Veeder-Root TLS-50, TLS-50C Series Manual

TLS-50
Site Prep Manual
Manual No: 577013-608 Revision: N
Notice
Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root.
DAMAGE CLAIMS / LOST EQUIPMENT
Thoroughly examine all components and units as soon as they are received. If any cartons are damaged or missing, write a complete and detailed description of the damage or shortage on the face of the freight bill. The carrier's agent must verify the inspection and sign the description. Refuse only the damaged product, not the entire shipment.
VEEDER-ROOT’S PREFERRED CARRIER
1. Contact VR Customer Service at 800-873-3313 with the specific part numbers and quantities that were missing or received damaged.
2. Fax signed Bill of Lading (BOL) to VR Customer Service at 800-234-5350.
3. VR will file the claim with the carrier and replace the damaged/missing product at no charge to the customer. Customer Service will work with production facility to have the replacement product shipped as soon as possible.
CUSTOMER’S PREFERRED CARRIER
1. It is the customer’s responsibility to file a claim with their carrier.
2. Customer may submit a replacement purchase order. Customer is responsible for all charges and freight associated with replacement order. Customer Service will work with production facility to have the replacement product shipped as soon as possible.
3. If “lost” equipment is delivered at a later date and is not needed, VR will allow a Return to Stock without a restocking fee.
4. VR will NOT be responsible for any compensation when a customer chooses their own carrier.
RETURN SHIPPING
For the parts return procedure, please follow the appropriate instructions in the "General Returned Goods Policy" and "Parts Return" pages in the "Policies and Literature" section of the Veeder-Root North American Environmental Products price list.
©Veeder-Root 2006. All rights reserved
.
ii

Table of Contents

Table of Contents
Introduction
Relat e d Ma n ua l s ............ .. .......... ... .. .......... .. .......... .. ... .......... .. .......... .. ... ......... ... ......... ... ....2
Safety Symbols .................................................................................................................2
Site Considerations
Control Drawing ................................................................................................................3
National Electrical Code Compliance .. .. .......... .. .. .................... .. ...................... .......... .. ......4
Probe-to-Console Wiring..........................................................................................4
Shielded Cable or Veeder-Ro ot Di rect Burial Cable Required ................... .. .4
Wire Length ....................................................................................................4
Splices ...........................................................................................................4
Wire Gauges - Color coded ...........................................................................4
Power Wiring ............................................................................................................4
Probe Ju n c tion Boxes . .......... .. .. .......... ... ......... ... .. .......... .. .......... ... .. .......... .. .......... .. ..4
Probe W ir in g Sa fe t y Is s ue s ....... ... ......... ... .. .......... .. .......... ... .. .......... .. .......... .. ... ......... ... .... 5
Selec ti n g a Con so l e L oc a ti o n ......... .. .......... ... .. .......... .. .......... .. ... .......... .. .......... .. ... ......... ..5
Console Installation
Mounting the Con s o le .............. .. ... ......... ... ......... ... .. .......... ... ......... ... .. .......... .. .......... .. .......7
Wirin g th e Con s o le ...... ......... ... .. .......... .. .......... .. ... .......... .. .......... .. ... ......... ... .......... .. .. ....... 9
Probe Installation
Probe M a n ho le In s ta ll at i o n ........ ... .. .......... .. .......... .. .......... ... .. .......... .. .......... .. ... ......... ... ..10
Determining Mag Probe Length for Installation in a Dedicated Riser ............................ .10
Probe In stallatio n ......... .. .......... .. ... ......... ... ......... ... .......... .. ... ......... ... ......... ... .. .......... .. ..... 10
Spec ia l In s tru c ti o ns fo r U S T ’s wit h Meta l Ris e r C a ps ..... .......... ... ......... ... .. .......... ..12
Installing Field Wiring from Probes to TLS-50 Console ..................................................13
Buried Rigid Conduit .......................................................................................................13
Sealing Field Connections......................................................................................14
Direct Burial Cable - Probe to Console Field Wiring .......................................................15
Direc t B ur ia l C a bl e Fie ld Wiring..... .......... .. .......... ... .. .......... .. .......... .. ... .......... .. .......15
Connecting Probes to the Consol e ................... .......... .. .......... .. .......... .................... .. ......16
Precautions To Follow When Connecting Probes to TLS-50 Console ...........................16
Input/Output Wiring Positions and Label ing .................................... .......... .......... ...16
Wirin g A ssignments ..... .. .......... ... ......... ... .. .......... .. .......... ... ......... ... .. .......... ..16
Grounding Probe Shields and Drain Wires ..................................................17
Connecting Probes to the Consol e - Observe Polarity......................... .. .......... .. ....17
Syste m S et u p S e curity ............ ......... ... .......... .. .. .......... ... ......... ... .. .......... .. .......... ... .. .......18
Overfill Alarm Relay ........................................................................................................18
Applyi ng Po wer to Sys tem
Cold Boot - Initial Power Up (Consoles w/Display) .........................................................20
Cold Boot - Initial Power Up (Consoles w/o Display) ......................................................20
Cold Boot - RAM Clear ...................................................................................................20
Cons o le s with Display ....... ... .. .......... .. .......... .. ... .......... .. .......... .. ... ......... ... ......... ... ..20
Cons o le s Wi th o ut Di sp la y .. .......... .. .......... .. ... .......... .. .......... .. ... ......... ... .......... .. .. ..... 2 0
Warm B oo t .............. .. .......... .. ... ......... ... .......... .. .. .......... ... ......... ... .. .......... .. .......... ... .. .......21
Cons o le s with Display ....... ... .. .......... .. .......... .. ... .......... .. .......... .. ... ......... ... ......... ... ..21
Cons o le s without Disp la y ....... .. ... .......... .. .......... .. ... ......... ... .......... .. .. .......... ... .........21
iii
Table of Contents
RS-232 Communications
RS-232 Peripheral Equipment Requirements .................................................................22
RS-2 3 2 Co nn e c ti on s . .......... .. .......... .. ... .......... .. .......... .. ... ......... ... .......... .. .. .......... ... .........22
To a Devi ce Less Than 50 Feet fro m th e Con so l e... ... .. .......... .. .......... .. ... ......... ... ..22
To a Device More Than 50 Feet from the Console........................... .......... .......... .22
Surge P ro te c tion for Com mu n ication Dev ic e s ...... .. .......... ... .. .......... .. .......... .. ... ......... ... ..23
Syste m S er ia l S e cu r ity ..... ... .......... .. .. .......... ... ......... ... .. .......... .. .......... ... ......... ... .. .......... ..24
RS-2 3 2 Se ria l C o m mu n ic a tio n Se t up .... ... .. .......... .. .......... ... .. .......... .. .......... .. ... ......... ... ..24
DB-9 Connector Pin-Outs ......... .. ............ ............ ...................... .................................. ....25
RS-232 Commands
Function Code: 001 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....27
Function Code: 003 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....28
Function Code: 201 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....29
Function Code: 205 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....30
Function Code: 504 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....31
Function Code: 50C ........................... .............................. .. .............................. .. .. .......... .32
Function Code: 50D ........................... .............................. .. .............................. .. .. .......... .33
Function Code: 50E .................... ............ .......... .. .......... ............ .......... .................... .. .. ....34
Function Code: 517 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....35
Function Code: 601 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....36
Function Code: 604 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....37
Function Code: 605 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....38
Function Code: 606 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....39
Function Code: 607 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....40
Function Code: 608 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....41
Function Code: 609 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....42
Function Code: 60A .................... ............ .......... .. .......... ............ .......... .................... .. .. ....43
Function Code: 621 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....44
Function Code: 624 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....45
Function Code: 628 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....46
Function Code: 638 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....47
Function Code: 881 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....48
Function Code: 882 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....49
Function Code: 883 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....50
Function Code: 884 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....51
Function Code: 902 ....................... .......... .. .......... .......... .. .......... .......... ..................... .. ....52
Function Code: A01 .................... .................... .. .......... .. .......... .. .......... .................... .. ......53
Function Code: A02 .................... .................... .. .......... .. .......... .. .......... .................... .. ......54
Function Code: A10 .................... .................... .. .......... .. .......... .. .......... .................... .. ......55
Function Code: A11 .................... .................... .. .......... .. .......... .. .......... .................... .. ......56
Function Code: A12 .................... .................... .. .......... .. .......... .. .......... .................... .. ......57
Troubleshooting
Dual-Function Front Panel Keys (consoles w/Keypads Only) ........................................58
Probe Troubleshooting ...................................................................................................58
consoles w/o Disp la y.............. .. ... .......... .. .......... .. ... ......... ... .......... .. .......... .. ... .........58
Cons o le s w/D i sp lay......... .. .......... .. ... ......... ... .......... .. ... ......... ... ......... ... .. .......... .. ..... 5 8
Probe D ia g no s ti c R e p or t ........ ......... ... .. .......... ... ......... ... .. .......... .. .......... .. ... ..61
Replacing the CPU Board ...............................................................................................61
PROM Chip Replacement (Software Upgrade) ..............................................................63
Replacing the Power Supply Boar d ........ .......... .. .................... .. .......... ............ .......... .. ....66
iv
Table of Contents

Figures

Console Specifications
Physical Specifications...........................................................................................67
Environmental Specifications .................................................................................67
Elect ric a l S p ec if ic a tio n s............ ... .. .......... .. .......... ... .. .......... .. .......... .. ... .......... .. .......67
Signal Input Specifications .....................................................................................67
Signa l Ou tp u t S p ec if ic a tio n s ........ .. .......... .. ... .......... .. .......... .. ... ......... ... .......... .. .. .....67
Front Panel User Interface (Consoles w/ Display)......... .......... .. .......... .. .......... .. ......67
Probe Circuit Codes ........................................................................................................68
Appendix A: TLS-50 and TLS-50C Safety Instructions ...................... A-1
Figure 1. Locating the console form number.............................................................1
Figure 2. Control Drawing - Example TLS-50 System Site Layout............................3
Figure 3. Re com m ended Mounting of Console............................................... .. ........7
Figure 4. Co nsole Dimensions and Designated Conduit Knockouts............... .. ........8
Figure 5. Wiring AC Power to the Console................................................................9
Figure 6. Determining the Minimum Mag Probe Length. .........................................10
Figure 7. TLS-50 Probe Installat ion Example - Underground Stor age Tank...........11
Figure 8. TLS-50 Probe Installat ion Example - Above ground Storage Tank..........11
Figure 9. Installing the Riser Adapter ......................................................................12
Figure 10. Example Probe Wiring Run in Buried Rigid Conduit................. .. .. ...........13
Figure 11. Probe Field Wiring Connection.................................................................14
Figure 12. Epoxy Sealing Connections.............. .......... .......... .. .......... .. .......... ...........14
Figure 13. Example Probe Wiring Run via Direct Burial Cable................................ .15
Figure 14. Probe Installation Directory......................................................................17
Figure 15. Connecting Prob e Wiring to Console .......... .. .......... .. .. .......... .. .......... .. ....17
Figure 16. DIP switch 4 in closed posi tion to enable menu lockout.............. .......... ...18
Figure 17. Connecting I/O Devices to Console........................ .......... .. .................... .19
Figure 18. Console Connected to a Remote Device via Short-Haul Modem ............23
Figure 19. Console Dip Switch Settings....................................................................24
Figure 20. DB9, RS-232 Pin-Outs .............................................................................25
Figure 21. Dual-Function Keys..................................................................................58
Figure 22. Diagnos tic Menu - Over v ie w ..... .. ... .......... .. .......... .. ... ......... ... .......... .. .......59
Figure 23. Diagnos tic Menu - Explanation ......... ... .......... .. .. .......... ... ......... ... .. .......... ..60
Figure 24. CPU Board Voltage Test Point s (Keypad/Display vers ion shown).......... .62
Figure 25. Removing PROM Chip.............................................................................64
Figure 26. Replacing PROM Chip (Keyp ad/Display version shown).........................65
v

Introduction

Label on top of console
This manual describes the site preparation and console installation procedures for all TLS-50 Monitoring Systems. Except where noted, the procedures described herein apply to all consoles. TLS-50 is used throughout Table 1 lists the various TLS-50 consoles and options by form number. Figure 1 shows where on the top of the console you can find the information about your console’s form number.
Table 1.- TLS-50 Consoles and Features
Console Form No. Console T ype
8469X0-060 TLS-50 w/keypad and display, up to 6 probes 8469X0-160 TLS-50 w/keypad and display, w/relay, up to 6 probes 8469X0-260 TLS-50 w/keypad and display, w/com and relay, up to 6 probes 8469X0-230 TLS-50C w/o keypad or display, w/com, up to 3 probes 8469X0-460 TLS-50 w/o keypad or display, w/com and relay, up to 6 probes
MANUFACTURED BY: VEEDER-ROOT, 125 POWDER FOREST DR. SIMSBURY, CT. 06070 U.S.A.
FORM NO.: 846960-XX0 SERIAL NO.: XXXXXXXXXXXXXX
consoles\formlabel.eps
Console Form No.
Figure 1. Locating the console form number
This manual assumes that you installing the monitoring system in a new site (before pavement is put down and with no wiring runs in place). Some of the topics covered in this manual are listed below.
Laying out the site
Mounting the console and connecting power wiring
Assembling and installing probes
Installing wiring conduit between the console and probes
Field wiring probes
Connecting probes to the console
RS-232 serial communication connection requirements and available serial commands (consoles with com option)
Troubleshooting information
1
Introduction Related Manuals
TLS-50 system specifications
After the console is wired to its power source and probes, you should program the console following the setup instructions contained in the TLS-50 Setup & Operation Manual.

Related Manuals

577013-609 TLS-50 Setup & Operation Manual
576013-635 RS-232 Serial Interface Manual
576013-859 Direct Burial Cable Installation Manual
577013-744 Mag Plus Probe Assembly Guide

Safety Symbols

The following safety symbols are used in this manual to alert you to important safety hazards and precautions.
EXPLOSIVE
Fuels and their vapors are extremely explosive if ignited.
ELECTRICITY
High voltage exists in, and is supplied to, the device. A potential shock haz­ard exists.
INJURY
Careless or imp roper handling of materi als can resul t in bo di ly injury.
WEAR EYE PROTECTION
Fuel spray from residual pressure in the lines can cause serious eye inju­ries. Always wear eye protection.
WARNING
Heed the adjacent inst ructions to av oi d equ ip me nt d amage or pe rson al injury.
FLAMMABLE
Fuels and their vapors are extremely flammable.
TURN POWER OFF
OFF
Live power to a device creates a potential shock hazard. Turn Off power to the device and associated accessories when servicing the uni t.
GLOVES
Wear gloves to protect hands from irritation or injury.
READ ALL RELATED MANUALS
Knowledge of all rel ated procedures before you begi n wo rk is impor t an t . Read and understand all manuals thoroughly. If you do not underst an d a procedure, ask someone who does.
STATIC SENSITIVE COMPONENTS
Handling static se ns itive electr o nic components without grounding your body can subject them to damaging voltage po tentials.
2

Site Considerations

g

Control Drawing

Double Wall Tank
MP
MP
I.S.
Circuit breaker panel or Fused, switched, neon indication spur
120 or 240 Vac
12 AWG barrier
ground wire
I.S.
NOTE: Intrinsically safe wiring (marked ) shall be installed in accordance with Article 504-20 of the NEC, ANSI/NFPA 70.
Note: conduit requirements are dependent on local electrical regulations. For probe-to-console wiring, shielded cable is required regardless of conduit requirements.
WARNING: Substitution of components may impair intrinsic safety.
Circuitry within the TLS-50 Console barrier forms an intrinsically safe, energy-limited system. This system makes TLS-50 probes safe for use in a Class I, Group D hazardous location. TLS-50 probe wiring is intrinsically safe only when connected to Veeder-Root's TLS-50 Consoles. Reference Form Number 8469 (TLS-50/TLS-50C Consoles) and Form Number
8462, 8463, 8468, and 8473 (Probes).
I.S.
Non-Hazardous
Area
ALL FUNCTIONS NORMAL
PA
T1 VOL: 9889 GAL
Hazardous
Area
TLS-50
Single Wall Tank
MP
le Wall Tank
Sin
DP
DISPENSERS
Hazardous Area
LEGEND
Magnetostrictive Probe
MP
Expoxy Sealed Connection in a Weatherproof Junction Box
Seal-Off
Terminal Connection
1/2'' (12.7 mm) Rigid Conduit
IS
Conduit Enters Console in an Intrinsically Safe Area Knockout
PA
Conduit Enters Console in a Power Area Knockout
Product piping
consoles\50sysdia.eps
Figure 2. Control Drawing - Example TLS-50 System Site Layout
3
Site Consid era tion s National Electrical Code Compliance

National Electrical Code Compliance

The following information is for general reference and is not intended to replace recommended National Electric Code (NEC) procedures. It is important for the installer to understand that electrical equipment and wiring located in Class I, Division 1 and 2 installations shall comply with the latest appropriate articles found in the National Electric Code (NFPA 70) and the Automotive and Marine Service Station Code (NFPA 30A), or other local code such as the CEC, Canadian Electrical Code.

PROBE-TO-CONSOLE WIRING

Shielded Cable or Veeder-Root Direct Burial Cable Required
To ensure the best operating systems available, Veeder-Root REQUIRES the use of shielded cable for all probes regardless of conduit material or application. In these installations, shielded cable must be rated less than 100 pF/ foot (100 pF/304 mm) and be manufactured with a material suitable for the environment, such as Carol or Belden
88760, 876 0, o r 8770.
Note: Throughout this manual, when mentioning any cable being used for probe-to-console wiring, it will be referring to shielded cable.
Wire Length
Improper system operation could result in undetected potential environmental and health hazards if the probe-to­console wire runs exceed 1000 feet (304 m). Wire runs must be less than 1000 feet to meet intrinsic safety requirements.
C2534
Splices
Veeder-Root recommends that no splices be made in the wire run between a probe junction box and the console. Each splice degrades signal strength and could result in poor system performance.
Wire Gauges - Color coded
Shielded cable must be used in all installations. Probe-to-console wires should be #14 - #18 AWG (2.5 to 0.8
2
) stranded copper wire and installed as a Class 1 circuit. As an alternate method when approved by the
mm local authority having jurisdiction, #22 AWG (>0.3 mm
2
) wires such as Belden 88761 may be suitable in
installations with the following provisions:
- Wire run is less than 750 feet (228 m)
- Capacitance does not exceed 100 pF/foot (100 pF/304 mm)
μ
- Inductance does not exceed 0.2
Total cable length per installation: 22,000 feet (6700 m).
H/foot (0.2 μH/304 mm)

POWER WIRING

2
Wires carrying 120 or 240 Vac from the power panel to the console should be #14 AWG (2.5 mm for line, neutral and chassis ground (3); and #12 AWG (4 mm
2
) copper wire for barrier ground (1).
) copper wire

PROBE JUNCTION BOXES

Weatherproof electrical junction boxes with a gasketed cover are required on the end of each probe conduit run at the manhole location. Gasketing or sealing compound must be used at each entry to the junction box to ensure a waterproof junction. The interior volume of each junction box must be a minimum of 16 cubic inches (262 cm
3
).
Veeder-Root recommends the following junction box or equivalent:
Appleton Electric Co. - JBDX junction box, JBK-B cover, and JB-GK-V gasket.
Crouse-Hinds Co. - GRFX-139 junction box, GRF-10 cover, and GASK-643 gasket.
4
Site Consid era tion s Probe Wi ring Safety Issues

Probe Wiring Safety Issues

WARNING
Probes operate in area s wher e flammabl e li quid s and ex plos ive v apors may be
present.
Improper installation may result in fire or explosion causing serious injury or
death.
Practice the following:
1. Read thoroughly and f ollow the instructions shipped with each probe.
2. Probe wiring must enter the consol e only thr ough their designated areas.
3. Power wires and condui t must not enter the intrinsically safe compartment of the console.
4. Substitution of components may impair intrinsi c safety.
Wiring between the console and the probes is of limited electrical power so that there is insufficient energy to ignite fuel. In the console, the low power probe wiring is considered intrinsically safe because it is physically isolated from all high power wiring. To maintain the integrity of this safety feature probe wiring can not share the same conduit with power wiring. In addition, probe cables can only enter the console through the designated intrinsically safe area knockouts.
If the TLS-50 System is being retrofitted into a paved site, you can cut grooves in the pavement, run direct burial cable to the probes, and then seal over the cable grooves, subject to approval of the local authority having jurisdiction.
Before trenching, you should diagram all conduit runs between the console’s intended location and its deployed probes. Your site diagram will help you calculate conduit and wiring lengths, and necessary quantities of junction boxes, sealing boxes, clamps, brackets, etc.
Throughout this planning process and in the actual installation, you must follow all latest National Electric Codes, and applicable federal, state, and local codes as regards conduit type, depth below grade, sealing, grounding, wire capacities, direct burial (if permitted), etc.

Selecting a Console Location

WARNING
Explosive vapors or flammable liquid s could be pre sent near locations where fuels are stored or being dispensed. The TLS-50 Console is not explosion proof.
An explosion or fire resulting in serious injury or death, property loss and equipment damage could occur if the console is installed in a volatile, combustible or explosive atmosphere (Class I, Division 1 or 2).
Do not install this c onsole in a v olatile, comb ustib le, or e xplosiv e atmosph ere.
5
Site Consid era tion s Selecting a Console Location
Select a mounting location on the inside of any building. The console must be protected from severe vibration, extremes in temperature and humidity, rain, and other conditions that could harm computerized electronic equipment.
The equipment is designed to operate safely under the following range of conditions:
Temperature range 0 to 40°C - ( storage temperature range of -40 to +74°C).
A maximum relative humidity of 95% RH (non-condensing) at temperatures up to 40°C.
Console may be powered by either 120 or 240 Vac. A switchmode power supply automatically detects the input voltage (no jumpers required).
Main supply voltage fluctuations not exceeding ±10%.
Pollution Degree Category 2.
Installation Category II.
Important! Consoles must be installed within the interior of buildings. They are not suitable for any external location.
Ensure that the console is located where neither the console nor its associated cabling will be damaged by doors, furniture, barrows, etc. Consider the ease of routing wiring, ducting, and probe cables to the console. Check that the mounting surface is strong enough to support the console’s weight of about 4 pounds.
Important! If the unit requires cleaning, do not use any liquids, wipe only with a clean, dry cloth.
6

Console Installation

consoles\tls-50\50mnt.eps
T O s f m d

Mounting the Console

Figure 3 illustrates recommended console mounting. Install the console fastening devices to the mounting surface using the hole pattern (6.7” x 5.7”) shown in Figure 4. Mounting screws up to 3/16” diameter may be used.
Install metal conduit (1/2” I.P.S.) between the console and the power panel. Figure 4 shows the three designated knockouts (one each on top, left side, and bottom) through which power wiring can safely enter the console.
1000 mm
(Maximum)
ALL FUNCTIONS NORMAL T1 VOL: 9889 GAL
TLS-50
o an external alarm (i.e., Forecourt Alarm)-
ne 2 ampere fused, switched, neon indication
pur or a dedicated circuit breaker rated
or 120 Vac or 240 Vac. NOTE, circuit breaker
ust be marked as the external alarm
isconnect for the console.
One 5 ampere fused, switched, neon indication spur (for 240 Vac), or a dedicated circuit breaker rated for 15 amperes, 120 Vac or 240 Vac. NOTE, circuit breaker must be marked as the power disconnect for the console.
From an independent 24 hour supply at the distribution panel, run three 2.5 mm (minimum) standard color coded wires; live, neutral, and earth, to the fused spur. Run one 4 mm wire, color coded green/yellow, from the earth bus bar at the distribution panel direct to the console location. Leave at least 1 metre of free cable for connection to the console.
Communication cable
1000 mm
(Maximum)
1500 mm
(Maximum)
Conduit for probe field cables
Figure 3. Recommended Mounting of Consol e
7
Console Installation Moun tin g the Co ns ol e
)
5.3''
(
(30 mm)
0.7'' 17,8)
consoles\tls50dimen.eps
6.4''
(163 mm)
0.93''
(23,6 mm)
0.93''
(23,6 mm)
0.34''
(8,6 mm) typ.
5.7''
(145 mm)
(135 mm)
7.4"
(188 mm)
6.7"
(170 mm)
2.6'' (66)
0.22'' (5,6 mm) dia. console mounting holes (4 places)
0.93''
(24 mm)
1/2-inch IPS and .56 inch (22 & 14 mm) Power wiring only - conduit knockouts (4 places)
1.25''
(32 mm)
3.75"
(95mm)
1/2, 3/4, & 1 inch IPS (22, 28, & 35 mm) Intrinsically safe wiring only - conduit knockouts (2 places)
0.93''
0.4''
(10 mm)
(24 mm)
1.18''
2" (51 mm
Figure 4. Console Dimensions and Designated Conduit Knockouts
8
Console Installation Wiring the Console
A t
A w

Wiring the Console

WARNING
The console contains voltages which can be letha l. It is connected to devices that must be intrinsically safe.
Connecting power wires to a live circuit can cause electrical shock that may resul t in serious inju r y o r dea th.
OFF
1. Turn power off at the circuit breaker connecting the power supply wires.
2. Attach conduit from the power panel to the console's Power Area knockouts only (1 on top and bottom, ref. Figure 4).
1. Pull four wires between the power panel and the console; three #14 AWG color-coded wires for AC line (L), AC neutral (N) and chassis ground; and one #12 AWG (4 mm
2
) green and yellow wire for barrier ground.
For international applications using 240 Vac, pull four wires between the power panel and a 5 A fused, switched, neon indication spur; three #14 AWG color-coded wires for AC line (L), AC neutral (N) and chassis
2
ground; and one #12 AWG (4 mm
) green and yellow wire for barrier ground. Pull four identical wires be-
tween the spur and the console.
2. Open the right door of the console and connect the four power/ground wires as shown in [Figure 5]. Do not connect the power wires to breaker panel at this time.
L2 L4
WARNING!
ttach neutral wire to top
erminal ("N") of J4
CONSOLE
POWER
RELAY RATING
120/240 VAC
2 A MAX
Attach hot wire to bottom terminal ("L") of J4
ttach chassis ground ire to ground lug
N
J4
C24 C27
L
J5
1234
OPEN
SW1
SEC
SETUP
J3
POWER WIRING NOTES:
1. Barrier ground must be #12 AWG (4 mm or larger diameter.
2. Check to be sure that the electrical resistance between the console ground lug and a known good earth ground is less than 1 ohm.
3. Connect the power supply wires in the power panel to a separate dedicated circuit.
4. Electrical rating power input -- 120 Vac or 240 Vac, 50/60 Hz, 2 A maximum.
5. See the "Console Dimensions and Designated Conduit Knockouts" figure for actual locations of power conduit knockouts into the console. Power wiring must enter only in Power Area conduit knockouts.
Protective Earthing Conductor (Green and Yellow) Attach #12AWG
2
(4 mm
) barrier ground
wire to ground lug
Shock hazard. Do not touch metal ends of capacitors C24/C27 or the metal bands on chokes L2/L4.
2
)
WARNING
SUBSTITUTION OF COMPONENTS
MAY IMPAIR INTRINSIC SAFETY.
NO REPAIRS SHOULD BE ATTEMPTED.
REFER SERVICING TO QUALIFIED
PERSONNEL ONLY.
PROBE 6
PROBE 5
PROBE 4
PROBE 3
PROBE 2
PROBE 1
AVERTISSEMENT
LA SUBSTITUTION DE COMPOSANTS
PEUT COMPROMETTRE LA SECURITE
INTRINSEQUE.
+
+
+
+
+
+
consoles\tls50\50powr.eps
Power Side
Intrinsically Safe Side
Figure 5. Wiring AC Power to the Console
9

Probe Installation

Probe Manhole Installation

At each underground probe location, install a 14-inch (355 mm) minimum diameter approved manhole according to the manufacturer’s instructions (Note: probes should be located at least 24 inches (610 mm) from the submersible pump to avoid erroneous probe readings when the pump is running). Position the manhole so that there is necessary clearance for junction box installation and wiring.

Determining Mag Probe Length for Installation in a Dedicated Riser

1. Measure the distance from the bottom of the tank to the top of the probe manway - this is the minimum probe length (ref. Figure 6).
2. The probe canister must be within the riser pipe (minimum length of 10 inches [254mm]).
3" (76mm) min. clearance from top of canister to top of riser
10" (254mm) minimum
riser length Probe canister must be within riser pipe
Manway cover
STP manway
Tank
probes\probemeasurement.eps
24" ( 610 mm) min.
Top of probe manway
Minimum
Probe length
Figure 6. Determining the Minimum Mag Probe Length

Probe Installation

1. Turn OFF power to the console.
2. Remove any sludge from the bottom of the tank.
3. Check that floats, boot, and cable are assembled correctly on probe (ref. Mag Probe Assembly Manual).
4. Gently slide the float(s) to the bottom of the probe shaft before raising the probe. Carefully lower the probe into the riser pipe until the boot rests on the bottom of the tank [See Figure 7 for UST installation or Figure 8 for AST installation].
10
Probe Installation Probe Installation
e
CAUTION! Handle probes carefully. Striking or dropping the probe will result in loss of calibration and could cause permanent damage.
14'' min. dia. manhole
Riser cap with cord grip bushing and nut
Concrete slab or packed earth per NFPA 80
A = 14" minimum for global mag plus/mag plus probes. When installing a probe longer than the the tank diameter, increase this minimum dimension to compensate. (Example: a 7'-6'' diameter tank will use an 8' probe, in which case you must add 6" to minimum riser length 'A', i.e., 20").
Use bushing and body of grip fitting supplied with probe and Adaptor nut supplied with AST kit.
Riser pipe: 2-, 3-, or 4'' API schedule 40 - depending on probe type
A = 14" minimum for global mag plus/mag plus probes. When installing a probe longer than the the tank diameter, increase this minimum dimension to compensate. (Example: a 7'-6'' diameter tank will use an 8' probe, in which case you must add 6" to minimum riser length 'A', i.e., 20").
.
.
.
.
.
.
.
.
.
.
.
..
.
Tank
Mag Probe (rests on bottom)
Probe cable
Weatherproof junction box with 1/2" NPT threads (16 cubic inch minimum)
Cord grip seals
.
.
.
.
.
.
.
.
.
.
.
..
.
Seal-off, epoxy seal per NFPA spec
A
1/2" Rigid conduit (to Console)
Riser pipe: 2-, 3-, or 4'' API schedule 40 depending on probe type (To prevent erroneous probe readings, install probe riser a minimum of 24'' from the submersibl pump.)
Split-Ring Collar (P/N 576008-617) required if probe enters the riser.
Top view
3/4" ID
Side view
probes\pbinstcen.eps
Figure 7. TLS-50 Probe Installation Example - Underground Storage Tank
Flexible metal conduit supplied with AST kit
Liquidtight fittings from AST kit
Weatherproof junction box with 1/2" NPT threads (16 cubic inch minimum)
Epoxy seal per NFPA specs
A
Split-Ring Collar (P/N 576008-617) required if probe enters the riser.
Top view
3/4" ID
Side view
Rigid conduit
probes\astpbins.eps
Mag Probe (rests on bottom)
Figure 8. TLS-50 Probe Installation Example - Above ground Storage Tank
11
Probe Installation Probe Installation
A

SPECIAL INSTRUCTIONS FOR UST’S WITH METAL RISER CAPS

If you are installing the metal cap and adapter ring, screw the ring onto the 4” riser until the gasket contacts the pipe, then use a pipe wrench to tighten it an additional 3/4 turn. Push the cable through the metal cap and cord grip, then clamp the cap onto the ring.
At sites that require installation of a riser adaptor (Phil-Tite M/F 4X4 or equivalent) at the top of the riser, do so following the manufacturer’s instructions. Next screw the adapter ring from the Veeder-Root kit (
P/N 312020-952)
onto the riser adaptor by hand until the gasket contacts the sealing surface. Then use a torque wrench attached to an appropriate strap wrench (K-D Specialty tools nylon strap oil filter wrench, or equivalent) and tighten the ring to 35 - 45 ft-lbs. Loosen the cord grip nut and push the cable through the metal cap and cord grip, then clamp the cap onto the ring (see Figure 9).
Make sure there is a minimal amount of slack between the probe and cap, then tighten the cord grip nut until the cable is held firmly. Push the end of the cable through the field J-box cord grip, then tighten that cord grip nut as well. Splice and seal the wires in the J-box as shown in Figure 12.
.
.
.
.
.
.
.
.
.
..
Metal cap from kit
dapter ring from kit
Riser adaptor (Phil-Tite M/F4X4, or equivalent)
probes\riseradapt.eps
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
Tank
Figure 9. Installing the Riser Adapter
12
Probe Installation Installing Field Wiring from Probes to TLS-50 Console

Installing Field Wiring from Probes to TLS-50 Console

Two wiring run methods are commonly used for probes - Shielded wiring pulled through buried, sealed 1/2” rigid conduit (discussed in the following paragraphs); or direct burial cable (discussed on page 15).
WARNING
Probes operate in areas where flammable liquids and explosive vapors may be present. Improper inst all atio n may res ult in fir e or explo si on causi ng se rious injury or death. Practice the f ollowing:
1. Read thoroughly and follow the instructions shipped with each probe.
2. Probe wiring conduit must not contain any other wires.
3. Probe wiring and conduits must enter the console only through their designated areas ( se e Figure 4).
4. Power and communication wires and conduit must not enter the intrinsically safe compartment of the conso le. (see Fi gure 4).

Buried Rigid Conduit

The preferred method, especially in new sites before driveway surfaces are paved, is to pull probe wiring through buried 1/2” rigid conduit [Figure 10].
Weatherproof junction box with 1/2-inch N.P.T. threads (16 cubic inch
Splice Closure
Seal-Off
minimum)
Cord grip seals
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
..
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
. .
.
.
.
..
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Epoxy seal per NFPA spec
1/2'' rigid conduit (to console)
Tank
probes\pconduit.eps
Figure 10. Example Probe Wiring Run in Buried Rigid Conduit
Pull shielded cable consisting of two conductors, color-coded #14-18 AWG stranded copper wire, between the console and the junction box at each
probe location (do not gang wires together). Use single lengths of wire with
no splices to ensure optimum signal strength.
IMPORTANT! Maximum probe-to-console cable length is 1000 feet (305m).
Since wires for multiple probes may enter the console through a single conduit, it is recommended that you use a different color-code for each wire or individually mark each wire to identify probe inputs. Also, if the intrinsically safe wires enter the building in a wiring trough, only intrinsically safe wires (from TLS-50/-50C probes) can be in the trough. Keep all low power (intrinsically safe) wiring physically isolated from high power wires in all wiring troughs per the NEC.
13
Probe Installation Buried Rigid Conduit
e
p

SEALING FIELD CONNECTIONS

1. Pull the wires from the probe canister into the junction box. Pull two wires from the console through the seal-off box and into the junction box.
2. Using wire nuts, connect the two wires from the probe to the two wires coming from the console. Be sure to observe color codes or tags when making these connections. Figure 11 diagrams a typical probe field wiring connection in the junction box.
3. Do NOT terminate drain wire at this location, ground drain wire at console only.
4. Seal wire nuts with epoxy sealant using one bag for two-wire nut connections (Figure 12).
5. Push the tie-wrapped, epoxy sealed bag into the junction box. Replace and tighten the junction box cover.
Do not ground drain wire in junction box
To
PROBE
Terminal
Seal-off
Block In Console
1/2'' rigid conduit
robes\3mpwir.eps
Epoxy sealed connections in a
weatherproof junction box
ACB
Instructions:
NOTE: When temperature is below 50˚F (10˚C), keep
resin in a warm place prior to mixing (e.g., in an inside pocket next to body).
1. Open epoxy sealant package, and remove resin pak.
2. Holding resin pak as shown in A, bend pak along long length.
3. As shown in B, firmly squeeze the RED SIDE of the resin, forcing it through the center seal and into BLACK SIDE.
Black
From
Prob
White
Figure 11. Probe Field Wiring Connection
From probe, sensor, or transducer
Make sure that the ends of cable sheathing are sub­merged in sealant
4. Mix thoroughly to a uniform color by squeezing contents back and forth 25-30 times.
5. Squeeze mixed, warm resin into one end of bag and cutoff other end.
6. Slowly insert wiring connections into sealing pack until they fit snugly against the opposite end as shown in C.
7. Twist open end of bag and use tie wrap to close it off and position the tie wrapped end up until the resin jells.
To console
Tie wrap
Wire nuts
CAUTION: Epoxy sealant is irritating to eyes, respiratory system, and skin. Can cause allergic skin reaction. Contains: epoxy resin and Cycloaliphatic epoxycarboxylate.
Precautions: Wear suitable protective clothing, gloves, eye, and face protection. Use only in well ventilated areas. Wash thoroughly before eating, drinking, or smoking.
consoles\epxy2w.eps
Figure 12. Epoxy Sealing Conn ect ion s
14
Probe Installation Direct Burial Cable - Probe to Console Field Wiring
G
n.

Direct Burial Cable - Probe to Console Field Wiring

An alternative to trenching through existing pavement is to use direct burial cable.
IMPORTANT! Maximum probe-to-console cable length is 1000 feet (305m).
Prior to installing direct burial cable with epoxy splices, consult with the local authority having jurisdiction. Use of direct burial cable is only allowed in locations where local codes permit the use of buried cable.
The direct burial method requires grinding a 1/4” to 3/8” wide by 1-1/4” deep groove (adding 1/4” of depth for each additional cable) in the pavement surface, laying Veeder-Root supplied direct burial cable down in the bottom of the groove, laying an expanded polyethylene foam backer rod over the cable(s), and then a placing a 1/4” to 1/ 2” bead of Veeder-Root recommended silicone sealant over the backer rod to within a minimum of 3/8” below the pavement surface [see Figure 13].
If you decide to use the direct burial method, you should order the Veeder-Root Direct Burial Cable Preparation Kit, P/N 848100-500.
Splice closure
Cord grip
rade
. .
.
..
Epoxy filled splice enclosure
Drill oversized hole in manhole for cable
890-SL silicone sealant
SOF ROD backer rod
1
2
Direct burial cable
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
CONCRETE
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
. .
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
...
Seal-off
Rigid conduit
3'' Mi
ASPHALT
EARTH
1
Dow Corning Silicone Pavement Sealant
2
Expanded polyethylene foam rod - trademark of Applied-Extrusion Technologies.
probes\pdburial.eps
Figure 13. Example Probe Wiring Run via Direct Burial Cable

DIRECT BURIAL CABLE FIELD WIRING

When using direct burial cable for probe-to-console wiring runs, the wiring connections are the same as shown in Figure 11 on page 14, but the sealing materials and procedure is completely different. If you are using Direct Burial Cable you seal the field wiring connections as instructed in the Direct Burial Cable Installation Manual.
15
Probe Installation Connecting Probes to the Console

Connecting Probes to the Console

WARNING
The equipment is used in location where lethal voltages and explosive vapors or flammable fuels may be present.
Care must be taken when installing, servicing or replacing part s in the syst em or serious injury or death from explosion, fire or shock may occur.
For this system:
1. Comply with the latest Nati onal Electric Code, feder al, state, and local codes, and an y other a pplicab le safet y codes . In ad diti on, take necess ary precautions during installation, service, and re pair to prevent personal injury, property loss and equipm ent damage.
2. Refer servicing to trained and qualified personnel only.
3. Substitution of components may impair intrinsi c safety.
OFF
4. Be sure AC power is “Off” before opening the console panel cover and connecting probe wires. Do not short any voltage across any barrier terminal including probes.

Precautions To Follow When Connecting Probes to TLS-50 Console

To The Installer! You Must Read And Understand This Information.

INPUT/OUTPUT WIRING POSITIONS AND LABELING

In all cases, the devices wired to the console’s input/output terminal blocks must be recorded to prevent improper replacement during installation or service. A circuit directory is listed below for this purpose.
During programming, the probes wired to each position are identified and stored in memory. If a probe is removed and reconnected to a different set of input terminals after programming, the system will not properly recognize the data being received.
Wiring Assignments
1. Identify all probe wires according to their terminal block location using the self-adhesive numbering labels
furnished. Accurately record on the circuit directory in Figure 14 the location of each probe as you attach wires to the probe input terminal block.
2. Important! Once a device has been wired to certain terminals and the system has been programmed, the wires from that device may not be relocated to other terminals without reprogramming the system.
16
Probe Installation Precau t i on s To Follow When Conn ec ting Probe s to TL S- 50 Co ns ol e
consoles\tls50\prbtnk.eps
drain wire to grounding lug
Probe Number
PROBE 1 IN
TANK
TANK Number & Product
PROBE 2 IN TANK
PROBE 3 IN TANK
PROBE 4 IN TANK
PROBE 5 IN TANK
PROBE 6 IN TANK
Figure 14. Prob e Ins t al lation Dire ctory
Grounding Probe Shields and Drain Wires
Connect probe cable shields and drain wires to ground in the console only, not at the field junction boxes. Do not ground both ends of the shield.

CONNECTING PROBES TO THE CONSOLE - OBSERVE POLARITY

Connect the two color-coded/marked wires from the each probe to the appropriate terminals of the Probe Terminal Block as shown in Figure 15.
SW 1
SW1
WARNING
SUBSTITUTION OF COMPONENTS
MAY IMPAIR INTRINSIC SAFETY.
OPEN
J3
1234
SEC SETUP
Attach probe cable shield and/or
NO REPAIRS SHOULD BE ATTEMPTED.
REFER SERVICING TO QUALIFIED
PERSONNEL ONLY.
PROBE 6
PROBE 5
PROBE 4
PROBE 3
PROBE 2
PROBE 1
AVERTISSEMENT
LA SUBSTITUTION DE COMPOSANTS
PEUT COMPROMETTRE LA SECURITE
INTRINSEQUE.
+
+
+
+
+
+
Black wire from probe connects to terminal
White wire from probe connects to + terminal
consoles\tls50\50prbwir.eps
Figure 15. Connecting Probe Wiring to Console (TLS-50C has 3 probe inputs only)
17
Probe Installation System Setup Security
p

System Setup Security

To protect against unauthorized access to system operation DIP switch 4 of SW1 on the Power Supply board lets you lockout setup and diagnostic menus after making initial programming (for consoles w/display only). Consoles are shipped from the factory with this switch in the open (disabled) position.
See Figure 15 for location of this switch. Figure 16 shows the switch in the closed position, enabling setup lockout. Switch 2 and Switch 3 are not used and can be in any position.
1 2 3 4
OPEN
Sw 4 - blocks access to
SETUP
setup/diag menus after setu (consoles w/display only)
consoles\tls50\sw4.eps
Figure 16. DIP switch 4 in closed position to enable menu lockout

Overfill Alarm Relay

All consoles except those having form numbers 8469X0-060 and 8469X0-230 have one dry contact relay output that closes when an overfill alarm is activated. You can connect an external audible/visual warning device to this relay.
Important! Note these Output Relay Connection Restrictions:
1. Do not connect output relays to a device that draws more than 2 amperes of current. Output power: output relay contact, resistive load - 120/240 Vac, 2 A max.
2. Alarm relays cannot be used for flow control. Alarm relays provide only a momentary closure and cannot actuate flow control devices such as valves and pump motor relays for extended periods of time.
OFF
With power to the console turned Off, connect the two wires from the external warning device to the either of the two overfill relay terminals (J5) [see Figure 17].
18
Loading...
+ 53 hidden pages