Veeder-Root makes no warranty of any kind with regard to this publication, including but not
limited to, the implied warranties of merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential
damages in connection with the furnishing, performance, or use of this publication.
The information contained in this publication may be subject to change without notice.
This publication contains proprietary information which is protected by copyright. All rights
reserved. No part of this publication may be photocopied, reproduced, or translated to another
language without the prior written consent of Veeder-Root.
Table 1. Activate/Revert Screen Field Descriptions ..............................................59
Table 2. DB Backup Screen Field Descriptions ....................................................60
Table 3. DB Restore Screen Field Descriptions ....................................................61
Table 4. Download Screen Field Descriptions ......................................................62
Table 5. System Snapshot Screen Field Descriptions ..........................................63
Table 6. Upgrade Features Screen Field Descriptions .........................................64
iv
Introduction
This manual contains instructions for using the Workflow Wizard Setup Application in the TLS450PLUS and TLS4/8601
Series consoles. Workflow Wizard guides the user through the Veeder-Root recommended setup screens during the
console’s initial commissioning.
This manual assumes all devices are connected the console and that a site diagram of all probes, sensors and tanks is at
hand to assist in determining the correct console addresses for these devices. The procedures herein are intended to be
followed using the console’s touch screen. Other setup interface methods vary in feature and accessibility options.
Some of the screens are only visible if the applicable features/devices are installed in your console. Skip over programming
instructions for any features/devices that are not installed in your console.
Contractor Certification Requirements
Veeder-Root requires the following minimum training certifications for contractors who will install and setup the equipment
discussed in this manual:
Installer (Level 1) Certification: Contractors holding valid Installer Certification are approved to perform wiring and
conduit routing; equipment mounting; probe, sensor and carbon canister vapor polisher installation; wireless equipment
installation; tank and line preparation; and line leak detector installation.
ATG Technician (Level 2/3 or 4) Certification: Contractors holding valid ATG Technician Certifications are approved to
perform installation checkout, startup, programming and operations training, system tests, troubleshooting and servicing for
all Veeder-Root Series Tank Monitoring Systems, including Line Leak Detection. In addition, Contractors with the following
sub-certification designations are approved to perform installation checkout, startup, programming, system tests,
troubleshooting, service techniques and operations training on the designated system.
Related Documents
577014-073TLS450PLUS Site Prep Manual
577014-075TLS-450PLUS Troubleshooting Guide
577014-022TLS4 Site Prep Manual
577014-058TLS4 Troubleshooting Manual
577013-465Electronic Line Leak Detectors Application Guide
577013-770Media-Isolated Mag Plus Probe LPG-ISO Kit Installation Guide
577013-773Media-Isolated Mag Plus Probe Chem-ISO Kit Installation Guide
577014-056Mag-FLEX Probe Low Level Water Float Kit Installation Guide
1
Console Touch Screen Overview
T 1: DELIVERY NEEDED01/20/2016 06:01 PM
Tank Overview
TANK 1: reg
Fuel Volume3655
Fuel Height38.6
Ullage 100%6345
Temperature61.9
Water Height3.0
1 Warning(s)0 Alarms(s)
Print (0)
Home
Favorites
Menu
Actions
Overview
!
See Example
Status Bar
Types Below
Bread Crumbs
0
M
)
0
)
P
)
p
le
Bar
Date & Time
Print Button
SYSTEM STATUS
0 Warning(s)
0 Alarms(s)
SAVING
0 Warning(s)
0 Alarms(s)
T2: DELIVERY NEEDED
1 Warning(s)
0 Alarms(s)
L 10: FUEL ALARM
0 Warning(s)
1 Alarms(s)
Power On to console and no warnings or
alarms from system.
System tasks message bar.
Something needs to be reviewed and/or assessed. In
this state, touching the status/warning bar brings you
to the Reports > Alarms > Active screen so you can
see the cause of the warning. While in that screen,
touching the status/warning bar again acknowledges
the warning and shuts off the beeper.
Something needs to be acted upon immediately. In
this state, touching the status/warning bar brings you
to the Reports > Alarms > Active screen so you can
see the cause of the alarm. While in that screen,
touching the status/warning bar again acknowledges
the alarm and shuts off the beeper.
The following section console features, touch screen layout and how to access and navigate the setup procedure using the
touch screen controls.
Console Home Screen
An example Tank Overview Screen (Default Home Screen) is shown below which has 2 Tanks Monitored and 1 active
Warning
1 Warning(s
Alarms(s
1/20/2016 06:01 P
rint (0
ee Exam
Front Panel Status Lights
Warning
Normal
Alarm
Example Touch Screen Status Bar Notifications
2
Console Touch Screen OverviewExample Touch Screen Status Bar Notifications
1
Touch Screen Icon Descriptions
Home Screen Icon - Touch to navigate to the home screen. Default is the Tank Overview screen (Home screen shown
above).
Favorites Screen Icon - Touch to setup/access your favorite screens and designate which screen will be the home
(default) screen.
Touch to add the current screen to your Favorites list. You can have up to six Favorites screens. If you want to delete a
screen from your Favorites list, touch next to that screen.
Touch to set the current screen as the home screen.
Menu Icon - Touch to access System Setup Menus, Reports, Diagnostics and other screens (Administrator assigned
access). For initial setup of the console, touch Menu>Setup>Workflow Wizard which steps you through the console setup
screens in the proper sequence. See Workflow Wizard setup
Actions Icon - Touch to access Help. Touch the Help iconto open On-Board Help. Also, if the Shifts feature is set up,
touching the Actions icon will display the Close Shift iconwhich can be touched to close a shift.
Unrelated to the choices above, when entering data in any screen, a Red Circle may appear on the Actions icon to indicate that additional tasks/menu choices for that screen.
Screen Dependent Icons - The number in the circle under the Actions icon indicates the device you are viewing or
setting up. Touching the circled number displays all of the similar devices in a row along the bottom of the screen (other
tanks, ports, probes, etc.) that you have set up. Touching the circled number again hides the device icon row. A highlighted
icon indicates the device you are viewing or setting up. Some of the device icons you may see depending on system
features installed in your console are shown below:
1
TankEthernet
Port
Device
ProductSensorPrinterSiphon
ProbeExternal
Input
Set
Relay
Serial
Port
3
Console Touch Screen OverviewTLS4 Comm Ports - Menu>Setup>Communication
4
n
e
a
printers
g
h
r
t
w
o
e
c
nge to a
touch the ke
USB port (1) upper
USB port (2) lower
SWITCH ETH 2 & 3 - shown
in Setup menu as
Ethernet Port 2 (Optional)
Factory Installed,
Optional Module
Area
VR Bus port Ethernet port (1)RS-232 or RS-485 DB9 ports
EXPANSION
SERIAL 1
SERIAL 2
ETH 2
ETH 3
USB 1
USB 2
ETH 1
Entering Changes On A Touch Screen
The screen example below describes entering data into the screen’s field windows.
Touch down arrow in a menu
breadcrumb to view all additional setup
s
creens, select any in list to jump
White (empty) radio button indicates item is not selected.
Touch radio button to select Disabled and deselect Enabled.
to that screen
System Status
Printers
Home
Favorites
Menu
Actions
1
Printer
Setup
Configured
Driver Selection
Setup
Printer
Is Default
Label
URI
1
Selecteddevice. Touch to select
additional devices to be programmed,
in this case additional printers.
0 Warning(s)
07/20/2013 09:01 AM
0 Alarms(s)
EnabledDisabled
APS_CP324HRS_640_USB_1
YesNo
TLSIntegralPrinter
dev/bus/usb?type=usb+vid=6868+pld=4
AutomaticManual
4
Touching in a white field displays
a pop-up keyboard/keypad to enter
or modify an entry.
Print (0)
*
A grayed-in field cannot be changed.
In this example, if there two or more
printers, the field would be white and
touching the down arrow woulddisplay
the additional printers.
After making any change to a screen
Aft
entry, touch the key to accept the
ent
change(s) or touch the key to
ch
cancel the change(s).
ca
If page scroll is visible, touch the up/down
makin
touc
(s) o
l the c
scroll
i
.
ange(s).
s visible, touch th
creen
pt the
to
up/d
arrows or slide bar with finger to scroll up
or down to view additional entry fields.
An asterisk (*) next to a field indicates you
changed
an entry for that field before you have accepted or
saved the change in a dialog window.
Console Comm Ports
When setting up comm ports, you should verify the connections to the console’s comm ports prior to entering their setup
parameters.
TLS4 Comm Ports - Menu>Setup>Communication
Your console’s Comm Port configuration will depend on features ordered. Note: Ethernet ports 2 and 3 are programmed as
the same ethernet device.
Figure 1. TLS4 Comm Ports
4
Console Touch Screen OverviewTLS-450PLUS Comm Ports - Menu>Setup>Communication
USB ports: (1) upper, (2) lower
Future expansion port
*Both ports of ethernet 2
are programmed the same.
Ethernet port:
(1) upper
Ethernet port 2:
middle and lower switched*
Front of
Console
Port 2
Bottom of
console
Port 1
Selectable Comm
Device slots
Fixed Comm
Device slots
12345
High Water Warning
High Water Alarm
Low Product
Delivery Overfill
Delivery Overfill
High Product
Max (Label) Volume
Full Volume (Ref.)
Full Volume (Ref.)
Pump Inlet (Ref.)
Delivery Limit
Delivery Limit
SAFE WORKING CAPACITY
Maximum Product Alarm Level
("Label" Volume)
High Product Alarm Level
Fuel Draw
Off Level
(Ref.)
High Water Warning Level
Low Product Alarm Level
High Water Alarm Level
Interstitial Sensor/Sump Sensor
Typical European TankTypical North American Tank
TLS-450PLUS Comm Ports - Menu>Setup>Communication
Your console’s available Comm Port configuration will depend on features ordered.
Figure 2. TLS-450PLUS Comm Ports
Alarm Limit Settings - Menu>Setup>Tank>Limits
The diagrams below show the relative position of tank alarm (Limit) settings. See “Setup>Tank>Limits” on page 27 for
more information about tank alarm limits.
5
Console Touch Screen OverviewOn-board Help Topics of Interest - Actions>Help
Username:
Password:
Language:
Sign InCancel
Default
Logout
Security Login
If the console Security Feature is Enabled - Touch the Login button to open the login screen so you can login as a
Login
user:
Once the screen displays, log in to the system
with your Username and Password. NOTE: If you
do not log in, you are only permitted to view
system status screens and to print out end-user
reports.
Touch the Logout buttonto log out of
the console. NOTE: If the console is inactive for
15 minutes, the console will automatically log
you out. You will need to log back in to access
your user account.
Using On-Board Help - Actions>Help
Note: On-board help covers all console features, some of which may not be on visible/applicable if they were not ordered
with your console.
To access On-Board Help touch the Actions iconthen touch the Help icon.
Upon entering Help, the topic associated with the currently displayed screen will be visible. Repeatedly touch the side
scroll bar up/down arrows to scroll through a topic. You can also drag and pan through a topic. Touch the ‘X’ in the right
corner of the Help screen title bar to return to the TLS4/TLS-450PLUS screen you were viewing.
•To show or hide the help Table of Contents (TOC) pane on left side of screen - Quickly tap the text (Show TOC or Hide
TOC) twice with your finger.
•To expand () or close () a book - Touch the icon of the book once with your finger.
•To go to a topic () within a book - Quickly tap the book topic twice with your finger.
•Touch the side TOC scroll bar, and either move your finger up (to scroll down) or move your finger down (to scroll up).
•Repeatedly touch the side TOC scroll bar upper arrow to scroll up, or repeatedly touch the side scroll bar down arrow to
scroll down.
On-board Help Topics of Interest - Actions>Help
• Understanding ATG -This help section explains the fundamentals of automatic tank gauges (ATG) as implemented by
Veeder-Root.
• Configuration and Maintenance - This help book discusses Comm Ports, Initial Console Setup Sequence, and Periodic
Maintenance recommendations.
• Welcome (Help Intro) , Screen Icons, On-Screen Keyboards, and Touchscreen navigation are essential help topics which
you can view in the On-Board Help’s Table of Contents.
• Reference Tables - This help section contains topics that cover a wide variety of useful information replaceable fuses, VR acronyms, system device identifiers, tank tilt calculation information, DIM data, etc.
6
Console Touch Screen OverviewBackup System Data - Menu>Software Maintenance>DB Backup
System Status
07/20/2013 09:10 AM
0 Warning(s)
0 Alarms(s)
Print (0)
Home
Favorites
Menu
Actions
Software Maintenance
Current Version
Available Version
Current Operations
Backup Destination
Version
1.gB 230.4
Not available
Select a source to retrieve versions available
IDLE
DB Backup
Select destination device
System Status
07/20/2013 09:18 AM
0 Warning(s)
0 Alarms(s)
Print (0)
Home
Favorites
Menu
Actions
Overview
Console Series # 8601
Software Part # 342004-001.gB230.4r71119
ATG Functionality
Email Notification
Custom On-Board Help
Custom Alarms
Web Enabled
Extended Storage L2
CreatedJul 29 2013 17:43:52
About
Hardware Description
Installed Features
Serial #
CPU11260090
iButton000D016283f20b
UNIV SENS I/O MODULE (B1.S1)000D016283f20b
Max Allowed Ports9
System Status
07/20/2013 09:10 AM
0 Warning(s)
0 Alarms(s)
Print (0)
Home
Favorites
Menu
Actions
Software Maintenance
Current Version
Available Version
Current Operations
Backup Destination
Version
1.gB 230.4
Not available
Select a source to retrieve versions available
IDLE
Download
Select Source
System Maintenance Screen Examples
Backup System Data - Menu>Software Maintenance>DB Backup
Insert your Fat 32 formatted thumb drive (mini-
mum 4 GB) in a USB port and touch the down
arrow in the Backup Destination field to select
the thumb drive, then follow the on-screen
instructions to backup console data.
You should perform a DB Backup weekly.
To View The Console’s Software Version - Menu>Overview>About
This screen provides important information about
your console's software version and installed
features. If you should be experiencing problems
with the console, please have the information on
this screen available with you before contacting
us.
The Veeder-Root Technical Support number is
(800) 323-1799.
To Download Console Software -Menu>Software Maintenance>Download
Insert your valid V-R Code thumb drive in a USB
port and touch the down arrow in the Backup
Destination field to select the coded thumb drive,
then follow the on-screen instructions to begin
the download. Once the download process has
completed, you must activate the software (see
“Activate/Revert Screen (Menu>Software
Maintenance>Activate/Revert)” on page 58).
7
Initial Setup Of The Console Using Workflow Wizard
After the console has been installed and connected to the power panel and to all site monitored devices, apply power to
the console and let it boot up and display the Home Screen (see below).
Figure 3. Initial Setup Home Screen
Access Workflow Wizard Setup by touching Menu>Setup>Workflow Wizard>Setup Workflow:
Figure 4. Accessing Workflow Wizard Setup
8
Initial Setup Of The Console Using Workflow WizardSetup>Display>Language/Units
Touch the Exit icon to quit
Workflow Wizard and return
to the Home screen
Touch to step back to
previous screen
Touch to step forward to
next screen
Touch the and icons
to access online help for the
current screen
The initial setup screen in the Workflow Wizard app is shown below. Note that the Workflow Wizard steps through the
setup screens in a V-R recommended sequence for initial setup of the console. This manual assumes all devices are
connected and recommends you are accessing WW setup from the console GUI. Other setup interface methods vary in
feature and accessibility options.
Navigating Workflow Wizard is described in the figure below. When you exit the Workflow Wizard app, or it times out,
reentering the app always returns you to the initial screen. To return to the screen you were working on after exiting the app,
touch the Next button repeatedly until the desired screen is displayed.
Once the console is setup and functioning and a screen needs modification, the user would likely use the standard quicker
path (from the home screen) to the desired screen, e.g., Menu>Setup>etc>etc..
Setup>Display>Language/Units
System Language
Touch to select the system lan-
guage used for all displays and
reports.
System Units
Touch to select U.S., Metric or
Imperial units to be used in all
displays and calculations.
Setup>Date and Time
This screen lets you enter the current date and time for the console.
Current Date
Touch to enter current date.
Current Time
Touch each field to enter time.
Note: the default time format is 12 hour AM/PM (hh:mm AP).
If 24 hour time is desired, enter the correct time on this
screen then select hh:mm in the Time Format field in the
next Workflow Wizard screen.
Note: Switching to and from Daylight Savings Time is automatic based upon your time zone entry below
.
Time Zone
Touch and scroll to select local time zone.
9
Initial Setup Of The Console Using Workflow WizardSetup>Display>Date/Time Format
Setup>Display>Date/Time Format
This screen lets you select the date and time format used in all screens and reports.
Date Format
Touch to enter desired date format.
Date Separator
Touch to enter desired date separator.
Time Format
Touch to select 24 hr time (hh:mm) or 12
hour AM/PM time (hh:mm AP).
Setup>Display>Number Format
This screen lets you select the numerical separators used in all screens and reports.
Decimal Separator
Touch to enter desired decimal separator.
Thousands Separator
Touch to enter desired thousands separator.
10
Initial Setup Of The Console Using Workflow WizardSetup>Headers
Setup>Headers
This screen lets you enter information to identify your site location, address, phone number, etc. This infor-
mation appears on the top of most inventory and BIR reports. This screen also lets you enter a fax sender name and fax number when sending faxes.
Header 1 - 4
Touch to enter desired Site Name (1),
Street (2), City and State (3) and Phone (4) up to 20 characters each header.
Fax Sender Name
Touch to enter data printed at top of transmitted faxes from console - up to 30 alphanumeric characters.
Fax Phone Number
Touch to enter phone number to which the
console will dial to send faxes - up to 40
digits.
Setup>System>Alarm Filtering
This screen lets you enable/disable Alarm Filtering. Alarm Filtering reduces the total num-
ber of alarms without compromising the reporting of critical alarms.
Alarm Filtering
When this feature is enabled, the console manipulates a combination of the detection time
(the time before an alarm sounds) and the clear time (the time before an alarm is reset) for
certain alarms that often go in and out of an alarm state in a short period of time. In addition, some alarm reports during the clear time are consolidated, reducing their number
without eliminating the alarm reports.
Mag Sensors
The following Mag Sensor alarms will be filtered:
• Mag sensor fault, install and communication alarms - NOTE:
Mag Sensor alarms are reset if the Mag Sensor is replaced
or deconfigured and then reconfigured.
Analog Sensors
The following Liquid, Vapor, Groundwater, Type A (2-wire) and
Type B (3-wire) alarms will be filtered:
• Open, Short, Water, Water Out, Liquid Warning, Low Liquid,
High Liquid and Fuel - NOTE: Liquid Warning, High Liquid,
Low Liquid and Fuel alarms are posted immediately even
when filtered.
DIMs (Dispenser Interface Modules)
The following DIM alarm will be filtered:
•Communication Alarm - NOTE: If there is more than one DIM
card in the console, each card is filtered independently. DIM
alarm filtering takes into account the possibility of lost POS
sales data by monitoring dispensing during the clear time,
but the possibility exists that the filter may not identify all
cases when POS sales data may be lost. Unfiltered DIM
Communication Alarm reports are available by contacting
Veeder-Root Technical Support.
Probes
The following Probe alarm will be filtered:
•Probe Out
11
Initial Setup Of The Console Using Workflow WizardSetup>Communication>System Hostname
Setup>Communication>System Hostname
This screen lets you specify and change the host name of this console (i.e., what the console
is called on the customer's network, such as "MyTLSConsole").
System Hostname
Touch to select the host name of the console as it appears on
the customer’s network, in this example TLS-450PLUS.The
default host name can be changed to accommodate the customer’s network needs.
A blank host name is not allowed. The host name may contain only ASCII letters ‘a’ through ‘z’ (case-insensitive), digits ‘0’ through ‘9’ and the hyphen ‘-’ with no spaces or other
characters allowed.
(Note: the console converts any uppercase letters in the host
name to lower case when they are saved.)
12
Initial Setup Of The Console Using Workflow WizardSetup>Communication>Ethernet Port
Setup>Communication>Ethernet Port
MAC Address [Read-only field] Physical address of the Ether-
net board and is automatically updated by the system (for example,
01:23:45:67:89:ab).
Serial Command Port
Address of serial port used for communications in the console
(default port is 10001). If the customer is using port 10001 already
for another device, you can select another port.
NOTES:
• Do not use ports 20001, 22, 80, or 443. These are used for other
communication purposes within the console.
• If each Ethernet comm device on the console has a different IP
address they can be setup with the same serial command port. Otherwise, when setting up two or more Ethernet devices with the
same IP address on the same serial command serial port, communications may be compromised and no warning messages will be provided.
• When the serial command port is disabled on the “Setup>System>Security” screen, the Serial Command Port field on this
This screen lets you configure the ethernet port(s) on the console which is used for
remote connectivity to a POS, remote printer, etc.. NOTE: Changes made in this screen
may take 10 - 15 seconds before they take effect and then display on the screen. The
fastest way to see changes is to accept the changes, go to the Home screen, then back
to this screen.
The default port selection is Ethernet Port 1. If more than one Ethernet Port is installed
(as in the example above), complete all of the entries for port 1, then select the next
Ethernet port from the icon list on the bottom of the screen that you want to configure
and repeat the complete field entry process for port 2.
IP Address Type
Dynamic - An Ethernet comm device can have a different IP address every time it connects to the network. This address is usually administered by a network service such as
DHCP (Dynamic Host Configuration Protocol).
Static[Default] - An Ethernet comm device will have a permanent IP address every
time it connects to the network. This is entered once on the console.
IP Address
[Field only available if IP Address Type is set to Static]
Enter an IP address that was assigned by the customer's IT department (the default
setting of 192.168.11.100 won't work).
IP Subnet Mask
[Field only available if IP Address Type is set to Static]
Default is 255.255.255.0 and is typical of console configurations. Do not change unless
assigned something different by the customer's IT department.
IP Gateway Address
[Field only available if IP Address Type is set to Static]
Enter a Gateway address that was assigned by the customer's IT department (the
default setting of 192.168.11.100 won't work).
IP Default Gateway
When set to Enabled, makes this Ethernet port the default pathway for outbound communications, such as email.
Primary DNS
[Field only available if ‘IP Address Type’ is set to Static]
Enter a Primary DNS address that was assigned by the customer's IT department.
Secondary DNS
[Field only available if ‘IP Address Type’ is set to Static]
Enter a Secondary DNS address that was assigned by the customer's IT department.
screen is not available.
SSH Port
A secure port that is required by the console to ensure protection on
the communication side of the device. The default port is 22 and
should not be changed.
NOTE: Any changes to this field will affect the same field for the
other Ethernet comm device (if one exists).
HTTPS port
A secure port used by the browser to ensure security on the
browser’s side of the device. The default port is 443 and should not
be changed.
NOTE: Any changes to this field will only affect the specific Ethernet
port being programmed.
Changes to the HTTPS port will affect web enable access.
Serial Command Security
Enables or disables the requirement of entering a security code to
make changes to the Ethernet comm ports.
Security Code
[Field available if Serial Command Security field is enabled]
Enter a security code (6 alphanumeric characters) that will be
required to make any change to the Ethernet comm port(s).
ETX Characters Display
[Field enabled only if RSR 232 End of Message field is enabled]
End-Of-Text (ETX) character. ETX is programmable if enabled via the
S53100f command. If it is disabled, the ETX is a fixed Control-C character (ASCII 03).
ETX Characters Computer
[Field enabled only if RSR 232 End of Message field is enabled]
End-Of-Text (ETX) character. ETX is programmable if enabled via the
S53100f command. If it is disabled, the ETX is a fixed Control-C character (ASCII 03).
13
Initial Setup Of The Console Using Workflow WizardSetup>Communication>Internal Modem
Setup>Communication>Internal Modem
This screen lets you configure the internal modem (TLS-450PLUS consoles only) which is used
for data collection (Note: in the above example screen no internal modem is installed).
Configured
Determines if the internal modem is enabled or disabled.
Label
Name of the internal modem.
Baud Rate
Choices are: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200. The default is
9600.
Byte Size/Data Bits
Choices are: 8 or 7
Parity
Choices are: Odd Parity, Even Parity, or None
Stop Bits
Choices are: 1 or 2
Use Handshaking
Choice is: No Handshaking
Modem Dial Type
Choices are: Tone or Pulse
Dial Tone Interval
Choose interval to wait if there is no dial tone: From 0001 to 9999 hours
Answer On
Choose answer on the number of rings selected: From 0 to 9
Dial In Config
Advanced setting. Leave blank unless directed by Support.
Dial Out Config
Advanced setting. Leave blank unless directed by Support.
Serial Command Security
Select Enable to require all incoming serial commands to
have a security code.
Security Code
[Field available and required if Serial Command Security
field is enabled].
This the security code that all serial commands must have
to be accepted by the console. Valid security codes must be
exactly 6 digits (0 - 9) long.
RS232 End of Message
Enables or disables the End of Message RS232 protocol.
This protocol is used by third party devices that may want
to interrogate the console for inventory or other related
data. These devices require an End-Of-Text command that
signals to the device when the communication string from
the console ends.
Please refer to the customer's third party device for the
type of code to enter in the ETX Characters Display and ETX
Characters computer fields below.
ETX Characters Display
[Field enabled only if RSR 232 End of Message field is
enabled]
End-Of-Text (ETX) character. ETX is programmable if
enabled via the S53100f command. If it is disabled, the ETX
is a fixed Control-C character (ASCII 03).
ETX Characters Computer
[Field enabled only if RSR 232 End of Message field is
enabled]
End-Of-Text (ETX) character. ETX is programmable if
enabled via the S53100f command. If it is disabled, the ETX
is a fixed Control-C character (ASCII 03).
14
Initial Setup Of The Console Using Workflow WizardSetup>Communication>CDIM Port
Setup>Communication>CDIM Port
DIM Protocol
This screen lets you configure the DIM protocol for the
optional CDIM (Current Loop Dispenser Interface Module).This module is used by the system to collect dispenser
transactions for the BIR feature.
Select a CDIM port from the icon list on the bottom of the
screen that you want to configure. NOTE: This field will be
grayed out for DIMs that do not support ‘pass-through’ com-munications.
Touch to select a DIM Protocol. Choices are:
• Gilbarco CL
•Wayne CL
• Unknown
Setup>Communication>TDIM Port
This screen lets you configure the TCP/IP DIM (Dispenser Interface Module) port. This is
used at sites where the console communicates to the dispensers via Ethernet (TCP/IP)
instead of the typical serial communications pathway.
Select a TDIM port from the icon list on the bottom of the screen that you want to configure.
Repeat the entry process for each TDIM Port.
Configured
Touch the radio button to enable or disable this port. NOTE:
When the card is auto-detected, this field will be enabled but
grayed out.
Label
Touch to enter a unique label (up to 20 alphanumeric characters) for the DIM device.
Port Number
Communications port number assigned to this device
(default is 35555). Note: this port is known as the listening
port.
Protocol
Touch to select applicable DIM protocol for your TDIM port.
Choices are:
GilbarcoEDIM, VRProtocolDIM, or Unknown.
Units Reported
Touch to select units for this protocol. Choices are: U.S.,
Metric, or Imperial.
15
Initial Setup Of The Console Using Workflow WizardSetup>Communication>IFSF
System Status
07/07/2016 09:10 AM
0 Warning(s)
0 Alarms(s)
Print (0)
Exit
Actions
Previous
Next
Setup
EnabledConfiguredDisabled
Device
LON Module
CommunicationIFSF
Node Id
01
UDP Port
3485
TCP Port
9000
Setup>Communication>IFSF
This screen lets you configure communication based on International Forecourt Standards
Forum (IFSF) standards for a TLS over TCP/IP or a LonWorks
®
card (LON Module). These
international standards for petroleum retail facilitate the interoperability of service stations
and equipment.
NOTE: A single console cannot support both TCP/IP and LON Module communications simultaneously, even though a site may have a mixed configuration on different consoles. The
maximum number of tanks a site can support is 30.
Configured
Touch the radio button to enable or disable IFSF communication.
Device
The device used for communication. Choices are: LON Module (if installed) or Eth1 for Ethernet Port 1 (for TCP/IP), depending on your hardware configuration.
NOTE: On the TLS450PLUS, Ethernet Ports 2a and 2b are not available for IFSF configuration.
Protocol
The protocol used for IFSF. The choice is: IFSF-China1. This
field is not available with the LON Module device option.
Node Id
The ATG Node Identifier. Each IFSF tank gauge present on a
network must have a unique node ID. The default is 01, but
you can change it as required. This field is not available with
the LON Module device option.
NOTE: With a LonWorks
®
card, the Node ID is set using the
IFSF Node Address Dip Switch on the IFSF Interface Module
during installation. Refer to the Console Troubleshooting
section of the TLS-450PLUS Troubleshooting manual (P/N
577014-075) or the Troubleshooting section of the TLS4 /
8601 Series Consoles Troubleshooting manual (P/N 577014-
058), as appropriate, for more information on IFSF module
cable connector assembly and Node ID switch settings.
UDP Port
The port used for User Datagram Protocol (UDP) communication. The default is 3486, but this field can be edited if you
need to use a different port (1024-65535). This field is not
available with the LON Module device option.
TCP Port
The port used for Transmission Control Protocol (TCP) connection requests. The default is 9000, but this field can be
edited if you need to use a different port (1024-65535). This
field is not available with the LON Module device option.
16
Initial Setup Of The Console Using Workflow WizardSetup>Communication>Serial Port
Setup>Communication>Serial Port
This screen lets you configure the serial ports which may be used for data collection or diag-
nostics purposes. Select a serial port from the icon list on the bottom of the screen that you
want to configure. Repeat the entry process for each Serial Port.
Configured
Touch to enable or disable the Serial Port.
Label
Touch to enter a name for this port.
Usage
Touch to select the type of communication card (board) in the console
Choices are: RS-232, RS485, EDIM, Satellite HJBox, Satellite SSAT, VMCI, Digicom GSM.
Protocol (only visible if EDIM is selected for Usage)
Touch to select applicable DIM protocol for your EDIM port.
Touch to select the communication data rate of this serial port. Choices are: 300, 600, 1200,
2400, 4800, 9600, 19200, 38400, 57600, 115200. The default is 9600.
Stop Bits
Choices are: 1 or 2
Byte Size/Data Bits
Choices are: 8 or 7
Parity
Choices are: Odd Parity, Even Parity, or None
Use Handshaking
Choice is: No Handshaking, RTSCTS or XON XOFF
Serial Command Security
Select Enable to require all incoming serial commands to
have a security code.
Security Code
[Field available and required if Serial Command Security
field is enabled].
This the security code that all serial commands must have to
be accepted by the console. Valid security codes must be
exactly 6 digits (0 - 9) long.
RS232 End of Message
Enables or disables the End of Message RS232 protocol.
This protocol is used by third party devices that may want to
interrogate the console for inventory or other related data.
These devices require an End-Of-Text command that signals
to the device when the communication string from the console ends.
Please refer to the customer's third party device for the type
of code to enter in the ETX Characters Display and ETX Characters computer fields below.
ETX Characters Display
[Field enabled only if RSR 232 End of Message field is
enabled]
End-Of-Text (ETX) character. ETX is programmable if enabled
via the S53100f command. If it is disabled, the ETX is a fixed
Control-C character (ASCII 03).
ETX Characters Computer
[Field enabled only if RSR 232 End of Message field is
enabled]
End-Of-Text (ETX) character. ETX is programmable if enabled
via the S53100f command. If it is disabled, the ETX is a fixed
Control-C character (ASCII 03).
17
Loading...
+ 48 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.