calibration
Manual Calibration using the POT on the VaporTEK Controller board ..................................... 41
Dry Calibration - A/L Adjustment ........................................................................................................ 42
Equipment Required .................................................................................................................... 42
Initial Setup .................................................................................................................................... 42
Gas Meter Calibration ........................................................................................................................... 44
Pulse Rate Setup With FB1 Terminal ................................................................................................ 45
Pulse rate setup on VaporTEK Interface ................................................................................. 45
Pulse Rate Setup with FB1........................................................................................................ 45
Auto-Calibration using FB1 Terminal ................................................................................................. 46
Simulation with FB1 Terminal .............................................................................................................. 48
VaporTEK Pump Troubleshooting and Quick Help
Troubleshooting and Quick Help ........................................................................................................ 50
Appendix A: VaporTEK System Reference Wiring Diagrams
iii

Figures

Table of Contents
Figure 1. VaporTEK System Components .......................................................................................1
Figure 2. VaporTEK Pump Dimensions ......................................................................................... 11
Figure 3. VaporTEK Controller ......................................................................................................... 13
Figure 4. VaporTEK Interface ........................................................................................................... 14
Figure 5. VaporTEK Interface LEDs ................................................................................................15
Figure 6. VaporTEK Pump Installation Orientations ................................................................... 19
Figure 7. Mount The VaporTEK Controller To The Inside Of The Support Bracket................ 20
Figure 8. VaporTEK Motor/Sensor Connector’s Labeling And Poke Yoke ........................... 20
Figure 9. Mount The VaporTEK Interface To The Back Side Of The Support Backet .......... 21
Figure 10. Attach The VaporTEK Controller Safety Cover .......................................................... 22
Figure 11. VaporTEK System - High Voltage Hook Signal Input ............................................... 24
Figure 12. VaporTEK System - Liquid Pulse Signal and Low Voltage Hook Signal Input........ 25
Figure 13. VaporTEK Interface - Low Voltage Nozzle Hook Signal Connections .................. 26
Figure 14. VaporTEK Interface - Liquid Pulse Signal Connections ........................................... 27
Figure 15. VaporTEK System - Low Voltage Hook Signal With Relay Switches ................... 29
Figure 16. VaporTEK System - High Voltage Hook Signal With Relay Switches .................. 30
Figure 17. VaporTEK Low Voltage Relay Diagram ........................................................................ 31
Figure 18. VaporTEK High Voltage Relay Diagram ....................................................................... 31
Figure 19. Set Configuration Example .............................................................................................40
Figure 20. POT (Potentiometer) ........................................................................................................ 41
Figure 21. Calibration Setup .............................................................................................................. 43
Figure 22. Locate the Burkert Gas Meter Calibration Factor ..................................................... 45
Figure A-1. VaporTEK System Plus For Collection Only - Encore 500S Dispenser..................A-1
Figure A-2. VaporTEK System Plus For Collection Only - Encore 500S Dispenser ................A-2
Figure A-3. VaporTEK System Plus for collection only with 3 color LED -
Using 900855-001 Interface Board for Encore 500S Dispenser ........................A-3
Figure A-4. VaporTEK System Ultra for Collection only Using VRC 390/3 Board
for Encore 500S Dispenser ...........................................................................................A-4
iv

Introduction

VaporTEK Controller
VaporTEK Interface
VaporTEK Pump
This manual contains installation and operation instructions for Veeder-Root’s VaporTEK. VaporTEK is a dispenser based, Stage II vapor recovery system that collects vapor during vehicle fueling and returns vapor to the underground storage tank (UST). Each VaporTEK system is designed to accommodate two active fueling points simultaneously.
VaporTEK System Components:
VaporTEK Pump
VaporTEK Controller
VaporTEK Interface
Figure 1. VaporTEK System Components
1
Introduction Contractor Certification Requirements

Contractor Certification Requirements

Veeder-Root requires the following minimum training certifications for contractors who will install and setup the equipment discussed in this manual:
Installer Certification (Level 1): Contractors holding valid Installer Certification are approved to perform wiring and conduit routing; equipment mounting; probe, sensor and carbon canister vapor polisher installation; wireless equipment installation; tank and line preparation; and line leak detector installation.
Technician Certification (Level 2/3): Contractors holding valid Technician Certifications are approved to perform installation checkout, startup, programming and operations training, system tests, troubleshooting and servicing for all Veeder-Root Series Tank Monitoring Systems, including Line Leak Detection. In addition, Contractors with the following sub-certification designations are approved to perform installation checkout, startup, programming, system tests, troubleshooting, service techniques and operations training on the designated system.
• Wireless 2
• Tall Tank
VR Vapor Products Certification: Contractors holding a certification with the following designations are approved to perform installation checkout, startup, programming, system tests, troubleshooting, service techniques and operations training on the designated system.
• ISD – In Station Diagnostics
• PMC – Pressure Management Control
• CCVP - Veeder-Root Vapor Polisher
• Wireless – ISD/PMC Wireless
• A current Veeder-Root Technician Certification is a prerequisite for the VR Vapor Products course.
Warranty Registrations may only be submitted by selected Distributors.

Related Manuals

577014-018 Encore 500 Stage II Vapor Recovery Retrofit/Commissioning Installation and Start-Up Instructions
577013-988 MPV 10 Valve Installation and Maintenance Manual
577013-985 AVRN Vacuum Assist Nozzle Installation and Maintenance Manual
MDE-5064 Encore 500 VaporTEK Service and Troubleshooting Manual

Safety Precautions

The following safety symbols may be used throughout this manual to alert you to important safety hazards and precautions.
EXPLOSIVE
Fuels and their vapors are extremely explosive if ignited.
FLAMMABLE
Fuels and their vapors are extremely flammable.
2
Introduction Safety Warnings
OFF
OFF
ELECTRICITY
High voltage exists in, and is supplied to, the device. A potential shock hazard exists.
NO OPEN FLAMES
Open flames from matches, lighters, welding torches, etc. can ignite fuels and their vapors.
NO VEHICLES
Moving vehicles in the area during service can cre­ate a potential for personal injury to you or others. Sparks from starting vehicles can ignite fuels and their vapors.
CLEAN WORK AREA
Dispose of fuel soaked materials properly and not into trash barrels that may be used by cus­tomers.
WAR N ING
Heed the adjacent instructions to avoid damage to equipment, property, environment or personal injury.
TURN POWER OFF
Live power to a device creates a potential shock hazard. Turn Off power to the device and associ­ated accessories when servicing the unit.
NO SMOKING
Sparks and embers from burning cigarettes or pipes can ignite fuels and their vapors.
USE SAFETY BARRICADES
Unauthorized people or vehicles in the work area are dangerous. Always use safety cones or barri­cades, safety tape, and your vehicle to block the work area.
INJURY TO EYES AND SKIN
Unauthorized people or vehicles in the work area are dangerous. Always use safety cones or barri­cades, safety tape, and your vehicle to block the work area.
READ ALL RELATED MANUALS
Knowledge of all related procedures before you begin work is important. Read and understand all manuals thoroughly. If you do not understand a procedure, ask someone who does

Safety Warnings

WARNING
This product is to be installed and operated in the highly combustible environment of a gasoline dispenser where flammable liquids and explosive vapors may be present.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY PR ECAUTION S COU LD CAUS E DAMAG E TO PR OPE RTY, ENVIRON M E NT, RESULTING IN SERIOUS INJURY OR DEATH.
The following hazards exist:
1. Electrical shock resulting in serious injury or death may result if power is on during installation and the device is improperly installed.
2. Product leakage could cause severe environmental damage or explosion resulting in death, serious personal injury, property loss and equipment damage.
Observe the following precautions:
1. Read and follow all instructions in this manual, including all safety warnings before installing this equipment.
2. Before installing this device, turn Off, tag/lock out power to the affected dispenser, including submersible pumps.
3. Evacuate of all unauthorized persons and vehicles from the work area.
4. To protect yourself and others from being struck by vehicles, block off your work area with cones, safety tape or barricades during installation or service.
5. Do not operate this equipment in hazardous locations with any securing screws or covers removed. Comply with all applicable codes including: the National Electrical Code; federal, state, and local codes; and other applicable safety codes.
3
Introduction Safety Warnings
Veeder-Root maintains a continuous process of product development and therefore product specifications may not be as described in this manual. Please contact the Veeder-Root office nearest you, or visit our website at www.veeder.com for information on new or updated products. Changes affecting products or procedures described in this manual will be reported in subsequent revisions.
Veeder-Root has taken every care in the compilation of this manual; however, it is the installers’ responsibility to take every precaution to safeguard themselves and others. Every person working with Veeder-Root equipment is expected to take every safety precaution possible and to have read this manual.
Deviation from the specifications contained in this manual can result in rework, delays in system installation and additional installation charges.
Contractors are advised to contact their nearest Veeder-Root office where local conditions may preclude using the specifications contained in this manual.
4
Introduction VaporTEK Configurations
VaporTEK UltraVaporTEK Basic VaporTEK Plus VaporTEK Enhanced
VaporTEK Pump
VDI 4205 21
st
BlmSchV 21st BlmSchV 21st BlmSchV
A/L Performance
GOOD BETTER BEST
VaporTEK Controller
VaporTEK Interface
MPV 10
Electronic Proportional Valve
Pulse signal required
Compatible with VDI 4205 A/L monitoring
A/L performance thru entire flow range w/1 fueling point
A/L performance with simultaneous fueling
*Site uptime
Energy efficiency
TUV certificates
VRC390/3 Controller Board
*Installation errors due to system complexity, nuisance A/L monitoring alarms, contractor visits for periodic adjustmen
ts.
●●
●●
●● ●●
●●
●●
●●
●●
●●
●● ●●
●●
●●

VaporTEK Configurations

VaporTEK is available in four different configurations depending on required A/L (air to liquid) performance, compatibility with localized A/L monitoring requirements and performance A/L thresholds (see table below).
Vap orTE K B a sic
Vap orTE K Plus
VaporTEK Enhanced
Vap orTE K Ultra
5
Introduction VaporTEK Pump Certifications & Markings

VaporTEK Pump Certifications & Markings

Safety Certification

Product ATEX IECEx
VaporTEK Pump
VaporTEK Controller N/A N/A
VRP2 Pump CML 18ATEX1245X N/A
VRM2 Motor CML 18ATEX1244X IECEx CML 18.0116X
ML 18ATEX6243X N/A
C
Certificates can be obtained upon request. The IECEx certificates can be obtained Online at:
http://iecex.iec.ch/

Hazardous Area Installation Instructions

1. VaporTEK Pump may be used with flammable gases and vapors with apparatus group II and temperature class T3.
VaporTEK Pump is certified for maximum operating ambient temperature of +55°C.
2.
3. The VaporTEK Pump is equipped with a temperature cut-off switch for thermal protection.
4. The VaporTEK Pump assembly certificate number has an “X” suffix, indicating that special condit safe use
application:
ions are for
When the vapor recovery pump is used as a flame arrester in vapor recovery pipes and a separate flame ar­rester is not fitted, the following maximum hose and pipe lengths are permitted between the filler nozzle an the vacuum pump accordi
ng to EN13463-1 standard:
Vapor recovery hose with an inside diameter < 10mm in the coaxial hose < 6m, or,
Coaxial hose < 6m with an outside diameter < 38mm and fitted together with a downstream pipeline DN 15
(G 1/2) <
3m.
d
In addition, the tanks mentioned in Test Reports PTB Ex 05-45017 and PTB Ex 05-45027 may be installed in the DN 15 (G 1/2) pipeline at a distance of between 0.3m and 2.5m in front of the VRP2 vapor recovery pump. The pipeline between hose and tank shall have a minimum length of 0.5m.
The ambient temperature and the temperature of the fuel vapor/air mixture taken in shall remain within the tem­perature range -20°C to +55°C at the intake end.
Flame paths shall not be repaired or reworked.

Equipment Marking

Product ATEX/IECEx
VaporTEK Pump
Ex db IIA T3 Ga/Gb
e II 1/2 G c d Ta=55°C
6
Introduction VaporTEK Kits
Material Compatibility With Constituents Of The Potentially Explosive Atmosphere
The VaporTEK Pump is suitable for temporary exposure to petrol and associated vapors, ethanol blended fuels, diesel, biodiesels, LPG and associated vapors, water with minimal salt content, mild cleaning agents, AdBlue anticipated vehicle exhaust emissions, and small traces of engine oil or other lubricants which could be transferred by hand contact. The pumping unit is suitable for permanent internal exposure to vapors of petrol, ethanol blended fuels and temporary exposure to liquid fuel.
The equipment is not suitable for use where external surfaces may come into regular exposure to substances which are incompatible with any of the following materials:
Aluminium and aluminium alloys, brass alloys, zinc plated steel, carbon/alloy steel, nitrile rubber.
TUV Certification
Product Test Standard
VaporTEK Basic VDI 4205 A/L 13.1 Goodyear Flex Steel Veeder-Root AVRN
VDI 4205 85-13.2 Goodyear Flex Steel Veeder-Root AVRN
VaporTEK Plus
VaporTEK Enhanced VDI 4205 85.13.3 Goodyear Flex Steel Veeder-Root AVRN
VaporTEK Ultra VDI 4205 85.13.4 Goodyear Flex Steel Veeder-Root AVRN
VDI 4205 85-2.172
EN 16321-1 VR2-1509/1-112EU
TUV Certificate
Number Hose Nozzle
ELAFLEX Conti ELAFLEX Slimline 2

VaporTEK Kits

VaporTEK Pump Kit - P/N 900612-001

Quantity Description
1
1 VaporTEK DATASHEET, P/N 576047-180
VaporTEK PUMP, P/N 900621-001
7
Introduction VaporTEK Kits

VaporTEK Controller Kit - P/N 900634-001

Quantity Description
1
1 Controller - Interface Mounting Bracket, P/N 900852-001
1 Controller - Cover, P/N 900850-001
VaporTEK Controller, P/N 900628-001
1 Controller - Label High Voltage Warning, P/N 900853-001
4 Support Post, M4.0 X 6MM LG (Plastic), P/N 579081-001
3 Hex Nut, M6 X 1, Steel, P/N 579082-001
8
Introduction VaporTEK Kits
Quantity Description
3 Socket Head Cap Screw M6X1 X 20MM LG, P/N 579281-001
2
1
1
1
M3.5 x 12 mm, Lockwasher M3, PH. Screw (Bracket ground), P/N 579158-001
18AWG, 3 Conductor Power Cable with Connector – 3 FT Long, P/N 900651-001
18AWG, 2 Conductor Hook Signal Cable (110-230V) – 4 FT Long, P/N 900644-001
18AWG, 1 Conductor Wire – 4 FT Long (For Grounding To Dispenser), P/N 616343-024
9
Introduction VaporTEK Kits

VaporTEK Interface Kit - P/N 900635-001

Quantity Description
1
4 Support Post, M3.5 X 4MM LG (Plastic), P/N 579080-001
1 RJ12 Cable – 3 FT Long, P/N 579084-001
1
1 24AWG, 8 Conductor Signal Cables – 3 FT Long, P/N 900643-001
VaporTEK Interface, P/N 900630-001
18AWG, 2 Conductor Power Cable with Connector – 4 FT Long, P/N 900652-001

VaporTEK High Voltage Relay Kit - P/N 900664-001

Quantity Description
1
High Voltage Relay

VaporTEK Low Voltage Relay Kit - P/N 900665-001

Quantity Description
1
Low Voltage Relay
10
Introduction VaporTEK Pump Characteristics
A

VaporTEK Pump Characteristics

1. The VaporTEK Pump is driven by the VaporTEK Controller.
2. The VaporTEK Pump has integrated flame arrestors at the inlet and outlet ports that prevent flame transmission.
3. The inlet/outlet ports have standard G ¼” female threads (ISO – 228-1).
Warning! DO NOT remove the flame arrestors. DO NOT install piping which can stress the pump housing.
4. Vapor flow is from the nozzle through the vapor pump to the UST (See Figure 2 for flow direction).
5. The following conditions must apply according to EN13463-1 for the maximum pipe and hose lengths between the nozzle and the VaporTEK Pump.
a. An inner diameter b. Coaxial hose of length
W = 140 mm
Outlet Port G 1/4”
Flame Arrester (1)
10mm in the coaxial hose of length ≤6m, OR
6m with an outer diameter ≤38mm together with a DN15 pipe (G ½”), length ≤ 3m.
65 mm
Sensor Cable
M22 x 1.5,6g Hex Cable Retainer (2)
Flame
rresters (2)
Inlet Ports G 1/4” (2)

VaporTEK Pump Specifications

Function Description
Flow medium Gasoline vapor Flame Arrestors Type: Ex IIA; Inlet & Outlet Ports Mounting Four M6 X 1 Mounting Boss (Either side of the pump) Motor Type Synchronous BLDC (Brushless DC) Motor Voltage (Single Phase) 230 VAC (±10%) Frequency 50/60 Hz Amps 1.2 A
Motor Cable
65 mm
Flow Direction to UST
Figure 2. VaporTEK Pump Dimensions
L = 245 mm
Mounting Boss (4) Both Sides (M6 x 1)
H = 235 mm
11
Introduction VaporTEK Controller
Function Description
Motor Speed 2500 rpm max. Maximum flow rate Up to 120 lpm Noise Level 59 dB (A)

VaporTEK Controller

The VaporTEK Controller board is shown in Figure 3. Mode selections for the VaporTEK Controller board require a jumper in the JP4 position(s) shown below:
Mode Selection Jumpers in JP4
Configuration Type VaporTEK Controller Input Type
Vap orTEK Basic VaporTEK Enhanced VaporTEK Ultra
Vap orTEK Basic VaporTEK Enhanced VaporTEK Ultra
Vap orTEK Plus Pu lse Si gnal YesNoNoNoNo
High Voltage Hook Signal No
Low Voltage Hook Signal YesNoNoNoNo
0 1 2 3 4
Ye s Ye s N o N o
12
Introduction VaporTEK Controller
Jumper JP4
0 - 4
Sensor
Connection
Motor
Connection
Input
Power
230VAC
110-230 VAC
Dispenser
Hook Signals
RJ12
(For Low Voltage
Hook Signal Or
Liquid Pulse Input)
NE P M1 M2
POT
Figure 3. VaporTEK Controller
13
Introduction VaporTEK Interface

VaporTEK Interface

The VaporTEK Interface is a dual-sided board which provides an electrical interface between the fuel dispenser and the VaporTEK Controller. The VaporTEK Interface has four input channels per side which can be configured as pulse train, low voltage nozzle hook signals (0-24V) and diesel disable inputs.
For the pulse input configuration, a fuel flow rate higher than 6 liter/min is required for the VaporTEK Controller to start the VaporTEK pump.
The VaporTEK Interface board is shown in Figure 4.
X4
Encoder Power Outputs
Power Supply Ratings
Voltage: 8 to 24VDC Current: 20mA@24V
24 VDC
Power Supply
Voltage: +5VDC
Current: 10mA@20°C)
+++
+ + – –
SIDE B - 4 channels (P1B to P4B) Liquid Pulses or 0-24VDC Hook Signals
USB Connector
X2
Encoder Power Outputs
Voltage: +5VDC
Current: 10mA@20°C)
RS-422
Connector
RJ-12
Connector
+++
SIDE A - 4 channels (P1A to P4A) Liquid Pulses or 0-24VDC Hook Signals
Figure 4. VaporTEK Interface
14
Introduction VaporTEK Interface
V15 LED Input 1B V11 LED Input 2B
V20 LED Input 3B V19 LED Input 4B
RS-422 Connector
USB
Connector
RJ-12 Connector
V9 Run LED
V4 Power LED
V8 Error LED
VEEDER-ROOT
VaporTEK interface
V17 LED Input 1A V24 LED Input 2A V23 LED Input 3A V14 LED Input 4A
V13 Rx LED V12 Tx LED V10 Flash LED
F6
F2
J1 Flash Jumper

VaporTEK Interface I/O

I/O Interface Description Function
USB Connection between laptop and
Diagnose or setup VaporTEK Interface using laptop
VaporTEK Interface
RJ12 Connection between VaporTEK Inter-
face and VaporTEK Controller
Transmits pulse rate or low voltage hook signal information to the VaporTEK Controller
RS422 Connection to FB1 Terminal Used to perform system calibration with hand held FB1 Terminal

VaporTEK Interface LEDs

Figure 5. VaporTEK Interface LEDs

Vap orTE K LEDs

LED Function Description
V4 Power Status Illuminates when the internal 24V power is present.
Side A Input Status V17 V24 V23 V14
P1A
P2A
P3A
P4A
Illuminate when input voltage is between 4V- 24VDC, Off when input voltage is less than 4VDC
15
Introduction VaporTEK Interface
LED Function Description
Side B Input Status V15 V11 V20 V19
P1B
P2B
P3B
P4B
Illuminate when input voltage is between 4V- 24VDC, Off when input voltage is less than 4VDC
V12 V13
V9 Run Status
Communication
Status
Both LEDs flash simultaneously when communicating properly. Any other status for the LED means communication to the VaporTEK Controller has been interrupted.
LED flashes with “1sec On-Off cycle” when there is no transaction. It starts flashing faster during an active fuel transaction. (Flow rate > 6 l/min).
V8 Error Status Normal operation is OFF. When it flashes, a communication error has occurred.
V10 Programming LED Engineering use only.
J1 Flash Jumper Engineering use only.
16
Introduction VaporTEK Pump Configuration

VaporTEK Pump Configuration

The VaporTEK Pump can be configured to operate in either a 2-Speed or a Variable-speed mode depending on the configuration type and available dispenser inputs/signals.
Vap orT E K
Configuration
Basic,
Enhanced, and
Ultra
Input Type
High Voltage Hook Signal (110-230VAC)
High Voltage Hook Signal (220/240VAC)
Low Voltage Hook Signal
(0-24VDC)
Mode of
Operation
Two Speed VaporTEK Controller
Two Speed
Two Speed
Required
Components
VaporTEK Controller, Switch Relay
VaporTEK Controller, VaporTEK Interface
Method of Operation
The VaporTEK Controller receives nozzle hook signals from either side of the dispenser.
With one fueling point active, the pump operates in low speed. With two fueling points active, the pump operates in high speed.
In this configuration a high voltage hook signal from either side of the dispenser operates a relay switch which in turn control’s the high volt­age input to the Vapor TEK Controller.
Note: One relay switch is required for each gasoline nozzle in the dispenser.
With one fueling point active, the pump operates in low speed. With two fueling points active, the pump operates in high speed. This configuration is typically used for Multi Product dispensers with high voltage hook signals and more than one nozzle grade per side
The VaporTEK Interface receives low voltage hook signals from either side of dispenser and transmits this signal to the VaporTEK Controller.
With one fueling point active, the pump operates in low speed. With two fueling points active, the pump operates in high speed.
Refer to VaporTEK Wiring section to set up low voltage liquid pulse inputs.
Plus
Low Voltage Hook Signal
(0-24VDC)
Liquid Pulse Signal
Two Speed
Variable Speed
VaporTEK Controller, Switch Relay
VaporTEK Controller, VaporTEK Interface
17
In this configuration a low voltage hook signal from either side of the dispenser operates a relay switch which in turn controls the high volt­age input to the VaporTEK Controller.
Note: One relay switch is required for each gasoline nozzle in the dispenser.
With one fueling point active, the pump operates in low speed. With two fueling points active, the pump operates in high speed. This configuration is typically used for Multi Product dispensers with low voltage hook signals.
VaporTEK Interface receives liquid pulses from an active encoder (from either side of the dis­penser) and calculates the petrol flow rate. This flow rate value is then transmitted to the VaporTEK Controller to determine the pump speed.
Refer to VaporTEK Wiring section to set up pulse rate inputs.

Installation

OFF

VaporTEK Pump

Before installing this device, turn off, tag/lock out power to the dispenser.
1. Remove the dispenser’s hydraulic cabinet sheet metal doors to access the dispenser hydraulics area.
2. Find a suitable location to install the VaporTEK Pump.
3. Ensure correct orientation of the pump, suction ports and discharge ports prior to installing in the dispenser. See Figure 6 for allowable VaporTEK Pump orientations (red arrows indicate direction of flow). Also ensure the electrical cables of the VaporTEK Pump’s location will reach the VaporTEK Controller installed in the electronic cabinet of the dispenser (Unclassified Area).
4. After identifying the desired pump orientation, secure the VaporTEK Pump onto the dispenser support structure. Excessive vibration may require additional support and vibration mounts to secure the VaporTEK Pump.
5. Route the two cables (Motor and Signal) from the VaporTEK Pump into the dispenser’s electronic cabinet. Tie wrap the cables neatly and securely against fixed support members away from moving parts.
6. Reinstall and secure the lower hydraulic doors.
18
Installation VaporTEK Pump
Preferred Pump Installation
Orientation
Fins Down
Acceptable Pump Installations
Orientation
Fins Up Motor Facing
Incorrect Pump Installation
Motor On Top Motor Down
Figure 6. VaporTEK Pump Installation Orientations
19
Installation VaporTEK Controller and VaporTEK Interface
OFF
5
4
6
7
4
1

VaporTEK Controller and VaporTEK Interface

Before installing this device, turn off, tag/lock out power to the dispenser until all steps in this section are complete.
The VaporTEK Controller and VaporTEK Interface must be installed in the non-hazardous location of the dispenser (unclassified area), and protected from weather.
1. Mount the VaporTEK Controller board to the sheet metal bracket 900852-001 with the 4 stand offs (579081-
001) from the kit (Figure 7).
Figure 7. Mount The VaporTEK Controller To The Inside Of The Support Bracket
Figure 8. VaporTEK Motor/Sensor Connector’s Labeling And Poke Yoke
20
Installation VaporTEK Controller and VaporTEK Interface
2
3
3
8
9
10
11
2. Mount the VaporTEK Interface board to the new sheet metal bracket 900852-001 with the 4 stand offs (579080-001) from the kit (Figure 9).
Figure 9. Mount The VaporTEK Interface To The Back Side Of The Support Backet
3. Attach VaporTEK Controller/Interface sheet metal bracket 900852-001 to the dispenser with M6 socket head bolt and M6 nut (Figure 9).
4. Plug the VaporTEK motor and sensor connectors to the VaporTEK Controller board (Figure 7).
5. Attach the motor ground wire to the sheet metal bracket with M3 screw (579158-001) included in the kit (Figure 7).
6. Plug the RJ12 cable socket to the VaporTEK Controller (Figure 7).
7. Attach the 900651-001 input power cables to the VaporTEK Controller (Black: phase; White: Neutral; Green­Yellow: Ground) and attach the Green-Yellow ground wire with the ring terminal to the sheet metal bracket with M3 screw (579158-001). The other end of the cable should be connected to the 230V power source (Figure 7).
8. Plug the 24V cable with connector to the VaporTEK Interface board (Figure 9).
9. Plug the Pulse Side B cables with connector to the VaporTEK Interface (Figure 9).
10. Plug the Pulse Side A cables with connector to the VaporTEK Interface (Figure 9).
11. Plug the RJ12 cable socket to the VaporTEK Interface (Figure 9).
21
Installation VaporTEK Controller and VaporTEK Interface
12
13
14
15
12. Attach the cover 900851-001 included in the kit (Figure 10.).
Figure 10. Attach The VaporTEK Controller Safety Cover
13. Use M6X12 socket head screw (579281-001) & M6 nut (579082-001) to attach the cover to the bracket (Figure 10).
14. Paste the High Voltage warning label 900853-001, included in the kit (Figure 10).
15. if the controller bracket mounting base plate is not grounded, connect the 18AWG, 1-conductor cable (616343-024) from the VaporTEK Controller kit as the ground wire between the mounting bracket and the dispenser frame (use ground screw and nut included in the kit).
22

Wiring Schematics

VaporTEK Wiring

1. Depending on the configuration used to actuate the pump, follow steps 2, 3, 4, 5 or 6.
2. VaporTEK with High Voltage Hook Signal (see Figure 11)
a. Refer to the dispenser manufacturer’s manual, to determine where to tap into the 110-230 VAC hook
signal. Using the 18AWG, 2 conductor cable included in the VaporTEK Controller Kit, connect the hook signal from Side A to M1 on the VaporTEK Controller and connect the hook signal from Side B to M2.
b. Set two jumpers in positions 1 and 2 on JP4 (see Figure 11).
3. VaporTEK with Low Voltage Hoo k Signal - Requires VaporTEK Interface Kit (see Figure 12)
a. Refer to the dispenser manufacturer’s manual, to determine the dispenser type (Blended or Multi product),
the number of available nozzle hooks and where to tap into the hook signals (0-24VDC).
b. The VaporTEK Interface can be connected to a maximum of four nozzle hooks per side.
c. Connect the available nozzle hook signal inputs to the VaporTEK Interface using 24AWG, 8 conductor
signal cables included in the Kit. (Note: 2 conductors used per hook signal input, see wiring diagram in Figure 13.)
d. Set one jumper in position 0 on JP4 (see Figure 12).
4. VaporTEK with Pulse Signal - Requires VaporTEK Interface Kit (see Figure 12).
a. Refer to the dispenser manufacturer’s manual, to determine the dispenser type (Blended or Multi product),
the number for available pulse signals and where to tap into the pulse signals.
b. The VaporTEK Interface can be connected to a maximum of 4 pulse signals per side.
c. Connect the pulse signal inputs to the VaporTEK Interface using the 24AWG, 8 conductor signal cables
included in the Kit. (Note: 2 conductors used per pulse signal input, see wiring diagram in Figure 14.)
d. Set one jumper in position 0 on JP4 (see Figure 12).
23
Wiring Schematics VaporTEK Wiring
3 1 2 4
G 1 2 3 4
Set JP4
1 and 2
Sensor
Cable
Motor Cable
MAIN POWER
Phase - 230 VAC
VaporTEK
Pump
DISPENSER SIDE 2
High Voltage Hook signal
(110 - 230 VAC)
L
N
PE
PE N L M1 M2
VaporTEK Controller
DISPENSER SIDE 1
High Voltage Hook signal
(110 - 230 VAC)
Attach the motor ground wire ring terminal to the sheet metal bracket with M3 screw from the kit.
POT
RJ-12
LEGEND:
PE - Protected Earth N - Neutral L - Main Phase 230 VAC JP4 - Jumpers (0 - 4) POT - Potentiometer (speed/gain control) M1 - Side 1 High Voltage hook signal M2 - Side 2 High Voltage hook signal
Figure 11. VaporTEK System - High Voltage Hook Signal Input
24
Motor
Cable
3 1 2 4
G 1 2 3 4
Attach the motor ground
wire ring terminal to the
sheet metal bracket with
Sensor
M3 screw from the kit.
Set JP4 to 0
Cable
25
Pump
VaporTEK
L
N
PE
MAIN POWER
RJ12 Cable
Phase - 230 VAC
PE N L M1 M2
VaporTEK Controller
Terminal
FB1 Service
6
9
3
+
F5
F10
PgDn
PgUp
START
0
5
8
2
F7
F2
F9
F4
INS
7
1
4
F6F1F8
F3
END
Home
SHIFT SPACE ENTER
Dispenser
L
Power Supply
N
DC
24 - 28V
Figure 12. VaporTEK System - Liquid Pulse Signal and Low Voltage Hook Signal Input
(0 - 24 VDC)
Pulse or LV Hook
Signal Inputs Side 2
(0 - 24 VDC)
Signal Inputs Side 1
Pulse or Low Voltage Hook
Wiring Schematics VaporTEK Wiring
USB Cable
GND
GND
+24 V
+24 V
VaporTEK Interface
Wiring Schematics VaporTEK Wiring
Dispenser Side B
24 VDC
Power Supply
+ +
Gnd Gnd
Nozzle
Hook 1
GND
+
Nozzle
Hook 2
GND
+
Nozzle
Hook 3
GND
+
Nozzle
Hook 4
GND
+
+ GND + GND + GND + GND
Nozzle
Hook 1
Nozzle Hook2
Nozzle
Hook 3
Nozzle
Hook 4
Dispenser Side A
Figure 13. VaporTEK Interface - Low Voltage Nozzle Hook Signal Connections
26
Wiring Schematics VaporTEK Wiring
Dispenser Side B
Pulse 1 Gnd Pulse 2 Gnd Pulse 3 Gnd Pulse 4 Gnd
24 VDC
Power Supply
+ +
Gnd Gnd
Pulse 1 Gnd Pulse 2 Gnd Pulse 3 Gnd Pulse 4 Gnd
Dispenser Side A
Figure 14. VaporTE K Interface - Liquid Pulse Signal Connections
27
Wiring Schematics VaporTEK Wiring
5. VaporTEK with Low Voltage hook signal with relay switches (see Figure 15)
a. Refer to the dispenser manufacturer’s manual to determine the dispenser type (Blended or Multi product),
the number of available nozzle hooks and where to tap into the hook signal (Verify the low voltage hook signal voltage rating is 3-32 VDC).
b. Using the 18AWG, 2 conductor cable from the kit, connect each nozzle hook signal on Side A of the
dispenser to one relay circuit.
c. A High Voltage source (110-230VAC) is connected to the M1 on the VaporTEK Controller through all the
relay circuits on Side A (See Figure 17 for low voltage relay wiring diagrams).
d. Make similar connections on Side B and connect to M2 on the VaporTEK Controller.
e. Set two jumpers in positions 1 and 2 on JP4 (see Figure 15).
6. VaporTEK with High Voltage hook signal with relay switches (see Figure 16)
a. Refer to the dispenser manufacturer’s manual to determine the dispenser type (Blended or Multi-product),
the number of available nozzle hooks and where to tap them (Verify the hook signal voltage rating is 220/ 240 VAC).
b. Using the 18AWG, 2 conductor cable from the kit, connect each nozzle hook signal on Side A of the
dispenser to one high voltage relay circuit.
c. A High Voltage source (110-230VAC) is connected to the M1 on the VaporTEK Controller through all the
relay circuits on Side A (See Figure 18 for high voltage relay wiring diagrams).
d. Make similar connections on Side B and connect to M2 on the VaporTEK Controller.
e. Set two jumpers in positions 1 and 2 on JP4 (see Figure 16).
28
DISPENSER - SIDE A
VaporTEK
Neutral
Neutral
110 - 230 VAC
110 - 230 VAC
Switched 2
110 - 230 VAC
+5VDC
Ground
Ground
PPU3
Power
110-230VAC
Low Voltage
Relay
Reed Contact
Switch 1
Reed Contact
Switch 2
Reed Contact
Switch 3
Distribution
Cable
Set JP4
1 and 2
POT
RJ-12
VaporTEK
Pump
L (Phase 230 VAC)
PE
PE N L M1 M2
VaporTEK Controller
LEGEND:
PE - Protected Earth
N - Neutral
L - Main Phase 230 VAC
JP4 - Jumpers (0 - 4)
POT - Potentiometer (speed/gain control)
M1 - Side 1 High Voltage Hook Signal
M2 - Side 2 High Voltage Hook Signal
Grade 1
Low Voltage
Relay
Grade 2
Low Voltage
Relay
Grade 3
See Figure 16 for
low voltage relay
wiring diagrams
DISPENSER SIDE 2
High Voltage Hook Signal
(110 - 230 VAC)
Note: wiring similar
to side A.
PPU1 PPU2
3 1 2 4
G 1 2 3 4
Sensor
Cable
Motor
Cable
Attach the motor ground
wire ring terminal to the
sheet metal bracket with
M3 screw from the kit.
29
Figure 15. VaporTEK System - Low Voltage Hook Signal With Relay Switches
Wiring Schematics VaporTEK Wiring
DISPENSER - SIDE A
VaporTEK
Neutral
Neutral
110 - 230 VAC
110 - 230 VAC
Switched 2
110 - 230 VAC
Line
Neutral
Neutral
PPU3
Power
110-230VAC
Reed Contact
Switch 1
Reed Contact
Switch 2
Reed Contact
Switch 3
Distribution
Cable
Set JP4
1 and 2
VaporTEK
Pump
DISPENSER SIDE 2
High Voltage Hook Signal
(110 - 230 VAC)
L (Phase 230VAC)
PE
PE N L M1 M2
VaporTEK Controller
LEGEND:
PE - Protected Earth
N - Neutral
L - Main Phase 230 VAC
JP4 - Jumpers (0 - 4)
POT - Potentiometer(speed/gain control)
M1 - Side 1 High Voltage Hook Signal
M2 - Side 2 High Voltage Hook Signal
POT
RJ-12
High Voltage
Relay
High Voltage
Relay
High Voltage
Relay
Grade 1 Grade 2
Grade 3
See Figure 17 for
High voltage relay
wiring diagrams
Note: wiring similar
to side A.
PPU2PPU1
3 1 2 4
G 1 2 3 4
Sensor
Cable
Motor
Cable
Attach the motor ground
wire ring terminal to the
sheet metal bracket with
M3 screw from the kit.
30
Figure 16. VaporTEK System - High Voltage Hook Signal With Relay Switches
Wiring Schematics VaporTEK Wiring
Wiring Schematics VaporTEK Wiring
4
3
1
2
110 - 230 VAC
to VaporTEK
Controller
110 - 230 VAC
Power Mains
3 - 32 VDC
VaporTEK Low
Voltage Relay
Output
Gnd
013-26.eps
Low Voltage Nozzle Hook Signal Input
110 - 230 VAC
to VaporTEK
Controller
110 - 230 VAC
Power Mains
Neutral Line
013-27.eps
2
4
6
8
VaporTEK High
Voltage Relay
1
3
5
7
High Voltage Nozzle Hook Signal Input
Figure 17. VaporTEK Low Voltage Relay Diagram
Figure 18. VaporTEK High Voltage Relay Diagram
31

Communication Setup - VaporTEK Interface

Connection Description
OK Cancel
? X
New Connection
Name:
Enter a name and choose an icon for the connection:
VaporTEK Interface
Icon:

Setup with Laptop

Connect your laptop to the VaporTEK Interface using a USB cable (see Figure 12).
1. On your laptop, go to Start / All Programs / Accessories / Communications / HyperTerminal.
Note: “HyperTerminal” is an inbuilt program for Windows XP and earlier operating systems. It is not readily available on Windows 7 and needs to be downloaded from the internet. Also, a non-commercial program like “M16 –Terminal” can be downloaded and used instead of HyperTerminal.
Once the Hyperterminal menu screen appears, click on File in the menu bar and select New Connection.
2. In the Connection Description dialog box Name field, enter VaporTEK Interface. Click OK (see example below).
32
Communication Setup - VaporTEK Interface Setup with Laptop
VaporTEK Interface
Connect using:
Detect Carrier Loss
Connect To
Enter details for the phone number that you want to dial:
Enter the area code without the long-distance prefix.
Country/region:
Area code:
Phone number:
Use country/region code and area code Redial on busy
Configure...
OK Cancel
COM X
? X
Enter details for the phone number that you want to dial:
Enter the area code without the long-distance prefix.
Country/region:
Area code:
Phone number:
Use country/region code and area code Redial on busy
Port Settings
COM X Properties
Restore Defaults
OK Cancel
Flow control
Stop bits
Parity
Data bits
Bits per second
None
1
None
8
9600
? X
Apply
Apply
3. Select the appropriate COM port on your laptop (COM X in example below). To verify COM port, go to Control Panel/System/Device Manager and select ports. Check to see which COM port says USB 2.0. Click OK.
4. In the COM Properties dialog box (COM X in the example below, set the all of the port setting fields as shown and click OK.
33
Communication Setup - VaporTEK Interface Setup with Laptop
ASCII Sending
ASCII Setup
OK Cancel
? X
ASCII Receiving
Send line ends with line feeds
Echo type characters locally
Line delay: milliseconds.
100
Character delay: milliseconds.
0
Append line feeds to incoming line ends
Force incoming data to 7-bit ASCII
Wrap lines that exceed terminal width
5. Click File in the HyperTerminal window and select Properties, then click the Settings tab to open the dialog box shown below. Double check and make sure all settings match the example below.
VaporTEK Interface Properties
SettingsConnect To
Function, arrow, and ctrl keys act as
Terminal keys
Backspace key sends
Crtl+H Del Crtl+H, Space, Crtl+H
Emulation:
Auto detect
Telnet terminal ID:
Backscroll buffer lines:
Play sound when connecting or disconnecting Allow remote host initiated file transfers Exit program upon disconnecting
Windows keys
Terminal Setup...
Terminal Setup...
ANSI
500
OK Cancel
? X
Colors...
ASCII Setup...Input Translation...
6. Click the ASCII Setup button to and set the properties shown below:
7. C l i c k OK to return to the main window of HyperTerminal.
34
Communication Setup - VaporTEK Interface Setup with Laptop
New Connection Hyperterminal
File Edit View Call Transfer Help
Print echoCaptureNUMCAPSSCROLL9600-8-N-1Auto detectConnected 0:02:44
************************ * VaporTEK Interface * * Init-Software * * SW 1.03 (MUX) * * Chip Version M16C26A * * Device No: 000000003 * * * ************************
VaporTEK-Potentiometer is in use!
Pulse rate [Imp/l] = 136 Pulse Prescaler = 1 Pulse Prescaler x Pulse rate = 136 pulses/l
Run Status:
----------­Status 1 Idle Status 2 Idle
8. On power up the current settings display:
9. Type m on your keyboard to display the following menu:
New Connection Hyperterminal
File Edit View Call Transfer Help
************************************ * VaporTEK Interface * * Init-Software * * SW 1.03 (MUX) * * Chip Version M16C26A * * Device No: 000000003 * * * ************************ ************************ * MAIN MENU * ************************
1. Show Config
2. Set Config
3. Set Factory Defaults
4. Debug Fuel Flow and Com_RJ12
5. Show Calibration Table
6. A/L - Ratio
7. Pulse - Ratio
8. Reregulation Factors
9. MUXI - Function Test h. Show Hot Keys
Please select:_
Print echoCaptureNUMCAPSSCROLL9600-8-N-1Auto detectConnected 0:02:44
35
Communication Setup - VaporTEK Interface Setup with Laptop
1. Show Config
--------------­****** Inputs ****** Side A Side B 1 Pulse Input 1 2 Pulse Input 2 3 Pulse Input 3 4 Pulse Input 4
VaporTEK-Potentiometer is in use!
2. Set Config
--------------­****** Inputs ****** Side A Side B 1 Pulse Input 1 2 Pulse Input 2 3 Pulse Input 3 4 Pulse Input 4
VaporTEK-Potentiometer is in use!
Input 1 what type?(1-Pulse,2-Nozzle):1 Input 2 what type?(1-Pulse,2-Nozzle):1 Input 3 what type?(1-Pulse,2-Nozzle, 3-D_Disable):2 Input 4 what type?(1-Pulse,2-Nozzle, 3-D_Disable):3
you’ve set Input(s) as a Nozzle Input what logic do you need H or L active? (0=l, 1=H):1
Please select the VaporTEK Control Mode (0 = Potentiometer, 1 - Auto Calibration Tables):1
Config has been stored successfully
****** Inputs ****** Side A Side B 1 Pulse Input 1 2 Pulse Input 2 3 Nozzle Input 38l/min(H) 3 4 Diesel disable Input(H) 4
Auto Calibration Tables are in use!
10. Show Config: Press 1 Shows the input configuration currently set.
11. Set Configuration: Press 2
a. Choose “Input Type”: Press 1 for “Pulse”, Press 2 for “Nozzle” or Press 3 to select “Diesel Disable” on
Inputs 3 & 4.
b. Select “Nozzle Logic” in case a nozzle input has been chosen: Press 0 for “L – Low”, Press 1 for “H –
High”.
c. Choose “Control Mode”: Press 0 for “Potentiometer” - The A/L Ratio is controlled adjusting the Pot
setting on the VaporTEK Controller or Press 1 for “Auto Calibration tables” - The A/L Ratio is controlled by the auto calibration tables in the VaporTEK Interface.
The control mode will be set automatically to ‘Auto Calibration Table’ mode when the auto calibration has been accomplished. Please consider that the auto calibration needs to be accomplished for each side separately.
36
Communication Setup - VaporTEK Interface Setup with Laptop
4. Debug Com_RJ12
-----------------­Press ‘f’ to toggle to real time fuel flow Press ‘d’ to debug RJ12 Com Port Messages Press ‘t’ to toggle between flow and speed messages
5. Calibration Table
--------------------
MP Flow A Flow B Speed [No] [l/min] [l/min] [rpm]
--------------------------­ 0 0 0 0 1 4 4 80 2 8 8 160 3 12 12 240 4 16 16 320 5 20 20 400 6 24 24 480 7 28 28 560 8 32 32 640 9 36 36 720 10 40 40 800 11 44 44 880 12 48 48 960 13 52 52 1040 14 56 56 1120 15 60 60 1200
12. Set Factory Defaults: Press 3
This function sets all configuration parameter into default conditions.
All inputs are pulse inputs
The Pulse Ratio is set to 136p/l
The A/L - Ratio is set to 100% and the Speed offset is set to 0
The control mode is set to Potentiometer
1. Set Factory defaults
-----------------------­Are you sure? [Y.N]:N!
13. Debug Fuel Flow and Com_RJ12: Press 4
This sub-menu allows a debug mode selection. If fuel flow debug mode is selected the screen will show the fuel flow rate when a transaction is running. Pressing f again will disable the flow debug mode. During flow de­bug mode no other mode can be activated.
Press d to activate Com port message prints to the VaporTEK – Controller. This feature is useful to analyze the quality of communication between VaporTEK – Interface and VaporTEK – Controller. To toggle between speed and flow message press t. Both messages should be supported by the VaporTEK – Controller.
14. Show Calibration Table: Press 5
Displays factory set calibration table when connected for the first time; thereafter shows the latest calibrated table.
37
Communication Setup - VaporTEK Interface Setup with Laptop
6. A/L - Ratio
-----------------­Recover-Ratio Speed-Offset 104% 1
do you want to change it [Y/N]? Y Recover Ratio = 104 new Ratio = 100 Speed Offset = 1 new Offset = 0
Data have been written successfully
Recover-Ratio Speed-Offset 100% 0
7. Pulse - Ratio
-----------------­Pulse rate [Imp/l] = 100 Pulse Prescaler = 1 Pulse Prescaler x Pulse rate = 100 pulse/1
do you want to change these [Y/N]? Y
Input Pulse Ratio [pulse/l] (10 - 250):132 Neuer Impulsvorteiler(1...10):1
Data have been written successfully
Pulse rate [Imp/l] = 132 Pulse Prescaler = 1 Pulse Prescaler x Pulse rate = 132 pulse/1
8. Show Reregulation faxtors
---------------------------­side A = 100 side B = 100
do you want to change these [Y/N]? N
15. A/L – Ratio: Press 6 Sub item 6 can be used to modify the A/L – Ratio. Set A/L – Ratio according to value which is mentioned on the certificate. NOTE: Set Speed Offset to "0”.
16. Pulse – Ratio: Press 7 This sub items allows a modification of Pulse Ratio. The pulse ratio defines the fuel flow rate which has to match the dispenser flow rate. Refer to the dispenser manufacturer’s manual to input the correct pulse ratio.
17. Reregulation factors: Press 8 Use item 8 to review the reregulation factors those will be controlled by the intelligent reregulation of monitoring. The permitted reregulation range is (85 – 125)%. A factor value of 100 represents 100%.
18. Function Test - menu option 9 Do not select - the function test requires special testing equipment and is for factory use only.
19. Show Hot Keys: Press h This item shows all other available hot keys.
38
Communication Setup - VaporTEK Interface VaporTEK Interface for Input Configuration
**** Hot-Keys ****
---------------------------­‘m’ show the Main Menu ‘h’ show this Help Menu ‘f’ toggle ON/OFF real time fuel Flow ‘d’ debug ON/OFF RJ12 Com Port messages ‘t’ toggle between flow/speed messages

VaporTEK Interface for Input Configuration

The VaporTEK Interface has four inputs per side and each of them can be configured separately. This configuration setup applies to both sides of the dispenser. For instance if the Input 1 is configured as a pulse input, then Input 1 side A and B are set to the same input configuration.
It is recommended that you determine the current configuration before making changes. As explained in the previous section, type m in the HyperTerminal to retrieve the VaporTEK Interface Menu.
Press 1 “Show Config” to determine the current configuration. If this setup doesn’t match the system application, change the configuration by pressing 2 “Set Config” (see Figure 19).
When in the Set Config screen, all four Inputs can be configured as either Pulse or Nozzle by pressing 1 or 2 respectively. Inputs 3 and 4 can also be configured as Diesel Disable by pressing 3 (see Figure 19).
1. Pulse Input: VaporTEK pump starts only with fuel flow (>6 liters/min) Liquid pulses from an active encoder calculates the petrol flow rate. This flow rate value is then transmitted to the VaporTEK Controller to operate the pump. NOTE: Set any unused inputs as “pulse input” to avoid malfunction on these inputs.
2. Nozzle Input: VaporTEK pump starts when nozzle hook signal is energized. In order to setup the correct nozzle logic when nozzle is removed from the cradle, the logic signal needs to be identified as either high (H) or low (L) as shown in the table below.
Remove The Nozzle And Measure Its Status
Voltage, Or Check Its VaporTEK Interface
Nozzle Status Voltage
(Logic Signal)
Nozzle Status LED
VaporTEK Interface
Nozzle Status LEDs:
V17, V24, V23, V14,
V15, V11, V20 and
V19 (see Figure 5)
Nozzle
Input
Selection Remarks
> 4VDC ON H The active nozzle Logic = High (H)
< 1VDC OFF L The active nozzle Logic = Low (L)
Note: An open input is always on low (L) state.
3. Diesel disable Input: VaporTEK pump will never start. This option suppresses the diesel signal. When a pulse train output from the encoder sends all gasoline grade and diesel signals, the diesel nozzle hook signals are connected to the VaporTEK Interface and set to “Diesel Disable”. In this configuration when diesel hook is activated, all generated flow rate will be ignored. If this input becomes active (H or L), the VaporTEK Interface will ignore the incoming pulse train and any active nozzle inputs for the dedicated side.
39
Communication Setup - VaporTEK Interface VaporTEK Interface for Input Configuration
2. Set Config
--------------­****** Inputs ****** Side A Side B 1 Pulse Input 1 2 Pulse Input 2 3 Pulse Input 3 4 Pulse Input 4
VaporTEK-Potentiometer is in use!
Input 1 what type?(1-Pulse,2-Nozzle):1 Input 2 what type?(1-Pulse,2-Nozzle):1 Input 3 what type?(1-Pulse,2-Nozzle, 3-D_Disable):2 Input 4 what type?(1-Pulse,2-Nozzle, 3-D_Disable):3
you’ve set Input(s) as a Nozzle Input what logic do you need H or L active? (0=l, 1=H):1
Please select the VaporTEK Control Mode (0 = Potentiometer, 1 - Auto Calibration Tables):1
Config has been stored successfully
****** Inputs ****** Side A Side B 1 Pulse Input 1 2 Pulse Input 2 3 Nozzle Input 38l/min(H) 3 4 Diesel disable Input(H) 4
Auto Calibration Tables are in use!
Figure 19. Set Configuration Example
40

VaporTEK Calibration

Note: Refer to dispenser manufacturer’s manual for VaporTEK system commissioning before conducting the A/L calibration procedure.

Manual Calibration using the POT on the VaporTEK Controller board

The flow rate of VaporTEK pump can be adjusted by changing the position of the POT setting in the VaporTEK Controller. The flow rate will increase as the POT is rotated CW from 1 to 8 (see Figure 20).
To adjust the POT (potentiometer) on the VaporTEK Controller use a non-conductive mini-screwdriver until the desired flow rate is achieved. Note: changing the pot position impacts both low and high speeds.
Warning! Use a non-conductive screwdriver while setting the POT.
Figure 20. POT (Potentiometer)
41
VaporTEK Calibration Dry Calibration - A/L Adjustment

Dry Calibration - A/L Adjustment

A/L adjustment using dry calibration can be performed only with the VaporTEK Plus or VaporTEK Ultra configurations.

Equipment Required

FB1 hand held terminal with 15-pin to RS422 cable
Gas meter
A/L nozzle adapter (varies by nozzle manufacturer)
Hoses

Initial Setup

1. Verify power is available at the VaporTEK Interface by confirming V4 LED is RED (see Figure 5).
2. Connect the FB1 Terminal to the RS422 connector on the VaporTEK Interface (see Figure 21).
3. Connect the gas meter encoder cable to the FB1 Terminal.
4. Connect the hoses to the gas meter.
5. Remove the nozzle from the dispenser holder and secure the A/L nozzle adapter to the spout of either the ARVN or Elaflex nozzle as appropriate. The A/L adapter o-rings prevent air leakage into the nozzle’s vapor collection holes (see nozzle close up detail in Figure 21). After ensuring the nozzle shutoff port is not covered by the adapter body, tighten the two knurled end rings to secure the adapter to the nozzle.
6. See manufacturer’s nozzle manual on method to open the nozzle vapor valve for dry calibration.
7. FB1 Terminal key description:.
START Power ON the FB1 Terminal
ENTER Confirm selection
SHIFT Cancel selection
42
VaporTEK Calibration Dry Calibration - A/L Adjustment
1
2
3
4
5
6
7
8
9
0
E
N
T
E
R
S
H
I
F
T
S
T
A
R
T
V
R
C
-
T
Y
P
G
a
s
m
e
s
s
u
n
g
(
1
)
M
V
R
(
2
)
V
R
C
(
3
)
F
l
o
w
Dir
e
c
t
io
n
N
o
z
z
le
En
d
T
M
OR
Connect vapor flow meter to barbed fitting on adapter
Connect vapor flow meter to barbed fitting on adapter
AVRN Nozzle
Vapor collection holes
Nozzle hold-open clip
Nozzle hold-open clip
Nozzle shutoff port (don’t cover)
Tighten rings (2)
O-rings (2)
Pin
RS-422
Connector
Elaflex Nozzle
Air
flow
Gas Meter
F6
F1
F8
F3
Home
7
END
1
SHIFT SPACE ENTER
INS0—
+
2
PgDn
3
4 5
6
PgUp
9 8
F9F4F10
F5
F7F2
START
Figure 21. Calibration Setup
43
VaporTEK Calibration Gas Meter Calibration
* Gasmeter** Calib. factor Cur : 05 New : 07
ENTER
7

Gas Meter Calibration

Gas meter calibration must be completed before conducting simulation.
1. Press the Start button until below screen appears. Press the keys as shown:
*** SERVICE *** SAL – pump (1) S&B – pump (2) GIL – pump (3)
2. When the display below appears, press the keys shown:
*** SERVICE *** Gas measuring (1)
SYS–Identify (2) EC2000 (3)
3. When display below appears, press the key shown:
VAPOR CONTROLLER * Gas measuring * Tot : 000,0 liter
F5
Cur : 000,0 l/min
4. Match the calibration factor on the gas meter (see Figure 15) with the following display on the FB1 Terminal. If the calibration factor already matches, press ENTER. If not, press F2 to change the calibration factor.
* Gasmeter** Calib. factor Cur : 05
F2
Change with F2
5. When display below appears, input the calibration factor shown on the gas meter (example: 07 is now the New factor) and press ENTER.
Refer to the Burkert Gas meter product manual for the calibration factor. It is typically marked “K-Factor” (see Figure 22).
44
VaporTEK Calibration Pulse Rate Setup With FB1 Terminal
Kal Faktor 7
2
Figure 22. Locate the Burkert Gas Meter Calibration Factor

Pulse Rate Setup With FB1 Terminal

Pulse rate setup on VaporTEK Interface

The VaporTEK Interface receives pulses from an active encoder and calculates the current flow rate by using of the adjusted pulse rate - Range: 50 to 200 Pulses/liter (1 US Gallon = 3.785 liters). For example, the pulse rate for a VaporTEK Interface should be set to 136 pulses/litre for Gilbarco Encore 500S.
If the dispenser is running, the FB1 Terminal will show the current petrol flow rate on the FB1’s display by using the FB1 - Sub menu item “Petrol flow (3)” (see step 4 below).
The pulse rate adjustment can be setup either using the service terminal FB1 connected to the VaporTEK Interface, or a Laptop connected to the VaporTEK Interface.

Pulse Rate Setup with FB1

1. Switch on the FB1. Press the Start button until below screen displays, then press the keys shown:
*** SERVICE *** SAL – pump (1) S&B – pump (2) GIL – pump (3)
2. When the display below appears, press the keys shown:
*** SERVICE *** Gas measuring (1)
SYS–Identify (2) EC2000 (3)
3. When the display below appears, press the keys shown:
45
VaporTEK Calibration Auto-Calibration using FB1 Terminal
4
Press number keys to enter desired pulse rate, e.g., 136
*** SERVICE *** SAL – pump (1) S&B – pump (2) GIL – pump (3)
*** SERVICE *** Gas measuring (1) SYS–Identify (2) EC2000 (3)
Service (1) Parameter (2) Autocalib (3) Simulation (4)
4. When the display below appears, press the keys shown:
10 Errors (1) Production (2) Fuel Flow (3) Impulse (4)
5. When the display below appears, if necessary to change the pulse rate, press the keys shown:
VAPOR CONTROLLER Pulse assignment Cur: 050 Change with F2
6. Enter Pulse Rate 136 for Encore 500S/500/300 dispensers.
F2

Auto-Calibration using FB1 Terminal

1. Press the Start button until below screen appears. Press the keys as shown:
2. When the display below appears, press the keys shown:
ENTER
3. When the display below appears, press the keys shown to start the auto-calibration:
2
46
VaporTEK Calibration Auto-Calibration using FB1 Terminal
Service (1) Parameter (2) Autocalib (3) Simulation (4)
Select Side Side 1 (1) Side 2 (2)
**Adjustment** Rate 100 % Offset 001 Change with F2
Auto Calibration Side: 1 Test point: 15 Vap: 048.00 l/min
VAPOR CONTROLLER Rate 99.5 % Set 40.0 l/min Cur 39.8 l/min
3
4. At the display below, select the dispenser side (1 or 2) that you want to calibrate:
1 2
or
5. Set the A/L Ratio rate:
6. Wait while the auto-calibration is calibrating through 15 points:
The auto calibration procedure will complete at test point 1.
After the auto-calibration has been accomplished the result of calibration needs to be verified using dry simula­tion. Follow the steps 1- 6 of the Simulation section and verify the A/L – Ratio which is shown as “Rate”:
The Rate as displayed on the FB1 Terminal shall be within the legislated range established by local regulation.
47
VaporTEK Calibration Simulation with FB1 Terminal
2
Service (1) Parameter (2) Autocalib (3) Simulation (4)
4
Simulation Max 40 l/min (1) Max 35 l/min (2) Free Input (3)

Simulation with FB1 Terminal

1. Press the START green button on the FB1 Terminal until the below screen appears. Press the keys as shown:
*** SERVICE *** SAL – pump (1) S&B – pump (2) GIL – pump (3)
2. When the display below appears, press the keys shown:
*** SERVICE *** Gas measuring (1)
SYS–Identify (2) EC2000 (3)
3. When the display below appears, press the keys shown to start the simulation:
4. At the display below, select the dispenser side (1 or 2) that you want to simulate:
5. At the display below, select the simulation rate of petrol you want to check by pressing the keys shown:
When the flow rate input is provided through the FB1 Terminal the VaporTEK pump will start if greater than 6 liters/minute. The flow rate achieved by the VaporTEK Pump will be displayed in the FB1 Terminal.
6. The FB1 Terminal will start the simulation and display the results as in the example below:
Select Side Side 1 (1) Side 2 (2)
48
1 2
or
1
,
2 3
or
VaporTEK Calibration Simulation with FB1 Terminal
VAPOR CONTROLLER Rate 99.5 % Set 40.0 l/min Cur 39.8 l/min
Where:
- Rate is the ratio of current vapor flow (Cur) divided by the simulated petrol flow (Set).
- Set is the simulated petrol flow established in Step 5 above. NOTE: Set value must be greater than 6 lpm to
start the VaporTEK Pump.
- Cur is the vapor or air flow measured by the gas meter.
Adjust the POT until the Rate as displayed on the FB1 Terminal is within the legislated range established by local regulation (see Figure 20).
49

VaporTEK Pump Troubleshooting and Quick Help

Troubleshooting and Quick Help

Problem Cause Corrective Procedure
Electrical system fuse or circuit breaker tripped Replace fuse or reset the breaker
No power to VaporTEK Controller
F1 fuse blown out on the VaporTEK Controller Replace Controller if F1 fuse blown out.
Verify power circuit breaker is switched on. Restore input power. Verify input voltage rating.
Pump Fails To Start
No Power to VaporTEK Interface
wire schematic per Figure 12. Restore input power. Verify input voltage rating.
Verify the V4 light is illuminated. If not, check
F1 fuse (T250mA) blown out on the VaporTEK Interface
Replace F1 fuse rated for 250V/250mA.
Incorrect wiring will damage both VaporTEK
Pump and the Controller. Check cable connec­VaporTEK Pump and VaporTEK Controller wired incorrectly
tions. Verify the cables are connected per the
appropriate schematic in the Equipment Wiring
Schematics Section. Replace both VaporTEK
Pump and Controller if wired incorrectly.
Verify wiring connection per the appropriate VaporTEK Interface inputs wired incorrectly
schematic in the Equipment Wiring Schematics
Section.
No hook signal input
Verify wiring and hook signal input voltage rat-
ing.
Check pulse input wiring on VaporTEK Inter­No input fuel pulses
face. Also verify input LED's (Refer VaporTEK
Interface LED section).
RJ 12 cable missing or incorrectly connected between VaporTEK interface and Controller
No Communication between VaporTEK Inter­face and Controller
Refer to the equipment wiring schematic and
connect RJ 12 cable.
Verify if LED V12 and V13 are flashing simulta-
neously. Defective RJ12 Cable. Replace RJ12
cable.
Pot setting too low Increase pot setting.
Pump Fails To
Start
Flow Rate below 6 lpm Increase fuel flow rate beyond 6 lpm
VaporTEK Interface inputs configured incor­rectly
Blocked outlet/discharge
Configure inputs correctly. Refer to the
VaporTEK Interface setup.
Clean outlet/discharge line. Replace flame
arrestors if clogged.
VaporTEK Controller requires high voltage hook Low Voltage hook signal wired directly to VaporTEK Controller
signals (110-220 VAC). Add VaporTEK Inter-
face or Switch Relays as discussed
in“VaporTEK Pump Configuration” on page 17.
Temperature in the hydraulics area of the dis­penser is below the VaporTEK pump’s rating and is creating too much starting torque friction.
Install appropriate heater as defined by the dis-
penser manufacturer.
Ambient temperature above rated temperature Pump Thermal protector Trips
of the product. Verify proper ventilation for the
VaporTEK Pump. Wait a couple of minutes
before starting the pump again.
Defective VaporTEK Controller or, if equipped, VaporTEK Interface Board
Replace VaporTEK Controller or VaporTEK
Interface Board.
50
Appendix A: VaporTEK System Reference Wiring Diagrams
0 1 2 3 4
MODE
JP4
F1
COMMS
JP1
POT
ENPM1M2
JP6
+14 - 28V POWER
P1105
VAPORVAC ISOLATION
25
26
1
2
15
RJ12 Cable
(579084-001)
VAPORTEK INTERFACE BOARD
(900630-001)
PUMP CONTROL NODE
VAPORTEK PUMP
(900621-001)
VAPORTEK CONTROLLER BOARD
(900628-001)
6-Conductor Cable
(M12970A001)
Motor CableSensor Cable
G12 3 4
P1B
P2B
GND
P1A
P2A
GND
421 3
Mode jumper
(0 position)
P1110
SIDE B
SIDE A
ORANGE
GREEN
YELLOW
RED
BLACK
BROWN
Attach the ground terminal to the corner of the controller board’s mounting bracket .
FB1
Terminal
LAPTOP
USB 2.0 A-Male, to B-Male Cable
15 pin Serial RS-422 Cable
CAUTION: Motor and Sensor cable connectors are keyed to avoid interchangeability. Cross connection may damage the VaporTEK Controller and the pump.
F6
F7F2
F1
F8
F9F4F10
F3
Home
7
8
4 5
END
1
2
INS0—
SHIFT SPACE ENTER
START
F5
PgUp9
6
PgDn
3
+
Figure A-1. VaporTEK System Plus For Collection Only - Encore 500S Dispenser
A-1
Gilbarco, Inc. 24V 135W
TB3
Check Fuses on Fuse Module before replacing
Power Supply
This cover MUST
be replaced upon
completion of
servicing
HIGH
VOLTAGE
WARNING
P2
TB3
J1
VAPORTEK INTERFACE BOARD
(900630-001)
VAPORTEK CONTROLLER BOARD
(900628-001)
VALVE BOARD
POWER SUPPLY
Ground wire
connect to
“C” channel
P1200A
J1200
Ground wire
connect to
Controller
bracket using
M3 screw
2-Conductor Cable
(P/N M12083A002)
2-Conductor Cable
(P/N M05547A006)
2-Conductor Cable
(P/N M13884A001)
+24
GND
01234
MODE
JP4
F1
COMMS
JP1
POT
PNL M1M2
JP6
L
N
BLACK
RED
WHITE
BLACK
GREEN/YELLOW
PNL
VAP OR VA C
CASH (A)
TRIND
SMRT
CASH (B)
LN
Orange
Connector
3-Conductor Cable
(900651-001)
AC Power
Distribution Cable
(P/N M04406A001)
P1201
P1200
P1207
10
STEERING VALVE
P1300
J1300
J1200A
A-2
Figure A-2. VaporTEK System Plus For Collection Only - Encore 500S Dispenser
Appendix A: VaporTEK System Reference Wiring Diagrams
A-3
01234
MODE
JP4
F1
COMMS
JP1
POT
JP6
VAPORTEK PUMP
(900621-001)
VAPORTEK CONTROLLER BOARD
(900628-001)
Motor CableSensor Cable
G12 3 4
421 3
Set J4-0
Attach the ground terminal
to the corner of the controller
board’s mounting bracket .
CAUTION:
Motor and Sensor cable connectors are
keyed to avoid interchangeability. Cross
connection may damage the VaporTEK
Controller and the pump.
NEPM1 M2
MAIN
L1
N
L1
N
230VAC
M12970A001
900857-001
900857-001
3-Color LED Functions
Dispenser Panel
Failure Status and LED Color
1
26
3-Color LED V1
(900856-001)
3-Color LED V2
(900856-001)
VEEDER-ROOT VaporTEK
Interface with LED
(900855-001)
0 Green idle
0 green (flashing) busy
> 9 Red idle
> 9 Red (flashing) busy
1 - 9 Orange idle
1 - 9 Green / Orange (flashing) busy
impact the front panel led color.
- Each failure during an acve transacon will increase an internal error counter and will be
Error counter Front panel LED Color Run Status
- Failure status and Led color
Each acve transacon without communicaon error between VaporTEK – Interface and
VaporTEK – Controller will reset the error counter.
Remark: An acve transacon is a transacon with a fuel flow rate higher than 6l/min.
Figure A-3. VaporTEK System Plus for collection only with 3 color LED - using 900855-001 Interface Board for Encore 500S Dispenser
Appendix A: VaporTEK System Reference Wiring Diagrams
L1 N
L1
N
230VAC
MAIN
MAIN
01234
MODE
JP4
F1
COMMS
JP1
POT
JP6
VAPORTEK PUMP
(900621-001)
VAPORTEK CONTROLLER BOARD
(900628-001)
Motor CableSensor Cable
G12 3 4
421 3
Set J4-1
Set J4-2
Attach the ground terminal
to the corner of the controller
board’s mounting bracket .
CAUTION:
Motor and Sensor cable connectors are
keyed to avoid interchangeability. Cross
connection may damage the VaporTEK
Controller and the pump.
NE P M1 M2
Controlled in two speed mode over
high voltage hook signal
CABLE TYPE M12970A001
CABLE TYPE
M12970A001
A-4
Figure A-4. VaporTEK System Ultra for Collection only Using VRC 390/3 Board for Encore 500S Dispenser
Appendix A: VaporTEK System Reference Wiring Diagrams
For technical support, sales or
other assistance, please visit:
www.veeder.com
Loading...