Vapac VapaNet Series, LE05, LE30, LE45, LE55 Operation Manual

...
These instructions contain operating information and should be left with the unit.
Electrode Boiler Units
LE
Installation & Operation Manual
Edition 3.2.2
(For use with Software version 7.1 & subsequent issues)
Installation in countries covered by EC Directives:
This product meets the requirements of the RoHS Directive 2002/95/EEC
This product will meet the requirements of the Low Voltage Safety Directive
Directive
2004/108/
Failure to comply with these instructions may invalidate the manufacturer's warranty or any
certificate/declaration of conformance requested to be supplied with the unit.
EEC when installed in accordance with the instructions contained in this manual.
2006/95/
EEC and the EMC
2
CONTENTS
Important Installation Points .................................................................................................................... 3
1.0 Installation. .................................................................................................................................... 4
1.1 Vapac LE unit dimensions ......................................................................................................... 4
1.1.1 LE weights ............................................................................................................................. 8
1.2 Positioning the steam pipes ...................................................................................................... 8
1.2.1 General .................................................................................................................................. 8
1.2.2 Steam Hose Connection ........................................................................................................ 8
1.3 Plumbing Considerations. ......................................................................................................... 9
1.4 Electrical Connections ............................................................................................................. 10
1.4.1 Important E.M.C. Considerations ....................................................................................... 10
1.4.2 Power Supply Connection ................................................................................................... 11
1.4.2.1 Volt free alarm outputs ........................................................................................................ 11
1.4.2.2 Unit control terminals ........................................................................................................... 11
1.4.3 Electrical Connections ......................................................................................................... 12
1.4.4 Cable Entry Provision .......................................................................................................... 12
1.4.5 Vapac Control Circuit Transformer ...................................................................................... 12
1.4.6 RDU Connection .................................................................................................................. 12
1.5 Cylinder Electrical demand loads ............................................................................................ 14
1.5.1 LExx Units............................................................................................................................ 14
1.5.2 LExxP Units ......................................................................................................................... 17
1.6 Control Circuit Connections .................................................................................................... 19
1.6.1 Control Circuit Wiring ........................................................................................................... 19
1.6.2 Proportional Control ............................................................................................................. 19
1.6.3 Control Signal Selection ...................................................................................................... 19
1.6.4 On/Off Control ..................................................................................................................... 19
1.6.5 Sensing Head ...................................................................................................................... 20
1.6.6 Security Circuit / E.P.O. Shutdown ...................................................................................... 20
1.6.7 Load Shed Option ................................................................................................................ 20
1.6.8 Master/Slave System ........................................................................................................... 21
2.0 Start-Up / Operation .................................................................................................................... 22
2.0.1 Start-up check list ................................................................................................................ 22
2.0.2 Start-Up Instructions ............................................................................................................ 22
2.0.3 Commissioning/Start-Up ...................................................................................................... 22
2.0.4 Features of VAPANET Electode Boiler Unit ........................................................................ 22
2.1 Service Advice......................................................................................................................... 23
2.1.1 Procedure for cylinder Exchange. ....................................................................................... 23
2.1.2 Typical Cylinder / Electrode Layouts ................................................................................... 23
2.2.1 Feed Valve with Strainer ..................................................................................................... 24
2.2.2 Drain Pump .......................................................................................................................... 24
3.0 Location of Indicators and Controls ............................................................................................ 25
3.1 Positioning of Indicators and controls on Vapac ® Vapanet ® LE Units. ............................... 25
3.2 Initial Set-up ............................................................................................................................ 26
3.3 Normal Run / Standby / Start-up – No User Intervention Required ........................................ 27
3.4 Fault / Service Indications – Requiring Operator Intervention. ............................................... 28
3.4.1 To Postpone the Sevice: ..................................................................................................... 28
3.4.2 To Service the unit: .............................................................................................................. 29
3.5 Fascia Label symbols .............................................................................................................. 30
3.6 Other Options .......................................................................................................................... 30
4.0 Trouble-shooting Check List ....................................................................................................... 31
5.0 Wiring diagram ............................................................................................................................ 32
Appendix 1. ............................................................................................................................................ 43
A Guide to Positioning Steam Pipes: ................................................................................................. 43
Appendix 2 ............................................................................................................................................. 45
A Guide to Positioning Multipipes: ..................................................................................................... 45
3
Important Installation Points
The unit must be installed to comply with national regulations and/or codes of practice. A qualified electrician must carry this out.
Ensure at least 1000 mm clear front access to the electrical and steam sections.
Do not locate the cabinet where the ambient temperature around the unit could exceed 35º C; or fall below 5º C e.g., an unventilated roof mounted enclosure – see minimum space / ventilation requirements page 7. * If below 5º C Frost protection kit required.
Do not locate the cabinet where a ladder is required for service access as this could make servicing and cylinder service or exchange hazardous.
Make sure steam line(s) have adequate slope (min 12%) for condensate drainage and use condensate separators if the pipe is lower than the unit.
Provide adequate support to prevent sags developing in flexible steam lines, which can fill with water and create a "trap".
Do not locate vented drain directly under the cabinet.
Important Electrical Connection Items
Control cabling should be run in screened cables and kept separate from any mains carrying cables (see page 10).
Before commissioning the unit, check that all electrical (power) connections - including those at the terminals and contactor are tight.
Check that the transformer primary winding connection is correct for the supply voltage at Vapac terminals A1 & A2.
The Vapac transformer must not be used to power other equipment.
Do not mount the 'LR' unit close to a source of strong electromagnetic emissions, such as a variable speed motor drive, Kva transformer, or 'UPS' unit. A minimum gap of 2 meters must be maintained between the unit and such devices. Larger output devices may require an increased gap distance, depending on the nature of screening / filtration measures fitted to the device.
Use a high-limit humidistat to ensure positive interruption of unit operation when over­humidification is detected (See page 17).
It is important that the control signal connected to terminals 5 & 6 must be referenced to ground at the control PCB – this can be done by linking either terminal 5 or 6 to terminal 7. NB if the controller output is referenced to ground, it is important that the “leg” which is connected to ground at the controller is also connected to ground at the Vapac unit. Grounding the opposite “leg” will cause damage to the controller and/or the Vapac control PCB.
Important Maintenance Items
Only a qualified electrician should carry out maintenance.
The boiler contains hot water, and must be drained before any maintenance is carried out on the steam section. This should be done prior to isolating the power, and removing the front access panel
ESD SENSITIVE DEVICES USED ON PCB. ENSURE ANTI-STATIC PRECAUTIONS ARE TAKEN WHEN REMOVING OR REPLACING PCB’S.
Cabinet Size 1.
LE18
All
points.
1.0 Installation.
Do’s
Do mount the unit as close to the steam distribution
pipe(s) as possible.
Do mount the unit at a height convenient for reading the
display window.
Do ensure adequate side ventilation (min 80 mm). Do ensure adequate service access to the front of the unit
(min 1000 mm).
Do ensure adequate service access below the unit (min
1000 mm).
Do ensure that the holes in the rear top panel remain
unobstructed to allow a free flow of air see fig 1.
Do use the marking on the side of the carton as a template
to mark the mounting hole positions.
Do remove the cylinder, if necessary, to access the
mounting holes in the back of the steam section.
Do use M6 projecting type wall bolts or equivalent to
mount the unit in position.
Do mount units with RDU’s so that steam pipe discharge is
above head height.
Do leave minimum gap between the top of an RDU and
the ceiling as per table in fig 2.
1.1 Vapac LE unit dimensions
Covering model references:
LE05 – All LE09 – All
6.0265.055.0
4
Don’ts
Don’t mount the unit close to sources of strong electro-
magnetic emissions e.g. variable speed lift motor drives, kVa transformers etc.
Don’t mount the unit in an unventilated enclosure. Don’t mount in a position requiring ladder access to the
unit.
Don’t mount the unit behind a false ceiling or other
situation where an unusual malfunction (e.g. water leak) would cause damage.
Don’t mount the unit in an area which will be hosed down. Don’t install the unit where the ambient temperature can
exceed 35oC; or fall below 5oC (Unless frost protection kit fitted).
Don’t mount the unit inside a cold-room or other place
where temperature and humidity conditions can cause condensation on electrical components.
Don’t mount the unit where the sound of a contactor
opening/closing and water flow in a pipe would be
unacceptable e.g. libraries, private apartments, etc. Don’t position an RDU to discharge directly over expensive equipment, desks or stored materials
203.0172.0
6.0
Left: Top view of unit showing steam outlet position (35 mm spigot)
Below: Rear view of unit showing wall mounting
.
Right: View from beneath unit showing the electrical gland plate (approx 120mm x 120mm) with an entry hole (approx 105mm x 90mm)
120.0
140.0
675.0
50.0
74.0444.0
Left: View from beneath unit showing:
‘F’ (Feed) 19mm BSP male connection for connection for flexible hose provided with unit.
‘D’ (Drain) connection for 35 mm pipe.
172.0203.0
285.0
430.0
70.0
F
D
204.0
For clearance around the unit for ventilation & access please see page 7
Cabinet Size 2.
LE55
-
All
Covering model references:
LE30 – All LE45 – All
6
360
55
165
330
305
5
6
186
Steam Outlet 54 mm
Left: Top view of unit showing steam outlet position (54 mm spigot)
Below: Rear view of unit showing wall mounting points.
165
Right: View from beneath unit showing the electrical gland plate (approx 120 mm x 120 mm) with an entry hole (approx 105 mm x 90 mm)
Gland Plate
810
120 X 120
299
62
52
520
73555
305
70
Left: View from beneath unit showing-
‘F’ (Feed) ¾ “ BSP male connection for connection
D
F
90
for flexible hose provided with unit.
‘D’ (Drain) connection for 35 mm pipe.
For clearance around the unit for ventilation and access and for units with RDU’s see page 7
Cabinet Size 4.
Covering model references:
LE60 – All LE90 – All LE110 – All
6
360
55
610
190
6
176
346
322
6
55
360
Steam Outlets 54 mm
Left: Top view of unit showing steam outlet positions (54 mm spigots)
Below: Rear view of unit showing wall mounting points.
610
990
190
73555
Right: View from beneath unit showing the electrical gland plate (approx 120 mm x 120 mm)
with an entry hole (approx 105 mm x 90 mm)
Gland Plate
120 X 120
810
20.5"(520)
70 850
F F
152
343
505
31.1"(790)
468
Left: View from beneath unit
Gland Plate
120 X 120
62
D
237
343
showing-
‘F’ (Feed) ¾ “ BSP male connection for connection for flexible hose provided with unit.
‘D’ (Drain) connection for 35 mm pipe.
For clearance around the unit for ventilation and access see page 7
Cabinet Sz 1 with RDU
Cabinet
Clearance around LE Units
LE09 All
LE18 All
LE30 All
LE45/LE55
LE45/55
Dimensions
size 2 with RDU
Dimensions
RDU 30 kg/h A = 602mm B = 205mm
RDU 45 kg/h A = 842mm B = 360mm
7
L L
H
H2
H1
Unit L
LE05 All
(No RDU)
LE05 All
(With RDU)
LE09 All
(No RDU)
(With RDU)
(No RDU)
LE18 All
(With RDU)
LE30 All
(No RDU)
(With RDU)
(No RDU)
(With RDU)
LE60 - 110 All (Twin
Cylinder No RDU)
H
min
85 1000 500 -
85 1000 - 200
85 1000 500 -
85 1000 - 250
85 1000 500 -
85 1000 - 500
85 1000 500 -
100 1000 - 750
85 1000 500 -
200 1000 - 775
85 1000 500 -
H1
min
H2
min
A minimum clear space of 1 m is required in
front of the unit for maintenance access
For guidance on positioning of steam pipes see Appendix 1.
8
1.1.1 LE weights
The unit dry weight is the delivered unit with no water in unit, the wet weight is the operational weight when the unit is running . The RDU weight must be added to the unit weight if fitted on top of the Electrode Boiler unit.
Vapanet model Dry Kg Wet Kg RDU
Kg LE05 and LE05P 23.5 29 6 LE09 and LE09P 24 31 10 LE18 and LE18P 24.5 36 12 LE30 and LE30P 34 62 14 LE45,LE45P & LE55 34 62 16 LE60 and LE60P 52 106 NA LE90, LE90P & LE110 52 106 NA
1.2 Positioning the steam pipes
1.2.1 General
Steam pipes should be positioned as shown below, allowing a minimum rate of fall back to the unit of
Do ensure radius hose bends are fully supported to
prevent kinks developing when in service.
Do add extra insulation to steam hose for longer
runs (2m-5m) and in cold ambient conditions to avoid excess condensate and reduction in delivered output.
Don'ts
Don't allow steam hose to develop kinks or sags. Don't include horizontal runs or 90o elbows in the
steam line.
Steam Distribution Pipe requirement
Electrode Boiler Unit Model
35mm ∅ Pipe No. 54mm . Pipe No.
Duct Pressure Pa.
LE05(P) LE09(P) LE18(P)
1
-
+2000
-600
LE30(P) LE45(P) LE55
-
1
LE60(P) LE90(P) LE110
-
2
+2000
-600
12% to allow the free flow of condensate back to the unit. If the above fall is not possible, then condensate separators must be fitted as shown in appendix 1. The position of the steam pipe or multipipe in a air-
No Sags!
Flexible Steam Pipe.
conditioning system relative to other items such as bends, filters, heat exchangers, etc., is critical. The steam pipe must not be located closer to such item, than the entrainment distance, and must be decided by the design engineer responsible for the project.
Do's Do obtain project engineer's instruction/drawing for
chosen location of pipe
Flexible Steam Pipe.
Distance to first bend.
Do obtain project engineer's instruction/drawing for
pipe position relative to the top & bottom of the duct (or sides if airflow is vertical.
R min for 35 R min for 54 Pipe = 500mm
Pipe = 250mm
Do check if alternative slope of Ø35mm pipe has
been specified.
Do use bracket/lug on the end of Ø54mm pipes for
extra support.
VAPAC HUMIDIFIER
1.2.2 Steam Hose Connection
Do's
Do use Vapac steam hose or well insulated copper
pipe.
Do keep steam hose as short as possible (under 2m
for max efficiency).
Do arrange to have a vertical rise immediately over
the unit of 300mm.
Do use the full height available between the unit
and steam pipe to provide maximum slope (min 12-20% for condensate to drain back to the steam cylinder (or down to a condensate
separator). Always provide a continuous slope. Do provide adequate support to prevent sagging a) fit pipe clips every 30-50cm or b) support straight lengths on cable trays
35 or 54 mm copper or stainless steel steam pipe with Insulation.
35mm ∅ Pipe Selection
Duct width
B mm 320-470 470-620 620-770 770-920
920-1070
1070-1200
In-duct Length
L mm
300 450 600 750 900
1050
Flexible pipe coupling to connect Steam pipe to Duct pipe coupling length to allow for line movement and expansion. Coupling clamp with Hose clips each end.
Fig 6
54mm ∅ Pipe Selection
Duct width
B mm
700-950
950-1450
1450+
In-duct Length
L mm
(Kg)
650 (1.8) 900 (2.2)
1400 (3.2)
or in heat resistant plastic pipe.
For guidance on use of Multipipes see Appendix 2.
9
1.3 Plumbing Considerations.
1.3.1 Cold water supply
General
The Vapanet range of electrode boilers is capable of operating with a range of “raw mains” water quality. The water supply should be within the following limits:-
.
Hardness 50 – 500 ppm Conductivity 80 – 1000µS PH 7.3 – 8.0 Silica 0 Pressure of between 1 - 8 bar.
In addition, if stainless steel electrodes are used the chlorine level must not exceed 170 ppm.
Water Supply rates
1.20 l/min
1.20 l/min
1.20 l/min
2.50 l/min
2.50 l/min
5.00 l/min
5.00 l/min
Do’s
Do install a stop-valve/Shut-off valve and a strainer close to
the unit.
Do provide a water supply with sufficient pressure and pipe
size to ensure an adequate flow rate to all units connected to the system.
Do use the water connection with nylon nut provided.
LE05 LE09 LE18 LE30 LE45/LE55 LE60 LE90/LE110
LE05P LE09P LE18P LE30P LE45P LE60P LE90P
A B C D F
K L M N
H G S V
Single Cylinder Units 30-55 kg/h
ALL Dimensions in mm
Don'ts
Don’t use a wrench or other tool to tighten the water supply
connection - the nylon nut and rubber washer provided, should only require tightening by hand to effect a seal. If water seepage occurs, undo the nut to wipe the washer clean and re-seat it.
1.3.2 Drain connection
General
Do's Do ensure metal drain and supply water pipework is grounded
electrically close to the unit (a ground/earth stud is positioned on the underside of the cabinet.
Drain capacity per cylinder.
(Max.pump flow rate at Power supply frequency)
Do’s Do use copper or plastic pipe rated for 110 oC. Do arrange to discharge drain water from the unit into a
trapped and vented drain at a position where flash steam rising from the drain line vent will not pose a problem for the Vapac or other equipment.
Do provide adequate fall for the drain pipework to allow free
flow of water drained from each unit.
Do ensure drain line pipe size will accommodate water being
drained at the same time from all the Vapac units which are connected to it.
KEY: -
A Tundish Fill-cup B Steam Cylinder C Feed Drain Manifold D Drain Pump F Feed Solenoid Valve G Water Connection ¾” BSP. H Flexible hose ¾” BSP. K 35 Steam Hose coupling and Hose
L 35 copper or plastic Drain for 110°C
M Tundish N U-trap side exit. S Optional Strainer V Isolation stop cock
Clips.
Water with supports.
.
l/min Hz
16.8
17.2
50
60.
Twin Cylinder units 60-110 kg/h
Fig 7
Control Cable / Security Circuit
Important Power Connection Information
Note:
1.4 Electrical Connections
10
24 V a.c. Control circuit -
9 V a.c. PCB Circuit -
Transformer Primary Circuit ­And RDU.
230V ac Pump Supply. -
Vapac 24V and 9 V secondary Transformer Primary supply connections: Vapac units are wired to allow connection to alternative site Voltages. Make the following simple checks before connecting the power supply:­Move the BROWN connection on the VAPANET transformer primary winding circuit to the position marked with the supply Voltage that is to be connected between VAPANET power terminals A1 and A2. The transformer primary circuit terminal positions are clearly marked:- 200V, 230V, 380, 415 & 440V. If the actual (measured) site voltage is 400v the preferred tapping is 380V. The transformer is fitted below the Drain tray, and is accessible by removing two screws and the cover, which should be slid it towards you.
6.3 A 20 mm (T – Time Lag) fuse (Pt.No. 1080093) mounted on VAPANET Echelon PCB (Pt.No.1150630).
2 A 20 mm (F - Quick blow) fuse (Pt No. 1080099) mounted on the VAPANET Echelon PCB (Pt, No. 1150630).
Two fuses protect the control circuit on Single cylinder units F1 2.0A (slow blow) (Pt. No. 1080095) mounted in fuse-terminal holder protects Primary transformer and RDU unit if fitted. F2 500 mA 20 mm (F - Quick blow) fuse (Pt No. 1080054) mounted in fuse-terminal holder protects Transformer Primary and Pump or both pumps if two pumps are fitted.
The pump or pumps on twin cylinder units are fed from the main transformer via a 230 volt auto winding. The pumps are protected by fuse F1 and F2 above feeding the transformer primary.
1.4.1 Important E.M.C. Considerations
Use a dedicated, earthed metal conduit for both the control signal cable and the security circuit cables along their entire length - they may share the same conduit where practicable. The earth must be made by "metal-to-metal" contact and should be a good RF (Radio Frequency) earth.
The control and security circuit connections should be run in screened cable with the screen grounded at the VAPANET end (onto the electrical section back panel). The screen should be maintained as close as possible to the cable ends and any tail between the screen and the earth point must be kept short (50 mm maximum).
Control Cable / Security Circuit Conduit Entry Arrangement
Electrical section metalwork
All metal surfaces which come into contact with each other, must be free of paint, grease, dirt, etc., thereby ensuring a good low impedance R.F. (Radio Frequency) path to ground.
Metal conduit
Cables to control terminals
Outer insulation
Screening Arrangement
Tail to be kept short (less than 50mm)
Screen left intact
Earthed back panel
11
1.4.2 Power Supply Connection
The unit requires the following connections as shown in the diagram below
1.4.2.1 Volt free alarm outputs
The unit has connections for volt free alarm outputs these are on the three double terminals next to the main power input terminals. The top terminals are for unit volt free fault alarm as follows:
The bottom terminals are for unit volt free run signal as follows:
542 common for fault alarm 543 Normally closed when no fault 544 Normally open when no fault
545 Common for run signal 546 Normally closed when unit is in standby or
fault (not running)
547 Normally open when unit is in standby or fault
(not running)
If the unit is part of a master slave system or network, the run & fault outputs can be selected (via keypad & display) as either network (system) or unit only. This is selectable at Service Engineers Level, in the Engineering Menu, in the window “Fault/Run Scope”. The default is “network”. It is possible to get both alarm & Run indication in all units: Single cylinder units will give this indication if the service interval has expired; Twin Cylinder & Networked units will give this indication if the service interval has expired or if the master cylinder is operating and any slave cylinder (or cylinders) are in fault.
1.4.2.2 Unit control terminals
For unit control and network termination see section
1.6 the terminal layout is shown here.
Notes:
-
FOR FULL EL
ECTRO
-
MAGNETIC COMPATIBILITY A NEUTRAL CONNECTION IS REQUIRED FOR ALL PROPORTIONAL
12
1.4.3 Electrical Connections
The wiring to the Vapac should be done by a qualified electrician. The external overcurrent protection and wiring should comply with the appropriate Regulations and Codes of Practice
Important: Make sure the connection to the primary Voltage winding of the Vapac transformer matches the supply Voltage which is to be connected between Vapac terminals A1 & A2.If the actual (measured) site voltage is
400v the preferred tapping is 380V
A fused disconnect/isolator or MCB should be used to disconnect the supply from all electrodes simultaneously.
This must be sized to suit the total maximum phase/line current of the unit and should be located adjacent to the Vapac cabinet or within easy reach and readily accessible.
In Vapac VAPANET units terminals A1, A2 and A3 are for the power supply connections as indicated in the diagrams below (twin cylinder units have two supplies A1,A2,A3 & B1,B2,B3).
Twin cylinder units’ have terminals for the connection of two power supply input circuits. On twin cylinder units’ this allows individual external protection of each steam cylinder. Fused disconnect/isolator or MCB provision must be linked to ensure both 3 phase supply inputs are disconnected simultaneously.
.
1. All units must have a PE earth connection connected to the units terminal.
2. Unit with N.A. in the following tables means NOT AVAILABLE there is not a unit available to run at the voltage and phases shown. Please check that the correct model reference is ordered and installed, for the low or high voltage required, and at the desired steam output.
3. Standard design is for 50 Hz. Supplies. Design for 60 Hz. Also available - 60 Hz. Supply must be specified with order as the standard pump is only 50Hz.
1.4.4 Cable Entry Provision
Cable glands must be used to ensure cables are held securely at the entry position. All Vapac cabinets are equipped with a removable gland-plate. The installing electrician should remove this and take it to a work­bench to drill for the required cable gland size.
1.4.5 Vapac Control Circuit Transformer
The internal control circuit of the Vapac unit operates at 24Vac - the transformer secondary is set at 24V.
.
As standard the Vapac VAPANET includes a transformer with alternative primary winding options 200V, 230, 380, 415, and 440V and requires on site adjustment to match it to the Voltage connected to Vapac terminals A1 and A2. The transformer also has a 9V secondary tapping which provides power to the VAPANET 1150630 PCB.
Important: The Vapac transformer must NOT be used to power other equipment or the warranty will be invalidated.
1.4.6 RDU Connection
Vapac terminals 25 & 26 are included to provide a 230Vac electrical supply for the fan motor in the RDU (Room Distribution Unit) . Note: The 230Vac at terminals is derived from the incoming electrical supply to the Vapac. If the local supply cannot provide 230Vac (example 400V No Neutral supply) it will be necessary for a transformer to be fitted in the RDU as indicated below.
UNITS AS INDICATED IN THE CONNECTION DIAGRAMS ON THE FOLLOWING PAGES.
RDU Connection
The three type’s of RDU are for various voltages and phase without neutrals connections that can be made to the Vapanet unit. Please refer to the Microvap connection diagram on the following three pages as to which type of unit is required. On twin cylinder units two fan circuits as shown below one for each cylinder will be in the RDU unit.
RDU electrical loads
Model RDU05LE RDU09LE RDU18LE RDU30L RDU45LE Number of fans 2 3 3 5 7 Fan voltage 230 v 230 v 230 v 230v 230v Each fan current 50Hz RDU total load current 50Hz
(60 Hz)
115 mA
(60 Hz)
225 mA
(105 mA)
(210 mA)
115 mA 345 mA
(105 mA)
(315 mA)
115 mA 345 mA
(105 mA)
(315 mA)
115mA 575mA
(105mA)
(525mA)
115 mA 805 mA
(105 mA)
(735 mA)
13
Power connection
Power connection
details for LExx
Units
(Units without Solid
State Relays).
Details for LExxP
Units
(Units fitted with
Solid State Relays)
200 – 250 V 1Ph. N + earth
200 – 250 V 2Ph. + earth
380 – 440 V 2Ph + earth
TRANSFORMER PRIMARY 380 – 440 V SECONDARY 210 – 250 V
Model Ref.
LE05
LE09
2
Model Ref.
LE05
-3
LE09
-3
2
Model Ref.
LE18
LE30
2
14
1.5 Cylinder Electrical demand loads
1.5.1 LExx Units
Nominal Output Kg/hr 5 5 5 5 5 5 9 9 9 9 9 9 Nominal Output lb/hr 11 11 11 11 11 11 19.8 19.8 19.8 19.8 19.8 19.8 Voltage V 200 230 380 400 415 440 200 230 380 400 415 440 Power input rating Kw 3.71 3.72 3.8 3.81 3.75 3.77 6.76 6.68 6.7 6.86 6.72 6.7 Electrical Supply Ph's Ph+N or
2Ph
No. of electrodes
2 2 2 2 2 2 2 2 2 2 2 2 Full load Current A 19.5 17 10.5 10 9.5 9 35.5 30.5 18.5 18 17 16 Maximum overcurrent A 29.25 25.5 15.75 15 14.25 13.5 53.25 45.75 27.75 27 25.5 24 Fuse Rating/phase A 32 32 20 20 16 16 63 50 32 32 32 32 Supply cable terminals mm
10 10 10 10 10 10 16 16 16 16 16 16 Wiring diagram Cabinet size
Nominal Output Kg/hr 5 5 5 5 5 5 9 9 9 9 9 9 Nominal Output lb/hr 11 11 11 11 11 11 19.8 19.8 19.8 19.8 19.8 19.8 Voltage V 200 230 380 400 415 440 200 230 380 400 415 440 Power input rating Kw 3.79 3.79 3.76 3.96 3.77 3.99 6.76 6.83 6.9 6.93 6.85 6.9 Electrical Supply Ph's 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph No. of electrodes
3 3 3 3 3 3 3 3 3 3 3 3 Full load Current A 11.5 10 6 6 5.5 5.5 20.5 18 11 10.5 10 9.5 Maximum overcurrent A 17.25 15 9 9 8.25 8.25 30.75 27 16.5 15.75 15 14.25 Fuse Rating/phase A 25 20 16 16 10 10 32 32 20 20 20 16 Supply cable terminals mm
10 10 10 10 10 10 10 10 10 10 10 10 Wiring diagram Cabinet size
Ph+N or
2Ph
Ph+N or
2Ph
Ph+N or
2Ph
Ph+N or
2Ph
Ph+N or
2Ph
Ph+N or
2Ph
Ph+N or
2Ph
Ph+N or
2Ph
A4-LZD-559 A4-LZD-559
1 1
A4-LZD-559 A4-LZD-559
1 2
Ph+N or
2Ph
Ph+N or
2Ph
Ph+N or
2Ph
Nominal Output Kg/hr 18 18 18 18 18 18 30 30 30 30 30 30 Nominal Output lb/hr 39.6 39.6 39.6 39.6 39.6 39.6 66 66 66 66 66 66 Voltage V 200 230 380 400 415 440 200 230 380 400 415 440 Power input rating Kw 13.36 13.47 13.48 13.53 13.35 13.43 22.43 22.38 22.25 22.43 22.25 22.5 Electrical Supply Ph's 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph No. of electrodes
3 3 3 3 3 3 6 6 3 3 3 3 Full load Current A 40.5 35.5 21.5 20.5 19.5 18.5 68 59 35.5 34 32.5 31 Maximum overcurrent A 44.55 39.05 23.65 22.55 21.45 20.35 74.8 64.9 39.05 37.4 35.75 34.1 Fuse Rating/phase A 50 50 32 32 25 25 80 80 50 50 40 40 Supply cable terminals mm Wiring diagram Cabinet size
16 16 16 16 16 16 35 35 16 16 16 16
A4-LZD-559 A4-LZD-560 A4-LZD-559
1 2
Loading...
+ 32 hidden pages