Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of
merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the
furnishing, performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication
may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root.
DAMAGE CLAIMS
1.Thoroughly examine all components and units as soon as they are received. If damaged, write a complete and detailed
description of the damage on the face of the freight bill. The carrier's agent must verify the inspection and sign the description.
2.Immediately notify the delivering carrier of damage or loss. This notification may be given either in person or by telephone.
Written confirmation must be mailed within 48 hours. Railroads and motor carriers are reluctant to make adjustments for
damaged merchandise unless inspected and reported promptly.
3.Risk of loss, or damage to merchandise remains with the buyer. It is the buyer's responsibility to file a claim with the carrier
involved.
RETURN SHIPPING
For the parts return procedure, please follow the appropriate instructions in the "General Returned Goods Policy" and "Parts
Return" pages in the "Policies and Literature" section of the Veeder-Root North American Environmental Products price list.
This manual describes the site preparation and console installation procedures for the TLS-HLD Console.
This manual assumes that you installing the TLS-HLD in a new site (before pavement is put down and with no wiring
runs in place). Among the topics covered are:
• Site layout considerations.
• Installing the console and connecting wiring from the 120 or 240 Vac power panel.
• Probe assembly and installation procedures.
• Installing wiring conduit between the console and its probes.
• Probe-to-console field junction box wiring diagram.
• Attaching probe wiring to the console.
• RS-232 serial communication connection requirements and serial commands.
• Troubleshooting information that contains diagnostic and maintenance information.
• System specifications.
After the console is wired to its power source and probes, you should program the console following the setup
instructions contained in the TLS-HLD Setup manual.
Regulatory Agency Console Documentation
The UL Console Form Numbers are listed by Underwriters Labs, in File Number: MH11766.
Related Manuals
577013-785TLS-HLD Setup manual
576013-635RS-232 Serial Interface manual
576013-859Direct Burial Cable Installation manual
1
IntroductionSafety Symbols
Safety Symbols
The following safety symbols may be used throughout this manual to alert you to important safety hazards and
precautions
EXPLOSIVE
Fuels and their vapors are extremely
explosive if ignited.
ELECTRICITY
High voltage exists in, and is supplied
to, the device. A potential shock hazard exists.
NO SMOKING
Sparks and embers from burning cigarettes or pipes can ignite fuels and
their vapors.
NO POWER TOOLS
Sparks from power tools (such as
drills) can ignite fuels and their
vapors.
WEAR EYE PROTECTION
Fuel spray from residual pressure in
the lines can cause serious eye injuries. Always wear eye protection.
FLAMMABLE
Fuels and their vapors are extremely
flammable.
TURN POWER OFF
OFF
Live power to a device creates a
potential shock hazard. Turn Off
power to the device and associated
accessories when servicing the unit.
NO OPEN FLAMES
Open flames from matches, lighters,
welding torches, etc. can ignite fuels
and their vapors.
USE SAFETY BARRICADES
Unauthorized people or vehicles in
the work area are dangerous. Always
use safety cones or barricades,
safety tape, and your vehicle to block
the work area.
INJURY
Careless or improper handling of
materials can result in bodily injury.
GLOVES
Wear gloves to protect hands from
irritation or injury.
READ ALL RELATED MANUALS
Knowledge of all related procedures
before you begin work is important.
Read and understand all manuals
thoroughly. If you do not understand
a procedure, ask someone who does.
2
Site Considerations
g
Control Drawing
Double Wall Tank
MP
MP
I.S.
Circuit breaker panel
or Fused, switched,
neon indication spur
120 or 240 Vac
12 AWG barrier
ground wire
I.S.
NOTE: Intrinsically safe wiring (marked ) shall be installed in
accordance with Article 504-20 of the NEC, ANSI/NFPA 70.
Note: conduit requirements are dependent on local electrical regulations.
For probe-to-console wiring, shielded cable is required regardless of
conduit requirements.
WARNING:
Substitution of components may impair intrinsic safety.
Circuitry within the TLS-HLD Console barrier forms an intrinsically safe,
energy-limited system. This system makes TLS-HLD probes safe for use
in a Class I, Group D hazardous location. TLS-HLD probe wiring is
intrinsically safe only when connected to Veeder-Root's TLS-HLD
Console. Reference Console Form Number 8469 and Probe Form
Numbers 8462, 8463, 8468, and 8473.
I.S.
Non-Hazardous
Area
VEEDER-ROOT
PA
Hazardous
Area
TLS-50
TLS
Height Level Display
Single Wall Tank
MP
le Wall Tank
Sin
DP
DISPENSERS
Hazardous Area
LEGEND
Magnetostrictive Probe
MP
Expoxy Sealed Connection in
a Weatherproof Junction Box
Seal-Off
Terminal Connection
1/2'' (12.7 mm) Rigid Conduit
IS
Conduit Enters Console in an
Intrinsically Safe Area Knockout
PA
Conduit Enters Console in a
Power Area Knockout
Product piping
consoles\hldsysdia.eps
Figure 1. Control Drawing - Example TLS-HLD System Site Layout
3
Site Considerations
National Electrical Code Compliance
National Electrical Code Compliance
The following information is for general reference and is not intended to replace recommended National Electric Code
(NEC) procedures. It is important for the installer to understand that electrical equipment and wiring located in Class I,
Division 1 and 2 installations shall comply with the latest appropriate articles found in the National Electric Code (NFPA
70) and the Automotive and Marine Service Station Code (NFPA 30A), or other local code such as the CEC, Canadian Electrical Code..
PROBE- TO-CONSOLE WIRING
Shielded Cable or Veeder-Root Direct Burial Cable Required
To ensure the best operating systems available, Veeder-Root REQUIRES the use of shielded cable for all probes
regardless of conduit material or application. In these installations, shielded cable must be rated less than 100 picofarad
per foot and be manufactured with a material suitable for the environment, such as Carol
8760.
Note: Throughout this manual, when mentioning any cable being used for probe-to-console wiring, it will be referring to
shielded cable.
Wire Length
Improper system operation could result in undetected potential environmental and health hazards if the probe-to-console
wire runs exceed 1000 feet. Wire runs must be less than 1000 feet to meet intrinsic safety requirements.
™
C2534 or Belden™ 88760,
Splices
Veeder-Root recommends that no splices be made in the wire run between a probe junction box and the console. Each
splice degrades signal strength and could result in poor system performance.
Wire Gauges - Color coded
• Shielded cable must be used in all installations. Probe-to-console wires should be #14 - #18 AWG stranded copper
wire and installed as a Class 1 circuit. As an alternate method when approved by the local authority having
jurisdiction, #22 AWG wires such as Belden 88761 may be suitable in installations with the following provisions:
- Wire run is less than 750 feet
- Capacitance does not exceed 100 pF/foot
- Inductance does not exceed 0.5 μH/foot
• Wires carrying 120 or 240 Vac from the power panel to the console should be #14 AWG copper wire for line, neutral
and chassis ground (3); and #12 AWG copper wire for barrier ground (1).
PROBE JUNCTION BOXES
Weatherproof electrical junction boxes with a gasketed cover are required on the end of each probe conduit run at the
manhole location. Gasketing or sealing compound must be used at each entry to the junction box to ensure a waterproof
junction. The interior volume of each junction box must be a minimum of 16 cubic inches.
Veeder-Root recommends the following junction box or equivalent:
• Appleton Electric Co. - JBDX junction box, JBK-B cover, and JB-GK-V gasket.
Probes operate in area s wher e flammabl e l iquid s and ex plos ive v apors may be
present.
Improper installation may result in fire or explosi on causing serious injury or
death.
Practice the following:
1. Read thoroughly and f ollow the instructions shipped with each probe.
2. Probe wiring must enter the consol e only through their designated a reas.
3. Power wires and condui t must not enter the intr insically safe
compartment of the console.
4. Substitution of components may impair intri nsic safety.
Wiring between the console and theprobes is of limited electrical power sothatthere is insufficientenergyto ignitefuel.In the console, the low powerprobe wiring is considered intrinsicallysafe because itis physicallyisolated from all high powerwiring. To maintain theintegrity of thissafetyfeatureprobewiring can notshare the same conduitwith powerwiring.In addition, probe cables can onlyenter theconsole through thedesignated intrinsically safeareaknockouts.
Ifthe TLS-HLD System is being retrofitted into a paved site,you can cut grooves in the pavement, run directburialcableto theprobes,and then seal overthe cable grooves, subject to approval of thelocal authority having jurisdiction.
Before trenching, you should diagram all conduitrunsbetween the console’sintended location anditsdeployed probes.Your site diagram will helpyou calculateconduit andwiringlengths, and necessaryquantities of junction boxes, sealing boxes, clamps, brackets, etc.
Throughout thisplanning process and inthe actualinstallation,you must follow all latestNationalElectric Codes, and applicable federal,state,and local codes as regards conduit type, depth below grade,sealing, grounding, wire capacities, direct burial (ifpermitted), etc.
Selecting a Console Location
WARNING
Explosive vapors or flammable liquid s could be pre sent near locations wher e
fuels are stored or being dispensed. The TLS-HLD Console is not explosion
proof.
An explosion or fire resulting in serious injury or death, property loss and
equipment damage could occur if the console is installed in a volatile,
combustible or explosive atmosphere (Class I, Division 1 or 2).
Do not install this c onsole in a v olati le, comb ustib le, or e xpl osive atmosph ere.
Select a mounting location on the inside of any building.Theconsole mustbeprotected from severe vibration, extremes in temperature and humidity, rain, and otherconditionsthat could harm computerized electronic equipment.
The equipmentisdesigned to operate safely under thefollowingrangeof conditions:
•
Temperaturerange 0to 40°C - (storagetemperature range of -40 to+74°C).
5
Site ConsiderationsSelecting a Console Location
• A maximum relative humidity of 95% RH (non-condensing) at temperatures up to 40°C.
• Console may be powered by either 120 or 240 Vac. A switch-mode power supply automatically detects the input
voltage (no jumpers required).
• Main supply voltage fluctuations not exceeding ±10%.
• Pollution Degree Category 2.
• Installation Category II.
Consoles must be installed within the interior of buildings. They are not suitable for any external location.
Ensure that the console is located where neither the console nor its associated cabling will be damaged by doors,
furniture, barrows, etc. Consider the ease of routing wiring, ducting, and probe cables to the console. Check that the
mounting surface material is strong enough to support the console’s weight of about 4 pounds.
If the unit requires cleaning, do not use any liquids, wipe only with a clean, dry cloth.
6
Console Installation
Mounting the Console
Figure 2 illustrates recommended console mounting. Install the console fastening devices to the mounting surface using
the hole pattern (6.7” x 5.7”) shown in Figure 3. Mounting screws up to 3/16” diameter may be used.
Install metal conduit (1/2” I.P.S.) between the console and the power panel. Figure 3 shows the three designated
knockouts (one each on top, left side, and bottom) through which power wiring can safely enter the console.
1000 mm
(Maximum)
VEEDER-ROOT
To an external alarm (i.e., Forecourt Alarm)One 2 ampere fused, switched, neon indication
spur or a dedicated circuit breaker rated
for 120 Vac or 240 Vac. NOTE, circuit breaker
must be marked as the external alarm
disconnect for the console.
One 5 ampere fused, switched, neon
indication spur (for 240 Vac), or a dedicated
circuit breaker rated for 15 amperes, 120 Vac
or 240 Vac. NOTE, circuit breaker must be
marked as the power disconnect for the console.
From an independent 24 hour supply at the distribution
panel, run three 2.5 mm (minimum) standard color coded
wires; live, neutral, and earth, to the fused spur. Run one
4 mm wire, color coded green/yellow, from the earth bus
bar at the distribution panel direct to the console location.
Leave at least 1 metre of free cable for connection to the
console.
1/2-inch IPS and .56 inch (22 & 14 mm)
Power wiring only - conduit knockouts
(4 places)
1.25''
(32 mm)
3.75"
(95mm)
1/2, 3/4, & 1 inch IPS (22, 28, & 35 mm)
Intrinsically safe wiring only - conduit knockouts
(2 places)
0.93''
0.4''
(10 mm)
(24 mm)
1.18''
(30 mm)
Figure 3. Console Dimensions and Designated Conduit Knockouts
2" (51 mm)
8
Console InstallationWiring the Console
Wiring the Console
WARNING
OFF
The console contains voltages which can be lethal. It is connected to devices
that must be intrinsically safe.
Connecting power wires to a live circuit can cause electrical shock that may
result in serious injury or death.
1. Turn power off at the circuit breaker connecting the power supply wires.
2. Attach conduit from the power panel to the console's Power Area
knockouts only (1 on top and bottom, ref. Figure 3).
1. Pull four wires between the power panel and the console; three #14 AWG (2.5 mm2) color-coded wires for AC line
(L), AC neutral (N) and chassis ground; and one #12 AWG (4 mm
2
) green and yellow wire for barrier ground.
For international applications using 240 Vac, pull four wires between the power panel and a 5 A fused, switched,
neon indication spur; three #14 AWG color-coded wires for AC line (L), AC neutral (N) and chassis ground; and one
#12 AWG green and yellow wire for barrier ground. Pull four identical wires between the spur and the console.
2. Open the right door of the console and connect the four power/ground wires as shown in [Figure 4]. Do not connect
the power wires to breaker panel at this time.
L2 L4
WARNING!
Attach neutral wire to top
terminal ("N") of J4
Attach hot wire to bottom
terminal ("L") of J4
Attach chassis ground
wire to ground lug
Protective Earthing
Conductor (Green and
Yellow) Attach #12AWG
2
(4 mm
) barrier ground
wire to ground lug
CONSOLE
POWER
RELAY RATING
120/240 VAC
2 A MAX
N
J4
C24C27
L
J5
1234
OPEN
SW1
SEC
SETUP
J3
POWER WIRING NOTES:
1. Barrier ground must be #12 AWG (4 mm
or larger diameter.
2. Check to be sure that the electrical resistance
between the console ground lug and a known
good earth ground is less than 1 ohm.
3. Connect the power supply wires in the power
panel to a separate dedicated circuit.
4. Electrical rating power input -- 120 Vac or
240 Vac, 50/60 Hz, 2 A maximum.
5. See the "Console Dimensions and Designated
Conduit Knockouts" figure for actual locations of
power conduit knockouts into the console. Power
wiring must enter only in Power Area conduit
knockouts.
Shock hazard. Do not
touch metal ends of
capacitors C24/C27
or the metal bands
on chokes L2/L4.
2
)
WARNING
SUBSTITUTION OF COMPONENTS
MAY IMPAIR INTRINSIC SAFETY.
NO REPAIRS SHOULD BE ATTEMPTED.
REFER SERVICING TO QUALIFIED
PERSONNEL ONLY.
PROBE 6
PROBE 5
PROBE 4
PROBE 3
PROBE 2
PROBE 1
AVERTISSEMENT
LA SUBSTITUTION DE COMPOSANTS
PEUT COMPROMETTRE LA SECURITE
INTRINSEQUE.
+
+
+
+
+
+
consoles\tls50\50powr.eps
Power
Side
Intrinsically
Safe Side
Figure 4. Wiring AC Power to the Console
9
Mag Probe Assembly
The following assembly instructions are for Global Mag Plus an Mag Plus probes. For other probe types follow assembly
instructions included with probe.
Attaching Probe Canister Spacer Rings
1. Open the probe shipping carton so that you have access to the probe. Also open the installation kit.
2. After setting the spacer vanes for a 3- or 4-inch riser (see Figure 5), install the two spacer rings as shown. Note: you
must slide the bottom spacer over the probe and onto the lower end of the canister. NOTE: spacers are not required
for a 2-inch riser.
Assembling Floats onto Probe Shaft
The Product floats, Water Floats (if ordered), and Boots from Probe Installation Kits are assembled on the probe shafts in
the exact
IMPORTANT! Failure to push the boot as far as possible onto the probe shaft could cause the boot and float(s) to fall
into the tank. The boot must be pushed on until it “locks” on the probe shaft. Also, water floats must be installed, if
ordered, for the probe to operate correctly.
Handle the probe carefully. Striking or dropping the probe will result in loss of calibration and could cause permanent
damage.
sequence and orientation shown in Figure 6.
Attaching Cable Connector to Probe Canister
Attach the connector end of the probe cable to the threaded connector on top of the probe canister and tighten down the
integral nut.
This completes the probe assembly. Save the remaining kit components. They will be needed to install the probe into the
tank.
10
Mag Probe AssemblyAttaching Cable Connector to Probe Canister
1
5
6
2
7
3
tls2/figure12.eps
Legend for numbered boxes
1After setting vanes (see insert) install top spacer ring. Orient locking tabs as shown, and then slide ring over top of canister
until tabs snap into groove in canister.
2Probe canister
3After setting vanes (see insert) install bottom spacer ring. Orient locking tabs as shown, and then slide ring over probe and
onto canister, until tabs snap in groove.
4Probe shaft
5Spacer Ring Riser Adjustment
6For 3"riser - set 4 spacer ring vanes as shown.
7For 4"riser - set 4 spacer ring vanes as shown.
Figure 5. Installing Probe Canister Spacer Rings
4
11
Mag Probe AssemblyAttaching Cable Connector to Probe Canister
389
77
444
1
2
Legend for numbered boxes
1Up
2Bottom of probe shaft
34-Inch Floats
4Product float - slide on probe shaft first
5Water float - (Optional) slide on probe shaft second.
6Boot - slide on probe shaft last
7Or (different float size)
83-Inch Floats
92-Inch Floats
555
666
tls2/figure13.eps
Figure 6. Probe Float/Boot Installation
12
Probe Installation
Probe Manhole Installation
At each underground probe location, install a 14-inch (355 mm) minimum diameter approved manhole according to the
manufacturer’s instructions (Note: probes should be located at least 24 inches (610 mm) from the submersible pump to
avoid erroneous probe readings when the pump is running).
Position the manhole so that there is necessary clearance for junction box installation and wiring.
Probe Installation
Each probe supplied by Veeder-Root is accompanied by an assembly manual which details the assembly of the probe.
Figure 7 and Figure 8 illustrate how to install the assembled probe either in an underground tank, and in an above ground
tank.
14'' min. dia. manhole
Riser cap with cord grip
bushing and nut
Concrete slab or packed
earth per NFPA 80
A = 18" minimum for standard mag
probes or 14" minimum for global
mag plus/mag plus probes. When
installing a probe longer than the
the tank diameter, increase this
minimum dimension to compensate.
(Example: a 7'-6'' diameter tank will
use an 8' probe, in which case you
must add 6" to minimum riser length
'A', i.e., 24" or 18" depending on
probe type).
Probe cable
.
.
.
.
.
.
.
.
.
.
.
..
.
Tank
Mag Probe
(rests on bottom)
Weatherproof junction box with 1/2" NPT
threads (16 cubic inch minimum)
Cord grip seals
.
.
.
.
.
.
.
.
.
.
.
..
.
Seal-off, epoxy seal per NFPA spec
A
1/2" Rigid conduit (to Console)
Riser pipe - 2, 3, or 4'' API schedule 40 depending
on probe type (To prevent erroneous probe readings,
install probe riser a minimum of 24'' from the submersible
pump.)
Split-Ring Collar
(P/N 576008-617)
required if probe
enters the riser.
Top view
3/4" ID
Side view
probes\pbinstcen.eps
Figure 7. TLS-HLD Probe Installation Example - Underground Storage Tank
13
Probe Installation
Probe Conduit Installation
Use bushing and body of grip
fitting supplied with probe and
Adaptor nut supplied with
AST kit.
Riser pipe - 2, 3, or 4'' API
schedule 40 - depending on
probe type
A = 18" minimum for standard mag
probes or 14" minimum for global
mag plus/mag plus probes. When
installing a probe longer than the
the tank diameter, increase this
minimum dimension to compensate.
(Example: a 7'-6'' diameter tank will
use an 8' probe, in which case you
must add 6" to minimum riser length
'A', i.e., 24" or 18" depending on
probe type).
probes\astpbins.eps
Flexible metal conduit
supplied with AST kit
Liquidtight
fittings from
AST kit
A
Mag Probe
(rests on bottom)
Figure 8. TLS-HLD Probe Installation Example - Above ground Storage Tank
Weatherproof junction box with
1/2" NPT threads (16 cubic inch
minimum)
Epoxy seal per NFPA specs
Rigid conduit
Split-Ring Collar
(P/N 576008-617)
required if probe
enters the riser.
Top view
3/4" ID
Side view
Probe Conduit Installation
Probes operate in areas where flammable liquids and explosive vapors may be
present.
Improper installation may result in fire or explosion causing serious injury or
death.
Practice the following:
1. Read thoroughly and follow the instructions shipped with each probe.
2. Probe wiring conduit must not contain any other wires.
3. Probe wiring and conduits must enter the console only through their
4. Power and communication wires and conduit must not enter the
WARNING
designated areas (see Figure 3).
intrinsically safe compartment of the console. (see Figure 3).
14
Probe InstallationWiring Run Methods
Wiring Run Methods
Two wiring run methodsare commonlyused for probes- Shielded wiring pulledthroughburied, sealed 1/2”rigid conduit; or directburial cable.
BURIED RIGID CONDUIT
The preferred method, especially in new sites before driveway surfaces are paved,is to pull probe wiring through buried 1/2” rigid conduit[Figure9].
Weatherproof junction
box with 1/2-inch N.P.T.
threads (16 cubic inch
Splice Closure
Seal-Off
minimum)
Cord grip seals
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
Epoxy seal per NFPA spec
1/2'' rigid conduit (to console)
Tank
probes\pconduit.eps
Figure 9. Example Probe Wiring Run in Buried Rigid Conduit
Pulling Wires for Probes
Pull shielded cable consisting of two conductors,color-coded #14-18AWG (2.5 -0.8 mm2) stranded copper wire, between theconsole and the junction box ateachwithno splices to ensure optimum signal strength.
probe location (do notgang wirestogether).Use singlelengthsofwire
IMPORTANT! Maximum probe-to-console cable length is 1000 feet (305m).
Since wires for multiple probesmay enterthe console through a single conduit, itis recommended that you use adifferent color-code for each wire or individuallymarkeach wire toidentifyprobe inputs.Also, if the intrinsicallysafe wires enter the building in a wiring trough, onlyintrinsicallysafe wires(from TLS-HLD probes) can be in the trough.Keepalllow power (intrinsically safe)wiring physically isolated from high powerwires in all wiring troughsper theNEC.
DIRECT BURIAL CABLE
An alternative to trenching through existing pavement is to use directburial cable.Prior to installing direct burial cable with epoxy splices, consult with the local authority having jurisdiction. Use of direct
burial cable isonly allowed in locations where local codespermit the use of buried cable.
15
Probe InstallationPulling Wires for Probes
G
Splice closure
n.
WARNING
Direct burial cable can be installed in hazardous locations where fuel and
vapor may be present. It is specifically designed for certain uses only. It must
be installed in the correct manner.
Installing the cabl e incorr ectl y or without pr oper precauti ons can resul t in fire,
explosion, ele ctr ical shock, hazardous conditions as well as equipment
damage or inaccurate inventory control.
Perform the following:
1. Use direct burial cable for intrinsically-safe wiring only. Do not use for
power wiring.
2. Do not share conduit f or intr insica lly- safe p robes wi th wiri ng of an y oth er
type or from any other system.
3. Maintain a physical separation of at least 2 inches between probe w iring
to all other wiring.
4. When cutting trenches for direct burial cable ensure that you do not cut
through exist ing fuel or wiri ng systems. Obtain as much site information
as possible befor e cutting the trench.
5. When grinding trenches in existing pavement for direct burial cables,
wear approved breat hing and hearing protection, goggles, and gloves.
Thedirect burialmethod requiresgrinding a 1/4” to 3/8” wide by1-1/4” deepgroove (adding 1/4” of depth for each additional cable) in thepavementsurface,laying Veeder-Root supplied direct burialcable down inthe bottom ofthe groove, laying an expanded polyethylene foam backerrod overthe cable(s), and then a placing a 1/4” to 1/2” bead of Veeder-Root recommended silicone sealantover the backer rod to withina minimum of 3/8” below the pavement surface[seeFigure10]. If you decide to use the directburial method, youshould ordertheVeeder-Root Direct Burial CablePreparation Kit, P/N848100-500.
Epoxy filled
Cord grip
splice
enclosure
rade
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
Tank
probes\pdburialcen.eps
Drill oversized hole
in manhole for DB cable
1
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
..
.
CONCRETE
.
.
.
.
.
..
.
.
890-SL silicone sealant
SOF ROD backer rod
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
2
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
...
EARTH
1
Dow Corning Silicone Pavement Sealant
2
Expanded polyethylene foam rod - trademark of
Applied-Extrusion Technologies.
Seal-off
Rigid conduit
..
.
.
ASPHALT
3'' Mi
Figure 10. Example Probe Wiring Run Via Direct Burial Cable
16
Probe InstallationSealing Field Connections
Figure 11 diagrams a typical probe field wiring connection in the junction box.
Do not ground drain wire
in junction box
To
PROBE
Terminal
Block In
Console
Seal-off
Black
From
Probe
White
1/2'' rigid
conduit
probes\3mpwir.eps
Epoxy sealed connections in a
weatherproof junction box
Figure 11. Probe Field Wiring Connection
Sealing Field Connections
WIRING RUN THROUGH RIGID CONDUIT
1. Pull the wires from the probe canister into the junction box. Pull two wires from the console through the seal-off box
and into the junction box.
2. Using wire nuts, connect the two wires from the probe to the two wires coming from the console. Be sure to observe
color codes or tags when making these connections.
3. Do NOT terminate drain wire at this location, ground drain wire at console only.
4. Seal wire nuts with epoxy sealant using one bag for two-wire nut connections (Figure 12).
CAUTION: Epoxy sealant is irritating to eyes, respiratory system, and skin. Can cause allergic skin reaction.
Contains: epoxy resin and cycloaliphatic epoxycarboxylate. Precautions: Wear suitable protective clothing, gloves,
eye, and face protection. Use only in well ventilated areas. Wash thoroughly before eating, drinking, or smoking.
5. Push the tie-wrapped, epoxy sealed bag into the junction box. Replace and tighten the junction box cover.
DIRECT BURIAL CABLE
When using direct burial cable for probe- or sensor-to-console wiring runs, the sealing materials and procedure are
completely different. If you are using Direct Burial Cable you must follow the sealing instructions in the Direct Burial
Cable Installation Manual.
17
Probe Installation
Connecting Probes to the Console
ACB
Instructions:
NOTE: When temperature is below 50˚F (10˚C), keep
resin in a warm place prior to mixing (e.g., in an
inside pocket next to body).
1. Open epoxy sealant package, and remove resin pak.
2. Holding resin pak as shown in A, bend pak along long
length.
3. As shown in B, firmly squeeze the RED SIDE of the
resin, forcing it through the center seal and into
BLACK SIDE.
Connecting Probes to the Console
From probe,
sensor, or
transducer
Make sure that
the ends of cable
sheathing are submerged in sealant
4. Mix thoroughly to a uniform color by squeezing
contents back and forth 25-30 times.
5. Squeeze mixed, warm resin into one end of bag and
cutoff other end.
6. Slowly insert wiring connections into sealing pack
until they fit snugly against the opposite end as
shown in C.
7. Twist open end of bag and use tie wrap to close it off
and position the tie wrapped end up until the resin
jells.
Figure 12. Epoxy Sealing Connections
To console
Tie wrap
Wire nuts
consoles\epxy2w.eps
WARNING
The equipment is used in location where lethal voltages and explosive vapors
or flammable fuels may be present.
Care must be taken when installing, servicing or replacing parts in the system
or serious injury or death from explosion, fire or shock may occur.
For this system:
1. Comply with the latest National Electric Code, federal, state, and local
codes, and any other applicable safety codes. In addition, take necessary
precautions during installation, service, and repair to prevent personal
injury, property loss and equipment damage.
2. Refer servicing to trained and qualified personnel only.
3. Substitution of components may impair intrinsic safety.
OFF
4. Be sure AC power is “OFF” before opening the console panel cover and
connecting probe wires. Do not short any voltage across any barrier
terminal including probes.
18
Probe InstallationProbe Wiring Precautions
Probe Wiring Precautions
To The Installer! You Must Read And Understand This Information.
INPUT/OUTPUT WIRING POSITIONS AND LABELING
In all cases, the devices wired to the console’s input/output terminal blocks must be recorded to prevent improper
replacement during installation or service. A circuit directory is listed below for this purpose.
During programming, the probes wired to each position are identified and stored in memory. If a probe is removed and
reconnected to a different set of input terminals after programming, the system will not properly recognize the data being
received.
Wiring Assignments
1. Identify all probe wires according to their terminal block location using the self-adhesive numbering labels furnished.
Accurately record on the circuit directory in Figure 13 the location of each probe as you attach wires to the probe
input terminal block.
2. IMPORTANT! Once a device has been wired to certain terminals and the system has been programmed, the wires
from that device may not be relocated to other terminals without reprogramming the system
Probe Number
PROBE 1 IN
PROBE 2 IN TANK
PROBE 3 IN TANK
PROBE 4 IN TANK
PROBE 5 IN TANK
PROBE 6 IN TANK
TANK
TANK Number & Product
consoles\tls50\prbtnk.eps
Figure 13. Probe Installation Directory
Grounding Probe Shields and Drain Wires
Connect probe cable shields and drain wires to ground in the console only, not at the field junction boxes. Do not ground
both ends of the shield.
CONNECTING PROBES TO THE CONSOLE - OBSERVE POLARITY
Connect the two color-coded/marked wires from the each probe to the appropriate terminals of the Probe Terminal Block
as shown in Figure 14.
19
Probe InstallationProbe Wiring Precautions
g
g
WARNING
SUBSTITUTION OF COMPONENTS
MAY IMPAIR INTRINSIC SAFETY.
SW1
OPEN
1234
SEC
SETUP
NO REPAIRS SHOULD BE ATTEMPTED.
REFER SERVICING TO QUALIFIED
PERSONNEL ONLY.
PROBE 6
PROBE 5
PROBE 4
PROBE 3
PROBE 2
PROBE 1
+
+
+
+
+
+
Black wire from probe
connects to terminal
White wire from probe
connects to + terminal
SW 1
J3
Attach probe cable shield and/or
drain wire to
rounding lu
AVERTISSEMENT
LA SUBSTITUTIONDE COMPOSANTS
PEUT COMPROMETTRE LA SECURITE
INTRINSEQUE.
consoles\tls50\50prbwir.eps
Figure 14. Connecting Probe Wiring to Console
20
Applying Power to System
TLS-HLD Cold Boot - Initial Power Up
Once all devices are connected to the TLS-HLD Console attach the console power wires to the appropriate power panel
connections. Close the front panel of the console. Switch on the AC power breaker. The system will automatically run a
cold boot self-diagnostic program when you power up the TLS-HLD for the first time:
Test Passed
RAM TEST - OKRAM FAILReplace CPU board
ROM TEST - OKROM FAIL“““
COLD BOOT
EEPROM TEST - OKEEPROM FAIL“““
STARTUP COMPLETE
Following a cold boot, if the probes and console are configured correctly, the display will read:
ALL FUNCTIONS NORMAL
Following a cold boot, if the probes and console are not configured correctly, the display will read:
NO TANKS CONFIGURED
Follow the Setup instructions in the TLS-HLD Setup manual to program the system.
Test Fa iled Action (If Failed)
TLS-HLD Cold Boot - RAM Clear
If the system has previously been setup, a cold boot can be initiated and the system reset (such as for a software upgrade)
as follows:
Move the RAM clear jumper (J3 in Figure 4) off of pins 1 and 2 and onto pins 2 and 3. The display will acknowledge the
RAM clear request with the message: RAM CLEAR, then turn the power Off. Move the jumper back onto pins 1 and 2.
TLS-HLD Warm Boot
Once the system is setup, every time power to the TLS-HLD is switched Off and On, the software will run a selfdiagnostic warm boot program and display the test results:
Test Passed
RAM TEST - OKRAM FAILReplace CPU board
ROM TEST - OKROM FAIL“““
WARM BOOT
STARTUP COMPLETE
If a fault is detected an error message will be displayed and the system will halt. When the warm boot completes the
display returns to the top level status message. Once the Boot Up successfully completes, go to the Setup manual to
program the console.
Test Fa iled Action (If Failed)
21
RS-232 Communications
RS-232 Peripheral Equipment Requirements
Any peripheral equipment connected to an RS-232 serial port must meet the following criteria:
1. Peripheral equipment must be UL listed.
2. The equipment must have an EIA standard RS-232C or RS-232D communications protocol.
3. The equipment must NOT be installed over or in a hazardous location.
RS-232 Connections
TO A DEVICE LESS THAN 50 FEET FROM THE CONSOLE
Veeder-Root recommends that you use a null-modem cable no longer than 50 feet (15 m) for direct connections between
the console and a remote device. Cable runs longer than 50 feet can result in data errors, component damage, or both.
TO A DEVICE MORE THAN 50 FEET FROM THE CONSOLE
If cable runs longer than 50 feet are needed, two short-haul modems should be used, one at the console and one at the
remote device. We recommend an asynchronous short-haul modem, Black Box model ME800A, or equivalent at the
console and at the remote device. For more information, you can contact Black Box at - phone: 1-724-746-5500, fax: 1724-746-0746, or at their Internet address http://www.blackbox.com
Figure 15 illustrates how to connect two short-haul modems between the console RS-232 Interface Module’s or
Auxiliary RS-232 Interface Module’s DB-25 connector and the remote device.
Connections to telephone lines must meet the following criteria:
• Connection to telephone equipment is subject to local regulations.
• Maximum short circuit current: 0 amperes.
• Maximum open circuit voltage: 0 volts.
22
RS-232 CommunicationsSurge Protection for Communication Devices
r
DCE
DB-9
Connector
To
Available
Port
DB-25
Connector
Color 1
Color 1
Color 2
Computer
Color 2
RTS/DTR
CONTROL
DB-25 Connector
EN
DIS
Console
VEEDER-ROOT
TLS
DB-9 Connector
2 Twisted Pairs (24 - 26 AWG)
Height Level Display
DCE
consoles\tlshld\shmodm.eps
Color 1
Color 2
Color 1
Color 2
RTS/DTR
CONTROL
DB-25 Connecto
EN
DIS
S1
DTE
TDRD
Flash red & green
Gnd
TX-
TX +
RX-
RX+
Black Box Model: ME800A
Loopback
Normal
S2
= Required selection
S1
DTE
TD
Flash red & green
TX +
Gnd
TX-
RX-
RX+
RD
S2
Loopback
Normal
Black Box Model: ME800A
Figure 15. Console Connected to a Remote Device Via Short-Haul Modem
Surge Protection for Communication Devices
In locations that are subject to high levels of noise and power surges, the use of a surge protector is recommended. The
following models are available from B&B Electronics, telephone 1-815- 433-5100, or at their Internet address http://
www.bb-elec.com:
• Telephone Line Surge Protector, model TLSP
• RS-232 Surge Protector, model 232DSP
23
RS-232 CommunicationsRestricting System Programming Access
Restricting System Programming Access
To protect against unauthorized access to system operation, two security features can be enabled. These switches are
located on the Power Supply Board next to the power wiring terminals (see Figure 16 below). Consoles are shipped from
the factory with all switches in the open position.
SERIAL SECURITY
Enabling Switch position 1 allows the operator to enter a 6-digit security code before the system will respond to a serial
command. The default serial security code is 000000. The security code itself can be changed with a serial command.
However, the serial security code switch must be reset to the Open position to inhibit the security code requirement.
SETUP SECURITY
A switch in the console can be set to prevent access to the setup and diagnostic menus after initial programming. Closing
or turning on Switch position 4 inhibits use of the setup and diagnostic menus.
COMM
1 2 3 4
Security
OPEN
Security switches
(shown enabled)
SETUP
DIP SWITCH SETTINGS
In Figure 16 above, rocker switches 1 and 4 are shown in the closed (enabled) position. Switch 1 is Communications;
Switch 4 is Setup and Diagnostics. To inhibit a function, press the left side of the switch down to the Open position.
Switch 2 and Switch 3 are not used and can be in any position.
(Switches 2 & 3
are not used)
Setup
consoles\tlshld\dipswitch.eps
Figure 16. Console Dip Switch Settings
RS-232 Serial Communication Setup
• Interface mode type: printer, modem, serial; default serial
• Parity options: None, Odd, or Even; default None
• Data length options: 8 or 7; default 8
• Number of stop bits options: 1 or 2; default 1
• Handshaking options: None, XON/XOFF, or Hardware; default XON/XOFF
• Printer page eject options: Yes or No; default No
• Answer On options: 0 to 9; default 1
24
RS-232 CommunicationsDB-9 Connector Pin-Outs
• Serial Language options: English; default English
• Veeder-Root RS-232 command protocol format. For more information on the command format, consult the Veeder-
Root Serial Interface Manual.
DB-9 Connector Pin-Outs
Communicating with the Console from a remote computer is done through a RS-232 serial port (DB-9 connector) on the
bottom of the console.
Pin layout to connect the Console’s Serial Interface DB-9 connector to a 25-pin computer terminal connector are shown
in Figure 17. These connections are standard for “AT” style modem cables.
6. NN - Number of eight character Data Fields to follow (Hex)
7. FFFFFFFF - Probe Data (ASCII Hex IEEE float)
8. && - Data Termination Flag
9. CCCC - Message Checksum
45
Troubleshooting
This section contains information to help diagnose system problems. The Diagnostic Menu and Report can help
determine if a probe is functioning correctly. The sections describing system boots help determine if the console
hardware is functioning correctly.
A brief section is included that describes how install a software upgrade. Other sections detail CPU and Power Supply
board replacement should the self-diagnostic programs indicate a hardware failure.
At the end of the Troubleshooting section you will find a list of specifications and a chart showing the probes that can be
used with the TLS-HLD Console.
Dual-Function Front Panel Keys
Two of the six front panel keys have dual functions [Figure 18].
1
Back
1
Dual function keys
1
SelectEnter
SilentPrintTank
consoles\tlshld\dkey.eps
Figure 18. Dual-Function Keys
Pressing the Enter key down for an extended period (longer than 2 seconds) will change the system language to the next
available language queued in software. Repeat this procedure until the desired language is displayed.
Pressing the Back key down for at least 2 seconds will change the system setup units. Repeat this procedure until the
desired units are displayed.
A short beep from the console beeper will inform the operator that these keys have been held in long enough to select the
alternate function. When the operator is ready to return to the originally programmed language and/or units, switch the
console power Off and then back On. The system will perform a warm boot and return to the originally programmed
language and units.
Probe Diagnostic Menu
The Diagnostic Menu is accessed from the front panel of the console. Press the Select key until the display reads
DIAGNOSTICS. Table 1 below discusses all of the display messages in the Diagnostic Menu.
Press ↵ key to enter Diagnostics. You can also press the Print key to print
out the Diagnostic Report if you have made the correct comm setup selections and you have a serial printer connected.
Console’s current software version. Note: from this display on, you press
key to move from one display to the next.
Probe type installed in tank (in this example, T1). At any ‘T’ display below,
press the Tank key to view equivalent data for other tanks.
Serial number of the probe.
Manufacturing code of the probe.
Length of the probe.
Probe calibration factor used to calculate water height and product height.
Number of probe measurement sets made before posting water height,
product height, and product temperature. (A measurement set consists of
probe counts 00 - 18 discussed below.)
Historical total of probe measurements read.
→
T1: Samples Used
XXXXXX
T1: Counts
00 XXXXX 01 XXXXX
(Continue to press the
→
key to move through
all of the count pairs until
you reach the last count
below)
T18: Counts
18 XXXXX
Historical total of probe measurements used.
Probe counts used to calculate water height, product height, and product
temperature. Counts 00 - 18 constitute one probe measure set.
47
TroubleshootingProbe Diagnostic Report
Probe Diagnostic Report
The Diagnostic Report example below is a printout of probe information, for all tanks. The probe functions are discussed
in Table 1.
The CPU board in the TLS-HLD must be replaced when:
• A system self-test failure occurs during a warm or cold boot, or
• The display contains garbled messages and/or the voltage between the GND and 8V test points on the back of the
CPU board is within 7 - 9 Vdc; or,
• The voltage between the GND and 5V test points [Figure 19] on the back of the CPU board is not within 4.75 - 5.25
Vdc.
OFF
1. Turn Off power to the system.
48
TroubleshootingReplacing the CPU Board
s
5V
Cable to Power
Supply Board
GND 8V
LED1
These voltage test points are on the back of
the CPU board (directly behind this upper left
corner)
J1
Y2
TLS-50 CPU
consoles\tls50\cpu.ep
PROM chip
+
C5
STATIC SENSITIVE - WEAR
GROUNDED ANIT-STATIC
WRIST STRAP BEFORE
HANDLING THIS BOARD!
U5
Figure 19. CPU Board Voltage Test Points
2. Attach the anti-static strap to your wrist and to a good ground.
3. Disconnect the CPU cable from the Power Supply board.
4. The CPU board snaps securely into place in the door of the console without the use of screws. There are two tabs on
the top of the board that fit into two slots in the top edge of the door. The bottom of the CPU board snaps in place
between two pairs of detents protruding from the bottom edge of the door. The CPU board is removed by inserting a
straight-slot screwdriver into one of the two indents on the bottom of the board and then gently prying against the
door until the board clears the upper detents, then rotating the board up slightly and toward you to clear the top tabs
from the slots in the door.
5. Replace the CPU board reversing the above steps.
6. Follow the instructions in “TLS-HLD Cold Boot - Initial Power Up” on page 21.
The PROM chip is replaced when a software upgrade is installed. This procedure requires that you perform a RAM clear.
1. If possible, record the current setup information. Turn Off power to the system.
2. Open the front door of the console. The CPU board is installed in the door.
3. Attach anti-static strap to your wrist and to a good ground.
4. Disconnect the CPU board cable from the Power Supply board. Remove the CPU board following the instructions in
“Replacing the CPU Board” on page 48.
5. Locate the PROM chip on the board [Figure 19].
6. Remove the PROM chip following instructions in Figure 20.
7. Replace the PROM chip following instructions in Figure 21.
8. Replace the CPU board in the front door of the TLS-HLD. Connect the CPU board cable to J1 on the Power Supply
board.
9. Follow the instructions in “TLS-HLD Cold Boot - Initial Power Up” on page 21.
These voltage test points are on the back of
the CPU board (directly behind this upper left
corner))
J1
PROM chip
socket
consoles\tls50\50cpurm.eps
STATIC SENSITIVE - WEAR
GROUNDED ANIT-STATIC
WRIST STRAP BEFORE
HANDLING THIS BOARD!
+
C5
U5
Y2
1) Orient PROM so that the small indented dot on
top of the chip is on the same side with the small
triangle embossed in the socket's base; or,
2) If the chip is covered with a label you can also orient
the chip correctly if you insert the chip in the socket
with its angled corner in the same angled corner of the
socket.
3) Carefully align the chip's pins with the socket's pins.
(If you have the pins aligned correctly, the chip will seem to
drop into the socket.) Then push down firmly and evenly
on the chip until it snaps into the socket.
4) Check to see that all pins are in place and none are bent.
Figure 21. Replacing PROM Chip
52
TroubleshootingReplacing the Power Supply Board
Replacing the Power Supply Board
The Power Supply board must be replaced when:
• Probe data is not being processed, or
• The voltage between the GND and 8V test points [Figure 19] on the back of the CPU board is less than 7 Vdc.
OFF
1. Turn Off power to the system.
2. Disconnect the CPU cable from the Power Supply board.
3. Tag and disconnect probe and power.
4. The Power Supply board is secured by two T-15 Torx screws in the top of the board. You must also remove the two
screw locks which go through the bottom of the console into the DB-9 connector before you can lift out the board.
After removing the Torx screws (and screw locks), slowly lift up on the board until the lower tabs on the board clear
the slots in the bottom of the console, then continue to lift the board out.
5. Replace the board by reversing the above steps.
6. Turn on power to the system. The system will perform a warm boot procedure [page 21] and the display will return to
the top level status screen. You do not have to reprogram the console after replacing the Power Supply board.
Display Messages
TANK PARAMETERS
The following tank parameters are displayed one at a time as the operator scrolls through the Top Level Menu.
• Product Height,
• Product Temperature (requires probes that have temperature measurement capability),
• Water Height (requires probes that have water measurement capability).
Pressing the Tank key allows the user to select which tank's data is displayed. If a parameter is not available for any tank
in the system, that display will not appear as you scroll through the menus. When viewing a display that is available in
one of the tanks, but is not available for the current tank, a “
NO DATA” message will be displayed for that parameter.
Alarms
When an alarm occurs, the console’s internal beeper will activate (if enabled), the front panel LED will flash red, and the
top line of the display will contain the alarm message. In the case of multiple alarms, the main display screen will
automatically scroll through the active alarms. Press the Silent key to switch Off the internal beeper and acknowledge the
alarm. The red LED will continue to flash until the alarm condition is remedied.
When an alarm condition returns to the normal state the alarm will be removed from the list of alarms. If no alarms are
active, the LED will return to the Normal state (continuous green), the beeper will be switched Off, and the top line of
the display status line will read ALL FUNCTIONS NORMAL.
Displayed Alarm Messages
• PROBE OUT (all probes) - If the console is not reliably communicating with the probe, the Probe Out alarm will
activate.
53
TroubleshootingAlarm Cause/Action Table
• INVALID HEIGHT (only probes that use two floats) - If the water float and the product float are too close together to
provide reliable height data, the Invalid Height alarm will activate.
• LOW TEMPERATURE (only probes with temperature option) - If the Probe is reporting a temperature lower than -4°
F (-19.8° C), the Low Temperature alarm will activate.
• NO TANKS CONFIGURED - This message displays in the top line of the display until at least one tank has been
configured in the Tank Setup menu. The front panel red LED will be flashing, but the console’s internal beeper will
not be switched On.
Alarm Cause/Action Table
Table 2 lists each of the displayed alarms, a possible cause, and a suggested corrective action.
Table 2.- Alarm Index, Cause, and Corrective Action
AlarmCauseAction
PROBE OUT
INVALID HEIGHT
LOW TEMPERATURE
NO TANKS CONFIGURED
If the console is not reliably communicating
with the probe, the Probe Out alarm will activate.
(Only probes that use two floats) - If the water
float and the product float are too close
together to provide reliable height data, the
Invalid Height alarm will activate.
(Only probes with temperature option) - If the
Probe is reporting a temperature lower than 4° F (-19.8° C), the Low Temperature alarm
will activate.
This message displays in the top line of the
display until at least one tank has been configured in the Tank Setup menu. The front panel
red LED will be flashing, but the console’s
internal beeper will not be switched On.
Call for service following the
procedures established for your
site.
Call for delivery.
Probe returns to normal operation after probe temperature
rises above -4°F (-19.8°C).
Configure at least one tank in
Tank Setup.
54
Console Specifications
PHYSICAL SPECIFICATIONS
Width (door closed): 7.6”, open 9.6”) Depth (door closed 2.6”, open 9”))
•
• Height: 6.7” Weight: 3.5 lbs.
• Two PC boards in console: CPU (in door) and Power Supply (in unit)
ENVIRONMENTAL SPECIFICATIONS
Console storage and operation: indoor, climate controlled.
•
ELECTRICAL SPECIFICATIONS
Console operating voltage: 120/240 Vac, 2 A max.
•
• The Power Supply board fuses F1 and F2 are NOT field replaceable The rating for both fuses is 2 A, Type T [Time
Lag].
SIGNAL INPUT SPECIFICATIONS
Up to 6 probes monitored with TLS-HLD
•
• Probe data: 0.15 A at 12 volts
SIGNAL OUTPUT SPECIFICATIONS
One dry contact relay output: 120 Vac, 2 A
•
FRONT PANEL USER INTERFACE
Two line, graphic LCD display
•
• Visible annunciator (bi-color LED)
Green - all functions normal
Flashing red - alarm active
• Push keys
Select
Enter
Print
Back
Silence
Tank
• Audible annunciator: internal beeper
55
Console SpecificationsTLS-HLD Probe Circuit Codes
TLS-HLD Probe Circuit Codes
Table 3 lists the probes that can be used with the console.
Table 3.- Mag Probe Minimum Detected Fluid Levels
2” Floats
Circuit
CodeMag Probe Type
Name
Plate
Color
Water
Detect
Min.
Fuel
Level
Min.
Water
Level
Mag Probes - Form Number 8473
C000Std., 2 floatBlackYes9.5”0.75”
C001Std., 2 floatRedYes9.5”0.75”
D000Std., Inv. only, 2 fltGreenYes9.5”0.75”
D001Alt., 1 floatBlackNo7”—
D002Alt., 1 floatRedNo7”—
D003Alt., Inv. onlyGreenNo7”—
Mag Probes - Form Numbers 8463 & 8493
D004 2 floatBlackYes3.23”.867”
D005 2 floatRedYes3.23”.867”
D006Inv. only, 2 fltGreenYes3.23”.867”
D0071 floatBlackNo3”—
D0081 floatRedNo3”—
D009Inv. only, 1 fltGreenNo3”—
Mag Probes - Form Number 8468
D021Inv. only 2 fltBlueYes3.23”0.867”
D022Inv. only, 2 fltBlueYes3.23”0.867”
D023Inv. only, 1 fltBlueNo3”—
D024Inv. only, 1 fltBlueNo3”—
56
For technical support, sales or
other assistance, please visit:
www.veeder.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.