A103 OPTION MODULES
INSTALLATION
Top View
After the base unit is installed in the panel, the option module can be attached to the
back of the instrument. Orient the module so that terminals A, B. C and D are on
top. Slide the module on to the back of the instrument so that the tabs on the module
fit underneath the grooves on the top of the instrument and above the grooves on the
bottom. The two pieces will fit together tightly enough so that the instrument will
support the weight of the module during wiring. Terminals 1 - 8 on the module
Tabs
connect through to the base unit (Refer to the Technical Manual of the instrument
for corresponding functions and specific wiring instructions). Provided with the
module are 8 long screws and up to 8 short screws. The long screws provide the
connections for terminals 1- 8, and as secure the module to the instrument. The
short screws are for wiring terminals A through E, which are the functions of the
option module.
WIRING
4
3
2
1
A B C D
J H G F E
AC Power
For 115 VAC power, connect the Line from the
source to terminal E and the Neutral to H.
Jumper H to F and G to E so that the inputs are
in parallel. For 230 VAC connect the inputs so
they are in series with the Line to E and the
Neutral to H, then jumper terminals G and F.
H G F E
H G F E
5
6
7
8
Relay Output
Connect AC or DC load circuits to relay
contacts on terminals A, B and J as
shown below.
NO COM
A B
All modules contain 17 terminals. The exact functions that are
present are determined by the model of instrument and option
module.
1 - 8. Connection to instrument. (Refer to
appropriate manual)
A. Normally Open Relay Contact
B. Relay Common
C - D. High or Low Voltage Input (No polarity)
E. 115 VAC Line Input
F. 115 VAC Neutral
G. 115 VAC Line Input
H. 115 VAC Neutral
J. Normally Closed Relay Contact
High/Low Voltage
Connect the High or Low Voltage Input
(depending on which Option Module you have)
to terminals C and D. Polarity of the
connection doesn't matter for either AC or
DC.
AC
or
DC
115 VAC
J
C D
230 VAC
NC
A103 OPTION MODULES
SPECIFICATIONS
AC Power Input
Voltage: 115 or 230 VAC (based on how terminals are wired)
Frequency: 50/60 Hz
Sensor Power Supply: Terminal 8 provides an unregulated 10 - 20
VDC supply for powering sensors up to 50 mA.
Relay Output
Type: SPDT (Form C) mechanical relay
Contact Rating: 5 Amps @ 120/240 VAC or 30 VDC
Contact Material: Silver Alloy
Electrical Life: 500,000 minimum operations
High Voltage Input
Voltage Range: 100 - 260 VAC or VDC
Count Speed: 30 Hz max (50 % duty cycle)
Minimum Pulse Width: 12 ms
Impedence: 200 KΩ
Low Voltage Input
Voltage Range: 5 to 30 VAC or VDC
Count Speed: 30 Hz max (50 % duty cycle)
Minimum Pulse Width: 12 ms
Impedence: 17 KΩ
Mechanical Life: 10 miilion minimum operations
Operate Time: 6 ms
WARRANTY
Standard products manufactured by the
Company are warranted to be free from defects
in workmanship and material for a period of one
year from the date of shipment, and products
which are defective in workmanship or material
will be repaired or replaced, at the option of the
Company, at no charge to the Buyer. Final
determination as to whether a product is
actually defective rests with the Company. The
obligation of the Company hereunder shall be
limited solely to repair and replacement of
products that fall within the foregoing
limitations, and shall be conditioned upon
receipt by the Company of written notice of any
alleged defects or deficiency promptly after
discovery within the warranty period, and in the
case of components or units purchased by the
Company, the obligation of the Company shall
not exceed the settlement that the Company is
able to obtain from the supplier thereof. No
products shall be returned to the Company
without its prior consent. Products which the
Company consents to have returned shall be
shipped F.O.B. the Company's factory. The
Company cannot assume responsibility or accept
invoices for unauthorized repairs to its
components, even though defective. The life of
the products of the Company depends, to a large
extent, upon the type of usage thereof, and THE
COMPANY MAKES NO WARRANTY AS TO
FITNESS OF ITS PRODUCTS FOR SPECIFIC
APPLICATIONS BY THE BUYER NOR AS TO
PERIOD OF SERVICE UNLESS THE COMPANY
SPECIFICALLY AGREES OTHERWISE IN
WRITING AFTER THE PROPOSED USAGE HAS
BEEN MADE KNOWN TO IT.
THE FOREGOING WARRANTY IS EXCLUSIVE
AND IN LIEU OF ALL OTHER WARRANTIES
EXPRESSED OR IMPLIED, INCLUDING, BUT
NOT LIMITED TO ANY WARRANTY OF
MERCHANTABILITY OR OF FITNESS FOR A
PARTICULAR PURPOSE.
Printed in U.S.A.
#701955-0001
Revision B
1675 N. Delany Road
Gurnee, IL 60031–1282
Phone: 847.662.2666
Fax: 847.662.6633