Vector TCY-FT2-U-W01, TCY-FT2-U-W02, TCY-FT2-U, TCY-FT4-U User Manual

U ( )
Temperature PID controller

Features

Temperature PID control for HVAC systems.
Up to two 3-point outputs for 24VAC actuators.
1 internal temperature sensor and up to 2 external sensor inputs
Multiple remote control functions on external input
Password protected programmable user and control parameters
Blue backlight

Applications

Various temperature control applications
Water Only Systems: Radiator, floor heating or chilled ceilings
Individual room control for offices, residential, hotel rooms,
meeting rooms, etc.

General Description

The TCY-FT-U is a stand-alone electronic universal controller with one temperature control loop. It may use up to 2 PID sequences. The TCY-FT-U features 1 internal NTC temperature sensor, up to two external sensors inputs and up to four binary outputs. The configuration has been reduced to a minimum to allow for a simple and off the shelf usage. For more advanced features the TCI product range may be used. The TCY-FT-U can be configured using the standard operation terminal. No special tool or software is required.
TCY-FT-U

Name

T C Y
-
F
T
2
-
Housing: U = Vertical (2x4”) housing, Standard is square housing Function: 2 = 2 = 2-Pipe, 4 = 4-Pipe Input: T = Temperature, H = Humidity Output: F = 3-point, M = Modulating, B = Binary Series: TCY

Ordering

Item Name Item code Control Type Key-data
TCY-FT2-U-W01 40-10 0068-1 Cooling only
TCY-FT2-U-W02 40-10 0068-2 Heating only
TCY-FT2-U 40-10 0068 2-Pipe system TCY-FT4-U 40-10 0072 4-Pipe system 1 TI, 2 3-point outputs
Accessories S-Tn10-2
SD-Tn10-12-2 SD-Tn10-20-2 SDB-Tn10-12 SDB-Tn10-20 SRA-Tn10
40-20 0001 40-20 0002 40-20 0003 40-20 0051 40-20 0004 40-20 0005
Flying lead sensor with 2 m cable Flying lead duct sensor 12cm immersion depth, 2m cable Flying lead duct sensor 20cm immersion depth, 2m cable Duct sensor with housing, 12cm immersion depth Duct sensor with housing, 20cm immersion depth Room sensor
Compact PID controller with: 2 TI, 1 3-point output
Selection of actuators and sensors Temperature Sensors:
Use only our approved NTC sensors to achieve maximum accuracy. Recommended is SDB-Tn10-20 as Duct sensor, SRA­Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.

3-point Actuators:

Actuators with constant running time are recommended. Observe power limits. Do not use actuators with power consumption > 6VA. Adjust running time in SW. Default running time is 90s for fully open / close running time.
Doc: 70-00-0128B, V1.2, 20110621 © Vector Controls GmbH, Switzerland Page 1 Subject to alteration
)
)
(
)

Technical specifications

Power Supply
Signal inputs
Signal outputs
Environment
Standards
General
Operating Voltage 24 V AC ± 10 %, 50…60 Hz, Class 2, 48VA max
Power Consumption Max. 1.5 VA
Electrical Connection Terminal Connectors,
Temperature Input Range Accuracy
TRIAC Outputs Switching power
Operation Climatic Conditions Temperature Humidity
Transport & Storage Climatic Conditions Temperature Humidity Mechanical Conditions
conform according to EMC Standard 89/336/EEC EMEI Standard 73/23/EEC
Product standards Automatic electrical controls for household and similar use Special requirement on temperature dependent controls
Degree of Protection IP30 to EN 60529
Safety Class III (IEC 60536)
Cover, back part Mounting Plate
Dimensions (H x W x D) Front part: 112 x 73 x 15 mm (4.4” x 2.9” x 0.6”)
Weight (including package) 260 g (9.2 oz)
TCY-FT-U
Technical Specifications
wire 0.34…2.5 mm
2
(AWG 24…12)
0…50 °C (32…122 °F)
0.5 K
24 VAC, 250mA max Do not use actuators with power consumption > 6VA
To IEC 721-3-3 class 3 K5 0…50 °C (32…122 °F) <95 % r.H. non-condensing
To IEC 721-3-2 and IEC 721-3-1 class 3 K3 and class 1 K3
-25…70 °C (-13…158 °F) <95 % r.H. non-condensing class 2MT2
EN 61 000-6-1/ EN 61 000-6-3
EN 60 730 –1
EN 60 730 – 2 – 9
Fire proof ABS plastic (UL94 class V-0) Galvanized Steel
Power case: ø 58 x 32 mm (ø 2.3” x 1.3”)

Dimensions [mm] (inch)

73 (2.9
112 (4.4)
32 (1.2
15
0.6
58 (2.3)
Doc: 70-00-0128B, V1.2, 20110621 © Vector Controls GmbH, Switzerland Page 2 Subject to alteration
Connection diagram
24V AC/DC
COM
TCY-FT-U
Technical Specifications
X
T CO
IN
COM
X
T EXT
IN
2 G
1
G0
0V (COM)
24V AC/DC
2 G
1
G0
0V (COM)
5
M
3
Y1
OPEN
3
Y1
Heat
OPEN
6
X2
4
Y2
CLOSE
4
Y2
Heat
CLOSE
7
M
Signal
COM
7 M
5
Y3
Cool
OPEN
8
X1
X
T EXT
IN
8
X1
6
Y4
Cool
CLOSE
X
T INT
TCY-FT2-U
X
T INT
TCY-FT4-U
Description:
G0 0V Power supply: 0VAC, internally connected to signal common G 24V Power supply: 24VAC M 0V Signal common: Common 0 potential for analog inputs and analog outputs. X1 RT External temperature input: NTC 10k @ 25°C (77°F)
TCY-FT2-U: X2 CO Change over input: NTC 10kΩ @ 25°C (77°F) Y1 DO1 Binary output: Valve open Y2 DO2 Binary output: Valve close
TCY-FT4-U: Y1 DO1 Binary output: Heating valve open Y2 DO2 Binary output: Heating valve close Y3 DO3 Binary output: Cooling valve open Y4 DO4 Binary output: Cooling valve close

Mechanical Design and installation

The unit consists of two parts: (a) The power case with attached mounting plate and (b) the front part.

Mounting location

On an easy accessible interior wall, approx. 1.5 m (4.5’) above the floor in an area of average temperature.
Avoid exposure to direct sunlight or other heat sources, e.g. the area above radiators and heat emitting electrical
equipment.
Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.
Location of mounting is less critical if external temperature sensors are used

Installation

1. Connect the wires to be connected to the terminals of the power case according to wiring diagram
2. Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is
facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2”) off the surface of the mounting plate.
3. Ensure that the jumpers are set correctly.
4. Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.
5. Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle
way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is normal. Do not use excessive force!
6. With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to
the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the screw too much
Doc: 70-00-0128B, V1.2, 20110621 © Vector Controls GmbH, Switzerland Page 3 Subject to alteration