VDH MC 785 CHILLER-2 User Manual

Page 1
Description : MC 785 CHILLER-2 Doc.no.: 032189
Type: MANUAL No. of pages: 16 Version: V1.5
File: Do032189 MC785-CHILLER v15 EN.wpd Software: 021913_MC785 CHILLER V2.02
By: BJB Date: 29-03-2012
VDH Products BV - Roden - Holland Signed: File: Doc'02
MC 785 CHILLER-2
(Panel-mounted)
Page 2
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 2 of 16
This document has been prepared with great care and the information it contains is assumed to be accurate. However, VDH Products does not accept any liability for eventual mistakes and errors and reserves the right to alter or adapt the document without notice.
Table of contents
1 Technical specifications ........................................................3
1.1 General ...............................................................3
1.2 Front ..................................................................3
1.3 Inputs and outputs ....................................................... 4
1.4 On LMS Modules ........................................................4
2 Functional specifications .......................................................5
3 Operation ...................................................................6
3.1 Switching the chiller on and off ............................................. 6
3.2 Readout of different pressure and temperature sensors ..........................6
3.3 Switching from cooling/heating ............................................. 6
3.4 Changing the temperature setpoint ..........................................6
3.5 Changing the chiller pump .................................................6
3.6 Changing the sea pumps mode ............................................. 6
3.7 Switching cooling/heating capacity and the sequence of the regulator ...............6
3.8 Maximum compressor capacity ............................................. 7
3.9 Switching off the carter delay ............................................... 7
3.10 Readout the counters ....................................................7
3.11 Resetting all counters ....................................................7
3.12 Resetting alarms ........................................................7
3.13 Shifting the generator capacity (reduced generator load) ......................... 7
3.14 Emergency stop .........................................................7
3.15 Compressor startup release contacts ........................................7
4 Programming internal parameters ................................................ 7
4.1 Parameter table .........................................................8
4.2 Cooling control operation .................................................10
6 Sensor calibration ........................................................... 11
7 Alarms .................................................................... 11
8 Front ......................................................................12
9 Connection diagrams .........................................................13
9.1 Connections of MC 785-CHILLER 2 ........................................13
9.2 Principle of LMS modules connections ......................................14
9.3 Connections of LMS Modules. .............................................15
10 Dimensions ................................................................ 16
Page 3
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 3 of 16
1 Technical specifications
1.1 General Type : MC 785 CHILLER Housing : Panel-mounted steel plate Material : Silver grey steel plate Dimensions : 217 x 155 x 85mm (whd) Panel cutout : 208 x 146mm (wh) Front : Polycarbonate (IP-44) Temperature range : -40/+50OC per 0.1OC Supply : 230 Vac; 50/60 Hz (-10/+5%). Power supplied : 9 VA Working temperature : -20/+50OC Storage temperature : -20/+60OC Working RH : 10/+90 % RH non-condensing Accuracy : ± 0.5 % of the range
1.2 Front Displays : 4-digit display for the inlet temperature
4-digit display for the temperature setpoint 4-digit display for the outlet temperature 4-digit display for the capacity
LEDs : High-1 Alarm = Failure high pressure-1 alarm (yellow)
Oil-1 Alarm = Failure oil pressure-1 alarm (yellow) Low-1 Alarm = Failure low pressure-1alarm (yellow) High-2 Alarm = Failure high pressure-2 alarm (yellow) Oil-2 Alarm = Failure oil pressure-2 alarm (yellow) Low-2 Alarm = Failure low pressure-2 alarm (yellow) Oil heat delay = Oil heating starting-up-delay active (yellow) Alarm = General alarm indication (red) Comp-1 Alarm = Compressor-1 failure (red) Comp-2 Alarm = Compressor-2 failure (red) Pump-1 = Pump-1 active (green) Pump-2 = Pump-2 active (green) Cool = Regulator in cooling mode (green) Heat = Regulator in heating mode (green) Comp-1 = Compressor-1 active (green) Comp-2 = Compressor-2 active (green) SeaP-1 = Sea water pump-1 active (green) SeaP-2 = Sea water pump-2 active (green)
Keys: ON/OFF = On/off key controller
SET = Setpoint push button PRG = Programming key + = Increasing values key
- = Decreasing values key PRESS SENS = Readout pressure sensors key CAP. LIMIT = Readout capacity limits key PUMP 1 / 2 = Pump choice key COOL / HEAT = Function choice key for cooling/heating mode RESET ALARM = Alarm reset key
Page 4
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 4 of 16
1.3 Inputs and outputs Sensors : Inlet temperature sensor (10K, 2-wire)
Outlet temperature sensor (10K, 2-wire) HP-2 Pressure sensor-1 PX77 range: 0-25 bar (2-wire 4/20mA output) OIL-2 Pressure sensor-2 PX77 range: 0-10 bar (2-wire 4/20mA output) LP-2 Pressure sensor-3 PX77 range: 0-10 bar (2-wire 4/20mA output) HP-1 Pressure sensor-4 PX77 range: 0-25 bar (2-wire 4/20mA output) OIL-1 Pressure sensor-5 PX77 range: 0-10 bar (2-wire 4/20mA output) LP-1 Pressure sensor-6 PX77 range: 0-10 bar (2-wire 4/20mA output) Note: Pressure sensors need external supply thru SM615 (15Vdc)
Communication: I2C-bus (for LMS-units) (2-wire shielded min. 0.75mm2)
RS485-network-1 (for LMS Analog-out mod.) (2-wire shielded min. 0.75mm2) RS485-network-2 (for PC) (2-wire shielded min. 0.75mm2)
1.4 On LMS Modules
Modules on the I2C expansion-bus of the MC785-CHILLER 2 controller;
LMS Dig.in-1 : IN-1: Failure chiller pump-1 (NC potential free input contact) (max. 6 inputs) IN-2: Failure chiller pump-2 (NC potential free input contact)
IN-3: Waterflow-1 contact (NC potential free input contact) Jumpers IN-4: Waterflow-2 contact (NC potential free input contact) J2 IN-5: Thermistor INT69-1 (NC potential free input contact) J1 IN-6: Thermistor INT69-2 (NC potential free input contact)
LMS Dig.in-2 : IN-1: Failure compressor-1 (NC potential free input contact) (max. 6 inputs) IN-2: Failure compressor-2 (NC potential free input contact)
IN-3: Failure sea water pump-1 (NC potential free input contact) Jumpers IN-4: Failure sea water pump-2 (NC potential free input contact) J2 IN-5: Maximum thermostat heating (NC potential free input contact) J1 IN-6: Cabinet cooling thermostat (NC potential free input contact)
LMS Dig.in-3 : IN-1: Generator load reduction (NC potential free input contact) (max. 6 inputs) IN-2: Emergency stop (NC potential free input contact)
IN-3: Interlock cooling water failure (NC potential free input contact) Jumpers IN-4: Maximum compressor capacity (NC potential free input contact) J2 IN-5: Release startup compressor-1 (NC potential free input contact) J1 IN-6: Release startup compressor-2 (NC potential free input contact)
LMS Relay-1 : RY1: Start compressor-1 U1/SN (SPDT C-NO-NC, 250Vac/8A non-inductive) (max. 7 outputs) RY2: Start compressor-2 U2/SN (SPDT C-NO-NC, 250Vac/8A non-inductive)
RY3: Start sea water pump-1 U3/SN (SPDT C-NO-NC, 250Vac/8A non-inductive) Jumpers RY4: Start sea water pump-2 U4/SN (SPDT C-NO-NC, 250Vac/8A non-inductive) J2 RY5: Start chiller pump-1 (SPST C-NO, 250Vac/8A non-inductive) J1 RY6: Start chiller pump-2 (SPST C-NO,250Vac/8A non- inductive)
RY7: Anti-condensation heating (SPST C-NO, 250Vac/8A non-inductive)
LMS Relay-2 : RY1: Alarm circuit A (SPDT C-NO-NC, 250Vac/8A non-inductive) (max. 7 outputs) RY2: Alarm circuit B (SPDT C-NO-NC, 250Vac/8A non-inductive)
RY3: Supply fluid valve compr-1 (SPDT C-NO-NC, 250Vac/8A non-inductive) Jumpers RY4: Supply fluid valve compr-2 (SPDT C-NO-NC, 250Vac/8A non-inductive) J2 RY5: Startup request compr-1 (SPST C-NO, 250Vac/8A non-inductive) J1 RY6: Startup request compr-2 (SPST C-NO, 250Vac/8A non-inductive)
RY7: Cooling cabinet (SPST C-NO, 250Vac/8A non-inductive)
Page 5
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 5 of 16
LMS Relay-3 : RY1: Electric heater-1 (SPDT C-NO-NC, 250Vac/8A non-inductive) (max. 7 outputs) RY2: Electric heater-2 (SPDT C-NO-NC, 250Vac/8A non-inductive)
RY3: Electric heater-3 (SPDT C-NO-NC, 250Vac/8A non-inductive) Jumpers RY4: Electric heater-4 (SPDT C-NO-NC, 250Vac/8A non-inductive) J2 RY5: Oil heating-1 (SPST C-NO, 250Vac/8A non-inductive) J1 RY6: Oil heating-2 (SPST C-NO, 250Vac/8A non-inductive)
RY7: Spare (SPST C-NO, 250Vac/8A non-inductive)
Modules on the local RS485-Network-1 of the MC 785-CHILLER-2 controller;
LMS 4x10K-1: IN-1: 10K NTC Exchanger sensor-1 (10K, 2-wire) (max.4 inputs) IN-2: 10K NTC Exchanger sensor-2 (10K, 2-wire) Jumpers IN-3: 10K NTC Exchanger sensor-3 (10K, 2-wire) J3 2 1 IN-4: 10K NTC Exchanger sensor-4 (10K, 2-wire) IN-5: spare (RH-sensor-1, 3-wire)
IN-6: spare (RH-sensor-2, 3-wire)
LMS MDR : OUT-1: Compressor-1 0/+10Vdc (Rbmin 10Kohm, programmable) (max. 4 outputs) OUT-1: Compressor-2 0/+10Vdc (Rbmin 10Kohm, programmable) Jumpers OUT-1: Sea water pump-1 0/+10Vdc (Rbmin 10Kohm, programmable) J1 2 3 4 5 6 OUT-1: Sea water pump-2 0/+10Vdc (Rbmin 10Kohm, programmable)
Remarks: = Jumper placed (on),
= Jumper not placed (off)
2 Functional specifications
The MC 785 CHILLER is a control system which brings the water for a heating- or an airconditioning system to the desired temperature.
The MC 785 CHILLER has two pumps. One of these pumps is always working when the unit is on and ensures that the water is circulated. The other pump can be selected by pressing the key PUMP 1 / 2 on the front.
The choice for heating or cooling can be made by using the COOL / HEAT key.
For heating, the temperature is regulated by 1 to 4 electric heaters. The heating steps are switched on or off on the basis of the return temperature. The sequence of the heaters and the maximum capacity can be adjusted.
For cooling, two compressors are available. These are regulated by the return temperature. The sea water pump of each of the compressors is switched on shortly before a compressor goes on. The different pressures in the compressors are measured and can be viewed on the front when the PRESS SENS key is pressed. When the values of one of these pressure sensors are improper, the compressor switches off and an error-code appears on the display. The sequence of the compressors and the maximum capacity can be adjusted by means of keys on the front.
After power-up there is a 60 seconds delay before initialisation of the controller. After initialisation or switch-on of the controller there is a 30 seconds delay before checking the flow switches.
Page 6
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 6 of 16
3 Operation
During normal operation the top left-hand display shows the INLET temperature, the top right-hand the OUTLET temperature, and below left (SETPOINT) shows the OUTLET setpoint temperature. The display below right (CAPACITY) shows the capacity currently being used for heating/cooling.
3.1 Switching the chiller on and off. The regulator can be switched on or off by pressing the ON/OFF key.
3.2 Readout of different pressure and temperature sensors. By using the PRESS SENS key the values of the different pressure sensors will be shown consecutively in the top left-hand display. With the help of the LEDs next to this display you can see which sensor value is being shown. If there is no LED on next to the display then the INLET temperature is shown on the display. If the PRESS SENS key is then pressed once or more the exchange temperature sensors of the LMS 4x10K/2xRH unit can be read consecutively. This is indicated by the ‘EC1..4' in the right­hand display and the value of the sensor in the left-hand display.
3.3 Switching from cooling/heating. If the COOL/HEAT key is pressed, the regulator will switch from cooling to heating or vice versa. The LEDs next to the bottom left-hand display indicates whether the regulator is cooling or heating.
3.4 Changing the temperature setpoint. When the regulator is cooling the bottom left-hand display shows the current cooling setpoint. When heating is taking place the heating setpoint is indicated there. The setpoint can be altered by pressing the SET key. The regulator will now ask for the ‘user password’. The ‘user password’ can be entered by using the UP and DOWN keys. If it is correct the setpoint can be changed by pressing the SET key. The setpoint will now start to blink, and the setpoint can be adjusted with the UP and DOWN keys. The cooling setpoint can be set at between 5°C and 10 /C, the heating setpoint at between 30°C and 40 /C. Now if no key is pressed for 30 seconds the setpoint will stop blinking and the new septoint will become active.
3.5 Changing the chiller pump. A switch can be made to the other chiller pump by means of the PUMP1/2 key. All compressors and heaters will be switched off while the regulator goes to the other pump. Then they will turn themselves on again (with possible delay times). The LEDs next to the bottom left-hand display indicate which chiller pump is in operation
3.6 Changing the sea pumps mode. With the help of the sea pumps mode setting (P217) we can choose between two modes P217=0: Fixed couplings between sea pumps and compressors
Now sea-pump-1 belongs with compressor-1 and sea-pump-2 with compressor-2.
P217=1: Choose for 1 sea pump
Now a choice can be made as to which sea pump will be used. The choice should be made as follows: First, turn the regulator off with the ON/OFF key. Then use the COOL/HEAT key to choose which sea pump will be used, then the appropriate LED will light up. When the choice has been made, the regulator can be turned on again.
3.7 Switching cooling/heating capacity and the sequence of the regulator. By pressing the CAP.LIMIT key next to the bottom right-hand display the current maximum heating capacity will be shown. The word ‘HEAT’ will appear in the display above to show that we are dealing with heating. With the help of the UP and DOWN keys the capacity can be adjusted. If the CAP.LIMIT key is pressed once more the heater sequence appears in the display; a different sequence can be selected with the UP and DOWN keys. Next, press the CAP. LIMIT key once again and the capacity and the regulating sequence of the cooling can be changed in a similar way.
Page 7
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 7 of 16
3.8 Maximum compressor capacity. If contact input 4 of LMS Dig-in module 3 is closed, then only 1 compressor is active.
3.9 Switching off the carter delay. By pressing the PRG key and the SET key simultaneously and then entering the service code, and by then pressing the SET key as confirmation, the carter heating delay will be switched off if the code is correct. (This operation to be carried out by H&H).
3.10 Readout the counters. When the PRG key and the PRESS.SENS key are pressed simultaneously the hour and cycle counters for the compressors, heaters, seawater-pumps and chiller-pumps will be displayed. The upper left display shows ‘C.1 h’ = compressor-1 hours and the lower left display shows the counted hours. The upper right display shows ‘cYcl’ = cycle counts and the lower right display shows the cycle counter value. By pressing the PRG key once or more times the following hour and cyle counts will be shown:
C.2 compressor-2 S.1 sea pump-1 H.1 heater-1 S.2 sea pump-2 H.2 heater-2 P.1 chiller pump-1 H.3 heater-3 P.2 chiller pump-2 H.4 heater-4
3.11 Resetting all counters. When the PRG key and the RESET ALARM key are pressed simultaneously and the service code is then entered, all the operational hours and the cycle counters are reset to zero.
3.12 Resetting alarms. As soon as an alarm situation occurs and an error code appears in the temperature display the alarm can be reset by pressing the RESET ALARM key. The error code warning remains in the display until the cause of the error has been solved.
3.13 Shifting the generator capacity (reduced generator load). By closing the digital inlet (LMS dig.in 3 input-1) the generator capacity is decreased by parameter P232 percent.
3.14 Emergency stop. By closing the digital inlet (LMS dig.in 3 input-2) the emergency stop function is activated. Everything is turned off and ‘Egy-‘ and ‘STOP’ appear alternating in the display to indicate this.
3.15 Compressor startup release contacts. If a compressor wants to startup, the according startup request relay is activated and the compressor waits for the according release startup compressor input to be closed to startup the (released) compressor.
4 Programming internal parameters
By pressing the PRG key for a few seconds and then entering the service code digit by digit with the UP, DOWN and SET keys, the internal parameter mode can be entered.
‘P P’ appears in the upper right display while the number of the parameter will appear in the upper left display. Using the UP and/or DOWN keys the desired parameter can then be selected. The lower left display shows the value of the parameter. By pressing the SET key and the UP or DOWN key at the same time the value can be adjusted. If no key is pressed for 30 seconds the display will return to the normal operational status.
Page 8
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 8 of 16
4.1 Parameter table.
No. Description Range Unit Default
Sensor settings
P 01 P 02
Offset inlet temperature sensor-1 Offset outlet temperature sensor-2
-10.0...+10.0
-10.0...+10.0
O
C
O
C
0.0
0.0
P 10 P 11 P 12 P 13
Value HP2 pressure sensor-1 at 4mA Value HP2 pressure sensor-1 at 20mA Offset HP2 pressure sensor-1 Delay factor pressure sensor-1
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar bar bar %
0.0
25.0
0.0 10
P 14 P 15 P 16 P 17
Value OIL2 pressure sensor-2 at 4mA Value OIL2 pressure sensor-2 at20mA Offset OIL2 pressure sensor-2 Delay factor pressure sensor-2
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar bar bar %
0.0
10.0
0.0 50
P 18 P 19 P 20 P 21
Value LP2 pressure sensor-3 at 4mA Value LP2 pressure sensor-3 at 20mA Offset LP2 pressure sensor-3 Delay factor pressure sensor-3
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar bar bar %
0.0
10.0
0.0 50
P 22 P 23 P 24 P 25
Value HP1 pressure sensor-4 at 4mA Value HP1 pressure sensor-4 at 20mA Offset HP1 pressure sensor-4 Delay factor pressure sensor-4
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar bar bar %
0.0
25.0
0.0 10
P 26 P 27 P 28 P 29
Value OIL1 pressure sensor-5 at 4mA Value OIL1 pressure sensor-5 at20mA Offset OIL1 pressure sensor-5 Delay factor pressure sensor-5
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar bar bar %
0.0
10.0
0.0 50
P 30 P 31 P 32 P 33
Value LP1 pressure sensor-6 at 4mA Value LP1 pressure sensor-6 at 20mA Offset LP1 pressure sensor-6 Delay factor pressure sensor-6
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar bar bar %
0.0
10.0
0.0 50
P 40 P 41 P 42 P 43 P 44
Number extra LMS exchanger sensors Offset LMS exchanger sensor1 Offset LMS exchanger sensor2 Offset LMS exchanger sensor3 Offset LMS exchanger sensor4
0..4
-10.0...10.0
-10.0...10.0
-10.0...10.0
-10.0...10.0
O
C
O
C
O
C
O
C
2
0.0
0.0
0.0
0.0
Heating
P100 P101 P102
Offset first heater Differentiation first heater Delay first heater
-10.0...+10.0
0.1...10.0
0...999
O
C
O
C
Sec.
0.0
1.0 60
P103 P104 P105
Offset second heater Differentiation second heater Delay second heater
-10.0...+10.0
0.1...10.0
0...999
O
C
O
C
Sec.
-1.0
1.0
120
P106 P107 P108
Offset third heater Differentiation third heater Delay third heater
-10.0...+10.0
0.1...10.0
0...999
O
C
O
C
Sec.
-2.0
1.0
180
P109 P110 P111
Offset fourth heater Differentiation fourth heater Delay fourth heater
-10.0...+10.0
0.1...10.0
0...999
O
C
O
C
Sec.
-3.0
1.0
240
Page 9
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 9 of 16
No. Description Range Unit Default
P120 P121 P122
Minimum adjustable temperature setpoint heater Maximum adjustable temperature setpoint heater Heaters present
0.0..+90.0
0.0..+90.0 0 = no, 1 = yes
O
C
O
C
-
+30.0 +40.0
1
Cooling
P200
P201
Start delay compressors if the regulator has been out for more than P201 hours. Regulator out - hours limit
0...100
0...100
hour
hour
8
4
P202 P203 P204 P205 P206
Cool offset-1 (see function flow) Cool offset-2 Cool offset-3 Cool offset-4 Cool offset-5
-10.0...+10.0
-10.0...+10.0
-10.0...+10.0
-10.0...+10.0
-10.0...+10.0
°C °C °C °C °C
0.0
0.0
3.0
3.0
6.0
P207
P208
P209
P210 P211
Minimum time that the compressor runs at minimum capacity Time in which the frequency of the compressor increases from 0,0 to 10,0 Volt Time in which the frequency of the compressor decreases from 10,0 to 0,0 Volt Anti shuttle time of compressors Delay before compressor-2 switches on
0...999
0...999
0...100
0...100
0...999
Sec.
Sec.
Sec.
Min. Sec.
60
180
15
5
60
P212
P213
High pressure in which the frequency of the sea pump is zero. High pressure in which the frequency of the sea pump is ten.
0...99.9
0...99.9
bar
bar
14.0
19.0
P214 Maximum chill per minute 0.0...10.0 °C 0.2
P215 P217
Offset set point at cooling Sea pump mode 0 = fixed coupling
1 = 1 sea pump
-15.0...+15.0
0..1
°C
-
1.5 0
Setpoint
P220 P221
Minimum adjustable temperature setpoint cooling Maximum adjustable temperature setpoint cooling
0.0...+90.0
0.0...+90.0
°C °C
5.0
12.0
Capacity reduction
P230
P231 P232
Cooling capacity reduction with “Generator load reduction” input closed Time in which cooling capacity is reduced with P230 Capacity reduction heating-mode with reduced generator power
0...100
5...300
0...100
%
Sec. %
40
20 50
Page 10
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 10 of 16
No. Description Range Unit Default
Alarm
P300 P301
P302 P303
Minimum temperature alarm sensor-1 Minimum temperature alarm sensor-2 and exchanger sensors (LMS) Maximum temperature alarm sensor-1 Maximum temperature alarm sensor-2
0...+100.0
0...+100.0
0...+100.0
0...+100.0
°C °C
°C °C
5.5
2.0
45.0
45.0
P304 P305 P306 P307 P308 P309 P310 P311
High pressure alarm high pressure sensors Low pressure alarm low pressure sensors Low pressure alarm real oil pressure Delay low pressure alarm real oil pressure High pressure too low alarm High pressure too low alarm delay Water flow alarm delay Number of flow switches
0...+99.9
0...+99.9
0...+99.9
0...200
0...+99.9
0...200
0...200
1..2
bar bar bar Sec. bar Min. Sec.
-
22.0
2.0
0.7 45
3.0 30
1 2
User password
P400 User password 0...9999 - 0000
General
P502 P990 P991 P995 P996 P997
Digital inputs filter time Network identification number Log interval Software version Serial number Production date
0.0...5.0
1...250
0...120
-
-
-
seconds
­minutes
-
­Year.week
1.0 1 5
-
-
-
4.2 Cooling control operation: The following function flow diagram is designed to explain the operation of the compressor control:
Page 11
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 11 of 16
6 Sensor calibration
With parameters P1, P2, P41, P42, P43 and P44 the temperature sensors can be calibrated. If a temperature sensor readout is 0.2/C too high, for example, the offset of the appropriate temperature sensor should be set 0.2/C lower.
The pressure sensors can be calibrated with parameters P12, P15, P18, P21, P24 and P27. If a pressure sensor readout is 0.3 bar too low, for example, then the offset of the appropriate pressure sensor must be set 0.3 bar higher.
In addition, every pressure sensor has a 4mA and a 20mA value setting for setting its range.
For example: The settings for a pressure sensor with a range of 0.00 .... +10.00 bar and an
output of 4...20mA are as follows: The parameter for the value at 4mA must be set at 0.00, and the parameter for the value at 20mA must be set at 10.00.
7 Alarms
An alarm can be caused by:
E1 Temperature sensor-1 inlet defect. E2 Temperature sensor-2 outlet defect.
E3 Pressure sensor-1 (HP2) defect. E4 Pressure sensor-2 (OIL2) defect. E5 Pressure sensor-3 (LP2) defect.
E6 Pressure sensor-4 (HP1) defect. E7 Pressure sensor-5 (OIL1) defect. E8 Pressure sensor-6 (LP1) defect.
E10 No contact with LMS extra sensors E11 Temperature LMS sensor 1 too low E12 Temperature LMS sensor 2 too low
E15 Temperature LMS sensor-1 defect E16 Temperature LMS sensor-2 defect
E20 Too low pressure pressure sensor-6
compressor-1
E 21 Too low pressure pressure sensor-3
compressor-2
E22 Too high pressure pressure sensor-4
compressor-1
E23 Too high pressure pressure sensor-1
compressor-2
E24 Too low pressure pressure sensor-5 oil
pressure-1
E25 Too low pressure pressure sensor-2 oil
pressure-2
E26 Too low pressure pressure sensor-4
compressor-1
E27 Too low pressure pressure sensor-1
compressor-2
E30 Inlet temperature lower than outlet temperature
E31 Temperature sensor-1 inlet too low E32 Temperature sensor-2 outlet too low
E33 Temperature sensor-1 inlet too high E34 Temperature sensor-2 outlet too high
E40 Cabinet cooling failure E41 Error waterflowswitch 1
E42 Chiller pump-1 failure E43 Chiller pump-2 failure
E44 Compressor-1 failure E45 Compressor-2 failure
E46 Maximum thermostat
E47 INT69-1 failure E48 INT69-2 failure
E49 Sea pump-1 failure E50 Sea pump-2 failure
E51 Error waterflowswitch 2 E52 Interlock cooling water fault
E60 Communication error LMS dig-in module-1 E61 Communication error LMS dig-in module-2 E62 Communication error LMS dig-in module-3
E63 Communication error LMS relay module-1 E64 Communication error LMS relay module-2 E65 Communication error LMS relay module-3
The alarm warnings can be seen in the temperature display (top left).
By pressing the RESET ALARM key the alarm relay can be reset. The error code continues to appear in the display as long as the fault remains. The alarm LED will also continue to blink.
Page 12
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 12 of 16
8 Front
Front view of the MC785-CHILLER panel-mounted model, drawing 021773
Page 13
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 13 of 16
9 Connection diagrams
9.1 Connections of MC 785-CHILLER 2 (panel mount), drawing 021774w2.
Page 14
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 14 of 16
9.2 Principle of LMS modules connections.
Block diagram with I/O and network connections MC 785-CHILLER 2 drawing 071782w1
Page 15
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 15 of 16
9.3 Connections of LMS Modules.
Page 16
User manual Document no. : 032189 Version : V1.5
MC 785 CHILLER-2 Customer: Heinen & Hopman Page: 16 of 16
10 Dimensions
Dimensions MC 785 panel-mounted, drawing 961271
Dimensions LMS modules:
-.-.-.-.-.-.-.-.-.-
@
Loading...