Varmeteknikk MB 35, MB 45, MB 90, MB 105, MB 120 Installation, Operation & Service Manual

...
Installation - operating - servicing
MB – boilers
35 – 45 – 60 – 75 – 90 105 - 120 - 140 -150kW
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
2
Model
MB 35
MB 45
MB 60
MB 75
MB 90
Power 35kW 45kW 60kW 75kW 90kW
Nominal supply voltage
Power circuit 3 x 400V 3 x 400V 3 x 400V 3 x 400V 3 x 400V
Control circuit 1 x 230V
50/60Hz
1 x 230V
50/60Hz
1 x 230V
50/60Hz
1 x 230V
50/60Hz
1 x 230V
50/60Hz
Amps 51A 65A 87A 108A 130A
Number of elements 4 4 7 7 7
Temp.controller (steps) 7 7 7 7 7
Temp. range 30 – 95 °C 30 – 95 °C 30 – 95 °C 30 – 95 °C 30 – 95 °C
Water contents (liters) 75 75 75 75 75
Tube connections
Outlet/inlet DN65/16 DN65/16 DN65/16 DN65/16 DN65/16
Expansion/drain 1" 1" 1" 1" 1"
Water circulation Δt=20 °C (m³/h) 1,5 1,9 2,6 3,2 3,9
Pressure drop(Wc) 2 3 5 7 10
Water speed(m/s) 0,11 0,14 0,19 0,23 0,28
Max. working pressure 6bar 6bar 6bar 6bar 6bar
Min. working pressure 1bar 1bar 1bar 1bar 1bar
Dime
nsions size
(cm)
Height 128 128 128 128 128
Width 38 38 38 38 38
Depth 69 69 69 69 69
Weight empty, (kg) 130 130 135 135 140
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
3
Model
MB 105
MB 120
MB 140
MB 150
Power 105kW 120kW 140kW 150kW
Nominal supply voltage
Power circuit 3 x 400V 3 x 400V 3 x 400V 3 x 400V
Control circuit 1 x 230V
50/60Hz
1 x 230V
50/60Hz
1 x 230V
50/60Hz
1 x 230V
50/60Hz
Amps 152A 173A 202A 217A
Number of elements 7 7 7 8
Temp.controller (steps) 7 7 7 7
Temp. range 30 – 95 °C 30 – 95 °C 30 – 95 °C 30 – 95 °C
Water contents (liters) 75 75 75 75
Tube connections
Outlet/inlet DN65/16 DN65/16 DN65/16 DN65/16
Expansion/drain 1" 1" 1" 1"
Water circulation Δt=20 °C (m³/h) 4,5 5,2 6,0 6,5
Pressure drop(Wc) 14 18 24 28
Water speed(m/s) 0,33 0,37 0,43 0,47
Max. working pressure 6bar 6bar 6bar 6bar
Min. working pressure 1bar 1bar 1bar 1bar
Dimensions(cm)
Height 128 128 128 128
Width 38 38 38 38
Depth 69 69 69 69
Weight empty, (kg) 145 150 150 155
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
4
MB 35 - 150kW
590
690
NB! Fri høyde over kjel, ca. 100cm
1
2
3
4
5
6
7
8
9
10
1. Temp. controller
2. Safety temp .limiter
3. ON/OFF –switch
4. Contactors
5. Fuses/circuit breakers
6. Bus bars for connecting
Supply cables
7. Drain
8. Return
9. Flow
10. Expansion
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
5
Technical data 2
General information
Installation 6 Pressure safety valve 6 Connection 6 Control voltage 6
Commissioning
Start up 7 Temperature controller 7 Settings 8 Additional functions 9
Remote control
Boiler Start/stop 10 Temperature control 10 Power control 10
Monitoring
Operation signal 11 Failure signal 11 Output signals 0-10V 11 Terminal block 11
Menus 12
Maintenance 13
Troubleshooting 14
Circuit diagrams
Control circuit 15 Power circuit 16
Temp. controller
Terminals 17
Spare parts 18
Content
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
6
Installation
THE BOILER MUST BE POSITIONED IN SUCH A WAY THAT IT DOES NOT PREVENT PERFORMANCE OF SERVICE AND MAINTENANCE.
Required free height above the boiler for disassembly of heating elements is 1m. Front and at least one side should be free in order to perform service and maintenance.
Pressure safety valves
The boiler must be equipped with pressure safety valves. The pressure safety valves should be placed as close as possible to boiler and it should not be any shutoff between the valves and the vessel. The opening pressure must not exceed maximum operating pressure of the boiler. To avoid damage a pipe pointing down towards the floor, should be fixed to the pressure safety valves.
Connection
NOTE! INSTALLATION MUST ONLY BE EXECUTED BY QUALIFIED PERSONNEL
All applicable regulations must be observed when electrical and plumbing connections. Sufficient provision must be made for expansion, in accordance with applicable regulations
Supply cables
Connect supply cables to the bus bars by using a ring terminal or suitable cable clamps. Two earth clamps is located in bottom of the switch gear for earth cables.
Control voltage
220-230V control voltage is required. Connection to be done on F1 & F2 on the terminal block inside the boiler. See page 11.
E x p a ns io n
F lo w
R e tu rn
D r a in
C o n ne c ti n g m a in p o we r
C o n ne c ti n g co n tro l v olt a g e
A95-30A95-30
Li f tin g h o o k
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
7
Commissioning
Note! BEFORE SWITCHING ON THE BOILER CHECK THE FOLLOWING:
- Check that the water system is completely filled with water. To prevent heating element break down make sure there is no air pockets in plant.
- Switch on circulating pump and check water flow and direction.
- Hydraulic expansion system has to be controlled. Min. pressure, 1bar.
- Check for correct supply voltage
Note! Before start up, retighten all electrical connections.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Start up
Switch on the boiler by using the ON/Off-switch on the front panel. Display will after a few seconds show actual water temp., preset temp. in brackets. The line below shows connected power. Boiler will now step by step increase power to obtain preset temperature.
The temperature is factory set at 80 °C, and step time is set to 40 sec. Unless corrections of preset temperature or step time are required, no further adjustments are needed.
Note! If boiler is controlled by external signals, missing signal can prevent boiler from running.
Temperature controller
The boiler is equipped with a 7-steps electronic temperature controller located in front of the boiler. All settings can be done at the front. The controller has a proportional and integrating control and is designed to maintain constant boiler temperature. Temperature range is from 5 - 95°C in steps by 1 °C. 3 relays control the power contactors which are connected in a binary order. This gives a high degree of reliability
If a failure occurs, an alarm diode starts flashing. Type of failure will be shown in display and could be:
Don’t switch on the boiler if there is a possibility that the
water in boiler
is frozen.
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
8
Error temp: Temperature sensor is broken Alarm net: Control voltage < 190V Alarm power: Power supply missing*
* Alarm power is activated if controller when reaching step 3, doesn’t measure any power. The reason for this could be that main switch/circuit breaker on the switch board is OFF, security temp. limiter (STB) released because of high temperature, heating element/fuse is broken, or contactor is not connected.
Settings
Failure Menu button Enter button
Preset temperature:
Temperature range is from 30 – 95 °C. Preset temperature is factory set to 80 °C. If correction is needed do the following:
Press + or – button to set desired temperature. Then press enter to save new value.
Step time:
Step time is adjustable between 20-250 sec. (factory setting is 40 sec.) and refer to connection of power steps. When disconnecting power, step time is 5 sec. with step time below 60 sec., 10 sec with step time above 60 sec. If correction is required do the following: Press menu button once to enter step limitation mode. Then press + or – button. To enter step time mode press menu button. With +/- button choose desired step time. Press E button to save new value.
Step 0( 7)
Step time 40s
Step lim 0( 7
)
Step time 40s
Step lim 0( 7)
Step time 40s
Step 0( 7)
Step time 50s
To return to temp/power mode, press menu button.
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
9
Additional functions
The temp. controller has been provided with a large number of other functions in addition to several possibilities for remote control.
Remote boiler in/out
The temp. controller is equipped with a potential free input for start/stop of the boiler. The disconnecting signal can be either an “OFF” or an “ON” switch. With a clamp on the PCB the temp. controller can be adjusted to either type of signal (see page 30). If start signal is missing display shows:
Step S 0 ( 0)
Step time 40s
See page 11 for connecting start/stop signal.
Power limitation
The maximum output of the boiler can easily be limited. It is only possible to limit the boiler on a whole step base. Limitation can be done in the menu or on a potentiometer located on the PCB.
Limitation in menu:
Enter Step mode and press – button. Choose number of power steps and then press E button to save new value.
Step lim 0(30
)
Step time 40s
Step lim 0(25)
Step time 40s
For limitation on the PCB, see page 17
Outdoor temperature compensator
The temp. controller is prepared for outdoor temperature compensation. If outdoor sensor is connected, boiler will calculate and set flow temperature depending on outdoor temperature. Both curve and parallel are available for fine-tuning flow temperature. When outdoor sensor is connected, display shows:
TempU 47.0 (50)°C
Power 60kW
Temperature in brackets is calculated flow temperature depending on outdoor temperature. It is not possible to change calculated temperature when outdoor sensor is connected.
Outdoor t. 24°C
Parallel 0°C
For further information, contact Varmeteknikk.
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
10
Remote control by external signals
The boiler offers several possibilities for remote control. With a start/stop signal (potential free), boiler can be connected/disconnected from running. Maximum output or preset temperature can be controlled by a 0-10V DC signal.
Remote start/stop of boiler
Boiler can be switched On/Off by an external signal. Before connecting signal, remove bridge on terminal 1 & 2, see next page. If start/stop-signal is connected and boiler gets start signal, display shows:
Temp 47.0 (75)°C
Step 0 (30)
Temperature control by 0-10V signal
Desired temperature can be controlled by a 0-10V DC signal. 0V = 20°C, 10 V = 120C°. Normal temp. range is from 20 – 95°C, equivalent to 0 - 8,5V. Connection on terminal 30(-) and 31( +)
on PCB (see page 17). Signal must be activated in service menu, see page 12. "Temp IN" must be set in ”ON” position. Press + button twice and then E to enter new value.
Temp IN
ON
Press menu button twice to return to "Temp/Power" mode. When signal is activated display shows:
TempE 47.0(75)°C
Power 60kW
Note! When desired boiler temperature is controlled by a external 0-10V signal, internal set point
must be set as high as boiler should work. Internal thermostat is now working as a maximum thermostat and limit the temperature. This must be done before signal is activaded.
Power control by 0-10V signal
Boiler output can be controlled by a 0 -10V DC signal. 0V = 0 step, 10V = all steps (15/30). Con­nection on terminal 29(+) and 30(-) on PCB (see page 17). Signal must be activated in service menu, see page 12. "Power IN" must be set in "ON" position. Press + button twice and then
E to enter new value.
Power IN
ON
Press menu button twice to return to "Temp/Power" mode. When signal is activated display shows:
StepE 3 ( 7)
Step time 40s
Temp 47.0 (75)°C
Step S 0 ( 0)
If start signal is missing, display shows:
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
11
Monitoring
Boiler is prepared for output digital signals to a central monitoring system. The signal contacts are wired to a terminal block inside the boiler. The outlet signals are:
Operation signal: indicates boiler is ON connection on terminal 3 & 4.
Failure: indicates STB released, sensor broken or control voltage < 190V. Connection
on terminal 5 & 6. Type of error is shown in display.
Output 0-10V DC signals:
External power indication: 0V = 0kW, 10V = Max kW (terminal 36 & 39) External temp.indication: 0V = 20 °C, 10V = 120°C (terminal 36 & 38) External preset temperature: 0V = 20 °C, 10V = 120°C (terminal 36 & 37)
Connection diagram, see page 17.
Terminal block inside boiler
2
6
8
7
9
5
4
3
F2
F1 F1
F2
1
Transformer
Control voltage
On/off ext.
230V 50Hz, 10A
Styrespenning
Inn-/utkobling
Failure
6
8 9
7
Trafo
3
5
4
1
2
L2
L1
Operation
Driftsignal
Feilsignal
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
12
Menus
By pressing menu button, different modes appears
Start up:
EL 7 v0549
El 15: 7-steps controller v0549: version
Main menu
Temp 60.0(80)°C
Power 120kW
Step
1( 7)+
Step time 40s
Outdoor t.
-
15°C
Parallel 0°C
(appears only if outdoor sensor is connected)
Settings in main menu:
- Desired temperature
- Number of power steps
- Step time
Service menu
To get access to service menu, press and hold menu button for more than 5sec.
Temp 60.0(80)°C
Power 120kW
Curre
nt lim
0,0(5,0)A
Current marg
1,0A
Power
factor
60kW/A
Curve 40°C
Curve min 20°C
(Appears only if outdoor sensor is connected)
Test contactor 0
K1-4 0000 A1
Step time
Service 0
Power
IN
OFF
Temp IN
OFF
English
Node 0 Net 107
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
13
Maintenance
NOTE!
BEFORE SERVICE AND MAINTENANCE, BE SURE SUPPLY CABLES ARE DEAD.
Always use an appropriate voltage detector to verify that there is no voltage present.
After boiler has been in operation for some time, retighten electrical connections. To prevent breakdown, boiler should be checked annually. This check should contain the following points:
- Leakage control
Make a visual inspection of the boiler checking for signs of water leakage. Remove top cover and check on top of the pressure vessel for leakage from heating elements.
- Power checking
Check if circuit breakers have tripped. Check by resistance measurement if any heating elements are broken.
- Contactors
Check all individual contactors if they are in normal position. Undertake a visual inspection of all wiring to the contactors and check for signs of overheating or burning. Any noise from con­tactor indicates wear and requires a thorough check. Be aware that burnt contactors may cause major damage.
- Electrical connections
Retighten all electrical connections on fuse holders, contactors and heating elements.
- Temp.controller
Check if temp.controller connect or disconnect power steps when adjusting preset temp. up and down. By entering service menu connection of power groups/contactors can be checked.
- Safety temp.limiter
Check safety temp.limiter. This can be done by switching off circulation pump or close valves. The boiler will then soon reach release temp. Safety temp. limiter must be manually reset.
Note!
SERVICE AND MAINTENANCE SHOULD ONLY BE CARRIED OUT BY QALIFIED PERSONNEL
Tightening torques for contactors:
Contactor, type Connection screw Tightening torque AF9, AF12, AF 16 M3,5 1,5Nm AF26, AF30, AF 38 M4 2,5Nm AF40, AF52, AF 65 M6 4Nm
Tightening torques for circuit breakers:
type Connection screw Tightening torque
MS132/10 M3,5 1,2Nm
MS132/12 - 16 M4 1,5Nm MS132/20 - 32 M4 2Nm
XT1 M6 6Nm
Tightening torque for heating element: M4 - 1,2Nm M12 - 15Nm
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
14
Troubleshooting
NOTE! TROUBLESHOOTING MUST ONLY BE EXECUTED BY QUALIFIED PERSONNEL
FAILURE DISPLAY TEXT
POSSIBLE CAUSE OF TROUBLE
CONTROL /REPAIR
BOILER ”dead”
Control voltage missing Boiler needs separate
control voltage
Fuse/s for control voltage broken Check fuses and replace if
required
NO POWER
Temp 30.0 (80)°C
StepS 0 ( 0)
External start signal missing Check external signal. (See
terminal 1& 2 on –X1)
Temp 30.0 (80)°C
StepE 0 ( 0)
External signal for power control missing
Check external signal
TempE 20.0 (20)°C
Power 0kW
External signal for temperature control missing
Check external signal
Temp 0.0 (80)°C
Error Temp
Defect temp.sensor
Change temp.sensor and Replace if required
BOILER STOPS AT STEP 3
(Alarm diode is flashing)
Temp 30.0 (80)°C
Alarm Power
Connecting box mounted on left side without moving transformer
Transformer must be mounted on same side as connecting box
Temp 30.0 (80)°C
Alarm Power
Safety temp.limiter has tripped Reset safety temp.limiter
(STB) on front panel
Temp 30.0 (80)°C
Alarm Power
Main switch off or broken fuses Check switch board/fuses
Replace if required
LITTLE HEAT FROM BOILER
Temp 50.0 (80)°C
Step 4 ( 4)
Maximum power limited from outside
Check external signals from a central monitoring system
TempU 30.0 (30)°C
Power 0kW
Check if boiler is limited from outdoor compensator
Check curves for outdoor compensation
Defect heating elements,
fuses, contactors
Check heating elements, fuses, contactors and replace if required
STB, safety temp.limiter released
(Display shows "Alarm Power")
Temp 30.0 (80)°C
Alarm Power
circulation in boiler Check pump/valves
Burned contactor
Check contactors and replace if required
LEAKAGE
Loose screws for heating element Tighten screws
Gasket for heating element Replace if required
Defect heating element Replace if required
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
15
Circuit diagram MB 35 - 150kW
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
16
Power circuit MB 35-150kW
Appa ratplate
400V
MB 105 kW/120kW/140kW
Appa ratplate
400V
MB 60kW/75kW/90kW
Appa ratplate
400V
MB 35kW/45kW
-E1
-E2
-E3
-E4
-E1
-E2
-E3
-E4
-E5
-E6
-E7
-E1
-E2
-E3
-E4
-E5
-E6
-E7
Appa ratplate
400V
MB 150kW
-E1
-E2
-E3
-E4
-E5
-E6
-E7
-E8
Switc h gear
Switc h gear
Switc h gear
Switc h gear
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
17
Temp.controller, terminals
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
19
Spare parts MB 35 – 150kW
Number
Item
Article no.
35kW
45kW
60kW
75kW
90kW
105kW
120kW
140kW
150kW
Heating element 5kW 6613 0001-K 1 Heating element 6kW 6613 0001-P 1 Heating element 7,5kW 6613 0001-AR 2 Heating element 9kW 6613 0001-N 5 1 Heating element 10kW 6672 0242-A 3 3 3 1 Heating element 12kW 6613 0001-G 2 3 Heating element 15kW 6672 0242-D 1 4 7 4 Heating element 20kW 6672 0242-G 3 7 7 Gasket 2152 0022-4 4 4 7 7 7 7 7 7 8 Temp.controller 7-steps 901 310 1 1 1 1 1 1 1 1 1 Sensor temp.controller 200 232 1 1 1 1 1 1 1 1 1 ON/OFF-switch 6672 0235-3 1 1 1 1 1 1 1 1 1 Safety temp.limiter (STB) 6672 0235-1 1 1 1 1 1 1 1 1 1
230V
400V
230V
400V
230V
400V
230V
400V
230V
400V
230V
400V
230V
400V
230V
400V
230V
400V
Contactor AF12 41 175 16 1 1 Contactor AF16 41 175 32 1 1 1 1 1 1 Contactor AF26 41 175 48 3 1 3 1 2 3 1 3 4 1 1 1 1 2 Contactor AF30 41 175 56 1 1 1 3 1 Contactor A50 41 147 56 1 3 2 3 3 3 3 3 Contactor A63 41 148 16 3 Contactor A75 41 148 46 3 Contactor A95 41 149 36 2 Contactor A110 41 150 26 2 2 Fuse control voltage 10A 6672 0235-27 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Circuit breaker MS132/10-16 43 640 80 1 2 1 1 1 1 Circuit breaker MS132/16-20 43 640 81 1 Circuit breaker MS132/20/25 43 640 82 1 1 1 1 1 Circuit breaker MS132/25-32 43 640 83 1 1 1 1 1 Circuit breaker XT1-32 067 411 Circuit breaker XT1-40 067 412 1 1 1 1 1 Circuit breaker XT1-50 067 413 1 1 1 3 1 Circuit breaker XT1-63 067 414 1 1 1 3 1 3 3 Circuit breaker XT1-80 067 415 1 1 1 3 1 Circuit breaker XT1-100 067 416 1 3 Circuit breaker XT1-125 067 417 1 3 3 Circuit breaker XT1-160 067 418 1 Transformer Natek 200 018 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Transformer 100/5A 6672 0235-50 1 1 1 1 Transformer 200/5A 6672 0235-51 1 1 1 1 1 1 1 1 Transformer 300/5A 6672 0235-53 1 1 1 Transformer 400/5A 6672 0235-54 1 1 1
Spare parts valid from 29
.2015
Varmeteknikk AS August 2017 e-mail: post@varmeteknikk.no
21
Notes