Contact Temperature Sensor SC-T
Contact Temperature Sensor SC-T
Contact Temperature Sensor SC-T
Tightening strap for ½-3in pipes
Tightening strap for 3-6in pipes
Thermistor:
Range: (Probe only)
Accuracy:
-40…0°C (-40…32°F):
0…50°C (32…122°F):
50…100°C (122…212°F):
> 100°C (> 212°F):
NTC
-70…150°C (-94…302°F)
0.5 K
0.2 K
0.5 K
1 K
Platinum-Film:
Range: (Probe only)
Accuracy
PT according EN 60751
-70…200°C (-94…392°F)
EN 60751, Class B, ask for other class
Nickel Thin Layer:
Range: (Probe only)
Accuracy
1000 Ω at 0°C, 5000 ppm/K
-60…200°C (-76…392°F)
DIN 43760
Standard
Size
Insulation material
Operating Temperature
Ratings
2 x 0.20 mm2 (AWG 24)
PVC
-40…80°C (-40…176°F)
UL758, 1581/CSA C22.2 No 210.2
High temperature
Size
Insulation material
Operating temperature
Ratings
-H
2 x 0.35 mm2 (AWG 22)
FEP
-60...200°C (-76…392°F)
ULR/CSA C22.2 No 210.2
Plenum rated
Size
Insulation material
Operating temperature
Ratings
-P
2 x 0.5 mm2 (AWG 20)
Plenum PVC
-20…75°C (-4…167°F)
UL C(UL) PLENUM CMP OR E355847
FPLP UL
Single insulated PVC
Size
Insulation material
Operating Temperature
Ratings
-A
2 x 0.20 mm2 (AWG 24)
PVC
-40…80°C (-40…176°F)
UL758,1581 CSA C22.2 No.210.2
Operation
Climatic conditions
Temperature depends on cable
type
To IEC 721-3-3
class 3K5
See above
Transport & storage
Climatic conditions
Temperature
Humidity
Mechanical conditions
To IEC 721-3-2 and IEC 721-3-1
class 3K3 and class 1K3
-40…80°C (-40…176°F)
< 95% RH non-condensing
class 2M2
conform according to
EMC Standard 89/336/EEC
EMEI Standard 73/23/EEC
EN 61 000-6-1/ EN 61 000-6-3
Automatic electrical controls for
household and similar use
Special requirement on
temperature dependent controls
EN 60 730 –1
EN 60 730 – 2 – 9
Normal acc. to EN 60 730,
RoHS compliant
Dimensions (Diameter x L)
Probe: ø 6 x 35 mm (ø 0.25” x 1.4”)
Contact Plate: 20x30mm (0.8” x 1.2”)
Weight (including package)
SC-Tn10-2A
Cable type:
default: PVC cable double insulated
-H = High temperature
-P = Plenum rated
-A = PVC cable single insulated
Cable length in Meter
Sensing Element (see below)
Sensor Type: Sensor with flying lead
SC-T
SC-T, Flying Lead Contact Temperature Sensor
Features
Thermistors and PT sensing elements to fit your system
Strap-On mounting for pipes or arched surfaces
Simple installation
Wide range of temperature probes
Including 2m (6.5ft) wire
Applications
Measure temperature for heating, ventilation and air conditioning
applications
For heating or cooling mode detection in 2-pipe systems
As frost protection sensor
Temperature sensor
The sensor measures the temperature by use of a glass packed thermistor
with a negative temperature coefficient (NTC), a platinum film (PT) or a nickel
thin layer (NI) based probe. Its resistance changes according to the
temperature. The change follows a specified curve. A summary of such curves
is printed on the back of this document. Contact our sales department for
curves or sensing elements not yet listed below.
Compensating conductor resistance
The length and type of conductors used to connect the sensor to the
measuring electronic influences the accuracy of the measurement. Especially
for elements with low resistance this has to be taken into account.
Compensation needs to be performed by the measurement electronics.
Ordering
Technical Specification
Warning! This device is intended to be used for comfort applications. Where a
device failure endangers human life and/or property, it is the responsibility of the
owner, designer and installer to add additional safety devices to prevent or detect
a system failure caused by such a device failure. The manufacturer of this device
cannot be held liable for any damage caused by such a failure.
Failure to follow specifications and local regulations may endanger life, cause
equipment damage and void warranty.
Wiring & Installation
Wiring Diagram
Dimensions [mm](in)
Installation
Mount the sensor on a supply or return pipe depending on application.
Make sure the maximum allowed temperature limit is not exceeded.
For better temperature transfer between sensor and medium use heat
conducting paste or heat conducting pads.
If possible place the sensor on the upper side of the pipe to prevent
permeation by condensate.
Bend the wings of the contact sensor to fit to the radius of the pipe.
Place the heat conducting pad or liquid between pipe and sensor and use the
tightening strap to fix the sensor to the pipe. Use moderate torque, do not
crush the sensor.
Doc: 70-00-0215A, V1.0, 20140722 © 2012-2014 Vector Controls GmbH, Switzerland Subject to alteration
www.vectorcontrols.com