Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of
merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the
furnishing, performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication
may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root.
Contact Red Jacket Technical Support for additional troubleshooting information at 800-323-1799.
DAMAGE GOODS/LOST EQUIPMENT
Thoroughly examine all components and units as soon as they are received. If any cartons are damaged or missing, write a
complete and detailed description of the damage or shortage on the face of the freight bill. The carrier's agent must verify the
inspection and sign the description. Refuse only the damaged product, not the entire shipment.
VR must be notified of any damages and/or shortages within 30 days of receipt of the shipment, as stated in our Terms and
Conditions.
VEEDER-ROOT’S PREFERRED CARRIER
1.Fax Bill of Lading to V/R Customer Service at 800-234-5350.
2.Call V/R Customer Service at 800-873-3313 with the specific part numbers and quantities that were received damaged or
lost.
3.VR will file the claim with the carrier and replace the damaged/missing product at no charge to the customer. Customer
Service will work with production facility to have the replacement product shipped as soon as possible.
CUSTOMER’S PREFERRED CARRIER
1.Customer files claim with carrier.
2.Customer may submit a replacement purchase order. Customer Service will work with production facility to have the
replacement product shipped as soon as possible.
3.If “lost” equipment is delivered at a later date and is not needed, VR will allow a Return to Stock without a restocking fee.
4.VR will NOT be responsible for any compensation when a customer chooses their own carrier.
RETURN SHIPPING
For the parts return procedure, please follow the instructions in the “General Returned Goods Policy” pages of the “Policies and
Literature” section of the Veeder-Root North American Red Jacket Mechanical Products Price Book. Veeder-Root will not accept
any return product without a Return Goods Authorization (RGA) number clearly printed on the outside of the package.
Figure 26.Maxxum Yoke and Contractors Box Assembly .....................................39
Figure 27.2HP, 1-Phase Control Box ....................................................................40
Tables
Table A. ..................................................................................................................5
Table B. ................................................................................................................17
Table C. ................................................................................................................17
Table D. ................................................................................................................18
Table E. ................................................................................................................30
Table F. ................................................................................................................32
Table G. ................................................................................................................36
Table H. ................................................................................................................37
Table I. ................................................................................................................38
Table J. ................................................................................................................39
Table K. ................................................................................................................40
Table L. ................................................................................................................41
Table M. ................................................................................................................41
iv
Page 5
Introduction
OFF
WARNING
CAUTION
NOTICE
This manual provides step-by-step instructions for installing and wiring the Maxxum pump, tandem Maxxum pumps,
pump testing procedures, and pump service and repair.
Safety Precautions
The following safety symbols are used throughout this manual to alert you to important safety hazards and
precautions.
EXPLOSIVE
Fuels and their vapors are extremely explosive
if ignited.
ELECTRICITY
High voltage exists in, and is supplied to, the
device. A potential shock hazard exists.
WARNING indicates a hazardous situation
which, if not avoided, could result in death
or serious injury.
NO SMOKING
Sparks and embers from burning cigarettes or
pipes can ignite fuels and their vapors.
EYE PROTECTION
Wear eye protection when working with pressurized fuel lines or epoxy sealant to avoid possible eye injury
READ ALL RELATED MANUALS
Knowledge of all related procedures before you
begin work is important. Read and understand
all manuals thoroughly. If you do not understand
a procedure, ask someone who does.
FLAMMABLE
Fuels and their vapors are extremely flammable.
TURN POWER OFF
Live power to a device creates a potential shock
hazard. Turn Off power to the device and associated accessories when servicing the unit.
GLOVES
Wear gloves to protect hands from irritation or
injury.
NO OPEN FLAMES
Open flames from matches, lighters, welding
torches, etc. can ignite fuels and their vapors.
TURN OFF CELL PHONES/PAGERS
Sparks from electronic devices in the vicinity of
gasoline storage tanks could cause an explosion
or fire resulting in bodily injury or death.
CAUTION indicates a hazardous situation
which, if not avoided, could result in minor or
moderate injury.
NOTICE is used to address practices not
related to physical injury..
1
Page 6
IntroductionSafety Precautions
OFF
WARNING
This product operates in the highly combustible atmosphere of a gasoline storage
tank.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY
PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT,
RESULTING IN SERIOUS INJURY OR DEATH.
1. All installation work must comply with the latest issue of the National
Electrical Code (NFPA 70), the Code for Motor Fuel Dispensing Facilities and
Repair Garages (NFPA 30A), and any European, national, state, and local
code requirements that apply.
2. Turn off, tag, and lockout power to the STP before connecting or servicing the
STP.
3. Before installing pipe threads apply an adequate amount of fresh, UL
classified for petroleum, non-setting thread sealant.
4. When servicing unit, use non-sparking tools and use caution when removing
or installing equipment to avoid generating a spark.
5. To protect yourself and others from serious injury, death, or substantial
property damage, carefully read and follow all warnings and instructions in
this manual.
In addition to the specified torque values noted in this manual, when properly tightened, all flanged fittings should
have metal-to-metal contact.
2
Page 7
IntroductionWarnings and Instructions
WARNING
WARNING
Warnings and Instructions
IMPORTANT SAFETY INFORMATION
This section introduces the hazards and safety precautions associated with installing,
inspecting, maintaining or servicing this product. Before performing any task on this
product, read this safety information and the applicable sections in this manual, where
additional hazards and safety precautions for your task will be found. Fire, explosion,
electrical shock or pressure release could occur and cause damage to property,
environment, resulting in serious injury or death, if these safe service procedures are
not followed.
PRELIMINARY PRECAUTIONS
You are working in a potentially dangerous environment of flammable fuels, vapors,
and high voltage or pressures. Only trained or authorized individuals knowledgeable in
the related procedures should install, inspect, maintain or service this equipment.
Read the Manual
Read, understand and follow this manual and any other la
you do not understand a procedure, call 1-800-323-1799 to locate a qualified technician. It is imperative to your
safety and the safety of others to understand the procedures before beginning work. Make sure your
employees and any service contractors read and follow the instructions.
Follow the Regulations
Applicable information is available in National Fire Protection Association (NFPA) 30A; Code for Motor Field
Dispensing Facilities and Repair Garages, NFPA 70; National Electrical Code (NEC), Occupational Safety and
Hazard Association (OSHA) regulations and federal, state, and local codes. All these regulations must be
followed. Failure to install, inspect, maintain or service this equipment in accordance with these codes, regulations
and standards may lead to legal citations with penalties or affect the safe use and operation of the equipment.
Prevent Explosions and Fires
Fuels and their vapors will explode or burn, if ignited. Spilled or leaking fuels cause vapors. Even filling customer
tanks will cause potentially dangerous vapors in the vicinity of the dispenser or island.
Working Alone
It is highly recommended that someone who is capable of rendering first aid be present during servicing.
Familiarize yourself with Cardiopulmonary Resuscitation (CPR) methods, if you work with or around high voltages.
This information is available from the American Red Cross. Always advise the station personnel about where you
will be working, and caution them not to activate power while you are working on the equipment. Use the OSHA
Lockout/Tagout procedures. If you are not familiar with this requirement, refer to OSHA documentation.
Working With Electricity Safely
Ensure that you use safe and established practices in working with electrical devices. Poorly wired devices may
cause a fire, explosion or electrical shock. Ensure that grounding connections are properly made. Ensure that you
do not pinch wires when replacing covers. Follow OSHA Lockout/Tagout requirements. Station employees and
service contractors need to understand and comply with this program completely to ensure safety while the
equipment is down. Before you start work, know the location of the Emergency Power Cutoff Switch (the ESTOP). This switch cuts off power to all fueling equipment and submerged turbine pumps and is to be used in the
event of an emergency. The buttons on the console at the cashier’s station WILL NOT shut off electrical power to
the pump/dispenser. This means that even if you press a button on the console labeled EMERGENCY STOP,
ALL STOP, PUMP STOP, or something similar, fuel may continue to flow uncontrolled.
bels or related materials supplied with this equipment. If
3
Page 8
IntroductionFuel Compatibilities
WARNING
Hazardous Materials
Some materials may present a health hazard if not handled correctly. Ensure that you clean hands after handling
equipment. Do not place any equipment in the mouth.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY
PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT, RESULTING
IN SERIOUS INJURY OR DEATH.
FIRE HAZARD! Do NOT use power tools (Class I Division I and Class I Division II) during the installation or
maintenance of equipment. Sparking could ignite fuel or vapors, resulting in fire.
CHEMICAL EXPOSURE HAZARD!Wear appropriate safety equipment during installation or maintenance of
equipment. Avoid exposure to fuel and vapors. Prolonged exposure to fuel may cause severe skin irritations and
possible burns.
REQUIREMENTS FOR USE
• The Maxxum is designed for use only at facilities dispensing motor fuels.
• Application of the Maxxum must be consistent with NFPA Code 30A, OSHA regulations, and federal, state and
local fire codes, and other applicable local regulations.
• The selection of any Veeder-Root product must be based upon physical specifications and limitations and the
product’s compatibility with the materials to be handled. Veeder-Root makes no warranty of fitness for a
particular purpose.
• All Veeder-Root products should be used in accordance with applicable federal, state and local laws,
ordinances and regulations.
OPERATING PRECAUTIONS
• NO SMOKING. Extinguish all open flames and pilot lights, such as on RV appliances.
• TURN OFF cell phones and other electronic devices to avoid distractions while fueling.
Fuel Compatibilities
Pumps are designed to operate in a Class 1, Group D atmosphere and in accordance with CENELEC standard
and the European Directive 94/9/EC “Equipment for Potentially Explosive Atmoshpere” (II2 G Ex IIA T4).
All Models of the Maxxum are UL Listed for the Following Fuel Compatibility
Gasoline and up to
15%
DieselGasoline
Ethanol
The Maxxum is designed to be compatible with 100 percent gasoline, or diesel and 80 percent gasoline with 20
percent methanol, ethanol, TAME, ETBE, or MTBE .
15%
Methanol
20%
MTBE
20%
ETBE
20%
TAME
4
Page 9
Installation
WARNING
This pumping system requires the following elements:
1. Discharge Manifold Assembly - Installed below grade (NEC/Class I, Group D, Division I area)
2. Motor-Pump Unit Assembly - Installed below grade (NEC/Class I, Group D, Division I area)
3. Control Box/Magnetic Starter
An “all inclusive” name plate will be found attached to the Extracta Head and can be inspected by removing
the manhole cover directly over the pump.
An additional name plate will be found on the control box. It is important to give the model number and serial
number of this pump when corresponding with the factory for any reason.
INSTALLATION SAFETY NOTICES ATTENTION INSTALLER
Read This Important Safety Information Before Beginning Work.
1. Units should be installed with manholes, or with discharge manifold casting above grade, to allow for ease in
servicing.
Red Jacket line leak detection systems do not function if the submersible pump runs
continuously. Running a pump continuously will cause line leak detection systems to
not function which results in a hazard that can cause damage to property, environment,
resulting in serious injury or death.
2. Never wire a submersible pump to run continuously at less than minimum flow rate. The units are designed to
operate continuously at or above minimum flow rate, or with an intermittent duty cycle, not to exceed 20 on/off
cycles per hour. Should it be necessary to operate a unit continuously or when the demand is at a rate less
than required per the information below, a bypass pipe should be installed in the piping to allow for continual
product recirculation back into the storage tank. Regulation of the bypass flow back to the tank can be
accomplished by correct sizing of the bypass line or use of a gate valve. The recommended minimum bypass
per unit is shown in Table A.
Table A.
60 Hz, 208-240, 575 Volt
Two Stage Units
P200J1-2MB = 15 GPMP300J17-3HB = 20GPM
P200J4-2MB = 15 GPMP500J17-3K = 25 GPM
P300J4-2HB = 20 GPMP300J16-3HB = 20GPM
P500J4-2K = 25 GPMP500J16-3K = 25 GPM
P200J6-2K = 25 GPM
50 Hz 380-415 Volt
Three Stage Units
3. Red Jacket submersibles are not designed to handle abrasives or foreign particles in the product being
pumped.
4. Product temperature must never exceed 105°F (41°C) as the submersible motors are equipped with thermal
overload protection. Product temperature higher than 105°F (41°C) may result in tripping of the thermal
overload protector.
5
Page 10
InstallationFollow These Directions Carefully
WARNING
WARNING
5. Pumping water will overload the motor and damage the motor bearings.
6. These units are designed for use in Class I, Group D atmospheres.
7. Install pumping system in accordance to applicable codes.
Proper motor protection must be used on three phase pump models, or motor warranty is void. To maintain warranty, the magnetic starters used must be supplied by Red
Jacket, or have equivalent protection features defined as follows:
- 3-leg protection
- Properly sized quick trip heaters, and
- Ambient temperature compensated overloads.
8. The UMP (Unitized-Motor-Pump) contains no serviceable parts (other than the foot valve) and should not be
modified or adjusted.
Follow These Directions Carefully
Check these points before installing.
1. The power supply against the equipment voltage rating. For 3 phase units, request the power company identify
and tag the service wires for L-1, L-2, L-3 phase sequence.
2. Be certain that the pump with the siphon valve is installed into the correct tank.
3. Check the equipment which was received against Table B and Figure 8 for the tank diameter and bury depth.
Before installing pipe threads apply an adequate amount of fresh, UL classified for petroleum, non-setting thread sealant.
4. Apply thread sealant to the six-inch riser/flange male threads. Thread it into the tank port. Tighten the riser/
flange until the joint is water tight.
Installing The Pumping Unit
1. Apply a gasket compound to the bottom surface of the manifold and press the gasket onto the manifold’s
mating surface so the holes in the gasket and manifold align (reference Figure 1).
2. Coat the exposed surface of the gasket with gasket compound.
WARNING
3. Insert three 3/4-inch bolts, provided, and torque them to 200 ft-lb (271 N•m).
Confirm that the lifting eyebolts are properly torqued to 10 ft-lbs (13.6 N•m) with a
minimum of 6 full threads installed. Occasionally, eyebolts are removed after pump installation and corrosion may occur in the threaded areas of the extractable and the
eyebolt. If corrosion has occurred, the extractable and eyebolt should be replaced.
Utilize BOTH lifting eyebolts to suspend the pump vertically and lower the pumping
unit into position. Do not allow the gasket to contact the riser flange until the bolt
holes in the flange are aligned with those in the manifold and the discharge port is
aimed in the desired direction.
6
Page 11
InstallationAttaching the Expansion Relief Vent Line
Lifting eyes
Bolt torque 200 ft-lb. (3 places)
Manifold
Vent line
6" NPT riser
flange
3" NPT or BSP
discharge port
rj/051-301-1.eps
WARNING
NOTICE
Attaching the Expansion Relief Vent Line
1. Remove the metal protective shipping caps from the flare fittings (reference Figure 1).
2. Attach the vent line taking care not to cross thread the fittings.
3. Tighten the fittings 1/6 to 1/4 turn beyond hand tight.
4. Install the piping to the manifold discharge port. Pipe sealant should be used in this joint.
Line check-valves are not required since the pump has a built in check-valve. However, whenever two pumps are
manifolded together to the same discharge piping, check valves with expansion relief are required and should be
installed in the discharge piping of each pump, as close to the pump manifold as possible.
See instructions “INSTALLING TWO PUMPS FOR TANDEM OPERATION” and Figure 12.
Figure 1. Maxxum Packer-Manifold Assembly
Before installing pipe threads apply an adequate amount of fresh, UL classified for petroleum, nonsetting thread sealant.
Installation of a ball valve is recommended on the discharge side of the pump or discharge
of the “Big Flo” leak detector housing if used. This will aid in troubleshooting and line testing.
7
Page 12
InstallationWiring the Conduit Box
(1" Conduit)
Conduit from control box
Power and thermal overload
leads to pump
O-ring
Ground wire
Ground wire screw
1. For European installations, the End User must
use an ATEX EEX d IIB certified cable gland or
stopping box.
2. Use suitable AUS EX, ANZEx or IECEx certified
cable gland or flameproof entry device when
equipment is installed in accordance with ANZEx
certification for connection of the external circuit
conductors to the motor conductors used to close
the 1" NPT conduit connection.
Cup washer terminal
External toothed washer
rj/051-301-2.eps
WARNING
OFF
WARNING
Wiring the Conduit Box
When servicing equipment, use non-sparking tools and use caution when removing or installing
equipment to avoid generating a spark.
1. Connect the electrical conduit through the approved fittings to the conduit box.
2. Remove the conduit box cover.
3. Connect the wires from the power supply to the wires in the conduit box.
4. Install the gound wire from the power panel.
5. Sparingly lubricate the o-ring before screwing the cover into the manifold. Use light grease, oil, or petroleum
jelly. Replace the conduit box cover. Do not use pipe sealant on the conduit box cover’s threads. Torque to 35
ft-lb (50 N•m).
Figure 2. Conduit Box - Yoke Assembly
Disconnect, lock out, and tag power at the panel before servicing the
pump.
8
Page 13
InstallationWiring the Conduit Box
CAUTION
NOTICE
Wiring Instructions- 208-230 Volt Single Phase Pumps
The motor control box must be located away from the fueling area in a non-hazardous location (see Figure 3).
1. Connect the single phase 208-230 V power supply from the distribution panel to terminals L1 and L2 in the
motor control box. Each control box should be wired through a separate fused disconnect switch or circuit
breaker (including neutral, when used), furnished by customer.
2. Using properly color coded wires, connect wires from the red, black, orange and two blue terminals on motor
control box terminal strip to the corresponding color coded wires in the junction box of the proper submerged
pump.
The “on-off” control station must be of explosion-proof construction. Where loading racks and dispensers are
served by the same submerged pump, the 2-wire switches must be connected in parallel so the submerged
pump can be controlled from any dispenser or any loading rack.
3. Connect wires from terminal Blue-1 and terminal 3 in motor control box to dispenser control switches (if
dispensers are used) and “on-off” switch at loading rack as shown in Figure 3.
4. The pumps are equipped with a no-liquid, over-temperature switch in the motor and an overload switch in the
motor control box which will cut out if the motor is overloaded. If the pump fails to operate, or stops, when
there is sufficient product in the storage tank, check the manual overload reset switch in the control box cover.
Wait 10 minutes for the overload protector to cool off and then press the reset button.
If the reset button will not stay in position this indicates an overloaded motor, or a
short to ground. This condition must be corrected. If the reset button stays in but the
motor will not pump or continue to run, the tank is dry.
5. If an external pilot light is desired to indicate when the submerged pump is operating, wire as shown in
Figure 3, Figure 4 or Figure 5. Should this light continue to burn when all switches atdispensers and loading
racks are off, this indicates that one of the dispenser switches is out of adjustment. On installations with no
external pilot light, the submerged pump should be checked to make sure it is not operating when all switches
are turned off.
6. The magnetic contactor coil is shipped ready to accept 208-230 volts. No changes are required unless a 110-
120 volt coil is desired.
Wiring Instructions - 208-230, 380/415 or 575 Volt Three-Phase Pumps
On some installations, “phase converters” are used to obtain a three-phase power supply
from a single-phase power source. The use of phase converters may cause an imbalance
between the three phases and cause damage to the motor. For this reason, these
requirements must be followed in order to maintain warranty coverage.
• Static phase converters must not be used. Only rotary or electric phase converters are
allowed.
• The horsepower rating of the phase converter must be equal to at least three times the
horsepower rating of the pump(s).
• Current imbalance must not exceed 10% under varying flow conditions.
• Proper three-leg quick trip overloads must be used.
1. Installations where the magnetic starter is located away from the loading rack in a nonhazardous location. (See
Figure 6)
a.Connect the three phase power supply from the master panel to terminals L1, L2 and L3 in the magnetic
starter.
b.Using properly color coded wires, connect a black wire from terminal T1 in the magnetic starter to the
black motor lead, in the junction box of the proper submerged pump. Connect an orange wire from starter
terminal T2 to the orange motor lead and red wire from terminal T3 to the red motor lead. (See Figure 6
and Figure 7.)
9
Page 14
InstallationWiring the Conduit Box
NOTICE
WARNING
c.There are two remaining blue wires in the submerged pump junction box. Connect either blue wire to one
side of the ‘on-off’ controls or switched ‘hot’ from the electronic dispenser or Isotrol (dispenser handle
isolation). The ‘on-off’ controls must be of explosion-proof construction if located in a hazardous location.
Connect the other blue wire to the appropriate terminal on the other side of the ‘on-off’ controls. See
specific wiring diagrams provided with the magnetic starters matching pump voltage, coil voltage and type
of pump control.
d.Installations using loading racks only, may be connected for 2- or 3-wire control. For 3-wire control
(Figure 7), connect a black wire from terminal 3 in the magnetic starter to the ‘on-off’ switch. Connect a
red wire from terminal 2 in the magnetic starter to the ‘on-off’ switch. Connect either blue wire to the other
side of the ‘on-off’ switch and connect the other blue wire to L1 of the magnetic starter.
3-wire control requires the use of an auxiliary contact in the magnetic starter. This auxiliary
contact is standard equipment in the G.E. starters supplied by Red Jacket.
Installations with the magnetic starter in a hazardous location require explosion-proof
magnetic starters. The wiring is the same as for general purpose enclosures. (Section
1).
2. Install proper overload heaters in magnetic starter matching starter manufacturer and amperage rating of the
pump.
3. Motor Rotation
Where it is not convenient to predetermine the power supply phase rotation, proper rotation can be determined by pump performance. Pump head pressure and capacity will be considerably less than rated when rotating backwards.
Connect the pump motor leads to terminal T1, T2 and T3 of the magnetic starter observing color code shown
in Figure 6 and Figure 7. With ample product in the tank and the system purged of air, start the motor and
make a pressure gauge reading of the system pressure with the discharge valves closed; or, open one valve
and calculate pumping rate.
Next, reverse power leads at L1 and L2. Repeat either pressure or capacity tests, as described above. If results are higher than the first test, the rotation of the second test is correct. If the second test gives lower performance than the first, reconnect the power leads to L1 and L2 (as under test 1) for correct rotation.
Where the power supply has been properly marked L1, L2 and L3 in accordance with accepted phase rotation standards, it is possible to predetermine the proper rotation of these units. The motor power leads are color coded black, orange and red, and if connected through the magnetic starter to L1, L2 and L3 respectively,
the motor pump unit will rotate in the correct direction. It is recommended, however, that the performance
tests always be made whether or not the power supply has been properly “phased out”.
10
Page 15
InstallationWiring the Conduit Box
LINE
1
230V
115 115
LINE
2
ORANGE
BLACK
RED
BLUE
BLUE
1
2
3
EXT
PILOT
Grey
White
Seal
Seal
(Blue)1
Orange
Black
Red
(Black)3
On/Off
switch
To neutral of
115/230V
supply
Black
Customers 115V external
pilot light 50W max.
To neutral of
115/230V supply
The control box
must be grounded
for personal safety.
Refer to the National
Electrical Codes and
applicable local codes
for proper grounding
procedures.
115V Lighting circuit
(where needed) from
distribution panel
Approved component only - total system installed
shall comply with all local codes. Make Ground
Connection In Accordance With Local Codes.
The control box must be grounded for personal
safety. Refer to the National Electrical Codes and
applicable local codes for proper grounding
procedures.
Ground screw
Figure 4. Typical Mechanical Dispenser Motor Control Box, Wiring Diagram, 2HP
12
Page 17
InstallationWiring the Conduit Box
Line
1
230V
115
Line
2
Orange
Orange
Black
White
White
White
Starting relay
Starting
capacitor
Running
capacitor
Overload relay
reset button
Contactor
Contactor coil
terminals
1
5
2
T3
L3
L2
L1
T1T2
White
Orange
Red
Red
Red
Black
115V
Coil
Red
Black
Black
Black
Blue
Blue
Black
Black
Red
Red
Blue
Blue
Motor
Blue
Blue
1
2
3
Ext
pilot
Ground screw
Hot
115V External
pilot light
(50W max.)
Low liquid
protector
115
208-230, 2HP 1Ø CONTROL BOX
1. Remove red wire (coil to L2).
2. Relocate orange wire at L1 to coil.
3. Change to 115V coil assembly.
The control box must be grounded for personal
safety. Refer to the National Electrical Codes and
applicable local codes for proper grounding
procedures.
Approved component only - total system installed
shall comply with all local codes. Make Ground
Connection In Accordance With Local Codes.
WARNING
Figure 5. Representative Wiring Diagram For Use With Switched “Hot” Feed 208-230 Vac, 2HP Single-Phase Control Box
13
Page 18
InstallationWiring the Conduit Box
rj/051-301-6.eps
L1
Coil
L2 L3
T1
3
Red
Orange
Black
T2 T3
Blue
Local seals
where required
by code
Blue
BlueBlack
(2-Wire shown)
On-Off
switch
Seal
Black
No liquid protector circuit
If 115V is not available from power supply,
pilot lights may be operated from any 115V
lighting circuit by controlling with a
4-pole starter. Otherwise, 230V pilot lights
must be used.
3-PHASE POWER SUPPLY
The control box must be grounded for personal
safety. Refer to the National Electrical Codes and
applicable local codes for proper grounding
procedures.
WARNING
NOTICE
Figure 6. Representative Wiring Diagram, Three-Phase, Two-Wire Control
14
Page 19
InstallationWiring the Conduit Box
L1 L2L3
T1 T2T3
Switch at loading rack
Stop
Start
Thermal
overload
To ext. pilot
light 115V
supply
W
V
Blue
Red
Red
Orange
Black
Blue
Blue
Black
Coil
3-PHASE POWER SUPPLY
Observe color code L1, L2, L3 phase
sequence for proper rotation of motor.
rj/051-301-9.eps
3-wire control requires the use of
an auxiliary contract in the magnetic
contactor. Furnas auxiliary interlock
field kit 49D22125001 or equivalent.
NOTICE
NOTICE
The control box must be grounded for personal
safety. Refer to the National Electrical Codes and
applicable local codes for proper grounding
procedures.
WARNING
Figure 7. Three-Wire, Three-Phase Motor Wiring Diagram
15
Page 20
InstallationStarting the System and Completing the Installation
36.0" Diameter
18.0" Radius
3" NPT or BSP
by contractor
6" NPT riser with
flange ordered
separately
Center
of
sump
9.6"
1.3"
4.0" Minimum
4.0"
14.6"
"A"
Bury depth
"B" Max.
riser length
"D"
"C" Tank diameter
rj/051-301-10.eps
Distance between center
line of pump motor and
centerline of fill pipe
should be 3 feet minimum.
Air locking of pump may
occur at distances less
than this distance.
NOTICE
Starting the System and Completing the Installation
1. Do not start pumps unless ample product is in the storage tank.
2. Pump sufficient product through each dispenser to purge the entire system of air. If all air is not purged, the
computers may “creep” slightly when the dispenser switch is turned on, but no product has been dispensed.
3. On pumps equipped with built-in siphon, it is necessary to run the submerged pump at least 10 to 20 minutes
continuously to purge the air from the siphon manifold.
4. After the above checks have been made, the backfill can be completed and the manholes installed as shown
in Figure 8.
Figure 8.
16
Page 21
InstallationStarting the System and Completing the Installation
NOTICE
Table B.
Bury
Depth
“A”
30”10” (883-442-1)C = 72” / D = 78” C = 84” / D = 90”C = 96” / D = 102” C = 120” / D = 126” C = 144” / D = 150”
36”16” (883-445-1)C = 72” / D = 84” C = 84” / D = 96”C = 96” / D = 108” C = 120” / D = 132” C = 144” / D = 156”
42”21” (883-449-1)C = 72” / D = 89” C = 84” / D = 101” C = 96” / D = 113” C = 120” / D = 137” C = 144” / D = 161”
48”27” (883-449-1)C = 72” / D = 95” C = 84” / D = 107” C = 96” / D = 119” C = 120” / D = 143” C = 144” / D = 167”
60”36” (883-451-1) C = 72” / D = 104” C = 84” / D = 116” C = 96” / D = 128” C = 120” / D = 152” C = 144” / D = 176”
72”51” (883-454-1) C = 72” / D = 119” C = 84” / D = 131” C = 96” / D = 143” C = 120” / D = 167” C = 144” / D = 191”
NOTE: The above readings do not include the added resistance of the power supply wires to the submersible pump. Therefore, for
the readings to fall within the above limits, the resistance should be checked at the submersible pump junction box. If the resistance readings are taken at the control box or magnetic starter, they will be sightly higher.
WARNING
Disconnect, lock out, and tag power at the panel before servicing the pump and taking
these resistance readings.
Orange to Red
Winding Resistances (Ohms)
Orange to
BlackRed to BlackBlue to Blue
When servicing equipment, use non-sparking tools and use caution when removing or installing equipment to avoid generating a spark.
17
Page 22
InstallationStarting the System and Completing the Installation
Table D.
Branch Ckt.
Protection
Service
Factor
Cur.
HPVoltsPhase
2208-230*112.061.020201722749296731048H
2208-230*37.245.0151536157489914102197K
3208-230*310.562.015202554066359971552K
3380-41535.429.01515787125019563070---K
5208-230*317.292.02530---240376590920J
5380-41538.849.01515472750117318412867G
557537.037.01515929147723113627---K
*Figures represent maximum length in feet for 220 or 230 volt system. Use 75% of length for 208 volt system.
Wire Size for Max. Length of Run Shown
(From Service Entrance to Pump in Feet)
Nema
Codes
18
Page 23
InstallationFloating Suction Installation Information
rj/051-301-11.eps
4.0" Approx.
3" NPT male
thread
Pump
Veeder-Root only supplies
the adapter.
Red Jacket pumps are
centrifugal type and as
such are not designed to
pump product when level
is below the bottom of the
pump.
Before installing pipe
threads apply an adequate
amount of fresh, UL
classified for petroleum,
non-setting thread sealant.
1.
2.
3.
NOTICE
Floating Suction Installation Information
Figure 9.
19
Page 24
InstallationInstalling A Big Flo Diaphragm Valve
OFF
WARNING
NOTICE
Installing A Big Flo Diaphragm Valve
Disconnect, lock out, and tag power at the panel before servicing the
pump.
When servicing equipment, use non-sparking tools and use caution when removing or installing
equipment to avoid generating a spark.
The installation described herein is for a single pump system (reference Figure 10). If
two pumps are to be installed in tandem, contact your service representative for
instructions for your specific system.
1. Since the leak detector only checks for leaks down stream from itself it should be installed as close to the
pump as possible while still maintaining clearance for the removal of the pump check valve housing.
2. Install the “Big-Flo”diaphragm valve per the instructions included with the “Big-Flo” Diaphragm Valve.
3. Install the vent line from the FXV to the 1/4 NPT port in the six inch flange using tubing and fittings supplied
with the leak detector.
4. Test the installation per the instructions included with the “Big-Flo” diaphragm valve.
20
Page 25
InstallationInstalling A Big Flo Diaphragm Valve
WARNING
If Big Flo valve is installed in separate sump, a
passage way must be run between the two
sumps. The FX vent line can be easily routed
back to the tank through this passage way.
48" Diameter sump
3" NPT flanged Big Flo
valve (117-182-5). To be
used in conjunction with the
FX Series Leak Detector.
11.0"13.0"
1.5"
2.0"
sump
Center of
16.5"
18.3"
1.8"
20.5"
riser
Center of
4" Min.
3" NPT Ball valve
(recommended for
service)
FX leak detector
vent line
Figure 10.
Storage
tank
6" NPT
Flanged
riser
21
Page 26
InstallationAttaching the Siphon & Vacuum Lines with Factory Installed Siphon Assemblies
rj/051-301-13.eps
Vacuum line minimum
3/8" tubing to high
point of piping system
Minimum 2" NPT siphon line by
contractor must pitch upward (to
tank with pump) about 1/8" per foot.
3" (76mm)
3" NPT line
to dispenser
3" (76mm)
Vent pipe
Fill
pipe
Fill
pipe
3/8" NPT elbow
3/8" Bushing
1/4" NPT
nipple
Siphon
nozzle
3/8" tubing
elbow
3/8" tubing
provided by
contractor
Siphon line
check valve
OFF
WARNING
NOTICE
WARNING
Figure 11.
Attaching the Siphon & Vacuum Lines with Factory Installed Siphon Assemblies
Disconnect, lock out, and tag power at the panel before servicing the
pump.
When servicing equipment, use non-sparking tools and use caution when removing or installing
equipment to avoid generating a spark.
1. Remove the 1/4 inch pipe plug from the siphon nozzle.
Care should be taken to insure that the internal portions of the siphon nozzle and parts included in the siphon kit are clean and free of debris or contamination during assembly.
Before installing pipe threads apply an adequate amount of fresh, UL classified for petroleum, non-setting thread sealant.
2. Coat both of the male threads of the 1/4 X 2 inch long nipple with pipe sealant. Thread one end of the nipple
into the siphon nozzle and the other end into the 1/4 x 3/8 inch reduction bushing.
3. Apply pipe sealant to the male threads of the reduction bushing and thread it into the 3/8 inch female elbow.
4. Apply pipe sealant to the male threads of the siphon check valve and thread it into the 3/8 inch female elbow.
5. Apply pipe sealant to the male pipe threads of the compression fitting elbow and thread it into the 1/4 inch
hole in the siphon check valve.
22
Page 27
InstallationInstalling Two Pumps for Tandem Operation
WARNING
NOTICE
Installing Two Pumps for Tandem Operation
When greater flow rates are needed, two pumps may be required in the same piping system by means of a
manifold. If they are installed according to the illustration, a tandem system offers backup support so operations
can continue if one pump stops working. Install the pump as outlined above with the following additions.
1. If a siphon system is required, each pump must have 3/8 inch siphon vacuum line attached to the same
location on the siphon line (reference Figure 11).
Adjust the Pressurstat (see “Adjusting the Pressurstat Line Relief Pressure” on
page 28) on both packers to maximum relief pressure by rotating fully clockwise. If
maximum pump pressures are NOT a minimum of 5 psi below the Pressurstat relief
setting then proper check valves with pressure relief are required to be installed in the
discharge line of each pump to prevent product from being pumped through the pressure relief system of the adjacent pump when it is not operating. Readjust the Pressurstat to the desired pressure relief value for proper operation of the siphon system.
Installation of a ball valve is recommended on the discharge side of the pressure relief check
valve. This will aid in troubleshooting and line testing.
Figure 12 illustrates the requirement for in-line, pressure relief type check valves. It is not a
recommended guide for installation of piping downstream of the check valves.
As an option, install ball
valves downstream for
trouble shooting and
maintenance
WARNING
The check valves shown installed in
the discharge line of each pump are
necessary to prevent product from
being pumped through the pressure
relief system of the adjacent pump, if
that pump is not running. This is
because the expansion relief valve
operates at below pump pressures. If
check valves without pressure relief
were used, there would be no
provision for thermal expansion
between the valves and the
dispensers.
rj/051-301-14.eps
Figure 12.
23
Page 28
InstallationInstalling Two Pumps for Tandem Operation
BL2
2
XPL
Dispenser Sw.
115V Relay
Allen Bradley
700C201
NEU
3
BL2
2
XPL
NEU
3
115V
PUMP 2PUMP 1
rj/051-301-15.eps
BL2
2
XPL
115V Relay
Allen Bradley
700C201
Switch at loading rack
NEU
3
BL2
XPL
NEU
3
2
115V
PUMP 1PUMP 2
rj/051-301-16.eps
Start
Stop
It is preferable that the wiring allow both submersibles to operate simultaneously with any combination of
dispensers turned on. To operate individually, the appropriate disconnect switch must be turned off manually. (See
Figure 13 through Figure 16 for suggested wiring diagrams.)
Figure 13. Suggested Diagram For Wiring Dual Manifold System, Two-Wire Control, 208/230 Single Phase
Figure 14. Suggested Diagram For Wiring Dual Manifold System, Three-Wire Control, 208/230 Single Phase
24
Page 29
InstallationInstalling Two Pumps for Tandem Operation
Coil
L1 L2 L3
T1T2 T3
Coil
L1 L2 L3
T1T2 T3
Thermal overload
Dispenser sw.
Relay
Blue
Blue
Blue
Blue
Red
Orange
Black
Red
Orange
Black
Thermal
overload
To ext. pilot
light 115V
supply
To ext. pilot
light 115V
supply
Voltage rating of relay coil
must match power supply.
rj/051-301-17.eps
PUMP 2PUMP 1
Observe color code L1, L2, L3 phase
sequence for proper rotation of motor.
NOTICE
NOTICE
L1 L2 L3
T1T2 T3
Thermal overload
Blue
Blue
Red
Orange
Black
Thermal
overload
To ext. pilot
light 115V
supply
To ext. pilot
light 115V
supply
208/230V or 400V
three-phase power supply
Switch at loading rack
rj/051-301-18.eps
PUMP 2PUMP 1
Coil
L1 L2 L3
T1T2 T3
Blue
Blue
Red
Orange
Black
Coil
Stop
Start
Voltage rating of relay coil
must match power supply.
Observe color code L1, L2, L3 phase
sequence for proper rotation of motor.
NOTICE
NOTICE
Figure 15. Suggested Diagram For Wiring Dual Manifold System, Two-Wire Control, Three Phase
Figure 16. Suggested Diagram For Wiring Dual Manifold System, Three-Wire Control, Three Phase
25
Page 30
Testing the Installation
OFF
WARNING
WARNING
1" NPT port
1/4" NPT line test port
Two 1/4" NPT tank test ports
(180 degrees apart)
Check valve
lockdown screw
Screw out
(normal position)
Screw in for
line and tank
pressure testing
rj/051-301-19.eps
Testing the Piping
Disconnect, lock out, and tag power at the panel before servicing the
pump.
When servicing equipment, use non-sparking tools and use caution when removing or installing
equipment to avoid generating a spark.
1. Block the lines at each dispenser. (Trip the dispenser shear valve.)
2. Lock down the pump check valve by turning the check valve lock down screw clockwise as far as it will turn
(see Figure 17).
3. Remove the 1/4” NPT line test port plug and apply the line test pressure at the line test port (50 psi (345 kPa)
maximum).
Excessive pressure (above normal test pressure of 50-55 psi (345-380 kPa) may damage the pump check valve seat and other system components.
4. After the completion of the test, release the pressure by:
a.Turning the check valve lock down screw counter clockwise as far as it will go.
b.Remove the protective cover from the Pressurstat (see Figure 18) and turn the Pressurstat adjustment
screw counter clockwise until the screw protrudes 3/4”, this will relieve the line pressure to “0” psi.
Apply an adequate amount of fresh, UL classified for petroleum, non-setting thread sealant on the 1/4”
NPT line test port plug and replace it. Torque the plug to 14 - 24 ft-lbs (19.4 - 29 N•m).
Adjust desired relief pressure per instructions on page 28 and replace the protective cover.
5. If applicable, unblock lines at each dispenser.
Figure 17. Maxxum Packer-Manifold Assembly: Line And Tank Testing
26
Page 31
Testing the InstallationTesting the Tank
OFF
WARNING
rj/051-301-20.eps
Protective cover
Adjustment screw
(as shown 0 - 3 psi setting)
Testing the Tank
Disconnect, lock out, and tag power at the panel before servicing the
pump.
When servicing equipment, use non-sparking tools and use caution when removing or installing
equipment to avoid generating a spark.
1. Lock down the pump check valve by turning the check valve lock down screw clockwise as far as it will turn
(see Figure 17).
2. Remove the Tank Test Plug from the riser flange.
3. Apply tank test pressure at the tank test port.
4. After the completion of the test, release the pressure by:
a.Turning the check valve lock down screw counter clockwise as far as it will go.
b.Remove the protective cover from the Pressurstat (see Figure 18) and turn the Pressurstat adjustment
screw counter clockwise until the screw protrudes 3/4”, this will relieve the line pressure to “0” psi.
Apply an adequate amount of fresh, UL classified for petroleum, non-setting thread sealant on the 1/4”
NPT line test port plug and replace it. Torque the plug to 14 - 24 ft-lbs (19.4 - 29 N•m).
Adjust desired relief pressure per instructions on page 28 and replace the protective cover.
Purging the System
1. Pump a minimum of fifteen gallons (57 liters) of product through each dispenser.
2. Start with the dispenser furthest from the pump and work toward the pump.
Figure 18. Pressurstat - Pressure Adjustment
27
Page 32
Testing the InstallationAdjusting the Pressurstat Line Relief Pressure
Adjusting the Pressurstat Line Relief Pressure
NOTICE
Pressurstat line relief pressure is the line pressure after the pump stops.
1. All pumps are factory set to a line relief pressure of 23-28 psi (160-195 kPa).
2. Remove the protective cover (see Figure 18).
3. Adjust the relief pressure to the desired level. Turning the adjusting screw clockwise will increase the line relief
pressure. With the adjusting screw fully down the line relief pressure should be from 40 to 45 psi. With the
adjusting screw all the way up the pressure should be from 0 to 3 psi.
4. The line relief pressure can be verified in three locations:
a.The pressure can be observed from the control unit of the electronic line leak detector.
b.The pressure can be observed by attaching a gauge to the impact valve.
c.The pressure can be observed by attaching a gauge to the line test port.
5. After setting the desired line relief pressure replace the protective cap. DO NOT USE PIPE SEALANT.
Lubricate the o-ring with petroleum jelly. Tighten to just snug after the protective cover has fully bottomed out.
28
Page 33
Service and Repair
OFF
WARNING
WARNING
1/2-13 Hex bolt
5/8-11 Hex bolt
Protective cover
Yoke-disconnect
(disengaged and
rotated)
Check valve lockdown
screwed in (optional)
Lifting eyes
Removing the Extracta Assembly
Disconnect, lock out, and tag power at the panel before servicing the
pump.
When servicing equipment, use non-sparking tools and use caution when removing or installing
equipment to avoid generating a spark.
1.If a ball valve is installed down line from the pump, close it.
2.Unscrew the 5/8-inch bolt and pull the yoke up and rotate it 90° counterclockwise (see Figure 19).
3.Remove the protective cover from the Pressurstat. Rotate the adjustment screw counterclockwise to relieve pressure in
the packer/manifold assembly.
4.Unscrew and remove the four 1/2-inch Extracta retaining bolts.
Confirm that the lifting eyebolts are properly torqued to 10 ft-lbs (13.6 N•m) with a
minimum of 6 full threads installed. Occasionally, eyebolts are removed after pump installation and corrosion may occur in the threaded areas of the extractable and the
eyebolt. If corrosion has occurred, the extractable and eyebolt should be replaced.
Utilize BOTH lifting eyebolts to suspend the pump vertically. A vertical lift will ensure
that the o-ring in the manifold will not be damaged. Remove the pumping unit and
place it on a clean surface.
Removal of the extractable section of the pump must be conducted with caution. Make
certain that the extractable section remains centered within the riser pipe and that no
portion of the extractable binds during the removal process. If binding occurs during
removal, stop and determine the cause of the binding and correct the situation before
proceeding with removal
.
Figure 19. Maxxum - Extractable Section
29
Page 34
Service and RepairProcedure for Removal of Plug-in Type Pump - Motor Assembly
WARNING
WARNING
NOTICE
Procedure for Removal of Plug-in Type Pump - Motor Assembly
NOTICE
Not all installed pump/motor units will have a locknut securing the pump shell. Steps 3A and
11 can be skipped if no locknut is present.
The UMP (Unitized-Motor-Pump) contains no serviceable parts (other than the foot valve)
and should not be modified or adjusted.
1. Place pump in a horizontal position on a clean surface.
2. Block up under the 3-inch column pipe so that the pump/motor assembly is about 2 inches above supporting
surface.
3A. If a locknut is present; loosen setscrew in locknut. Unscrew the locknut from the discharge head. Slide the
adapter tube up to expose the four hex head machine bolts.
3B. Loosen and remove the four hex head machine bolts on the top of the pumping unit just above the shell and
around the motor.
4. Do not let the pump roll. Using your hands, (do not use a wrench) hold pump at the extreme bottom end and
use a slight up and down motion to pull the pump from the casting attached to the 3-inch pipe.
Up and down motion to remove the pump unit should not be greater than 1/4 inch.
Motion greater than 1/4 inch could damage a positioning dowel pin in the top of the
motor.
5. If the motor leads tend to stay plugged into the motor, finish removing the motor until the leads can be pulled
out of the top of the motor by hand (this is a “plug in” type connection). Verify the number of wires. If there are
only three wires, the pigtail and conduit seal must be replaced with the proper 5-wire version.
6. Pull the pigtail connector in the discharge head out far enough to see the o-ring in the sidewall of its socket.
Remove the connector’s o-ring from the connector’s socket and discard it. Get a 1.234” ID x 0.139” (-218 P/
N 072-712-1) wide o-ring and lubricate it with petroleum jelly. Slide the new o-ring over the pigtail connector
and push it in the groove in the wall of the connector’s socket. Lubricate the pigtail connector body with
petroleum jelly and push it back into its socket, making sure the index tab is in the socket’s notch.
Table E.
HPPigtailBuna SealSeal & Pigtail Kit
3213-065-4110-038-4213-065-5
5213-069-4110-038-4213-069-5
Installed pump/motor units with 3-wire pigtails must be upgraded to the proper 5-wire
pigtail and conduit seal assemblies.
7. Remove the block from the top of the new pump/motor.
8. Look at bottom of the discharge head casting which remains screwed to the 3-inch pipe. Note the position of
the one hex head bolt. Place the four machine bolts through the four bolt holes.
One hole (180 degrees away from the hex head) remains open, this is the locating pin hole.
9. Find the locating pin on top of the motor. This pin must go into the remaining open hole referred to in notice
following Step 8.
10. Place the new pump/motor assembly in position by starting the locating pin into the hole referred to above.
Gently push the motor into place until the shell starts to pass over the large “O”ring. Position the four machine
bolts into the bolt holes and start threads. Draw all bolts down evenly until all are snug. After all bolts are snug,
torque bolts to 24-34 ft-lbs (32-46 N•m).
30
Page 35
Service and RepairInstalling the Extracta Assembly (Ref. Figure 19)
WARNING
OFF
WARNING
WARNING
Draw all bolts down evenly until all are snug. This will help avoid damaging the connector and dowel pin.
11. If a locknut is present; slide the adapter tube down over the discharge head so that it sets against the shell.
Thread the locknut onto the discharge head and tighten until the adapter tube is firmly held in place against
the pump shell. Torque the locknut to 55-75 ft-lbs (75-102 N•m). Torque the setscrew in the locknut to 25-50
in-lbs (2.8-5.6 N•m).
Installing the Extracta Assembly (Ref. Figure 19)
Disconnect, lock out, and tag power at the panel before servicing the
pump.
When servicing equipment, use non-sparking tools and use caution when removing or installing
equipment to avoid generating a spark.
1. Replace the lower o-ring (see Figure 24, Item #4) in the manifold and the one in the lower face of the Extracta
head (see Figure 24, Item #3).
2. Sparingly lubricate the lower o-ring located in the inside the manifold and the o-ring in the lower face of the
Extracta head. Use light grease, oil, or petroleum jelly.
Confirm that the lifting eyebolts are properly torqued to 10 ft-lbs (13.6 N•m) with a
minimum of 6 full threads installed. Occasionally, eyebolts are removed after pump installation and corrosion may occur in the threaded areas of the extractable and the
eyebolt. If corrosion has occurred, the extractable and eyebolt should be replaced.
Utilize BOTH lifting eyebolts to suspend the pump vertically. Lower the Extracta into
position through the manifold assembly. Care should be taken to keep the unit as near
to vertical as possible to avoid damaging the o-rings. Start the four 1/2 inch Extracta
retaining bolts. DO NOT TIGHTEN THEM AT THIS TIME.
3. Rotate the yoke-disconnect into position so that the brass boss aligns with the disconnect port in the packer
assembly.
4. Tighten the 5/8 inch bolt to fully engage the yoke.
5. Torque the four 1/2 inch Extracta retaining bolts to 50 ft lbs.(68 N•m).
6. Torque the 5/8 inch bolt to 50 ft lbs.(68 N•m).
7. Rotate the adjustment screw on the Pressurstat to reset line relief pressure.
8. Lubricate the o-ring on the Pressurstat with petroleum jelly and install the protective cover by rotating it until it
contacts the Pressurstat body. Hand tightening is sufficient, as the o-ring completes the seal.
9. Visually inspect the pumping unit for leaks while the pump is running. This is to ensure that no seals or sealing
surfaces were damaged during removal or installation of the Extracta assembly.
31
Page 36
Service and RepairInstalling the Extracta Assembly (Ref. Figure 19)
rj/051-301-22.eps
Figure 20. UMP - Discharge Head Assembly
Table F.
Number Required
ItemPart No.Description
1036-043-3Head - Motor Discharge111
2213-065-5Pigtail & Conduit Seal - 2, 3, HP11--
2213-069-5Pigtail & Conduit Seal - 5 HP----1
3072-712-1Pigtail O-ring111
4072-714-1Motor Shell O-ring111
5026-179-1Bolt - 3/8-16 x 1 Hex111
6072-309-1Receptacle Housing O-ring111
7031-328-1Gasket Bolt888
8026-110-1Lockwasher 3/8” Spring444
9579025-004 Bolt - 3/8-16 x 2-3/16 Hex-Gr. 5444
10038-241-1Housing Pigtail111
11026-448-1Set Screw Fastener - 1/4”222
NS001-157-3Floating Suction Adaptor - HB--1--
2 HP3 HP5 HP
NS001-026-3Floating Suction Adaptor - K----1
NS001-158-3Floating Suction Adaptor - MB1----
Only the parts listed above are available for repairs of the lower end of the pump. If any other parts need replacing,
order Red Jacket pump-motor assemblies. See page 33 for ordering numbers.
32
Page 37
Service and RepairReplacing the Check Valve Assembly
OFF
WARNING
WARNING
rj/051-301-23.eps
1/2-13 Hex bolt
O-ring
Check valve
Vent line
Thread
protector
Pressure
adjustment
screw
Protective
cover
Replacing the Check Valve Assembly
Disconnect, lock out, and tag power at the panel before servicing the
pump.
When servicing equipment, use non-sparking tools and use caution when removing or installing
equipment to avoid generating a spark.
Close the ball valve in the discharge line if it has been installed.
Care should be taken to ensure that the internal portions of the vent line and check
valve assembly are clean and free of debris or contamination during servicing.
1. Relieve system pressure by removing the protective cover and then backing out the pressure adjustment
screw (see Figure 21).
2. Disassembly
a.Loosen or disconnect the lower vent line fitting.
b.Disconnect the upper vent line fitting.
c.Remove the four 1/2 inch hex bolts.
d.Pull the check valve housing assembly straight out of the manifold.
Figure 21. Maxxum Check Valve Assembly
33
Page 38
Service and RepairRepairing the Check Valve Lock-down Screw And Seals
OFF
WARNING
WARNING
3. Assembly
a.Be certain the two o-rings on the sealing face of the check valve housing are in place.
b.Lower the check valve assembly back down into the manifold taking care not to damage the rubber seal
on the check valve assembly.
c.Install the four 1/2 inch bolts. Torque these bolts to 50 ft-lbs (68 N•m).
d.Remove and discard the thread protector.
e.Re-attach the upper vent fitting then tighten both the upper and lower fittings1/6 to 1/4 turn beyond hand
tight.
4. Readjust the pressure adjustment screw to the desired pressure setting.
5. Replace the protective cover.
6. If applicable, open ball valve down line from the pump.
Repairing the Check Valve Lock-down Screw And Seals
Disconnect, lock out, and tag power at the panel before servicing the
pump.
When servicing equipment, use non-sparking tools and use caution when removing or installing
equipment to avoid generating a spark.
Care should be taken to ensure that the internal portions of the check valve housing
are clean and free of debris or contamination during servicing.
1. Close the ball valve in the discharge line if it has been installed.
2. Lock down screw removal (see Figure 22).
a.Remove the four wiper housing retaining screws.
b.Lift off the wiper housing from the lock-down screw.
c.Remove the wiper from the wiper housing. Avoid damaging the bores in the housing.
d.Unscrew the lock-down screw and remove it from the check valve housing.
3. Lock-down screw re-installation.
a.Replace the two o-rings on the lock-down screw. These o-rings should be installed from the non-threaded
end of the lock-down screw so as to avoid nicking or damaging the o-rings.
b.Sparingly lubricate the two o-rings before screwing the lock-down screw into the check valve housing.
Use light grease, oil, or petroleum jelly.
c.Using a flat piece of metal at least 1/2 inch larger than the OD of the wiper, carefully drive the new wiper
into the wiper housing, orienting the wiper as shown in Figure 22.
d.Sparingly lubricate the wiper ID lip before sliding it over the lock-down screw onto the check valve
housing. Use light grease, oil, or petroleum jelly.
e.Re-install the four #6 wiper housing retaining screws and torque to 20 in-lb (2.23 N•m).
4. If applicable, open the ball valve in the discharge line if it has been installed.
34
Page 39
Service and RepairRepairing the Check Valve Lock-down Screw And Seals
rj/051-301-24.eps
Protective cover
Adjustment screw
Pressurstat body
Spring
Plunger
Diaphragm
Lockdown screw
#8 Screw
Wiper seal
Wiper housing
O-ring
O-ring
1/4 Screws w/
lockwashers
Vent line disconnected
and rotated out of the way
NOTICE
Figure 22. Pressurstat And Check Valve Lock-Down Screw Assembly
35
Page 40
Parts
rj/051-301-25.eps
8
9
1
2
3
4
7
6
5
Figure 23. Check Valve And Pressurstat Assembly
Table G.
ItemPart No.DescriptionQty.
1076-447-1Screw - Adjustment1
2080-944-1Spring - Expansion Relief1
3067-278-1Plunger1
4017-573-1Diaphragm - Expansion Relief1
5072-642-1O-Ring (-112)1
6072-699-1O-Ring (-240)1
7026-752-1Lockwasher4
8026-748-1Screw - Hex Socket4
9072-684-1O-Ring (-910)1
36
Page 41
Parts6” Maxxum Big Flo - Repair Parts Packer Manifold Assembly Parts - Side View
rj/051-301-26.eps
1
2
6
3
4
5
6” Maxxum Big Flo - Repair Parts Packer Manifold Assembly Parts - Side View
Figure 24. Check Valve And Electrical Bushing Assembly
Table H.
ItemPart No.DescriptionQty.
1144-320-5Kit - Lock Down Screw1
2144-317-5Kit - Check Valve1
3072-695-1O-Ring (-366)1
4072-696-1O-Ring (-439)1
5031-334-1Gasket Flange1
6144-321-5Kit - 5 Wire Bushing1
37
Page 42
Parts6” Maxxum Big Flo - Repair Parts Packer Manifold Assembly Parts - Top View
rj/051-301-27.eps
9
7
8
12
10 - Not shown
1
2
11
3, 3A
shown with
siphon plug
installed
4
5
6
6” Maxxum Big Flo - Repair Parts Packer Manifold Assembly Parts - Top View
Figure 25. Maxxum Packer-Manifold Assembly
Table I.
ItemPart No.DescriptionQty.
1036-470-1Handle - Lifting2
2026-750-1Bolt - Hex 1/2-13 x 1-1/26
3144-307-5Kit - Siphon Components1
3a066-163-3Plug - Siphon Plug1
4026-759-1Bolt - Hex 3/4-10 x 1-3/43
5086-010-1Line - Steel Vent1
6027-240-1Plug - Square 1/4 NPT1
7027-276-1Fitting - Tube2
8026-757-1Bolt - Hex 1/2-13 x 14
9067-265-1Plug - 2” NPT With O-Ring1
10072-686-1O-Ring (-228)1
11072-642-1O-Ring (-112)1
12144-322-5Kit-Expansion Relief1
38
Page 43
Parts6” Maxxum Big Flo - Repair Parts Yoke Assembly
rj/051-301-28.eps
6
1
2
3
4
5
6” Maxxum Big Flo - Repair Parts Yoke Assembly
Figure 26. Maxxum Yoke and Contractors Box Assembly
Table J.
ItemPart No.DescriptionQty.
1072-700-1O-Ring (-223)1
2072-689-1Internal Retaining Ring1
3114-319-5Kit - 5 Wire Connector Assembly1
4072-710-1O-Ring (-130)1
5072-697-1External Retaining Ring1
6110-064-5Conduit Box Assembly - 5 Wire 1
39
Page 44
PartsUL Listed Motor Control Box For 2HP Pumps Model P200H1-CB
rj/051-301-29.eps
UL Listed Motor Control Box For 2HP Pumps Model P200H1-CB
1. ATEX Directive 94/9/EC approved 6” Maxxum Submersible Turbine Pumps (STP) marked with the
following information defining its limits for safe use.
• Location Classification:
Duncansville, PA U.S.A.
CE 1180 Ex II2G
2. Special Conditions for Safe Use:
• Certification Nu
• All submerged turbine pumps,
accordance with the manufacturer’s Installation, Operation and Service Manuals supplied.
• All installations shall provide reliable electrical connection between the pump/motor, frame, pipe,
manifold or junction box and the tank structure for both electrical protection and equipotential
bonding.
• The minimum fuel level shall be set 30mm above the highest product intake level at the botto
the pump motor.
• Where terminal boxes are used for termination of the cables from the motor and the supply
source, they shall be ATEX certified for use in gas group IIA and category 2.
• Where a differential pressure switch or transducer is installed, each must be capable of ensuring
that the nominated temperature classification is not exceeded.
• Fasteners
Ex ds IIA T4
mber: LCIE 05 ATEX 6120 X
non m
are
e
manifolds and associated equipment shall be installed in
m of
tric. They shall be replaced only with identical fasteners.
Page 47
Page 48
The City of New York Fire Department Condi
tions of Approval
Certificate of Approval #4970
1. Motor wiring shall be in accordance with the New York City Electrical code for hazardous locations.
2. The installation and use of pumps shall comply with applicable New York City Code, ru
3RCNY § 21-20 and/or 3RCNY § 21-21. Manufacturer’s and Underwriters Laboratories Inc.’s safety requirements
and limitations shall be complied with.
Note: To obtain a copy of the New York City Administrative Fire Code you may contact Citybooks Store at 212-669-
8246. For a copy of the Fire Department Rules of the City of New York please contact Command Information Services,
Legal Publishing Division at 518-436-8647.
3. Pumps shall b
requirements of Underwriters Laboratories Inc.
4. Equipment sh
requirements. The use of this product shall be limited to the indicated intent and has not been acceptable for other
uses or applications.
5. Certificate of Approval number shall be plainly and permanently stamped or
manufacturer. NOTE: Product must already be identified
York City job site.
6. The Certificate of Appr
patent, trade name, trade secret or other intellectual right.
7. The Fire Department Certificate of Approval does not constitute
by the Fire Department, but is a certification that your product, as represented, meets the standards as of the date of
issuance.
8. The Fire Department reserves the right to
that the product does not operate or perform as required by code, the conditions of this resolution or as represented in
your application.
9. The Fire Department’s conditions of approval shall be enumerated in th
provided to New York City buyers, users and installers.
10. As the manufacturer of th
condition as outlined in the approval will be subject to enforcement action which may include fines and imprisonment.
e Underwriters Laboratories Inc. listed and pump manufacturer shall retain follow up service
all have secured and shall maintain all required approvals and shall meet all applicable Federal and State
otherwise fixed upon each pump by the
with Certificate of Approval number before it arrives at New
oval is issued upon condition that the material or equipment’s technology does not violate any
an endorsement or recommendation of your product
withdraw this approval at any time in the event there is a reasonable doubt
e installation manuals and brochures that will be
is equipment/material, you should be aware that any end user who fails to comply with the
les and regulations including
Page 49
ANZEx CONDITIONS OF CERTIFICATION:
1. It is a condition of manufacture that each motor be subjected to the routine high
voltage test of clause 6.2 of AS2380.1.
2. It is a condition of safe use that all submerged turbine pumps, manifolds and
associated equipment be installed in accordance with the manufacturer’s
Installation, Operation and Service Manuals supplied
3. It is a condition of safe use that all installations must provide reliable electrical
connection between the pump motor, frame, pipe, manifold or junction box and
the tank structure for both electrical protection and equipotential bonding.
4. It is a condition of safe use that, where terminal boxes are used for termination of
the cables from the motor and the supply source, they shall be Australian certified
for use in Gas Group IIA and Zone I hazardous areas.
5. It is a condition of safe use that where a differential pressure switch or transducer
is installed, each must be capable of ensuring that the nominated temperature
classification is not exceeded.
Page 50
For technical support, sales or
other assistance, please visit:
www.veeder.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.