Veeder-Root RFMP Series, RFMP00, RFMP00R, RFMV Series, RFMV00R General Description Manual

...
Bulletin No. RFMO-G
Drawing No. LP0655
Released 12/12
Danaher Specialty Products
1-800-390-6405
www.danaherspecialtyproducts.com/Veeder-Root
MODEL RFMP - MINIATURE ELECTRONIC 5-DIGIT PROCESS METER
THREE SELECTABLE D.C. RANGES
0 to 10 V, 0(4) to 20 mA, 0 to 50 mA
MINIMUM AND MAXIMUM DISPLAY CAPTURE
LCD, REFLECTIVE OR RED/GREEN LED BACKLIGHTING
0.48" (12.2 mm) HIGH DIGITS
OPTIONAL SETPOINT OUTPUT CARD
OPTIONAL SERIAL COMMUNICATION CARD (RS232 or RS485)
OPERATES FROM 9 TO 28 VDC POWER SOURCE
FRONT PANEL PROGRAMMABLE
U
R
C
US LISTED
L
IND. CONT. EQ.
51EB
DISPLAY COLOR CHANGE CAPABILITY AT SETPOINT OUTPUT
NEMA 4X/IP65 SEALED FRONT BEZEL
GENERAL DESCRIPTION
The FLEX MINI Series provides the user the ultimate in flexibility, from its complete user programming to the optional setpoint control and communication capability. The FLEX MINI accepts a DC voltage or current input signal and provides a display in the desired unit of measure. The meter also features minimum and maximum display capture, display offset, units indicator, and programmable user input. The display can be toggled either manually or automatically between the selected displays.
The FLEX MINI display has 0.48" (12.2 mm) high digits. The LCD is available in two versions, reflective or red/green backlight. The backlight version is user selectable for the desired color and also has variable display intensity.
The capability of the FLEX MINI can be easily expanded with the addition of option cards. The setpoint output cards are field installable with programmable setpoints. Serial communications capability for RS232 or RS485 can be added with a serial option card.
The FLEX MINI can be powered from an optional Veeder Root Micro-Line/ Sensor Power Supply (MLPS), which attaches directly to the back of a FLEX MINI. The MLPS is powered from 85 to 250 VAC and provides up to 400 mA to drive the unit and sensors.
INPUT
The FLEX MINI is a DC Process meter. It features voltage and current input ranges, that are selected by the user via a programming jumper and software input range selection. The ranges consist of the following: 0 to 10 V, 0(4) to 20 mA, or 0 to 50 mA. Users should select the appropriate voltage range that
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
covers their maximum input.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use this meter to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the meter.
CAUTION: Risk of Danger.
Read complete instructions prior to
installationand operation of the unit.
CAUTION: Risk of electric shock.
SEL
2.95 (74.9)
RST
1.54 (39.1)
.15 (3.8)
.13 (3.3)
+.024
1.30
-.000 +6
(33 )
-0
1.71
(43.4)
1.29 (32.8)
2.68
(68 )
+.025
-.000 +8
-0
1
orderinG inforMation
TYPE MODEL NO. DESCRIPTION PART NUMBER
FLEX MINI FLEX MINI
FLEX MINI Single Relay Option Card RFMRL00
Optional Plug-in Cards
Accessories FLEX MINI +12 VDC Micro-Line Power Supply, 85 to 250 VAC source, 400 mA max out RFMPS1
FLEX MINI Dual Sinking Open Collector Output Card RFMSK00
FLEX MINI
FLEX MINI USB Programming Card RFMCOMUSB
Process Meter with Reflective Display RFMP00R Process Meter with Backlight Display RFMP00
RS485 Serial Communications Card RFMCOMM RS232 Serial Communications Card RFMCOMM2
General Meter SpecificationS
1. DISPLAY: 5 digit LCD 0.48" (12.2 mm) high digits RFMP00R: Reflective LCD with full viewing angle RFMP00: Transmissive LCD with selectable red or green LED backlight,
viewing angle optimized. Display color change capability with output state when using an output module.
2. POWER: Input voltage range is +9 to +28 VDC with short circuit and input polarity protection. Must use an VR model RFMPS or an NEC Class 2 or Limited Power Source (LPS) rated power supply.
MODEL
NO.
RFMPOOR --- 10 mA 40 mA
RFMPOO Red (max intensity) 85 mA 115 mA RFMPOO Green (max intensity) 95 mA 125 mA
DISPLAY COLOR
INPUT CURRENT
@ 9 VDC WITHOUT
RFMRLOO
INPUT CURRENT
@ 9 VDC WITH
RFMRLOO
3. INPUT RANGES: Jumper Selectable 0 to 10 V, 0(4) to 20 mA, 0 to 50 mA
4. SENSOR INPUTS:
INPUT
RANGE
20 / 50 mA 0.1% of span
10 VDC 0.1% of span
ACCURACY @23 °C, less than 85% RH
INPUT
IMPEDANCE
10
538 K
MAX INPUT
SIGNAL
150 mA 1 µA 70 ppm / °C
RESOLUTION
30 V 1 mV 70 ppm / °C
TEMP.
COEFFICIENT
5. OVERRANGE RATINGS, PROTECTION & INDICATION: 9 to 28 VDC power circuit is not isolated from the signal circuit.
Input Overrange Indication: “OLOL”. Input Underrange Indication: “ULUL”.
Display Overrange/Underrange Indication: “.....”/“-.....
6. RESPONSE TIME: Display: 500 msec min. Output: 800 msec max (with input filter setting of 0)
7. NORMAL MODE REJECTION: 60 dB 50/60 Hz
8. USER INPUT (USR): Programmable input. Connect USR terminal to USR COMM to activate function. Internal 10K pull-up resistor to +9 to 28 VDC.
Threshold Levels: VIL = 0.7 V max; VIH = 2.4 V min; V Response Time: 5 msec typ.; 50 msec debounce (activation and release)
= 28 VDC
MAX
9. CONNECTIONS: Wire clamping screw terminals
Wire Strip Length: 0.3" (7.5 mm) Wire Gage: 30-14 AWG copper wire Torque: 5 inch-lbs (0.565 N-m) max.
10. MEMORY: Nonvolatile E2PROM memory retains all programming parameters and max/min values when power is removed.
11. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range for RFMP00R: -35 to 75 °C Operating Temperature Range for RFMP00 depends on display color
and intensity level as per below:
Red Display 1 & 2 -35 to 75 °C
Green Display 1 & 2 -35 to 75 °C
Storage Temperature: -35 to 85 °C
Operating and Storage Humidity: 0 to 85% max. relative humidity (non-
condensing)
Vibration to IEC 68-2-6: Operational 5-500 Hz, 5 g Shock to IEC 68-2-27: Operational 30 g Altitude: Up to 2000 meters
12. CERTIFICATIONS AND COMPLIANCES: CE Approved
EN 61326-1 Immunity to Industrial Locations Emission EN 55011 Class A
IEC/EN 61010-1 UL Recognized Component: File #E179259 UL Listed: File #E137808 Type 4X Enclosure rating (Face only) IP65 Enclosure rating (Face only) IP20 Enclosure rating (Rear of unit)
Refer to EMC Installation Guidelines section of the bulletin for additional
information.
13. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 requirements for outdoor use. Installation Category I, Pollution Degree 2. High impact plastic case with clear viewing window. Panel gasket and mounting clip included.
14. WEIGHT: 3.2 oz (100 g)
INTENSITY LEVEL TEMPERATURE
3 -35 to 70 °C 4 -35 to 60 °C 5 -35 to 50 °C
3 -35 to 65 °C 4 -35 to 50 °C 5 -35 to 35 °C
2
optional pluG-in cardS
PANEL GASKET
BEZEL
PANEL
MOUNTING SCREW
NUT FASTENER
MOUNTING CLIP
ADDING OPTION CARDS
The FLEX MINI meters can be fitted with optional output cards and/or serial communications cards. The details for the plug-in cards can be reviewed in the specification section below. The plug-in cards, that are sold separately, can be installed initially or at a later date.
WARNING: Disconnect all power to the unit before installing
Plug-in card.
Note: Measurement errors may occur if signal input common is shared with
another circuit common (ie, serial common, Dual Sinking Output option card,
or Power Supply common) on multiple units.
SINGLE RELAY CARD
Type: Single FORM-C relay
Isolation To Sensor & User Input Commons: 1400 Vrms for 1 min.
Working Voltage: 150 Vrms
Contact Rating: 1 amp @ 30 VDC resistive; 0.3 amp @ 125 VAC resistive
Life Expectancy: 100,000 minimum operations
DUAL SINKING OUTPUT CARD
Type: Non-isolated switched DC, N Channel open drain MOSFET
Current Rating: 100 mA max.
V
: 0.7 V @ 100 mA
DS ON
1.0 inStallinG the Meter
INSTALLATION
The meter meets NEMA 4X/IP65 requirements when properly installed. The unit is intended to be mounted into an enclosed panel. Prepare the panel cutout to the dimensions shown. Remove the panel latch from the unit. Slide the panel gasket over the rear of the unit to the back of the bezel. The unit should be installed fully assembled. Insert the unit into the panel cutout.
While holding the unit in place, push the panel latch over the rear of the unit so that the tabs of the panel latch engage in the slots on the case. The panel latch should be engaged in the farthest
V
: 30 VDC
DS MAX
Offstate Leakage Current: 0.5 mA max.
RS485 SERIAL COMMUNICATIONS CARD
Type: RS485 multi-point balanced interface (non-isolated) Baud Rate: 300 to 38.4k Data Format: 7/8 bits; odd, even, or no parity Bus Address: 0 to 99; max 32 meters per line Transmit Delay: Selectable (refer to RFMCOMM bulletin)
RS232 SERIAL COMMUNICATIONS CARD
Type: RS232 half duplex (non-isolated) Baud Rate: 300 to 38.4k Data Format: 7/8 bits; odd, even, or no parity
USB PROGRAMMING CARD
Type: USB virtual comms port Connection: Type B Baud Rate: 300 to 38.4k Unit Address: 0 to 99
forward slot possible. To achieve a proper seal, tighten the latch screws evenly until the unit is snug in the panel (Torque to approx. 28 to 36 in-oz [0.202 to 0.26 N-m]). Do not over-tighten the screws.
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed the operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided.
The bezel should only be cleaned with a soft cloth and neutral soap product. Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the keypad of the unit.
2.0 SettinG the JuMperS
INPUT RANGE JUMPER
This jumper is used to select the proper input range. The input range selected in programming must match the jumper setting. Select a range that is high enough to accommodate the maximum input signal to avoid overloads. To access the jumper, remove the rear cover of the meter.
Warning: Exposed line voltage exists on the circuit boards. Remove all power to the meter and load circuits before accessing inside of the meter.
REMOVING THE REAR COVER
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd input terminals. To release the tab, insert a small, flat blade screwdriver between the tab and the plastic wall below the terminals. Inserting the screwdriver will provide enough pressure to release the tab locks. To replace the cover, align the cover with the input terminals and press down until the cover snaps into place.
+.025
2.68
-.000
+.8
(68 )
-.0
INPUT RANGE JUMPER
MAIN CIRCUIT
BOARD
3
+.024
1.30
-.000
+.6
(33 )
-.0
10 V
20/50 mA
INPUT RANGE
JUMPER LOCATION
3.0 inStallinG pluG-in cardS
The Plug-in cards are separately purchased option cards that perform specific
functions. The cards plug into the main circuit board of the meter
Range Jumpers
Setpoint Card
Comms or
Programming
Card
Locking Tab
4.0 WirinG the Meter
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the back of the meter. All conductors should conform to the meter’s voltage and current ratings. All cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that the power supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded wires should be tinned with solder.) Insert the lead under the correct screw-clamp terminal and tighten until the wire is secure. (Pull wire to verify tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two #18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to Electro­Magnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into the meter may be different for various installations. The meter becomes more immune to EMI with fewer I/O connections. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed below are some EMC guidelines for successful installation in an industrial environment.
1. The meter should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
CAUTION: The Plug-in cards and main circuit board contain static
sensitive components. Before handling the cards, discharge static charges from your body by touching a grounded bare metal object. Ideally, handle the cards at a static controlled clean workstation. Also, only handle the cards by the edges. Dirt, oil or other contaminants that may contact the cards can adversely affect circuit operation.
REMOVING THE REAR COVER
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd input terminals. To release the tab, insert a small, flat blade screwdriver between the tab and the plastic wall below the terminals. Inserting the screwdriver will provide enough pressure to release the tab locks. To replace the cover, align the cover with the input terminals and press down until the cover snaps into place.
c. Connect the shield to common of the meter and leave the other end of the
shield unconnected and insulated from earth ground.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be ran in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
4. Signal or Control cables within an enclosure should be routed as far as possible
from contactors, control relays, transformers, and other noisy components.
5. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional protection.
Install line filters on the power input cable to the unit to suppress power line
interference. Install them near the power entry point of the enclosure. The
following EMI suppression devices (or equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 TDK # ZCAT3035-1330A Steward # 28B2029-0A0
Line Filters for input power cables:
Schaffner # FN2010-1/07 Schaffner # FN670-1.8/07 Corcom # 1 VR3
Note: Reference manufacturer’s instructions when installing a line filter.
6. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
7. Switching of inductive loads produces high EMI. Use of snubbers across
inductive loads suppresses EMI.
Snubber: VR# PBN2002
4.1 POWER WIRING
DC Power
+9 to +28 VDC: +VDC Power Common: -VDC
CAUTION: 9 to 28 VDC
power circuit is not isolated from the signal circuit.
PWR COMMON
USR
USR COMM
-
COMM
+
INP +
+9-28 VDC
4.2 USER INPUT WIRING
Sinking Logic
USR COMM USR
The user input of the meter is internally pulled up to +9 to +28 V with 10 K resistance. The input is active when it is pulled low (<0 .7 V).
4
Connect external switching device between the
}
User Input terminal and User Input Common.
PWR COMMON
USR COMM
USR
COMM
INP +
+9-28 VDC
4.3 INPUT WIRING
CO
OSNK 1(2)
61
CAUTION: Power input common is NOT isolated from user and input
commons. In order to preserve the safety of the meter application, the power input common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth
or user inputs and input common terminals. Appropriate considerations must then be given to the potential of the user and input commons with respect to earth ground; and the common of the plug-in cards with respect to input common.
Before connecting signal wires, the Input Range Jumper should be verified for
proper position.
Input Signal (self powered)
Series Loop (must use separate supply for sensor power and each FLEX MINI)
ground potential. If not, hazardous voltage may be present at the signal
COMM
-
INP+
JUMPER
POSITION
10 VDC
+
20/50 mA DC
MAX SIGNAL
INPUT
30 VDC
150 mA
EXTERNAL POWER
COMM
+VDC
+
2 WIRE TRANSMITTER
_
2 Wire With External Power
_
2 WIRE TRANSMITTER
+
INP +
COMM
COMM
EXTERNAL POWER
COMM
+VDC
+VDC
JUMPER
POSITION
20/50 mA DC
2 Wire With RFMPS Power
_
2 WIRE TRANSMITTER
+
INP +
COMM
DC COMMON
MODEL MLPS1
INPUT POWER: 85-250 VAC, 50/60Hz, 14VA OUTPUT POWER: 12VDC UNREG. @ 400mA OPERATING TEMP: 0° TO 60°C
+12V
AC INPUT TERMINAL
!
M3424B
JUMPER
POSITION
20/50 mA DC
2 Wire With Separate Sensor And FLEX MINI Power
EXTERNAL POWER
COMM
+VDC
+
2 WIRE TRANSMITTER
_
COMM
+12V
AC INPUT TERMINAL
INP +
!
M3424B
POSITION
20/50 mA DC
DC COMMON
MODEL MLPS1
INPUT POWER: 85-250 VAC, 50/60Hz, 14VA OUTPUT POWER: 12VDC UNREG. @ 400mA OPERATING TEMP: 0° TO 60°C
COMM
+12V
AC INPUT TERMINAL
INP +
DC COMMON
!
M3424B
MODEL MLPS1
INPUT POWER: 85-250 VAC, 50/60Hz, 14VA OUTPUT POWER: 12VDC UNREG. @ 400mA OPERATING TEMP: 0° TO 60°C
4.4 SETPOINT (OUTPUT) WIRING
SINGLE SETPOINT RELAY PLUG-IN CARD
COM
N.O.
N.C.
DUAL SETPOINT N-FET OPEN DRAIN PLUG-IN CARD
COM
OSNK1
OSNK2
JUMPER
INP +
COMM
DC COMMON
MODEL MLPS1
INPUT POWER: 85-250 VAC, 50/60Hz, 14VA OUTPUT POWER: 12VDC UNREG. @ 400mA OPERATING TEMP: 0° TO 60°C
+12V
AC INPUT TERMINAL
!
M3424B
JUMPER
POSITION
20/50 mA DC
ELECTRICAL CONNECTIONS
COM
N.O.
N.C.
ELECTRICAL CONNECTIONS
(30 V MAX.)
M
Output Common is not isolated from DC Power Common. Load
must be wired between OSNK terminal and V+ of the load supply.
4.5 SERIAL COMMUNICATION WIRING
SERIAL COMMUNICATIONS PLUG-IN CARD
N/C
COMM
N/C
B-
534
61
RS485
RJ11 CONNECTOR PIN OUTS
N/C
A+
2
N/C
TX
5
RS232
COMM
43
COMM
2
N/C
RX
4.6 USB PROGRAMMING
USB PROGRAMING PLUG-IN CARD
5
5.0 revieWinG the front ButtonS and diSplay
SEL RST
BUTTON DISPLAY MODE OPERATION ENTERING PROGRAM MODE PROGRAMMING MODE OPERATION
SEL Index display through enabled values Press and hold for 2 seconds to activate Store selected parameter and index to next parameter
RST Resets values (MIN/MAX) or outputs
Advances through the program menu Increments selected parameter value or selection
OPERATING MODE DISPLAY DESIGNATORS
MAX - Maximum display capture value MIN - Minimum display capture value
Pressing the SEL button toggles the meter through the selected displays. If display scroll is enabled, the display will toggle automatically every four seconds between
the enabled display values.
“1” - To the right of the display indicates setpoint 1 output activated.
“2” - To the right of the display indicates setpoint 2 output activated.
6.0 proGraMMinG the Meter
DISPLAY
MODE
SEL
NO
Pro
Signal Input
Parameters
RST
SEL SEL SELSEL
Parameters
1-INP
PROGRAMMING MODE ENTRY (SEL BUTTON)
It is recommended all programming changes be made off line, or before installation. The meter normally operates in the Display Mode. No parameters can be programmed in this mode. The Programming Mode is entered by pressing and holding the SEL button. If it is not accessible then it is locked by either a security code, or a hardware lock.
MODULE ENTRY (SEL & RST BUTTONS)
The Programming Menu is organized into separate modules. These modules group together parameters that are related in function. The display will alternate between Pro and the present module. The RST button is used to select the desired module. The displayed module is entered by pressing the SEL button.
MODULE MENU (SEL BUTTON)
Each module has a separate module menu (which is shown at the start of each module discussion). The SEL button is pressed to advance to a particular parameter to be changed, without changing the programming of preceding parameters. After completing a module, the display will return to Pro NO. Programming may continue by accessing additional modules.
SELECTION / VALUE ENTRY
For each parameter, the display alternates between the present parameter and the selections/value for that parameter. The RST button is used to move through the selections/values for that parameter. Pressing the SEL button, stores and activates the displayed selection/value. This also advances the meter to the next parameter.
For numeric values, press the RST button to access the value. The right hand most digit will begin to flash. Pressing the RST button again increments the digit by one or the user can hold the RST button and the digit will automatically scroll. The SEL button will advance to the next digit. Pressing and holding the
SEL button will enter the value and move to the next parameter.
OVERVIEW
PROGRAMMING MENU
Secondary
Function
2-SEC
Display and Front
Panel Key
Parameters
3-dSP
PROGRAMMING MODE EXIT (SEL BUTTON)
The Programming Mode is exited by pressing the SEL button with Pro NO
displayed. This will commit any stored parameter changes to memory and return the meter to the Display Mode. (If power loss occurs before returning to the Display Mode, verify recent parameter changes.)
PROGRAMMING TIPS
It is recommended to start with Module 1 and proceed through each module in sequence. When programming is complete, it is recommended to record the parameter programming and lock out parameter programming with the user input or programming security code.
FACTORY SETTINGS
Factory Settings may be completely restored in Module 2. This is useful when encountering programming problems.
ALTERNATING SELECTION DISPLAY
In the explanation of the modules, the following dual display with arrows will appear. This is used to illustrate the display alternating between the parameter on top and the parameter’s Factory Setting on the bottom. In most cases, selections and values for the parameter will be listed on the right.
Setpoint
Output
Parameters
4-SPt
Indicates Program Mode Alternating Display
Parameter
USrIN
Factory Settings are shown.
Parameters
5-SEr
N0
Serial Setup
SEL
Selection/Value
6
6.1 Module 1 - SiGnal input paraMeterS (1-INP)
1-INP
SEL
rANGE
Input
Range
rAN6E
Select the input range that corresponds to the external signal. This selection should be high enough to avoid input signal overload but low enough for the desired input resolution. This selection and the position of the Input Range Jumper must match.
dECPt
Select the decimal point location for the Input, MIN and MAX displays. This selection also affects the dSP1 and dSP2 parameters and setpoint values.
OFSEt
The display can be corrected with an offset value. This can be used to compensate for signal variations or sensor errors. This value is automatically updated after a Zero Display to show how far the display is offset. A value of zero will remove the effects of offset.
FILtr
If the displayed value is difficult to read due to small process variations or noise, increased levels of filtering will help to stabilize the display. Software filtering effectively combines a fraction of the current input reading with a fraction of the previous displayed reading to generate the new display.
Filter values represent no filtering (0), up to heavy filtering (3). A value of 1 for the filter uses 1/4 of the new input and 3/4 of the previous display to generate the new display. A filter value of 2 uses 1/8 new and 7/8 previous. A filter value of 3 uses 1/16 new and 15/16 previous.
10u
0.000
0.000
dECPt
Display
Decimal
Point
OFSEt
Display
Offset
Value
RFMP INPUT RANGE
SELECTION
10u
DISPLAY DECIMAL POINT
DISPLAY OFFSET VALUE
-19999 to 19999
FILTER SETTING
0,1 2 3
1
FILtr
RANGE
RESOLUTION
10.000 V
Filter
Setting
SELECTION
0.02A
0.05A
PARAMETER MENU
bANd
Filter Band
StYLE
Scaling
Style
RANGE
RESOLUTION
20.000 mA
50.000 mA
0.000 0.00000.000.00
INP 1
Input Value for Scaling
Point 1
dSP 1
Display Value
For Scaling
Point 1
StYLE
(KEY) scaling style can be used. This allows scaling without the presence or changing of the input signal. If Input Values have to be derived from the actual input signal source or simulator, the Apply (APLY) scaling style must be used.
KEy
If Input Values and corresponding Display Values are known, the Key-in
INP 1
buttons. (The Input Range selection sets the decimal location for the Input Value).
retain this value, press the SEL button to advance to the next parameter. To change the Input Value, press the RST button and apply the input signal to the meter. Adjust the signal source externally until the desired Input Value appears. Press the SEL button to enter the value being displayed.
0.000
For Key-in (KEY) style, enter the known first Input Value using the front panel
For Apply (APLY) style, the meter shows the previously stored Input Value. To
dSP 1
for KEY and APLY scaling styles. The decimal point follows the dECPt selection.
0.000
Enter the first Display Value using the front panel buttons. This is the same
INP 2
10.000
For Key-in (KEY) style, enter the known second Input Value using the front
panel buttons.
For Apply (APLY) style, the meter shows the previously stored Input Value for
Scaling Point 2. To retain this value, press the SEL button to advance to the next parameter. To change the Input Value, press the RST button and apply the input signal to the meter. Adjust the signal source externally until the desired Input Value appears. Press the SEL button to enter the value being displayed.
INP 2
Input Value
for Scaling
Point 2
INPUT VALUE FOR SCALING POINT 1
DISPLAY VALUE FOR SCALING POINT 1
INPUT VALUE FOR SCALING POINT 2
dSP 2
Display Value
For Scaling
Point 2
SCALING STYLE
KEy APLY
0 to 59999
-19999 to 99999
0 to 59999
USrIN
User Input
Function
U-ASN
User Input Assignment
Pro
FILTER BAND
bANd
The filter will adapt to variations in the input signal. When the variation exceeds the input filter band value, the filter disengages. When the variation becomes less than the band value, the filter engages again. This allows for a stable readout, but permits the display to settle rapidly after a large process change. The value of the band is in display units, independent of the Display Decimal Point position. A band setting of ‘0’ keeps the filter permanently engaged at the filter level selected above.
10
0 to 199 display units
DISPLAY VALUE FOR SCALING POINT 2
dSP 2
Enter the second Display Value using the front panel buttons. This is the same
for KEY and APLY scaling styles.
General Notes on Scaling
1. When using the Apply (APLY) scaling style, input values for scaling points
must be confined to signal limits of the selected range.
2. The same Input Value should not correspond to more than one Display Value. (Example: 10 V can not equal 0 and 10.)
3. For input levels beyond the programmed Input Values, the meter extends the Display Value by calculating the slope from the two coordinate pairs (INP1 /
dSP1 & INP2 / dSP2).
7
10.000
-19999 to 99999
Operations
Operations
USrIN
P-Loc
ZErO
rESEt
d-HLd
d-SEL
d-LEV
COLOr
USER INPUT FUNCTION
NO
MODEDISPLAY
No Function
NO
Program Mode Lock-out
Zero Input (Edge triggered)
Reset (Edge triggered)
Display Hold
Display Select (Edge Triggered)
Display Intensity Level (Edge Triggered)
Backlight Color (Edge Triggered)
DESCRIPTION
User Input disabled.
See Programming Mode Access chart (Module 3).
Zero the Input Display value causing Display Reading to be Offset.
Resets the assigned value(s) to the current input value.
Holds the assigned display, but all other meter functions continue as long as activated (maintained action).
Advance once for each activation.
Increase intensity one level for each activation (backlight version only).
Change backlight color with each activation (backlight version only).
U-ASN
Input Assignment only applies if a selection of reset, display hold, or print and reset is selected in the User Input Function menu.
MODE DESCRIPTIONDISPLAY
Print Request
Print
Print and Reset
P-r5t
Setpoint 1 Reset
rSt-1
Setpoint 2 Reset
rSt-2
Setpoint 1 and 2 Reset
rSt12
USER INPUT ASSIGNMENT
dSP
Select the value(s) to which the User Input Function is assigned. The User
Serial transmit of the active parameters selected in the Print Options menu (Module 5).
Same as Print Request followed by a momentary reset of the assigned value(s).
Resets setpoint 1 output.
Resets setpoint 2 output.
Reset both setpoint 1 and 2 outputs.
HI-LO HI
dSPLO
6.2 Module 2 - Secondary function paraMeterS (2-SEC)
2-SEC
SEL
HI-En HI-t
YESNO
yESNO
Max Capture
Delay Time
Max Display
Enable
MAX DISPLAY ENABLE
HI-En
Enables the Maximum Display Capture capability.
HI-t
When the Input Display is above the present MAX value for the entered delay time, the meter will capture that display value as the new MAX reading. A delay time helps to avoid false captures of sudden short spikes.
LO-En
Enables the Minimum Display Capture capability.
LO-t
When the Input Display is below the present MIN value for the entered delay time, the meter will capture that display value as the new MIN reading. A delay time helps to avoid false captures of sudden short spikes.
FCS
Select yES to perform either of the Factory Service Operations shown below.
YESNO
NO
MAX CAPTURE DELAY TIME
0.0 to 999.9 seconds
2.0
MIN DISPLAY ENABLE
NO
MIN CAPTURE DELAY TIME
0.0 to 999.9 seconds
2.0
FACTORY SERVICE OPERATIONS
NO
PARAMETER MENU
LO-En LO-t FCS
Min Display
Enable
Pro
CodE
Min Capture
Delay TIme
CodE
CodE
CodE
For most applications, recalibration every 1 to 2 years should be sufficient.
Calibration of the RFMP involves a voltage or current calibration, which should only be performed by individuals experienced in calibrating electronic equipment. Allow a 30 minute warm up for eqiupment and unit before performing any calibration related procedures. The following procedures should be performed at an ambient temperature of 15 to 35°C (59 to 95°F).
CAUTION: The accuracy of the calibration equipment will directly affect the
accuracy of the RFMP.
Calibration
1. Connect the negative lead of a precision DC source with an accuracy of 0.01%
or better to the COMM. Leave the positive lead of the DC source unconnected.
2. With the display at CodE 48, press and hold the SEL button for 2 seconds. Unit
will display CAL NO.
3. Press the RST button to select the range to be calibrated.
4. Press the SEL button. Display reads 0.0A (0.0 V for voltage).
5. Apply 0 signal:
Current: leave the positive lead of the DC source unconnected. Voltage: apply a short to the input or connect the positive lead of the DC
Press SEL. Display reads CALC for about 8 seconds.
6. When the display reads the selected range (10 V, 20 mA, or 50 mA), connect
the positive lead of the DC source to INP+ and apply the full scale input signal
for the range. Press SEL. Display reads CALC for about 8 seconds.
7. Repeat steps 3 through 6 for each input range to be calibrated. When display
reads CAL NO, press the SEL button to exit calibration.
8
Factory Service
RESTORE FACTORY DEFAULT SETTINGS
the factory settings. The meter will display rESEt and then return to CodE 00. Press the SEL button to exit the module.
66
meter. The display then returns to CodE 00. Press the SEL button to exit the module.
50
48
source to INP+ and set the source to 0.
Access Code
For Service
Entering Code 66 will overwrite all user settings with
VIEW VERSION DISPLAY
Entering Code 50 will display the version (x.x) of the
CALIBRATION
The RFMP uses stored calibration values to provide accurate voltage and current measurements. Over time, the electrical characteristics of the components inside the meter could slowly change, therefore the stored calibration values may no longer accurately define the input circuit.
6.3 Module 3 - diSplay and front panel Button paraMeterS (3-dSP)
3-dSP
SEL
dSP-t SEL rSt ZErO UNItS COLOr CodE
Units
Indicator
Selection
DISPLAY COLOR (BACKLIGHT UNIT ONLY)
COLOr
Enter the desired display color, red or green. This parameter is active for
backlight units only.
DISPLAY INTENSITY LEVEL (BACKLIGHT UNIT ONLY)
d-LEV
Enter the desired Display Intensity Level (1-5). The display will actively dim
or brighten as levels are changed. This parameter is active for backlight units only.
CodE
The Security Code determines the programming mode and the accessibility
of programming parameters. This code can be used along with the Program Mode Lock-out (P-Loc) in the User Input Function parameter (Module 1).
Two programming modes are available. Full Programming mode allows all parameters to be viewed and modified. Quick Programming mode permits only the Setpoint values to be modified, but allows direct access to these values without having to enter Full Programming mode.
Programming a Security Code other than 0, requires this code to be entered at the CodE prompt in order to access Full Programming mode. Depending on the code value, Quick Programming may be accessible before the CodE prompt appears (see chart).
rEd
5
000
Front Panel
Display
Select Enable
DISPLAY UPDATE TIME
0.5
1
Front Panel
Reset Enable
2
seconds
Zero Display
W/Display
Reset
1
yES
FRONT PANEL RESET ENABLE (RST)
HI
NOyES
LO HI-LO
dSPNO
dSP
ZERO DISPLAY WITH DISPLAY RESET
NO
NOyES
Display
Update Time
dSP-t
This parameter sets the display update time in seconds.
FRONT PANEL DISPLAY SELECT ENABLE (SEL)
SEL
The yES selection allows the SEL button to toggle through the enabled
displays.
rSt
This selection allows the RST button to reset the selected value(s).
ZErO
This parameter enables the RST button or user input to zero the input display
value, causing the display reading to be offset.
Note: For this parameter to operate, the RST button or User Input being used
must be set to dSP and the Input value must be displayed. If these conditions are not met, the display will not zero.
Display
Scroll
Enable
Backlight Unit Only
d-LEVScroL
Display
Color
1 to 5
PROGRAMMING SECURITY CODE
000 to 999
Display
Intensity
Level
6rnrEd
PARAMETER MENU
Programming Security Code
Pro
DISPLAY SCROLL ENABLE
ScroL
The yES selection allows the display to automatically scroll through the
enabled displays. The scroll rate is every 4 seconds. This parameter only appears when the MAX or MIN displays are enabled.
UNItS
This parameter activates the Units Indicator on the display. There are two methods of selecting the Indicator. List will present a group of Units preprogrammed into the meter. Segments allows the user to choose which of the segments should light.
NO
UNITS INDICATOR SELECTION
NOyES
OFF
LISt SEGSOFF
USER INPUT
FUNCTION
not P-Loc
* Entering Code 222 allows access regardless of security code.
9
P-Loc
USER INPUT
______
Not Active 0-999
STAT E
Active
SECURITY
CODE
1-99
100-999
1-99
100-999
MODE WHEN “SEL”
BUTTON IS PRESSED
0
Full Programming Immediate Access
Quick Programming
CodE prompt
0
Programming Lock No Access
Quick Programming No Access
CodE prompt
Full Programming Immediate Access
FULL PROGRAMMING
MODE ACCESS
After Quick Programming
with correct code entry
at CodE prompt *
With correct code entry
at CodE prompt *
With correct code entry
at CodE prompt *
6.4 Module 4 - Setpoint output paraMeterS (4-SPt)
4-SPt
PARAMETER MENU
SEL
SPSEL
Setpoint
Select
The Setpoint Output Parameters are only active when an optional output
module is installed in the meter.
SPSEL
Enter the setpoint (output) to be programmed. The n in the following parameters will reflect the chosen setpoint number. After the chosen setpoint is completely programmed, the display will return to SPSEL. Repeat steps for each setpoint to be programmed. Select NO to exit the module. The number of setpoints available is setpoint output card dependent.
Enb-2
Select YES to enable Setpoint 2 and access the setup parameters. If NO is selected, the unit returns to SPSEL and setpoint 2 is disabled.
Act-n SPt-n HYS-n tON-n tOF-n rSt-n rEn-n ChC-n
On Time
Delay
Setpoint
Action
Setpoint
SETPOINT SELECT
Value
Hysteresis
Value
SP-2SP-1NO
NO
SETPOINT 2 ENABLE
NOYES
NO
Backlight Unit Only
Stb-n
Off Time
Delay
Output Reset
Action
Output Reset
W/Display
Reset
SETPOINT VALUE
SPt-n
Enter the desired setpoint value. The decimal point position for the setpoint
and hysteresis values follow the selection set in Module 1.
10000
HYSTERESIS VALUE
HYS-n
Enter desired hysteresis value. See Setpoint Output Figures for visual explanation of how setpoint output actions (balanced and unbalanced) are affected by the hysteresis. When the setpoint is a control output, usually balanced hysteresis is used. For alarm applications, usually unbalanced hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on the low side for high acting setpoints and functions on the high side for low acting setpoints.
Note: Hysteresis eliminates output chatter at the switch point, while time delay
can be used to prevent false triggering during process transient events.
2
Standby
Operation
-19999 to 99999
1 to 59999
Change Display
Color with
Output State
Pro
SETPOINT ACTION
SP
SP
HI-Ub
HI-bL LO-bL HI-Ub LO-Ub
OFF
OFF
HI-bL
=
High Acting, with balanced hysteresis
=
Low Acting, with balanced hysteresis
=
High Acting, with unbalanced hysteresis
=
Low Acting, with unbalanced hysteresis
SP + ½Hys
SP
Hys
SP - ½Hys
OFF
ON
TRIGGER POINTS
ON
TRIGGER POINTS
OFF
OUTPUT
STATE
Low Acting (Balanced Hys) = LO-bL
SP + Hys
Hys
OUTPUT
STATE
Low Acting (Unbalanced Hys) = LO-Ub
LO-UbHI-UbLO-bL
OFF
SP
OFF
ON
TRIGGER POINTS
ON
TRIGGER POINTS
Act-n
Enter the action for the selected setpoint (output). See Setpoint Output Figures for a visual detail of each action.
SP + ½Hys
SP - ½Hys
OUTPUT
STATE
High Acting (Balanced Hys) = HI-bL
SP - Hys
OUTPUT
STATE
High Acting (Unbalanced Hys) = HI-Ub
OFF
ON TIME DELAY
tON-n
Enter the time value in seconds that the output is delayed from turning on after the trigger point is reached. A value of 0.0 allows the meter to update the output status per the response time listed in the Specifications.
0.0
0.0 to 599.9 seconds
OFF TIME DELAY
tOF-n
Enter the time value in seconds that the output is delayed from turning off after the trigger point is reached. A value of 0.0 allows the meter to update the
Hys
output status per the response time listed in the Specifications.
OFF
0.0
0.0 to 599.9 seconds
OUTPUT RESET ACTION
rSt-n
Auto = Automatic action; This action allows the output to automatically reset off
Hys
at the trigger points per the Setpoint Action shown in Setpoint Output Figures. The “on” output may be manually reset (off) immediately by the front panel RST button or user input.The output remains off until the trigger point is crossed again.
Auto
Enter the reset action of the output. See figure for details.
LAtCHAuto L-dLY
LAtCH = Latch with immediate reset action; This action latches the output on at
the trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch means that the output can only be turned off by the front panel RST
10
button or user input manual reset, serial reset command or meter power cycle. When the user input or RST button is activated (momentary action), the corresponding “on” output is reset immediately and remains off until the trigger point is crossed again. (Previously latched alarms will be off if power up Display Value is lower than setpoint value.)
L-dLY = Latch with delay reset action; This action latches the output on at the
trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch means that the output can only be turned off by the front panel RST button or user input manual reset, serial reset command or meter power cycle. When the user input or RST button is activated (momentary action), the meter delays the event until the corresponding “on” output crosses the trigger off point. (Previously latched outputs are off if power up Display Value is lower than setpoint value. During a power cycle, the meter erases a previous L-dLY reset if it is not activated at power up.)
OUTPUT RESET WITH DISPLAY RESET
rEn-n
This parameter enables the RST button or user input to reset the output when
the display is reset.
Note: For this parameter to operate, the RST button or User Input being used
must be set to dSP and the Input value must be displayed. If these conditions are not met, the output will not reset.
YES
YESNO
STANDBY OPERATION
NO
CHANGE DISPLAY COLOR w/OUTPUT STATE
NO
SP - Hys
OUTPUT
STATE
SP
OFF
OFF
{
OFF
MANUAL RESET
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
Setpoint Output Reset Actions
OFF
OFF
OFF
( )
Auto
( )
LAtCH
( )
L-dLY
Hys
Stb-n
When YES, the output is disabled (after a power up) until the trigger point is
crossed. Once the output is on, the output operates normally per the Setpoint Action and Output Reset action.
ChC-n
This parameter enables the backlight FLEX MINI to switch the backlight color
when the output state changes. This parameter is only active for the backlight
6.5 Module 5 - Serial Setup paraMeterS (5-SEr)
5-SEr
SEL
PARAMETER MENU
YESNO
YESNO
Pro
bAUd dAtA
Data BitBaud Rate Parity Bit Print
The Serial Setup Parameters are only active when one of the optional serial communications/programming cards is installed in the meter. Refer to the RFMCOMM bulletin for details and setup for the FLEX MINI RS232 or RS485 serial communications. Refer to the RFMCOMUSB bulletin for details on the FLEX MINI USB programming and programming requirements.
The Company warrants the products it manufactures against defects in materials and workmanship for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Danaher Specialty Products harmless from, defend, and indemnify DSP against damages, claims, and expenses arising out of subsequent sales of DSP products or products containing components manufactured by DSP and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.
PAr Addr Abbr
Meter
Address
LIMITED WARRANTY
11
Abbreviated
Printing
OPt
Options
rfMp proGraMMinG QuicK overvieW
User Input
U-ASN
Assignment
Function
User Input
USrIN
Backlight
Unit Only
Point 2
for Scaling
dSP 2
Display Value
CodE
Programming
Security Code
Point 2
for Scaling
Input Value
INP 2
Level
Display
Intensity
d-LEV
Point 1
for Scaling
Display Value
Backlight Unit Only
COLOr
Display
Color
Change Display
Standby
Stb-n
Output Reset
Output Reset
Color with
Output State
Operation
Reset
W/Display
Action
Input Value
INP 1 dSP 1
StYLE
Scaling Style
Filter Band
bANd
FILtr
Filter Setting
OFSEt
Display Oset
dECPt
Point 1
for Scaling
Value
Decimal Point
CodE
FCS
LO-t
LO-En
For Service
Operations
Access Code
Service
Factory
Operations
Delay Time
Min Capture
Enable
Min Display
Delay Time
Max Capture
UNItS
ZErO ScroL
Selection
Units Indicator
Scroll
Display
Enable
Reset
W/Display
Zero Display
Front Panel
Reset Enable
Display
Front Panel
Select Enable
Act-n SPt-n HYS-n tON-n tOF-n rSt-n rEn-n ChC-n
Delay
O Time
Delay
On Time
Value
Hysteresis
Value
Setpoint
Action
Setpoint
OPt
Abbr
Addr
PAr
dAtA
Print
Options
Printing
Abbreviated
Meter
Address
Parity BitBaud Rate
Data Bit
Exit
End
Programming
SEL
Pro
Press and hold SEL button to
enter Programming Mode.
NO
RST
SEL
rANGE
Input Range Display
1-INP
RST
SEL
HI-En HI-t2-SEC
RST
Max Display
Enable
SEL
dSP-t SEL rSt
3-dSP
RST
Display
Update Time
SEL
SPSEL
4-SPt
Setpoint
RST
Select
SEL
bAUd
5-SEr
RST
Loading...