Veeder-Root makes no warranty of any kind with regard to this publication, including but not
limited to, the implied warranties of merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential
damages in connection with the furnishing, performance, or use of this publication.
The information contained in this publication may be subject to change without notice.
This publication contains proprietary information which is protected by copyright. All rights
reserved. No part of this publication may be photocopied, reproduced, or translated to another
language without the prior written consent of Veeder-Root.
Full GVR EMEA contact information contact information and product documentation is available
for viewing and download by distributors from the GVR Extranet: www.mygvr.com
Distributors requiring GVR Extranet login details should contact Eumarketing@gilbarco.com to
obtain an ID and password.
Figure 22.Pouring Sealing Compound Into Sleeve ..................................................22
Figure 23.Securing Splice Enclosure With Cable Tie...............................................23
Figure 24.Example Wireless Installation With Process Connection
And Single Channel Surge Protector .......................................................24
Figure 25.Example Wireless Installation With Riser Pipe
And Single Channel Surge Protector .......................................................24
Tables
Table 1.Calculation sheet for determining the correct probe length .....................16
Table 2.Dimensions for Steel Riser Pipes and Mag Probe Floats .......................17
iv
Introduction
General
This document describes the procedures necessary to prepare a site for the installation of the Veeder-Root TLS
Series Underground Storage Tank Monitoring Systems in locations governed by the ATEX Directive 94/9/EC or
locations that recognize the IECEx scheme.
For installing UL/cUL approved Mag Probes use Manual No. 577013-744.
Veeder–Root maintains a continuous process of product development and therefore product specifications may
not be as described in this manual. Please contact the Veeder-Root office nearest you, or visit our website at
www.veeder.com for information on new or updated products. Changes affecting products or procedures
described in this manual will be reported in subsequent revisions. Veeder–Root has taken every care in the
compilation of this manual; however it is the installers' responsibility to take every precaution to safeguard
themselves and others.
Every person working with Veeder–Root equipment is expected to take every safety precaution possible and to
have read this manual, particularly the sections referring to health and safety.
Deviation from the specifications contained in this manual can result in rework, delays in system installation and
additional installation charges.
Contractors are advised to contact their nearest Veeder–Root office where local conditions may preclude using
the specifications contained in this manual.
Product Description
SYSTEMS
All Veeder–Root systems have been designed for ease of operation. System consoles have liquid crystal display
screens and one-touch function keys to guide the user through all operating functions. The status of all in-tank
probes and leak detection sensors is available immediately on the LCD screen, on the system's printer or, through
the system's communication facilities, on the point-of-sale terminal or back office computer.
IN–TANK PROBES
Magnetostrictive probes are ATEX certified as:eII 1/2 G Ex ia IIA T4, II 1 G Ex ia IIA T4, per CERTIFICATE
NO. 06 ATEX 0508841X
And, IECEx certified as: Ex ia IIA T4 Ga/Gb, Ex ia IIA T4 Ga, per Certificate No. IECEx
UL 06.0001X
Mag Probe ingress protection rating is IP 68 at a depth of 3 meters with a duration of 30 days as tested by the
notified body (ExNB) UL LLC.
Depending on probe type, canister material may be aluminum or black conductive polymer.
For further information on the performance and specification of in-tank probes, please contact your local Veeder-
Root representative.
SURGE PROTECTORS
In a Veeder-Root system, each Intrinsically Safe Device may use an optional surge protector in place of the
weatherproof junction box located in Zone 1. Surge protectors consist of a certified in-line device or a simple
apparatus conforming to the requirements of Standard No. IEC/EN 60079-14, Electrical installations design,
selections and erection.
Surge Protectors are either an ATEX Certified Device as
13 ATEX 13060507X or are Simple Apparatus. Surge Protectors can also be an IECEx certified device per
Certificate No. IECEx UL 13.0074X.
e II 2 G Ex ia IIA Gb T4 per Certificate No. DEMKO
1
TLS Magnetostrictive Probes International Installation GuideHealth And Safety
Health And Safety
SAFETY SYMBOLS
The following safety symbols are used throughout this manual to alert you to important safety hazards and
precautions.
Explosive
Fuels and their vapors are extremely
explosive if ignited.
WARNING
Heed the adjacent instructions to avoid
equipment damage or personal injury.
GLOVES
Wear gloves to protect hands from irritation or injury.
Read All Related Manuals
Knowledge of all related procedures before you
begin work is important. Read and understand
all manuals thoroughly. If you do not understand
a procedure, ask someone who does
INJURY
Careless or improper handling of epoxy sealant
materials can result in bodily injury.
WEAR EYE PROTECTION
Epoxy sealant in contact with eyes can cause
serious injury. Always wear eye protection when
sealing wire splices.
GENERAL
Ensure that all local council, E.C. laws and regulations are complied with. Also ensure that all recognised safety
codes are followed.
Every person working with Veeder–Root equipment is expected to take every safety precaution possible in the
installation of TLS Systems.
Contractors must ensure that supervisory personnel on the installation site are aware of their presence and
requirements, especially the provision of safe working areas and isolation from AC electrical power.
Leaking underground tanks can create serious environmental and health hazards. It is the contractor's
responsibility to comply with the instructions and warnings found in this manual.
Substitution of specified components may impair intrinsic safety.
WARNING
Explosion could occur if other wires share ducts with intrinsically safe probe or
sensor wiring. Ducting for probes and sensors must not contain any other wiring
circuits except where permitted by local wiring codes and regulations.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY
PR ECAUTI ONS COULD CAU SE DAMAGE TO PROPE RTY, ENVI RON M ENT,
RESULTING IN SERIOUS INJURY OR DEATH.
EQUIPMENT PROTECTION
TLS monitoring equipment, including the Magnetostrictive Probe, is designed and certified to comply with the
Directive 94/9/EC (ATEX) and the IECEx scheme. The installer must consider any local regulations, which may
differ or be more stringent, prior to installing any equipment. The suitability/safety of any installation is ultimately
determined by the local authority having jurisdiction.
2
TLS Magnetostrictive Probes International Installation GuideHealth And Safety
The Magnetostrictive Probe that is part of the TLS Monitoring System is equipment Category 1 intended to be
installed in a Zone 0 hazardous location. Extreme care must be taken when determining the suitability of the
installation conditions and operation of the TLS Monitoring System. Procedures for installing either in a process
connection or riser pipe are detailed beginning on
aid in the determination if a probe is to be installed in a process connection or riser pipe:
1. Equipotential grounding of the installation site,
2. Minimizing static hazards associated with the underground storage of flammable liquids, and
3. Protection of the system against lightning strikes and any other source of possible electrical surges caused by
electrical railway systems, high voltage direct current facilities and the like.
page 13. At least the following items must be considered and will
EQUIPOTENTIAL GROUNDING
Consult any local regulations prior to installing a Magnetostrictive Probe into any tank. Veeder-Root supplies
approved process connections for installations where direct connection between the probe body and tank structure
is required (see Probe Installation Using Process Connection instructions below).
The intrinsically safe circuit in the TLS Monitoring System is derived from a fuse protected zener diode intrinsic safety
barrier. This type of explosion protection requires that the intrinsically safe electric circuit is referenced to the safety
ground associated to the mains circuit. If the site has a submersible pump (DIN/EN 15268) connected to the same
mains safety ground as the TLS Monitoring System Console and it is installed in a metallic riser of a metallic storage
tank, the zener diode barrier must be referenced to the same earth (safety) ground.
MINIMIZATION OF ELECTROSTATIC HAZARDS
Consult any local regulations prior to installing a Magnetostrictive Probe into any tank. Veeder-Root supplies
approved process connections for installations where direct connection between the probe body and tank structure
is required (see Probe Installation Using Process Connection instructions below).
The magnetostrictive probe housing complies with the 500 volt electrical strength requirements in IEC/EN 60079-
11. In addition, the probe housing provides an electrostatic dissipative path to the zener diode barrier earth ground
that must be referenced to the common grounding system. The electrostatic resistive path is less than 1 megohm.
All TLS Consoles provide an alarm if either of the two wires to the magnetostrictive probe is disconnected or short
circuited due to a malfunction.
If a probe must be serviced or replaced, observe any required relaxation time prior to opening any covers and
removing the probe.
LIGHTNING AND SURGE PROTECTION
Consult any local regulations prior to installing a Magnetostrictive Probe into any tank. Local rules or regulations may
require surge arrestors when installing equipment that crosses from a less restrictive zone, e.g., zone1 to zone 0
independent of the risk assessment. When required Veeder-Root can supply appropriate surge protection devices.
In locations where the intrinsically safe cables or circuits are considered to be at risk of developing hazardous
potential differences within Zone 0, an external surge protection device may be needed. Perform the lightning risk
analysis to determine if surge protection is required, and if necessary, the surge protector shall be installed in
accordance with IEC/EN 60079-25 and IEC/EN 60079-14. Reference
locations for a surge protector.
When they are deemed necessary, Veeder-Root requires the installation of external surge protection devices that are
classified as simple apparatus only. Only gas-discharge type surge protectors that comply with Clause 12 of IEC/EN
60079-25 are acceptable. Additional installation requirements for surge protection devices are defined in Clause
12.3 of standard IEC/EN 60079-14.
The Surge Risk Protection Assessment checklist (SRPA) is available on the Veeder-Root Tech Docs CD and on our
website at http://www.veeder.com/page/Probe_Manuals. An example of the SRPA appears in Appendix A of this
manual.
Figure 14 and Figure 15 for mounting
EC-TYPE CERTIFICATES FOR AN INTRINSICALLY SAFE SYSTEM
TLS Monitoring Systems are installed according to the conditions specified in the applicable Certificates. ATEX
Certificate Number DEMKO 06 ATEX 137480X and IECEx ULD 08.0002X are referred to as the system certificate
or parent certificate for all of the equipment in a TLS Monitoring System.
3
TLS Magnetostrictive Probes International Installation GuideBefore You Begin
Except for the cables used to connect intrinsically safe apparatus, information contained on the system certificate
and each of the device certificates, provide the safety related information (Ex ia) required to install a TLS
Monitoring System. Cables used to connect intrinsically safe apparatus must be considered in determining
compliance and are limited to the maximum allowable cable parameters listed in this manual. For assistance in
calculating the required (Ex ia) safety parameters, contact GVR as described on the inside cover of this manual.
For European Community (EC) installations, additional equipment compliance information is available on the EC
Declaration of Conformity including reference to the technical standards applied by the Notified Body in creating
the respective ATEX Certificates.
THESE ARE THE CONDITIONS FOR SAFE USE WHEN INSTALLING A MAG PROBE
1. The devices have been evaluated in conjunction with the intrinsic safety system defined in DEMKO 06 ATEX
137480X. The descriptive system documents and manuals included with the aforementioned certificate must
be followed during installation and the appropriate Veeder Root accessories must be used. Manual 577014031 details applicable process connections in accordance with EN 60079-26.
2. The following condition of safe use applies to the Mag Sump Sensor: Before installing or taking into a
hazardous area, earth the unit in a Safe Area to remove any static charge. Then immediately transport the unit
to the installation site; do not rub or clean the unit prior to installation. Cleaning is not required under normal
service conditions; do not rub or clean the device after installation. If the unit is not fixed to a known earth
point when installed, ensure that a separate earth connection is made to prevent the potential of static
discharge. When fitting or removing the unit, use of anti-static footwear & clothing is required.
3. The enclosure contains aluminum. Care must be taken to avoid ignition hazards due to impact of friction.
ATTENTION!
Important Considerations - Read Prior to Installation - Metallic/Steel Tanks
Process Connection (gland): Must be used in locations where it is mandatory that the Mag Probe be
equipotentially bonded to the tank structure.
Riser Pipe: May be used in locations that do not require bonding between the Mag Probe and the tank structure.
Reference European Norm IEC/EN 60079-14: Explosive atmospheres - Part 14: Electrical installations design,
selection and erection.
Cathodically Protected Tanks: Installation selection is dependent on the considerations listed above for the
Process Connection and the Riser Pipe.
Only install TLS Magnetostrictive Probes according to one of the four procedures listed below:
Wired Connections – Mag Probe to ATG Console wiring - see Figures 1 and 18.
1. Process Connection (gland) – Zone 1 installation, Surge Protector not required
Wireless Communication – Mag Probe with RF hardware - see Figures 2, 24 and 25
3. Process Connection (gland) – Zone 1 installation, surge protector not required
4. Riser Pipe – Zone 0 installation, Surge Protector required
Before You Begin
1. Consult any local regulations prior to proceeding to determine the best installation method. The instructions
below detail how to safely install probes with process connections or in a riser pipe and will also help in
determining when surge protection is required or may be necessary.
2. Depending on the considerations above, perform a Surge Risk Protection Assessment (SRPA) of equipment
in the site. A (SRPA) checklist is available on our website at http://www.veeder.com/page/Probe_Manuals.
3. Verify the equipment needed to complete the installation as described in this manual, and, if necessary, any
equipment required following completion of the site Surge Risk Protection Assessment (SRPA).
4
TLS Magnetostrictive Probes International Installation GuideProcedures for Installing Mag Probes
Procedures for Installing Mag Probes
Riser PipeProcess Connection
Procedure for installing Mag
Probes into storage tanks
using a tube gland.
NOTE: Use a tube gland in
locations where it is
mandatory that the Mag Probe
be equipotentially bonded to
the tank structure.
Install the Mag Probe with a
process connection according to
the instructions on Figure 14 of
this manual.
Procedure for installing Mag
Probes into storage tanks
using a riser pipe.
NOTE: Use a riser pipe in
locations that do not require
bonding between the Mag
Probe and the tank structure.
Install either a sleeve or an
adapter as shown on Figure 17,
then install the Mag Probe in a
riser pipe according to the
instructions on Figure 13 of this
manual.
Mag Probe
Installation Complete
Perform a surge risk protection
assessment (SRPA), located on
appendix page A-1 of this manual
to determine the possible use of a
dual channel surge protector for
the Mag Probe.
Is a
surge protector
required ?
Yes
Install a dual channel surge
protector, part number BA-350 or
848100-002, according to Figure
11 of this manual.
Mag Probe
Installation Complete
No
Figure 1. Procedures For Installing Mag Probes Using Wired Connections
5
TLS Magnetostrictive Probes International Installation GuideProcedures for Installing Mag Probes
Mag Probe
Installation Complete
Install either a sleeve or an
adapter as shown on Figure 17,
then install the Mag Probe in a
riser pipe according to the
instructions on Figure 13 of this
manual.
Install a single channel surge
protector, part number 848100-
001, according to Figure 25 of
this manual.
Install the Mag Probe with a
process connection according to
the instructions on Figures 14 and
24 of this manual.
Riser PipeProcess Connection
Mag Probe
Installation Complete
Procedure for installing Mag
Probes into storage tanks
using a riser pipe.
NOTE: Use a riser pipe in
locations that do not require
bonding between the Mag
Probe and the tank structure.
Procedure for installing Mag
Probes into storage tanks
using a tube gland.
NOTE: Use a tube gland in
locations where it is
mandatory that the Mag Probe
be equipotentially bonded to
the tank structure.
Figure 2. Procedures For Installing Mag Probes Using Wireless Connections
6
Loading...
+ 21 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.