Veeder-Root TLS-350, TLS-300, TLS-3 Series System Setup Manual

System Setup Manual
TLS-3XX Series Consoles
Manual No: 576013-623 • Revision: AM
Software Version X33
Notice
Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication may be modified or translated to another language without the prior written consent of Veeder-Root.
Contact TLS Systems Technical Support for additional troubleshooting information at 800-323-1799.
DAMAGE CLAIMS / LOST EQUIPMENT
Thoroughly examine all components and units as soon as they are received. If any cartons are damaged or missing, write a complete and detailed description of the damage or shortage on the face of the freight bill. The carrier's agent must verify the inspection and sign the description. Refuse only the damaged product, not the entire shipment.
Veeder-Root must be notified of any damages and/or shortages within 30 days of receipt of the shipment, as stated in our Terms and Conditions.
VEEDER-ROOT’S PREFERRED CARRIER
1. Contact Veeder-Root Customer Service at 800-873-3313 with the specific part numbers and quantities that were missing or received damaged.
2. Fax signed Bill of Lading (BOL) to Veeder-Root Customer Service at 800-234-5350.
3. Veeder-Root will file the claim with the carrier and replace the damaged/missing product at no charge to the customer. Customer Service will work with production facility to have the replacement product shipped as soon as possible.
CUSTOMER’S PREFERRED CARRIER
1. It is the customer’s responsibility to file a claim with their carrier.
2. Customer may submit a replacement purchase order. Customer is responsible for all charges and freight associated with replacement order. Customer Service will work with production facility to have the replacement product shipped as soon as possible.
3. If “lost” equipment is delivered at a later date and is not needed, Veeder-Root will allow a Return to Stock without a restocking fee.
4. Veeder-Root will NOT be responsible for any compensation when a customer chooses their own carrier.
RETURN SHIPPING
For the parts return procedure, please follow the appropriate instructions in the "General Returned Goods Policy” pages in the "Policies and Literature" section of the Veeder-Root North American Environmental Products price list. Veeder-Root will not accept any return product without a Return Goods Authorization (RGA) number clearly printed on the outside of the package.
©Veeder-Root 2014. All rights reserved
.
1 Introduction
Contractor Certification Requirements ...........................................................................1-1
Related Manuals ............................................................................................................1-1
Safety Precautions .........................................................................................................1-2
Safety Warnings ............................................................................................................1-2
2 Front Panel Keypads
Arrangement of Keys .....................................................................................................2-1
Operating Keys......................................................................................................2-1
Alphanumeric Keys................................................................................................2-1
Blue Key (Maintenance Tracker - TLS-350 Only)..................................................2-2
White Key (Maintenance Report - TLS-350 Only).................................................2-2
Using the Operating Keys ..............................................................................................2-2
Using the Alphanumeric Keys ........................................................................................2-3
Entering Alphanumeric Data..................................................................................2-4
Special Characters and Cursor Movement............................................................2-4
3 Setup Mode Organization
Functions .......................................................................................................................3-1
Steps ..............................................................................................................................3-1
Setup Mode Programming Table ...................................................................................3-1

Table of Contents

4 Prior to Applying AC Power to the Console
Security Code Enable/Disable .......................................................................................4-1
TLS-300 Consoles.................................................................................................4-1
TLS-350 Consoles.................................................................................................4-1
Battery Backup ..............................................................................................................4-6
Applying AC Power to the Console ................................................................................4-6
5 System Setup
Programming Guidelines ...............................................................................................5-1
Automatic Return to Operating Mode ............................................................................5-1
Setup Data Warning ......................................................................................................5-1
Printing a Setup Data Report .........................................................................................5-1
Selecting the System Setup Function ............................................................................5-2
System Language ..........................................................................................................5-2
System Units ..................................................................................................................5-2
Setting the Date and Time Format .................................................................................5-3
Current Date ..................................................................................................................5-3
Current Time ..................................................................................................................5-4
Report Headers .............................................................................................................5-4
Shift Start Times ............................................................................................................5-4
Shift BIR Printouts .........................................................................................................5-5
Daily BIR Printouts .........................................................................................................5-5
Ticketed Delivery ...........................................................................................................5-5
TC Ticketed Delivery .....................................................................................................5-6
Close Day of Week ........................................................................................................5-6
Variance Reports ...........................................................................................................5-6
Daily Delivery Variance Reports............................................................................5-6
Weekly Delivery Variance Reports ........................................................................5-6
Periodic Delivery Variance Reports.......................................................................5-7
iii
Table of Contents
Daily Book Variance Reports.................................................................................5-7
Weekly Book Variance Reports.............................................................................5-7
Periodic Book Variance Reports............................................................................5-7
Daily Variance Analysis Reports ...........................................................................5-7
Weekly Variance Analysis Reports........................................................................5-7
Periodic Variance Analysis Reports ......................................................................5-8
Tank Periodic Test Needed Warnings ...........................................................................5-8
Enable Tank Periodic Test Needed Warnings and Alarms ...................................5-8
Disable Tank Periodic Test Needed Warnings......................................................5-9
Tank Annual Test Needed Warnings .............................................................................5-9
Enable Tank Annual Test Needed Warnings and Alarms .....................................5-9
Disable Tank Annual Test Needed Warnings and Alarms ..................................5-10
Line Re-Enable Method ...............................................................................................5-10
Line Periodic Test Needed Warnings ..........................................................................5-10
Enable Line Periodic Test Needed Warnings and Alarms...................................5-11
Disable Line Periodic Test Needed Warnings .....................................................5-11
Line Annual Test Needed Warnings ............................................................................5-11
Enable Line Annual Test Needed Warnings and Alarms ....................................5-12
Disable Line Annual Test Needed Warnings and Alarms....................................5-12
Remote Printer Page Eject ..........................................................................................5-13
Print TC Volumes .........................................................................................................5-13
Temperature Compensation Value ..............................................................................5-13
Tanker Load Report - International Option ..................................................................5-14
Stick Height Offset - International Option ....................................................................5-14
Ullage ...........................................................................................................................5-14
H-Protocol Data Format - International Option ............................................................5-14
Precision Test Duration (PLLD/WPLLD Only) .............................................................5-15
Precision Line Test Auto-Confirm ................................................................................5-15
Daylight Savings Time .................................................................................................5-16
Re-direct Local Printout ...............................................................................................5-16
QPLD Monthly Printout - International Option ..............................................................5-17
Euro Protocol Prefix .....................................................................................................5-17
BDIM Trans Alarm Delay .............................................................................................5-17
System Security Code .................................................................................................5-17
Maintenance History ....................................................................................................5-18
Tank Chart Security .....................................................................................................5-18
Custom Alarm Labels ..................................................................................................5-19
Service Notice (TLS-350 Consoles Only) ....................................................................5-27
Inventory Alarms Threshold Units ................................................................................5-28
System Beeper ............................................................................................................5-29
Mass/Density ...............................................................................................................5-30
Fiscal Height Security ..................................................................................................5-30
Alarm Reduction ..........................................................................................................5-31
6 Communications Setup
Selecting the Communications Setup Function .............................................................6-1
Port Settings ..................................................................................................................6-1
Note: Port Settings - International Installations With SiteLink modems.................6-1
Baud Rate..............................................................................................................6-1
Parity .....................................................................................................................6-2
Stop Bit ..................................................................................................................6-2
Data Length...........................................................................................................6-2
Dial Type ...............................................................................................................6-3
iv
Table of Contents
Answer On.............................................................................................................6-3
Security Code........................................................................................................6-3
Setting the Modem Type (international Installations) ............................................6-4
Modem Setup String..............................................................................................6-4
Dial Tone Interval ..................................................................................................6-4
DTR Normal State .................................................................................................6-4
Specifying Port Settings for Additional Communication Modules..........................6-5
Continue Communications Setup..........................................................................6-5
Auto-Transmit Setup (RS-232 or RS-232/RS-485 Modules Only) .................................6-5
Auto-Transmit Method...........................................................................................6-5
Auto Delay Time ....................................................................................................6-6
Auto Repeat Time..................................................................................................6-6
Continue Communications Setup..........................................................................6-6
Phone Directory Setup ...................................................................................................6-7
Receiver Configuration ..........................................................................................6-7
Receiver Location..................................................................................................6-7
Receiver Telephone Number.................................................................................6-7
Select Modem........................................................................................................6-8
Receiver Type .......................................................................................................6-8
Retry Number ........................................................................................................6-8
Retry Delay Time...................................................................................................6-9
Confirmation Report ..............................................................................................6-9
Setting Up Additional Phone Numbers ..................................................................6-9
Continue Communications Setup..........................................................................6-9
Auto-Dial Setup ............................................................................................................6-10
Receiver Report List ............................................................................................6-10
Auto Dial Method: All Phones/Single Phone .......................................................6-11
Auto-Dial Frequency: Specific Date.....................................................................6-11
Auto-Dial Frequency: Annually............................................................................6-12
Auto-Dial Frequency: Monthly .............................................................................6-13
Auto-Dial Frequency: Weekly..............................................................................6-13
Auto-Dial Frequency: Daily..................................................................................6-14
Auto-Dial Frequency: BIR End ............................................................................6-14
Setting Up the Frequency for Additional Receivers
(Single Phone Only) ............................................................................................6-15
Continue Communications Setup........................................................................6-15
Auto-Dial Alarm Setup .................................................................................................6-15
In-Tank Alarms ....................................................................................................6-16
Remaining Alarm Groups ....................................................................................6-17
Liquid Sensor Alarms ..........................................................................................6-17
Vapor Sensor Alarms ..........................................................................................6-17
External Inputs Alarms ........................................................................................6-17
Line Leak Alarms (VLLD) ....................................................................................6-17
Groundwater Sensor Alarms ...............................................................................6-17
2 Wire C.L. Sensor Alarms ..................................................................................6-18
3 Wire C.L. Sensor Alarms ..................................................................................6-18
Receiver Alarms ..................................................................................................6-18
Power Side DIM Alarms ......................................................................................6-18
Reconciliation Alarms ..........................................................................................6-18
Pressure Line Leak Detector (PLLD) Alarms ......................................................6-18
Wireless Pressure Line Leak Detector (WPLLD) Alarms ....................................6-19
Communication Side DIM Alarms........................................................................6-19
Smart Sensor Alarms ..........................................................................................6-19
Pump Relay Monitor Alarm..................................................................................6-19
VMCI Dispenser Interface Alarms .......................................................................6-19
VMC Alarms ........................................................................................................6-19
v
Setting Up Auto-Dial Alarms for Additional Destinations .....................................6-20
RS-232 End of Message ..............................................................................................6-20
7 In-Tank Setup
Selecting the In-Tank Setup Function ............................................................................7-1
Tank Configuration ........................................................................................................7-1
How the System Configures In-Tank Probes ........................................................7-1
Specifying In-Tank Probe Positions.......................................................................7-1
Product Labels ...............................................................................................................7-2
Product Code .................................................................................................................7-2
Coefficient of Thermal Expansion ..................................................................................7-3
Tank Density ..................................................................................................................7-4
Tank Diameter ...............................................................................................................7-5
Tank Profile ....................................................................................................................7-5
Tank Profile Selections..........................................................................................7-5
Procedure ..............................................................................................................7-6
Full Volume ....................................................................................................................7-6
4 or 20 Point Tank Profiles Height/Volume Entries ...............................................7-7
50 Point Tank Profile Height/Volume Entries (Tank Chart Security Disabled) ......7-7
50 Point Tank Profile Entries With Tank Chart Security Enabled..........................7-9
Meter Data Present ......................................................................................................7-11
Vapor Loss Factor - International Option .....................................................................7-11
End Factor ...................................................................................................................7-12
Calibration Update .......................................................................................................7-12
Float Size .....................................................................................................................7-13
Water Warning .............................................................................................................7-14
High Water Limit ..........................................................................................................7-15
Water Alarm Filter ........................................................................................................7-15
Programmable Minimum Water Threshold ..................................................................7-16
Max or Label Vol ..........................................................................................................7-16
Overfill Limit .................................................................................................................7-16
High Product ................................................................................................................7-17
Delivery Limit ...............................................................................................................7-17
Low Product .................................................................................................................7-17
Leak Alarm Limit ..........................................................................................................7-18
Sudden Loss Limit .......................................................................................................7-18
Tank Tilt .......................................................................................................................7-18
Calculating Tank Tilt (H2)....................................................................................7-19
Entering the Tank Tilt Value ................................................................................7-19
Probe Offset .................................................................................................................7-20
Siphon Manifolded Tank Status ...................................................................................7-20
Line Manifolded Tank Status .......................................................................................7-21
Leak Minimum Periodic ...............................................................................................7-21
Leak Minimum Annual .................................................................................................7-22
Periodic Test Type .......................................................................................................7-22
Annual Test Fail ...........................................................................................................7-22
Periodic Test Fail .........................................................................................................7-23
Gross Test Fail ............................................................................................................7-23
Annual Test Averaging ................................................................................................7-23
Periodic Test Averaging ...............................................................................................7-24
Tank Test Notify ...........................................................................................................7-24
Tank Test Siphon Break ..............................................................................................7-24
Table of Contents
vi
Stick Offset (International Option) ................................................................................7-24
HRM Reconciliation Warning Limit (International Option) ............................................7-25
HRM Reconciliation Alarm Limit (international Option) ................................................7-25
Delivery Report Delay Time .........................................................................................7-26
Pump Threshold ..........................................................................................................7-26
Setting Up Additional Tanks ........................................................................................7-26
8 In-Tank Leak Tests
Selecting the In-Tank Leak Test Setup Function ...........................................................8-1
Leak Test Method: All Tank/Single Tank .......................................................................8-1
Leak Test Frequency .....................................................................................................8-2
Test On Date .........................................................................................................8-2
Annual Test ...........................................................................................................8-3
Monthly Test ..........................................................................................................8-3
Weekly Test...........................................................................................................8-4
Daily Test...............................................................................................................8-4
Automatic Test.......................................................................................................8-4
CSLD - Option .......................................................................................................8-5
Gross Test Auto-Confirm ...............................................................................................8-7
Leak Test Start Time .....................................................................................................8-7
Leak Test Rate ..............................................................................................................8-7
Leak Test Duration ........................................................................................................8-8
Leak Test Early Stop .....................................................................................................8-8
CSLD Report Only .........................................................................................................8-9
Leak Test Report Format ...............................................................................................8-9
Setting Up Additional Tanks ..........................................................................................8-9
Table of Contents
9 Fuel Management
Selecting the Fuel Management Function .....................................................................9-1
Delivery Warning Days ..................................................................................................9-1
Daily Time to Print Fuel Management Report ................................................................9-1
Average Daily Sales ......................................................................................................9-2
10 Pressurized Line Leak Detection
Line Manifolding Implications for AccuChart ................................................................10-1
PLLD Setup .................................................................................................................10-1
Activating PLLDs .........................................................................................................10-1
Labeling PLLDs ...........................................................................................................10-1
Piping Type ..................................................................................................................10-2
Piping Length ...............................................................................................................10-2
Entering Line Length for Dual Size Flexible Pipe Types .....................................10-3
Entering Line Length for 2.0/3.0 In. Fiberglass Pipe Type ..................................10-3
User Defined Pipe Type - Setup Parameters ...............................................................10-3
Thermal Coefficient ......................................................................................................10-4
0.2 gph (0.76 lph) Line Leak Test Scheduling .............................................................10-4
0.1 gph (0.38 lph) Line Leak Test Scheduling .............................................................10-5
Passive 0.1 gph Line Leak Testing ..............................................................................10-5
Shutdown Rate ............................................................................................................10-6
Low Pressure Alarm Shutoff ........................................................................................10-6
Tank Selection .............................................................................................................10-7
Selecting a Dispense Mode .........................................................................................10-7
Auto Active Switchover........................................................................................10-8
Pressure Transducer Type ..........................................................................................10-8
vii
Pressure Offset ............................................................................................................10-9
Venting The Line .................................................................................................10-9
Determining a Pressure Offset Value for each Transducer...............................10-10
Entering the Pressure Offset Value for each Transducer..................................10-10
Mechanical Blenders .................................................................................................10-11
Setting Up Additional PLLDs .....................................................................................10-11
11 Wireless Pressurized Line Leak Detection
Line Manifolding Implications for AccuChart ................................................................11-1
WPLLD Setup ..............................................................................................................11-1
Activating WPLLDs ......................................................................................................11-1
Labeling WPLLDs ........................................................................................................11-2
Piping Type ..................................................................................................................11-2
Piping Length ...............................................................................................................11-2
0.2 gph (0.76 lph) Line Leak Test Scheduling - Option ...............................................11-3
0.1 gph (0.38 lph) Line Leak Test Scheduling - Option ...............................................11-4
Shutdown Rate ............................................................................................................11-4
Pressure Offset ............................................................................................................11-4
Venting The Line .................................................................................................11-5
Determining a Pressure Offset Value for each Transducer.................................11-5
Entering the Pressure Offset Value for each Transducer....................................11-6
Tank Selection .............................................................................................................11-6
Selecting a Dispense Mode .........................................................................................11-6
Setting Up Additional WPLLDs ....................................................................................11-7
Table of Contents
12 Volumetric Line Leak Detection
VLLD Setup .................................................................................................................12-1
Activating VLLDs .........................................................................................................12-1
Pipe Label and Tank Identification ...............................................................................12-1
Enter Dispense Mode ..................................................................................................12-2
Fuel Type .....................................................................................................................12-3
Piping Length and Type ...............................................................................................12-3
Pump Pressure ............................................................................................................12-4
Shutdown Rate ............................................................................................................12-5
Pumpside Test .............................................................................................................12-5
Wait Mode ....................................................................................................................12-6
New Blender Protocol (NBP) Partner ...........................................................................12-6
Last Annual Test Passed .............................................................................................12-7
Setting Up Additional Line Leak Detectors ..................................................................12-7
13 Volumetric Line Leak Tests
Selecting the Line Leak Test Setup Function ..............................................................13-1
Leak Test Setup Method: All Lines/Single Lines .........................................................13-1
Leak Test Frequency ...................................................................................................13-2
On Date ...............................................................................................................13-2
Annual Test .........................................................................................................13-2
Monthly Test ........................................................................................................13-3
Weekly Test.........................................................................................................13-3
Daily Test.............................................................................................................13-4
Leak Test Start Time ...................................................................................................13-4
Leak Test Rate ............................................................................................................13-4
Setting Up Additional Lines ..........................................................................................13-5
viii
14 Line Leak Test Lockout
Selecting the Line Leak Test Lockout Function ...........................................................14-1
Lockout Schedule ........................................................................................................14-1
Daily Schedule .............................................................................................................14-1
Individual Schedules ....................................................................................................14-2
Entering Additional Test Lockout Schedules ...............................................................14-3
15 Pump Sense Setup
Selecting the Pump Sense Function ............................................................................15-1
Pump Sense Configuration ..........................................................................................15-1
How the System Configures Pump Sense Modules............................................15-1
Specifying Pump Sense Positions.......................................................................15-1
Pump Sense Tank Number .........................................................................................15-2
Pump Sense Dispense Mode ......................................................................................15-2
Auto Active Switchover........................................................................................15-3
16 Pump Relay Monitor Setup
Selecting the Pump Relay Monitor Function ................................................................16-1
Pump Relay Monitor Configuration ..............................................................................16-1
How the System Configures Pump Relay Monitor Modules ................................16-1
Specifying Pump Relay Monitor Positions...........................................................16-1
Labeling Pump Relay Monitors ....................................................................................16-2
Pump Relay Monitor Relay Input .................................................................................16-2
Pump Relay Monitor Delay Input .................................................................................16-2
Table of Contents
17 Reconciliation Setup
Dispenser Module Data String .....................................................................................17-1
Automatic Daily Closing ...............................................................................................17-1
Automatic Shift Closing ................................................................................................17-2
Periodic Reconciliation Mode ......................................................................................17-2
Periodic Reconciliation Alarm ......................................................................................17-3
Remote Report Format ................................................................................................17-4
Temp Compensation ...................................................................................................17-4
Meter Calibration Offset ...............................................................................................17-5
Modify Tank/Meter Map ...............................................................................................17-5
18 Liquid Sensor Setup
Selecting the Liquid Sensor Setup Function ................................................................18-1
Liquid Sensor Configuration ........................................................................................18-1
How the System Configures Liquid Sensors .......................................................18-1
Specifying Liquid Sensor Positions .....................................................................18-1
Liquid Sensor Location ................................................................................................18-2
Liquid Sensor Type ......................................................................................................18-2
Liquid Sensor Category (RS-232 and Remote Display) ..............................................18-3
Setting Up Additional Liquid Sensors ..........................................................................18-3
19 Vapor Sensor Setup
Selecting the Vapor Sensor Setup Function ................................................................19-1
Vapor Sensor Configuration ........................................................................................19-1
How the System Configures Vapor Sensors .......................................................19-1
Specifying Vapor Sensor Positions .....................................................................19-1
Vapor Sensor Location ................................................................................................19-2
Vapor Threshold ..........................................................................................................19-2
ix
Before You Begin ................................................................................................19-2
Specifying Vapor Threshold Levels .....................................................................19-3
Vapor Sensor Category ...............................................................................................19-3
Setting Up Additional Vapor Sensors ..........................................................................19-4
20 Groundwater Sensor Setup
Selecting the Groundwater Sensor Setup Function .....................................................20-1
Groundwater Sensor Configuration .............................................................................20-1
How the System Configures Groundwater Sensors............................................20-1
Specifying Groundwater Sensor Positions ..........................................................20-1
Groundwater Sensor Location .....................................................................................20-2
Groundwater Sensor Category ....................................................................................20-2
Setting Up Additional Groundwater Sensors ...............................................................20-2
21 2-Wire C.L. Sensor Setup
Selecting the 2-Wire C.L. Sensor Setup Function .......................................................21-1
2-Wire C.L. Sensor Configuration ................................................................................21-1
How the System Configures 2-Wire C.L. Sensors...............................................21-1
Specifying 2-wire C.L. Sensor Positions..............................................................21-1
2-Wire C.L. Sensor Location ........................................................................................21-2
2-Wire C.L. Sensor Type .............................................................................................21-2
2-Wire C.L. Sensor Category .......................................................................................21-2
Setting Up Additional 2-Wire C.L. Sensors ..................................................................21-3
Table of Contents
22 3-Wire C.L. Sensor Setup
Selecting the 3-Wire C.L. Sensor Setup Function .......................................................22-1
3-Wire C.L. Sensor Configuration ................................................................................22-1
How the System Configures 3-Wire C.L. Sensors...............................................22-1
Specifying 3-Wire C.L. Sensor Positions.............................................................22-1
3-Wire C.L. Sensor Location ........................................................................................22-2
3-Wire C.L. Sensor Mode ............................................................................................22-2
3-Wire C.L. Sensor Category .......................................................................................22-2
Setting Up Additional 3-Wire C.L. Sensors ..................................................................22-3
23 External Input Setup
Selecting the External Input Setup Function ................................................................23-1
External Input Configuration ........................................................................................23-1
How the System Configures Input Devices .........................................................23-1
Specifying Input Positions ...................................................................................23-1
External Input Name ....................................................................................................23-2
External Input Type ......................................................................................................23-2
Switch Orientation ........................................................................................................23-3
External Input Emergency Generator Data ..................................................................23-3
Pump Sense Setup Data .............................................................................................23-4
Selecting a Dispense Mode.................................................................................23-4
Auto Active Switchover........................................................................................23-5
Setting Up Additional Inputs ........................................................................................23-5
24 Output Relay Setup
Selecting the Output Relay Setup Function .................................................................24-1
Relay Configuration .....................................................................................................24-1
How the System Configures Output Relays ........................................................24-1
Specifying Output Relay Positions ......................................................................24-1
x
Table of Contents
Relay Designation ........................................................................................................24-2
Selecting Relay Type ...................................................................................................24-2
Assignment Method .....................................................................................................24-3
In-Tank Alarms ....................................................................................................24-3
Remaining Alarm Groups ....................................................................................24-5
Liquid Sensor Alarms ..........................................................................................24-5
Vapor Sensor Alarms ..........................................................................................24-5
External Inputs Alarms ........................................................................................24-5
Line Leak Alarms (VLLD) ....................................................................................24-5
Groundwater Sensor Alarms ...............................................................................24-5
2 Wire C.L. Sensor Alarms ..................................................................................24-6
3 Wire C.L. Sensor Alarms ..................................................................................24-6
Power Side DIM Alarms ......................................................................................24-6
Reconciliation Alarms ..........................................................................................24-6
Pressure Line Leak Detector (PLLD) Alarms ......................................................24-6
Wireless Pressure Line Leak Detector (WPLLD) Alarms ....................................24-6
Communication Side DIM Alarms........................................................................24-7
Smart Sensor Alarms ..........................................................................................24-7
Pump Relay Monitor Alarm..................................................................................24-7
VMCI Dispenser Interface Alarms .......................................................................24-7
VMC Alarms ........................................................................................................24-7
Setting Up Additional Relays .......................................................................................24-8
25 Line Disable Setup
Selecting the PLLD, WPLLD, or VLLD Line Disable Setup Function ...........................25-1
Alarm Assignment Notes.....................................................................................25-1
In-Tank Alarms ............................................................................................................25-1
Remaining Alarm Groups ....................................................................................25-2
Liquid Sensor Alarms ..........................................................................................25-3
Vapor Sensor Alarms ..........................................................................................25-3
External Input Alarms ..........................................................................................25-3
Line Leak Alarms.................................................................................................25-3
Groundwater Sensor Alarms ...............................................................................25-3
2 Wire C.L. Sensor Alarms ..................................................................................25-3
3 Wire C.L. Sensor Alarms ..................................................................................25-4
Power Side DIM Alarms ......................................................................................25-4
Reconciliation Alarms ..........................................................................................25-4
Pressure Line Leak Detector (PLLD) Alarms ......................................................25-4
Wireless Pressure Line Leak Detector (WPLLD) Alarms ....................................25-4
Communication Side DIM Alarms........................................................................25-5
Smart Sensor Alarms ..........................................................................................25-5
Pump Relay Monitor Alarm..................................................................................25-5
VMCI Dispenser Interface Alarms .......................................................................25-5
VMC Alarms ........................................................................................................25-5
Setting Up Additional Disables ....................................................................................25-6
26 Smart Sensor Setup
Selecting the Smart Sensor Setup Function ................................................................26-1
Sensor Configuration ...................................................................................................26-1
Smart Sensor Label .....................................................................................................26-2
Selecting Sensor Category ..........................................................................................26-2
Mag Sensor Setup .......................................................................................................26-3
Vac Sensor Setup ........................................................................................................26-4
xi
27 VMC Setup
Selecting the VMC Setup Function ..............................................................................27-1
Add a VMC Serial Number ..........................................................................................27-1
Edit a VMC Serial Number ...........................................................................................27-1
Remove a VMC Serial Number ....................................................................................27-2
28 Archive Utility
Accessing the Archive Utility Function .........................................................................28-1
Archiving Setup Data ...................................................................................................28-1
Restoring Archived Setup Data ...................................................................................28-2
Clearing Archived Setup Data .....................................................................................28-3
Table of Contents

Figures

Tables

Appendix A: Calculating Tank Tilt - International
Entering the Tank Tilt Value ................................................................................. A-3
Appendix B: Setup Parameters for TLS-300 System - International
System Setup ...............................................................................................................B-1
Comm Board (1, 2, etc.) Setup ..................................................................................... B-2
In-Tank Setup ............................................................................................................... B-2
Leak Test Method Setup ............................................................................................... B-3
Appendix C: Setup Parameters for TLS-350 System - International
Figure 4-1. Battery Backup Switch and DIP Switch Location - TLS-300
Console ................................................................................................4-3
Figure 4-2. Battery Backup Switch and DIP Switch Location TLS-350
Consoles with CPU Board ...................................................................4-4
Figure 4-3. Battery Backup Switch and DIP Switch Location TLS-350
Consoles with ECPU Board .................................................................4-5
Figure 7-1. Relative Positions of Tank Alarm Limits ............................................7-14
Figure 7-2. Siphon Manifolded Tanks ..................................................................7-20
Figure 7-3. Line Manifolding A Siphon Manifolded Set To A Single Tank ...........7-21
Table 2-1. Character Assignments for Numeric Keys .............................................2-4
Table 5-1. Alarm Labels ........................................................................................5-21
Table 5-2. Configurations For Setting Inventory Alarm Thresholds .......................5-29
Table 6-1. SiteLink Modem Default Port Settings ....................................................6-1
Table 6-2. Alarm List .............................................................................................6-21
Table 7-1. Typical Thermal Coefficients ..................................................................7-3
Table 7-2. Tank Tilt Calculation Worksheet ...........................................................7-19
Table 10-1. Reference of Absolute Pressure Offsets at Various Altitudes ..............10-8
Table 12-1. Submersible Pump Nominal Pressures ................................................12-4
Table A-1. Typical Tank Offset Values ................................................................... A-1
Table B-1. System Setup ........................................................................................B-1
Table B-2. Comm Board Setup ............................................................................... B-2
Table B-3. In-tank Setup .........................................................................................B-2
Table B-4. Leak Test Method Setup ....................................................................... B-3
Table C-1. System Setup ........................................................................................C-1
Table C-2. Comm Board (1, 2, Etc.) Setup .............................................................C-2
Table C-3. In-tank Setup .........................................................................................C-3
Table C-4. Leak Test Method Setup .......................................................................C-4
Table C-5. Reconciliation Setup ..............................................................................C-5
xii

1 Introduction

This manual lists programming instructions for every available TLS-3XX Console Setup Function. The manual is divided into sections for each Setup Function beginning with Section 5, System Setup. Depending on your console type and its installed features, you may only see (and be able to program) some of the Functions and/or Steps. Skip over the material in this manual that does not apply to your particular installation. You cannot perform these setup procedures until the console, probes, and sensors have been installed and connected.

Contractor Certification Requirements

Veeder-Root requires the following minimum training certifications for contractors who will install and setup the equipment discussed in this manual:
Installer Certification (Level 1): Contractors holding valid Installer Certification are approved to perform wiring and conduit routing; equipment mounting; probe, sensor and carbon canister vapor polisher installation; wireless equipment installation; tank and line preparation; and line leak detector installation.
Technician Certification (Level 2/3): Contractors holding valid Technician Certifications are approved to perform installation checkout, startup, programming and operations training, system tests, troubleshooting and servicing for all Veeder-Root Series Tank Monitoring Systems, including Line Leak Detection. In addition, Contractors with the following sub-certification designations are approved to perform installation checkout, startup, programming, system tests, troubleshooting, service techniques and operations training on the designated system.
• Wireless 2
• Tall Tank
VR Vapor Products Certification: Contractors holding a certification with the following designations are approved to perform installation checkout, startup, programming, system tests, troubleshooting, service techniques and operations training on the designated system.
• ISD – In Station Diagnostics
• PMC – Pressure Management Control
• CCVP - Veeder-Root Vapor Polisher
• Wireless – ISD/PMC Wireless
• A current Veeder-Root Technician Certification is a prerequisite for the VR Vapor Products course.
Warranty Registrations may only be submitted by selected Distributors.

Related Manuals

576013-610 TLS-3XX Series Consoles Operator’s Manual
576013-879 TLS-3XX Series Consoles Site Prep Manual
577013-874 Maintenance Service Code Quick Help
1-1
1 Introduction Safety Precautions
OFF

Safety Precautions

The following safety symbols may be used in this manual to alert you to important safety hazards and precautions.

Safety Warnings

EXPLOSIVE
Fuels and their vapors are extremely explosive if ignited.
TURN POWER OFF
Live power to a device creates a potential shock hazard. Turn Off power to the device and associated accesso­ries when servicing the unit.
ELECTRICITY
High voltage exists in, and is supplied to, the device. A potential shock hazard exists.
FLAMMABLE
Fuels and their vapors are extremely flammable.
READ ALL RELATED MANUALS
Knowledge of all related procedures before you begin work is important. Read and understand all manuals thor­oughly. If you do not understand a pro­cedure, ask someone who does.
WAR NING
Heed the adjacent instructions to avoid damage to equipment, property, envi­ronment or personal injury.
WARNING
This system operates near highly combustible fuel storage tanks. FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY
PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT, RESULTING IN SERIOUS INJURY OR DEATH.
Leaking tanks can create serious environmental and health hazards. Improper programming and operation may also result in equipment self-test failures and submersible pump shutdowns. It is the owner’s responsibility to:
1. Ensure that this equipment is properly programmed.
2. Promptly investigate any alarm conditions.
3. Operate this equipment in accordance with the instructions in this manual.
1-2

2 Front Panel Keypads

consoles\keypad.eps
MODE
BACKUP
FUNCT-
TION
PRINT CHANGE STEP
PAPER
FEED
ENTER
QZ.
ABC
DEF
GHI JKL MNO
PRS TUV WXY
ALARM
TEST
TANK
SENSOR
,
+/-
0
789
123
456
1
4 3
2
You use the front panel keypads to enter information into the system.

Arrangement of Keys

The keypads (see Figure 2-1) consist of two groups of 12 keys. The functions for each key have been established to make movement within the setup mode, entry of setup data, and selection of setup choices as simple as possible
.
Legend for numbered boxes:
1. Maintenance Report (white) key 3. Alphanumeric keypad
2. Maintenance Tracker (blue) key 4. Operating keypad
Figure 2-1. Console Keypads

OPERATING KEYS

The 12 left-hand keys are operating keys. They allow you to access and print data, start and stop in-tank leak test procedures, program the system, test system operation and review diagnostic information. (See “Using the Operating Keys” on page 2-2.)

ALPHANUMERIC KEYS

The 12 right-hand keys have alphanumeric and cursor movement functions for entering setup information.
2-1
2 Front Panel Keypads Using the Operating Keys
MODE
FUNC­TION
STEP
If a numeric value is required for entry of a particular setup parameter, the keys provide only numeric functions. If either alphabetic or numeric characters may be entered, the keys provide both alphabetic and numeric functions. (See “Using the Alphanumeric Keys” on page 2-3).

BLUE KEY (MAINTENANCE TRACKER - TLS-350 ONLY)

Contractor plugs a valid ID Key into the TLS and presses the blue key to log in for a work session. Note: This key is available in consoles with Version 27 and higher software. In addition to certain hardware requirements, the Maintenance Tracker feature must be enabled for this key to function.

WHITE KEY (MAINTENANCE REPORT - TLS-350 ONLY)

Press the white key to printout up to the last 75 maintenance history records. Additional records going back up to 3 years are also selectable. Note: This key is available in consoles with Version 27 and higher software and is functional only if the Maintenance History or Maintenance Tracker feature enabled.

Using the Operating Keys

Operating key functions are summarized below.
ALARM
TEST
ALARM/TEST
Shuts off audible alarm and clears alarms that have returned to normal condition. Will not shut off display indicators or disable alarm function. If your system has a printer, it will print an alarm or warning report when this button is pressed.
Used to activate and de-activate output relays when OUTPUT RELAY TEST function is used.
MODE
Select operating modes: Normal Mode, Setup Mode, Diagnostic Mode.
If MODE is pressed while in a Function or Step, the system will advance to the next Mode.
FUNCTION
The FUNCTION key is used to scroll through and access functions within a Mode.
If FUNCTION is pressed while in a Step, the system will advance to the next Function.
STEP
Use the STEP key to move from one procedure to the next within a Function.
2-2
2 Front Panel Keypads Using the Alphanumeric Keys
TANK
SENSOR
CHANGE
ENTER
BACKUP
PRINT
TAN K/ S EN S OR
The TANK/SENSOR key is used to advance by tank or sensor through setup procedures or dis­played data.
CHANGE
CHANGE is used in Normal and Setup modes to enter data, revise existing data or change an entry.
ENTER
ENTER completes a selection or enters data into a function. It is also used to start certain func­tions such as leak tests.
BACKUP
BACKUP lets you move back through Steps, Functions and Modes to access data or entries you have already passed in the normal progression. It eliminates the need to move completely through a function or mode to access a step recently passed.
BACKUP will move through the hierarchy of commands as follows: through Steps within a Func­tion to that Function; then back through Functions to Mode; then back through Modes.
PRINT
Press PRINT to generate inventory, delivery, leak test, status, setup, diagnostic and alarm history reports.

Using the Alphanumeric Keys

You use alphanumeric keys to enter data during the setup process. When a numeric value is required (i.e.gallons, time, etc.), the keys provide only a numeric function. When you can enter either alphabetic or numeric characters (i.e. station headers, sensor locations, etc.), the keys provide both functions.
2-3
2 Front Panel Keypads Using the Alphanumeric Keys

ENTERING ALPHANUMERIC DATA

Keys 0 through 9 provide both alphabetic and numeric capability by activating each character shown on the key with successive pushes of the key. Table 2-1 shows characters assigned to each of the numeric keys for all languages except Japanese, Russian, Turkish, and Greek.
Table 2-1. Character Assignments for Numeric Keys
Key 1st Key Press 2nd Key Press 3rd Key Press 4th Key Press 5th Key Press
Key 0 ‘space’ ‘-’ ‘,’ ‘0’ ‘*’
Key 1 ‘Q’ ‘Z’ ‘.’ ‘1’ ‘&’
Key 2 ‘A’ ‘B’ ‘C’ ‘2’ ‘=’
Key 3 ‘D’ ‘E’ ‘F’ ‘3’ ‘%’
Key 4 ‘G’ ‘H’ ‘I’ ‘4’
Key 5 ‘J’ ‘K’ ‘L’ ‘5’
Key 6 ‘M’ ‘N’ ‘O’ ‘6’
Key 7 ‘P’ ‘R’ ‘S’ ‘7’
Key 8 ‘T’ ‘U’ ‘V’ ‘8’
Key 9 ‘W’ ‘X’ ‘Y’ ‘9’
1
Character only available when entering the Modem Setup String.
1
1
1
For example, to enter an “A” in a station header, which accepts either alphabetic or numeric characters, you press the key once. Push the key again to change the character to a “B”, again to enter a “C”, and again to enter a “2”.
The period (.) is on key “1”.
When the correct selection is displayed, press the key to move the cursor to the next position and enter the required character as described. When all the characters have been entered, press ENTER.
If you enter an incorrect character, you may use the arrow keys to move the cursor to the character, press CHANGE, and enter the correct character.

SPECIAL CHARACTERS AND CURSOR MOVEMENT

Several keys let you enter special characters and move the cursor as follows:
The Zero key has a comma (,) plus two special characters that can be used in making alphanumeric entries. They are:
,
0
= Space (no character)
— = Dash
(a “*” character is generated by pressing this key 5 times).
2-4
2 Front Panel Keypads Using the Alphanumeric Keys
+/-
The Right-Arrow key lets you advance the cursor to the right when making alphanumeric entries such as station headers and when selecting certain parameters such as module configurations. The step-by-step setup instructions will identify when this function should be used. The . (decimal) is used in numeric entries as required. It is not used as a period for text entries.
The Left-Arrow key lets you move the cursor to the left.
The +/- is used to identify a positive or negative value.
2-5

3 Setup Mode Organization

The Setup Mode is used to enter information and operating parameters that govern the way your system monitors your installation. Setup data is entered via the front panel keypads. The previous section describes in detail the functions of each key.

Functions

Functions are the major groups in the Setup Mode of the console.
IMPORTANT! The list below contains all of the available Setup Mode functions. However, only the functions relevant to your console and its installed options and connected detection systems will be accessible in setup.
System Setup
Communications Setup
In-Tank Setup
Fuel Management Setup
In-Tank Leak Test Setup
Pressure Line Leak Setup
WPLLD Line Leak Setup
Line Leak Detector Setup [VLLD]
Line Leak Test Setup
Line Leak Lockout Setup
Pump Sensor Setup
Pump Relay Monitor Setup
Reconciliation Setup
Liquid Sensor Setup
Vapor Sensor Setup
Groundwater Sensor Setup
2-Wire C.L. Sensor Setup
3-Wire C.L. Sensor Setup
External Input Setup
Output Relay Setup
PLLD Line Disable Setup
WPLLD Line Disable Setup
Line Disable Setup [VLLD]
Smart Sensor Setup
VMC Setup
Archive Utility

Steps

Within each FUNCTION are STEPS at which you enter setup data.

Setup Mode Programming Table

The table below takes you through the complete setup mode as it appears in the console display with all features installed (all choices may not appear on your TLS). Always press the ENTER key after entering data. If you press the STEP, FUNCTION, or MODE key without pressing ENTER, the data will not be saved. It is a good idea to print
3-1
3 Setup Mode Organization Setup Mode Programming Table
a setup report for record keeping purposes after completing your system’s setup. In the System Setup Table below,
FUNCTION or STEP refers to pressing that key on the front panel.
Setup Mode Table
FUNCTION SYSTEM SETUP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
System Language - English/ and second language as ordered System Units (U.S./Metric/Imperial Gallons) Date/Time Format Set Month Day Year Set Time Station Header Line 1 (Line 2/Line 3/Line 4) Shift #1 Start Time (Shift 2/Shift 3/Shift 4) Shift BIR Printouts (Enable/Disable) Daily BIR Printouts (Enable/Disable) Ticketed Delivery (Enable/Disable) TC Ticketed Delivery (Enable/Disable) Close Day Of Week Daily Dlvy Var Rpts (Disable/Enable) Weekly Dlvy Var Rpts (Disable/Enable) Periodic Dlvy Var Rpts (Disable/Enable) Daily Book Dlvy Var Rpts (Disable/Enable) Weekly Book Dlvy Var Rpts (Disable/Enable) Periodic Book Dlvy Var Rpts (Disable/Enable) Daily Var Analy Rpts (Disable/Enable) Weekly Var Analy Rpts (Disable/Enable) Periodic Var Analy Rpts (Disable/Enable) Tank Per Tst Needed Wrn (Disable/Enable) Tank Per Tst Needed Wrn Days Tank Per Tst Needed Alm Days Tank Ann Tst Needed Wrn Days Tank Ann Tst Needed Alm Days Line Reenable Method (Pass Line Test/Alarm Acknowledge) Line Per Tst Needed Wrn (Disable/Enable) Line Per Tst Needed Wrn Days Line Per Tst Needed Alm Days Line Ann Tst Needed Wrn (Disable/Enable) Line Ann Tst Needed Wrn Days Line Ann TsT Needed ALM Days Remote Printer Page Eject Print Tc Volume Temp Compensation Tanker Load Report Stick Height Offset (Disable/Enable) Ullage (90%/95%) H-Protocol Data Format Precision Test Duration (12 - 744 hrs [w/o CSLD]/60 - 744 hrs [w/CSLD])
3-2
3 Setup Mode Organization Setup Mode Programming Table
FUNCTION
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
0.2 gph (0.76 lph) Line Test Auto-Confirm (Enable/Disable)
0.1 gph (0.38 lph) Line Test Auto-Confirm (Enable/Disable) Daylight Savings Time (Disable/Enable) HRM-QPLD Printouts (Enable/Disable) Re-direct Local PrintouT (Enable/Disable) Euro Protocol Prefix Bdim Trans Alarm Delay System Security Code Maintenance History (Enable/Disable) Tank C h a rt Se c u rity Custom Alarms Service Notice Inventory Alarms Threshold Units (Standard, All % Full, All Volume, All Height, Custom) System Beeper (Enable/Disable) Mass/Density Fiscal Height Security Alarm Reduction (Enable/Disable)
COMMUNICATION SETUP
STEP
Comm Board Port Settings - Repeat for each board (Baud Rate/Parity/Stop Bit/Data Length/ Dial Type/Answer On/Code/Modem Setup String/Dial Tone Interval/DTR Normal State
STEP
Auto Transmit Setup (Transmit Message Setup/Auto-Transmit Delay Time/Auto-Transmit Repeat Time)
STEP
STEP
STEP
STEP
Phone Directory Setup Auto Dial Setup Auto Dial Alarm RS-232 End Of Message
FUNCTION
IN-TANK SETUP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
Tank Config Module 1 (Up To 3) Product Label Product Code Thermal Coeff. Tank Density Tank Diameter Tank Profile (1 Pt/4 Pts/20 Pts/linear/50 Pts) Full Volume Meter Data Present Vapor Loss Factor End Factor (None/Flat/Hemispherical/Other) End Value Calibration Update Float Size Water Mini mum Water Warning Limit (Not Active For Tanks With High Alcohol Probes) High Water Limit (Not Active For Tanks With High Alcohol Probes) Water Alarm Filter (Not Active For Tanks With High Alcohol Probes) Max Or Label Volume
3-3
3 Setup Mode Organization Setup Mode Programming Table
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
Overfill Limit High Product Delivery Limit Low Product Leak Alarm Unit Sudden Loss Limit Tank Ti l t Probe Offset Siphon Manifolded Line Manifolded Leak Minimum Periodic Leak Minimum Annual Periodic Test Type Annual Test Fail Alarm Periodic Test Fail Alarm Gross Test Fail Alarm Annual Test Averaging Periodic Test Averaging Tank Te s t N oti f y Tank Te s t S iph o n B rea k Stick Offset Delivery Delay Pump Threshold
FUNCTION
FUNCTION
FUNCTION
FUEL MANAGEMENT SETUP
STEP
STEP
STEP
Delivery Warn Days XX.X Fuel Management Auto Print Average Daily Sales
IN-TANK LEAK TEST SETUP
STEP
STEP
Test M e t hod ( S i ngl e Ta n k/A ll Ta n k s ) Test Frequency (On Date/Annually [Month/Week, Day]/Monthly [Week, Day]/Weekly [Day]/
Daily/ Auto [If line leak or pump sense]/CSLD - if enabled [Prob. Detect.(9%/99%)]/Climate Factor [Moderate/Extreme])
STEP
STEP
STEP
STEP
STEP
STEP
Gross Test Auto-Confirm (If CSLD select with Pump Sense) Test Start Time Leak Test Rate (0.2gph [0.76 lph]/0.1 gph [0.38 lph]) Test D u r atio n Leak Test Early Stop Report Only - if CSLD selected (Disabled/End of Month/Day 15 and End of Month/Day 25 and
End of Month)
STEP
Leak Test Report Format (Normal/Enhanced)
PRESSURE LINE LEAK SETUP
STEP
STEP
STEP
STEP
Line Config. - Module 1 ( up to 3) Pressure Line Label Piping Type Line Length
3-4
3 Setup Mode Organization Setup Mode Programming Table
FUNCTION
STEP
User Defined Pipe Type - If selected in Piping Type (1st Line Length/2nd Line Length - if neces­sary/1st Bulk Modulus/2nd Bulk Modulus- if necessary/Thermal Coeff.)
STEP
STEP
STEP
STEP
Thermal Coefficient - If certain piping types selected
0.2 gph (0.76 lph) Line Leak Test Scheduling (Disabled/Repetitive/Monthly/Manual)
0.1 gph (0.38 lph) Line Leak Test SchedulingTest (Disabled/Repetitive/Auto/Manual) Passive 0.1 gph (0.38 lph) Line Leak Testing (if certain pipe type selections made and 0.1 gph
line leak test shedule selection is auto)
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
Shutdown Rate (3.0 gph [11.3 lph]/0.2 gph [0.76lph]/0.1 gph [0.38 lph]/None) Low Pressure Alarm Shutoff (No/Select Value) Select Tank - in which PLLD controlled pump is installed (None/Select Number) Dispense Mode Pressure Transducer (Non-Vented/Vented/High Pressure) Pressure Offset Value Mechanical Blender Blend Partners
WPLLD LINE LEAK SETUP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
Line Config. Module 1 ( up to 3) WPLLD Line Label Piping Type Line Length
0.2 gph (0.76 lph) Test (Disabled/Repetitive/Monthly/Manual)
0.1 gph (0.38 lph) Test (Disabled/Auto/Manual) Shutdown Rate (3.0 gph [11.3 lph]/0.2 gph [0.76lph]/0.1 gph [0.38 lph]/None) Dispense Mode Pressure Offset Value
FUNCTION
FUNCTION
LINE LEAK DETECTOR SETUP (Volumetric)
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
Line Config. Module 1 ( up to 8) Enter Pipe Label Tank # Dispense Mode (Standard/Manifold:Alternate/Manifold:Sequential/Manifold:All Pumps) Fuel Type (Gasoline/Diesel) 2-inch (50mm) Piping Length 3-inch (76mm) Piping Length Pipe Type (Steel/Fiberglass/2-wall Fiberglass/Flexible) Pump Pressure Shutdown Rate (3.0 gph [11.3 lph]/0.2 gph [0.76lph]/0.1 gph [0.38 lph]) Pumpside Test Wait Mode (Temp. Meas./Vol. Chg. Meas.) NPB Partner
LINE LEAK TEST SETUP
STEP
STEP
Leak Test Method (All Lines/Single Line) Test Frequency (On Date/Annually [Month/ Week, Day]/Monthly [Week, Day]/ Weekly [Day]/
Daily)
STEP
STEP
Leak Test Start Time Test Rate (0.2 gph [0.76 lph]/0.1 gph [0.38 lph])
3-5
3 Setup Mode Organization Setup Mode Programming Table
FUNCTION
FUNCTION
FUNCTION
FUNCTION
LINE LEAK LOCKOUT SETUP
STEP
Lockout Schedule (Daily [Start Time/Stop Time]/ Individual [Start Day/Time/Stop Day/Time])
PUMP SENSOR SETUP
STEP
STEP
STEP
Pump Sense Config. Module 1 ( up to 8) Select Tank Dispense Mode
PUMP RELAY MONITOR SETU P
STEP
STEP
STEP
Pump Relay Config. Module 1 ( up to 8) Enter Pump Monitor Label Select Pump Relay (None/PumpSense/PLLD/WPLLD/VLLD/Relay [Pump Control Output
only])
STEP
STEP
Stuck Delay - 5 - 600 sec (Visible only if Relay assigned) Select Max Run Time - 1 - 24 hr (Visible If None was selected for Pump Relay)
RECONCILIATION SETUP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
STEP
Dispenser Module Data String Automatic Daily Closing Time Auto Shift #1 Closing Time Auto Shift #2 Closing Time Auto Shift #3 Closing Time Auto Shift #4 Closing Time Periodic Reconciliation Mode (Monthly/Rolling [Length]) Periodic Reconciliation Alarm (Disabled/Enabled) Periodic Reconciliation Alarm Threshold Periodic Reconciliation Offset Remote Report Format (Line/Column) Temp Compensation (Standard/TC Vol) Meter Calibration Offset Modify Tank/Meter Map
FUNCTION
FUNCTION
FUNCTION
LIQUID SENSOR SETUP
STEP
STEP
STEP
Sensor Config. - Module 1 (up to 8) Sensor Location Sensor Types (Tri-State/NC/Dual Float Hydrostatic/Dual Float Discriminating/Dual Float High
Vapor/Interceptor)
STEP
Category (Annular Space/Dispenser Pan/Monitor Well/STP Sump/Piping Sump/Other)
VAPOR SENSOR SETUP
STEP
STEP
STEP
STEP
Sensor Config. - Module 1 (up to 8) Sensor Location Sensor Threshold Category (Annular Space/Dispenser Pan/Monitor Well/STP Sump/Piping Sump/Other)
GROUNDWATER SENSOR SETUP
STEP
Sensor Config. - Module 1 (up to 8)
3-6
3 Setup Mode Organization Setup Mode Programming Table
FUNCTION
FUNCTION
FUNCTION
STEP
STEP
Sensor Location Category (Annular Space/Dispenser Pan/Monitor Well/STP Sump/Piping Sump/Other)
2-WIRE CL SENSOR SETUP
STEP
STEP
STEP
STEP
Sensor Config. - Module 1 (up to 8) Sensor Location Sensor Types (Discrim. Interstitial/Ultra 2) Category (Annular Space/Dispenser Pan/Monitor Well/STP Sump/Piping Sump/Other)
3-WIRE CL SENSOR SETUP
STEP
STEP
STEP
STEP
Sensor Config. - Module 1 (up to 8) Sensor Location Sensor Mode (Standard/High Vapor) Category (Annular Space/Dispenser Pan/Monitor Well/STP Sump/Piping Sump/Other)
EXTERNAL INPUT SETUP
STEP
STEP
STEP
Input Config. - Module 1 (up to 8) Input Name External Input Type (Standard [NO/NC]/Generator [Select Orientation (NO/NC)/Generator
Tank [All Tanks/By Tank]/Pump Sense [Select Orientation (NO/NC)/Select Tank (Tank #/ None)/Dispense Mode)
STEP
Standard ACK (NO/NC)
FUNCTION
FUNCTION
FUNCTION
OUTPUT RELAY SETUP
STEP
STEP
STEP
Relay Config. - Module 1 (up to 8) Enter Relay Designation Select Relay Type (Standard [NO/NC]/Pump Control Output [Select Tank (None/Tank #)]/
Momentary [NO/NC]/Pump Comm Control [Select Tank (None/Tank #)])
STEP
Relay Assignments - for each relay except Pump Comm Control types (In-Tank Alarms [None/ All /Single]/ Liquid Sensor Alarms [None/All /Single]/ Vapor Sensor Alarms [None/All /Single]]/ External Inputs [None/All /Single]]/ Line Leak Alarms - VLLD [None/All /Single]/ Groundwater Alarms [None/All /Single]/ 2-Wire CL (Type A) Alarms [None/All /Single]/ 3-Wire CL (Type B) Alarms [None/All /Single]/ Power Side DIM Alarms [None/All /Single]/ Reconciliation Alarms [None/All /Single]/ PLLD Alarms [None/All /Single]/ WPLLD Alarms [None/All /Single]/ Comm Side DIM Alarms [None/All /Single]/ Pump Relay Monitor Alarms [None/All /Single]
PLLD LINE DISABLE SETUP
STEP
Relay Assignments - for each relay except Pump Comm Control types (In-Tank Alarms [None/ All /Single]/ Liquid Sensor Alarms [None/All /Single]/ Vapor Sensor Alarms [None/All /Single]]/ External Inputs [None/All /Single]]/ Line Leak Alarms - VLLD [None/All /Single]/ Groundwater Alarms [None/All /Single]/ 2-Wire CL (Type A) Alarms [None/All /Single]/ 3-Wire CL (Type B) Alarms [None/All /Single]/ Power Side DIM Alarms [None/All /Single]/ Reconciliation Alarms [None/All /Single]/ PLLD Alarms [None/All /Single]/ WPLLD Alarms [None/All /Single]/ Comm Side DIM Alarms [None/All /Single]/ Pump Relay Monitor Alarms [None/All /Single]
WPLLD LINE DISABLE SETUP
STEP
Relay Assignments - for each relay except Pump Comm Control types (In-Tank Alarms [None/ All /Single]/ Liquid Sensor Alarms [None/All /Single]/ Vapor Sensor Alarms [None/All /Single]]/ External Inputs [None/All /Single]]/ Line Leak Alarms - VLLD [None/All /Single]/ Groundwater Alarms [None/All /Single]/ 2-Wire CL (Type A) Alarms [None/All /Single]/ 3-Wire CL (Type B) Alarms [None/All /Single]/ Power Side DIM Alarms [None/All /Single]/ Reconciliation Alarms [None/All /Single]/ PLLD Alarms [None/All /Single]/ WPLLD Alarms [None/All /Single]/ Comm Side DIM Alarms [None/All /Single]/ Pump Relay Monitor Alarms [None/All /Single]
3-7
3 Setup Mode Organization Setup Mode Programming Table
FUNCTION
FUNCTION
FUNCTION
FUNCTION
LINE DISABLE SETUP (VLLD)
STEP
Relay Assignments - for each relay except Pump Comm Control types (In-Tank Alarms [None/ All /Single]/ Liquid Sensor Alarms [None/All /Single]/ Vapor Sensor Alarms [None/All /Single]]/ External Inputs [None/All /Single]]/ Groundwater Alarms [None/All /Single]/ 2-Wire CL (Type A) Alarms [None/All /Single]/ 3-Wire CL (Type B) Alarms [None/All /Single]/ Power Side DIM Alarms [None/All /Single]/ Reconciliation Alarms [None/All /Single]/ PLLD Alarms [None/All / Single]/ WPLLD Alarms [None/All /Single]/ Comm Side DIM Alarms [None/All /Single]/ Pump Relay Monitor Alarms [None/All /Single]
SMART SENSOR SETUP
STEP
STEP
STEP
SS Config. - Module 1 (up to 8) Enter SmartSensor Label Select SS Category (Air Flow Meter[ISD System Device - ref. manual 577013-800]/ Vapor
Pressure [ISD System Device - ref. manual 577013-800]/ Mag Sensor/ Vac Sensor/ ATMP Sensor/ Uknown)
VMC SETUP
STEP
Add/Edit/Remove VMC Serial Number
ARCHIVE UTILITY
STEP
STEP
STEP
Save Setup Data Restore Setup Data Clear Setup Data
3-8

4 Prior to Applying AC Power to the Console

Please read this section before applying AC power to the console.

Security Code Enable/Disable

Access to all setup functions through either the front panel and/or the RS-232 interface can be restricted by the use of security codes. Once this feature has been activated, only persons knowing the user-designated codes may enter or change any setup values.
This feature will prevent unauthorized persons from intentionally or accidentally entering or changing setup values.
Two separate Security Codes may be entered—one to restrict access to the Setup Mode from the front-panel keyboard and another to restrict remote access through the RS-232 interface.
Open the left front panel door and locate the slide switch for the battery and the DIP switch. See appropriate figure for your console (Figure 4-1 - Figure 4-3).

TLS-300 CONSOLES

IMPORTANT! DIP switch #2 controls the power to the front-panel display and must be in the OPEN position!
If you want to enable the security code feature and require entering of the security code(s) for front-panel and/or RS-232 system setup access, make sure that switches #3 and/or #4 on DIP switch S2 are in the Closed position.
If you want to disable the security code feature and allow front panel and RS-232 system setup access, make sure that switches #3 and #4 on DIP switch S2 are both in the OPEN position.

TLS-350 CONSOLES

If you want to disable the security code feature and allow front panel and RS-232 system setup access, make sure that switches #1 and #2 on DIP switch SW2 are both in the OPEN position.
If you want to enable the security code feature and require entering of the security code(s) for front-panel and/or RS-232 system setup access, make sure that switches #1 and/or #2 on DIP switch SW2 are in the Closed position.
IMPORTANT! DIP switch #3 controls the power to the front-panel display and must be in the OPEN position! When switch #3 is closed, the console display remains blank. For international operation only! - set DIP switch 3 to the Closed position to enable HRM.
DIP switch #4 is not used at this time and may be in either position. DIP switch #1 is not used at this time and may be in either position.
4-1
4 Prior to Applying AC Power to the Console Security Code Enable/Disable
consoles\keypad.eps
MODE
BACKUP
FUNCT-
TION
PRINT CHANGE STEP
PAPER
FEED
ENTER
QZ.
ABC
DEF
GHI JKL MNO
PRS TUV WXY
ALARM
TEST
TANK
SENSOR
,
+/-
0
789
123
456
1
4 3
2
Legend for numbered boxes:
1. Maintenance Report (white) key 3. Alphanumeric keypad
2. Maintenance Tracker (blue) key 4. Operating keypad
4-2
4 Prior to Applying AC Power to the Console Security Code Enable/Disable
1
1
2
3
S1
OPEN
1234
S2
6
5
4
consoles\300dp1.eps
8 7
Legend for numbered boxes:
1. Battery Backup Switch (S1) shown in OFF position 5. DIP switch 1 can be in either position - It is shown in closed
2. Front Panel Security Code (DIP Switch 4) 6. Switch (S2)
3. RS-232 Security Code (DIP Switch 3) 7. S1 and S2 Locations in Consoles with Through-Hole Mount
4. Front Panel Display (DIP Switch 2) 8. S1 and S2 Locations in Consoles with Surface Mount CPU
Figure 4-1. Battery Backup Switch and DIP Switch Location - TLS-300 Console
position (open side up, number side down)
CPU Board
Board
4-3
Loading...
+ 197 hidden pages