Veeder-Root PLLD Installation Manual

OFF
OFF
PLLD Grounding Clamp Manual No: 577014-012 • Revision: A
Installation Guide
Introduction
This guide contains instructions to install a grounding clamp onto an installed PLLD Transducer.
Related Documents
576013-902 PLLD Installation Guide 576013-879 TLS-3XX Site Prep 577013-879 TLS-450 Site Prep
Safety Precautions
EXPLOSIVE
Fuels and their vapors are extremely explosive if ignited.
ELECTRICITY
High voltage exists in, and is supplied to, the device. A potential shock hazard exists.
WARNI N G
Heed the adjacent instructions to avoid damage to equipment, property, environment or personal injury.
READ ALL RELATED MANUALS
Knowledge of all related procedures before you begin work is important. Read and understand all manuals thoroughly. If you do not understand a procedure, ask someone who does.
WARNING
This product is to be installed and operated in the highly combustible environment of a gasoline tank where flammable liquids and explosive vapors may be present.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT, RESULTING IN SERIOUS INJURY OR DEATH.
Observe the following precautions:
1. Read and follow all instructions in this manual, including all safety warnings.
2. To be installed in accordance with the National Electrical Code (NFPA 70) and the Code for Motor Fuel Dispensing Facilities and Repair Garages (NFPA 30A).
3. Before installing this device, turn Off, tag/lock out power to the system, including console and submersible pumps.
4. To protect yourself and others from being struck by vehicles, block off your work area during installation or service.
FLAMMABLE
Fuels and their vapors are extremely flammable.
TURN POWER OFF
Live power to a device creates a potential shock hazard. Turn Off power to the device and associated accessories when servicing the unit.
USE SAFETY BARRICADES
Unauthorized people or vehicles in the work area are dangerous. Always use safety cones or barricades, safety tape, and your vehicle to block the work area.
1
PLLD Grounding Clamp Installation Guide P/N 577014-012
OFF
Kit Contents
Veeder-Root parts required to install the PLLD Transducer grounding clamp are listed in Table 1.
Table 1. PLLD Grounding Kit (Part Number 330020-285)
Item Qty. Description P/N
1 1 Clamp grounding 331285-002
2 1 Ring terminal - 1/4”, 12-10 AWG 576048-061
3 1 1/4”-20 x 1.00 “ bolt 514100-407
4 1 1/4”-20 nut hx sst w/lock washer 511000-251
5 1 PLLD Grounding Clamp Installation Guide 577014-012
Installation Steps
FAILURE TO FOLLOW THE STEPS BELOW MAY IMPAIR INTRINSIC SAFETY, CAUSE DAMAGE TO PROPERTY, ENVIRONMENT, RESULTING IN SERIOUS INJURY OR DEATH
1. Before installing this device, turn Off, tag/lock out power to the system, including console and submersible pumps.
2
2. A separate 4mm
(minimum) wire must be run from the site earth ground to the STP sump in a non­intrinsically safe conduit or duct (see Figure 1). DO NOT CONNECT THE CLAMP OR BODY OF THE PLLD PRESSURE SENSOR TO ANY INTRINSCALLY SAFE WIRE THAT CONNECTS TO THE TLS CONSOLE.
3. Using the ring terminal supplied in the kit, insert the stripped ground wire into the barrel of the ring terminal.
4. Use a properly sized crimping tool to ensure a good tight bond (see Figure 2).
5. Place the clamp around the sensor and attach the ring terminal to the clamp with the clamp bolt.
6. Securely tighten the clamp bolt until the clamp tightly grips the sensor body and no longer can be rotated by hand.
7. Confirm continuity between the PLLD sensor body and ground at the electrical panel and between the electrical panel to the TLS console chassis (reference Figure 3).
2
PLLD Grounding Clamp Installation Guide P/N 577014-012
16mm earth to DB
2
STP in tank sump
4mm (minimum) earth to each PLLD sensor
2
Earth spike
Recommended Earth Layout for PLLD sites
1. Site has 16mm earth (typical) to each tank sump.
2. All sump earths are connected to common point.
3. From the common point, earth is connected to an Earth spike.
4. From the common point, earth is also connected to the building earth in the distribution panel.
Building electrical distribution panel
2
012-3.eps
Securely crimp stripped barrier wire in ring terminal. Slip ring terminal onto bolt and screw bolt into clamp nut. Tighten bolt until the clamp cannot be rotated by hand.
Figure 1.
Figure 2.
33
PLLD Grounding Clamp Installation Guide P/N 577014-012
NOTES:
1. All sensor wiring and intrinsically safe connections installed in accordance with 576013-902 and appropriate site prep manual (see related comments on page 1).
2. Intrinsically safe wiring shall be installed in accordance with article 504-20 of the NEC ANSI/NFPA 70 or local jurisdiction having authority.
3. Do not connect wire that is attached to the PLLD clamp to any intrins
ically safe
wiring.
012-1.eps
PLLD sensor
Earth ground bus
PLLD sensor cable
PRESSURE XMIT
MAXIMUM SENSOR
OUTPUT RATINGS:
15 VDC
.15 AMP
+ + + + + +
1 2 3 4 5 6
PRESSURE LINE LEAK INTERFACE MODULE
Conduit or ducting
Attach cable shield to ground lug closest to conduit/duct entry
+
Intrinsically Safe Bay of Console
AC Mains Breaker Panel
Shield
Ground wire with 4 mm cross­sectional area minimum. Connects to the site’s earth ground.
2
PLLD sensor grounding clamp Tighten bolt until clamp cannot be rotated by hand
Non-Intrinsically safe conduit or ducting
Site Earth ground
Earth ground to TLS Console
Intrinsically safe conduit or ducting
TLS ground wiring cross section must be 4 mm2 or larger. Connect the barrier ground to the earth ground bus at the power distribution panel.
Check continuity between electrical panel earthing bus and PLLD sensor body.
Check continuity between TLS console ground and electrical panel earthing bus.
Figure 3.
4