Vanner TruSine TSC24-4500, TruSine TSC24-4500D, TruSine 4500 TSC24-4500, TruSine 4500 TSC24-4500D Owner's Manual

Owner’s Manual
TruSine 4500
4.5 kW Inverter/Charger System
4.5 kW Power Inverter
Models TSC24-4500 TSC24-4500D
Owner’s Manual D98771 Rev B
TruSine 4.5 kW Inverter Page 1 Owner’s Manual
Notes
TruSine 4.5 kW Inverter Page 2 Owners Manual
Table of Contents
Table of Contents
1 SYSTEM FEATURES AND SPECIFICATIONS.................................................................................... 4
1.1 G
1.2 S
1.3 S
ENERAL DESCRIPTION YSTEM FEATURES PECIFICATIONS
...............................................................................................................................6
....................................................................................................................4
...........................................................................................................................4
2 DESCRIPTION OF OPERATION.......................................................................................................... 7
2.1 I
2.2 B
2.3 A
2.4 G
NVERTER
ATTERY CHARGER UTOMATIC TRANSFER SWITCH WITH SOLAR MODE
EN START
.........................................................................................................................................7
..........................................................................................................................7
............................................................................9
....................................................................................................................................10
3 TSR-2 REMOTE CONTROL PANEL (OPTIONAL)............................................................................10
3.1 G
3.2 A
3.3 O
3.4 M
ENERAL DESCRIPTION DJUSTABLE FACTORY SETPOINTS FOR THE TRUSINE
PERATION
ENU MAP
....................................................................................................................................11
.....................................................................................................................................13
..................................................................................................................10
.............................................................11
4500
4 FRONT PANEL WIRING IDENTIFICATION.......................................................................................18
4.1 AC I
4.2 DC (B
4.3 S
4.4 B
NPUT
ATTERY YSTEM ATTERY TEMPERATURE SENSOR PORT
4.5 V-NET P
4.6 S
4.7 I
4.8 S
4.9 R
ERIAL INTERFACE PORT
NVERTER OUTPUT CIRCUIT BREAKER
YSTEM EMOTE SIGNAL CONTACTS
UTPUT WIRING
& O
IRING
) W
NDICATOR
ON I
ORT
/ TSR-2 R
ON/OFF S
..........................................................................................................18
...................................................................................................................18
..................................................................................................................18
..........................................................................................18
EMOTE CONTROL PORT
..............................................................................18
................................................................................................................18
.............................................................................................18
WITCH
..............................................................................................................19
............................................................................................................19
5 INSTALLATION...................................................................................................................................19
5.1 B
5.2 DC W
5.3 AC W
ASIC GUIDELINES
IRING IRING
5.4 TSR-2 T
5.5 S
YSTEM START-UP AND TESTING
RUSINE REMOTE CONTROL PANEL INSTALLATION
..........................................................................................................................19
....................................................................................................................................19
....................................................................................................................................21
...............................................................22
.....................................................................................................22
6 GENERAL INFORMATION SECTION................................................................................................ 23
6.1 G
6.2 I
ENERIC INVERTER DESCRIPTION
NVERTER SIZING
6.3 DC P
6.4 B
6.5 S
6.6 B
6.7 B
ATTERY TERMINOLOGY AND RATINGS IZING THE INVERTER BATTERY ATTERY AND CHARGING SYSTEM CONSIDERATIONS ATTERY CHARGING GUIDELINES
............................................................................................................................23
OWER CONSUMPTION
....................................................................................................23
.............................................................................................................24
............................................................................................25
.......................................................................................................26
........................................................................26
....................................................................................................27
7 MAINTENANCE & TROUBLESHOOTING.........................................................................................27
7.1 P
REVENTATIVE MAINTENANCE
.........................................................................................................27
8 WARRANTY........................................................................................................................................ 29
TruSine 4.5 kW Inverter Page 3 Owner’s Manual

System Features and Specifications

Introduction
Thank you for purchasing a Vanner TruSine inverter system. We are confident that you will be satisfied with its performance and its many features. W ith pr oper ins tallation and c are, you can look forward to years of s ervic e from this high performance product.
This document will desc ribe the operation, technical s pecific ations and installation pr ocedures for the Tr uSine Inverter/Charger System. If you require additional information please contact your dealer, or contact us directly at the location shown on the cover of this manual.
1 System Features and Specifications
1.1 General Description
The TruSine system consists of a 4500 watt DC to AC true sine wave inverter, a 100 amp 24 volt battery charger, an automatic AC trans fer switch, and a microproces sor based controller with data c ommunications capability. A key feature of this system is the optional TSR-2 TruSine Remote Control Panel operator’s interface which utilizes a high speed “data highway” to connect one or more TSR-2 units to the inverter.
TRUSINE INVERTER /CHARGER SYSTEM
AC Output To
AC Loads
AC In put Utility
Power G en era tor
BATTERY
INV E RT E R
CHARGER
MICROPROCESSO R
TSR-2 Remote
Control Panel
AUTOMATIC
AC
TRANSFER
SWITCH
CONTROLLER
V-NET Data Bus
TSR-2 TSR-2
Figure 1 - System Diagram
1.2 System Features
Inverter
The inverter consists of two sine wave inverters built into one unit. A “ low power“ high efficiency 70 watt inverter supplies power for the small loads. The “high power” 4,500 watt main inverter supplies power when AC loads over 70 watts are applied. Designed for maximum efficiency this system conserves battery power when only small loads are present. T o further conserve battery power the Load Demand feature allows the inverter to ‘go to sleep’ if AC loads fall below a selected value. Load Demand may be disabled if very small AC loads must be operated. The inverter develops up to 4,500 watts of continuous power. Using TruSine quality pure sine wave is produced. Total harmonic distortion (THD) is less than 2.0 percent.
®
technology, a very high
TruSine 4.5 kW Inverter Page 4 Owners Manual
System Features and Specificatiions
Battery Charger with Automatic Power Management
A high efficiency 100 amp multi-stage battery charger allows fully automatic charging of f looded and gel lead acid battery banks. The efficient 0.85PF , compared to typical 0.59PF on triac type chargers, allows full charger output from a 30 amp aux AC source. The system ’s Bulk - Absorption - Float charge cycle quickly charges and maintains the charge on the battery bank. An Equalization charge cycle is provided for flooded lead acid battery maintenance. Automatic Power Management (APM) monitors the Aux AC Input amps and will reduce the battery charger output as needed to keep the Aux AC Input amps below the preset APM Limit.
Automatic AC Power Transfer Switch with Solar Mode
An automatic AC transfer switch pr ovides system output power s ourced f rom the Aux AC Input (generator or utility) or sourced from the battery, via the inverter. Solar Mode allows the inverter to oper ate on battery power while shore power is present.
Gen Start
The Gen Start feature provides a s tart/stop s ignal to control a generator used f or r echarging the batter ies. The start/stop signal consis ts of a c ontac t c losure to s tar t the generator bas ed on battery voltage and s top the generator based on battery charging amps.
System Control
The TruSine contains a System ON/OFF Switch to turn the system ON and OFF. A control microprocessor provides a variety of protection interlocks, system fault detection/reporting/recovery, storage of system data param eters, and high speed data comm unications to the optional T SR-2 Remote Control Panel. System protection functions include over load, over temperature, and high and low battery voltage. Use the ON/OFF Switch to reset the system after shutdown for a s ystem fault. T he optional T SR­2 Remote Control Panel provides a system status display and allows detailed control of individual system functions.
TSR-2 TruSine Remote Control Panel (Optional)
The optional TSR-2 Remote Control Panel / Programming Panel is an operator interface which connects to the TruSine Inverter/Charger via a 6­conductor data bus and allows system operation near the inverter or from remote areas. Multiple TSR-2 Remotes may be connected for optimum flexibility. The TSR-2 contains an alphanumeric LCD display and functional keypad making it easy to use. System status m essages are displayed, faults are reported, system functions m ay be enabled/disabled or turned ON/OFF, system setpoints may be examined and changed.
Figure 2: TSR-1 and TSR-2 Control Panels
Earlier production TSR Remotes, the TSR-1, are identical to the TSR-2 exc ept contain early software used with TruSine inverter/charger model TSC24-4000D. The TSR-1 will work with TruSine 4500 models but cannot access the GenStart and other new features of the TruSine 4500. The TSR-1 m ay be upgraded to TSR-2 status by changing software to part number A88769-A or newer. TSR-2 software is displayed upon startup and also is identified in the General Inform ation Menu step 52. TSR-1 software is identified in the System Info menu.
TruSine 4.5 kW Inverter Page 5 Owner’s Manual
System Features and Specifications
1.3 Specifications
Model TSC24-4500 Model TSC24-4500D
AC OUTPUT
Voltage (RMS) 120 VAC ± 3% adjustable 120/240 VAC ± 3% adjustable Frequency 60 Hz ± 0.5% 60 Hz ± 0.5% AC Waveform Sine Wave Sine Wave Total Harmonic Distortion (THD) Less than 2.0% Less than 2.0% Power Factor Allowed -1 to 1 -1 to 1 Continuous Output Rating @ 25ºC L1 to Neutral 4500 watts (37.5 amps) 2,250 watts (18.8 amps) L2 to Neutral N/A 2,250 watts (18.8 amps) L1 to L2 N/A 4,500 watts (18.8 amps) Surge Capacity @ 25ºC (3 sec.) 10,000 watts 10,000 watts
DC INPUT:
Operating Range (24 Volt Nominal) 21 to 34 Volts 21 to 34 Volts No Load, Inverter ON 1.8 amps 1.8 amps No Load, Search Mode 0.46 amps 0.46 amps Full power 210 amps 210 amps
INVERTER EFFICIENCY
15 watts 62.8% 63.1% 30 watts 72.6% 71.2% 60 watts 62.6% 75.2% 100 watts 72.3% 71.7% 400 watts 88.5% 88.3% 1100 watts 91.3% 92.2% 1500 watts 90.6% 90.7% 2000 watts 89.4% 89.50% 3200 watts 86.2% 86.7% 3900 watts 83.7% 84.1% 4600 watts 79.7% 82.5%
AC INPUT
Voltage (adjustable) 120 Volts nominal ± 10% 120/240 Volts ± 10%, 3wire 1Ø Frequency 60 Hz ± 12.5% (52.5 to 67.5) 60 Hz ± 12.5% (52.5 to 67.5)
AC TRANSFER SWITCH
Power Rating 30 amps @ 120 VAC 30 amps @ 240 VAC Transfer Time Less than 40 milliseconds Less than 40 milliseconds
BATTERY CHARGER
Charger Output Current maximum 100 amps 100 amps AC Input Current maximum 30 amps
SYSTEM
Ambient Operating Temperature Cooling Exhaust Fan Thermostatically controlled Thermostatically controlled Mounting Wall or Shelf Wall or Shelf Dimensions (wall mtd position) 17.5”H x 19”W x 8.5”D 17.5”H x 19”W x 8.5”D Weight 83 pounds 83 pounds TSR-2 Remote DC power draw 0.11 amps 0.11 amps
-40 to+40°C (-40 to+104°F) -40 to+40°C (-40 to+104°F)
(0.85PF @ rated output)
15 amps per leg (same)
TruSine 4.5 kW Inverter Page 6 Owners Manual

Description of Operation

2 DESCRIPTION OF OPERATION
2.1 Inverter
The System ON/OFF Switch, located on the f ront panel, allows the us er to turn the s ystem ON and OF F and to reset the system after a fault. The inverter will always begin operation in the large inverter “high power” mode. If the AC load is less than 70 watts the inverter will automatically switch to the “low power” high efficiency small inverter after 5 seconds. T he optional TSR-2 Remote Control Panel allows the inverter to be dis abled (turned OFF) while allowing the other system functions (charger, transfer switch) to continue to operate.
The Inverter AC Output Circuit Break er is a 2 pole, 20 amp breaker marked “O/I” located below the System ON/OFF Switch. The breaker protects the Inverter AC output and Battery Charger AC input against a severe overload. This breaker does not protect AC Passthrough Power. If the break er trips during inverter operation, the system must be reset. Do this by turning the System ON/OFF Switch OFF and bac k ON. Do not use the AC Output Circuit Breaker as an ON/OFF switch.
Protective Interlocks
Auto-restart After shutting down for any of the following fault conditions the inverter will try to restart
itself every 5 minutes. The inverter will restart if the fault condition is no longer present.
Manual restart Manually restart the system by resetting the inverter after the fault conditions is removed.
Reset the inverter by turning the System ON/OFF Switch OFF and then ON.
Low Battery The inverter continually monitors battery voltage. If battery voltage falls below the Low
Battery Shutdown setpoint the inverter will shut OFF. Auto-restart will restart the inverter
after battery voltage rises above the Low Battery Warning setpoint. High Battery The inverter will shut OFF if battery voltage rises above the High Battery setpoint. Over Temperature The inverter will shut OFF if internal temperature sensors detect a high temperature
condition that would damage the inverter.
While operating in Solar Mode a high temp shutdown will transfer back to shore power until
the over-temperature condition clears. Over Load - If a short circuit or an overload is applied to the inverter’s output the inverter will shut down. Additional details regarding protective interlocks are found in the Alarm Menu in section 3.
Load Demand
The TruSine Inverter’s Load Demand Mode is an energy-saving feature. Load Demand allows the inverter to go to sleep when the AC load is below the ‘Enter Load Demand’ (watts) setpoint f or 5 seconds. While in Load Demand (asleep) the inverter produc es only pulses of AC which are used to searc h for an AC load. When the inverter senses an AC load greater than the ‘Exit Load Dem and’ (watts) s etpoint, the inverter will turn fully ON. The Load Demand feature significantly reduces the DC amps drawn from the battery while the AC load is below the Load Demand enter and exit setpoints.
The inverter will not enter Load Demand from the High Power mode. T he inverter will only enter Load Demand from the 70 watt small inverter Low Power mode.
The ‘Enter Load Demand’ and ‘Exit Load Demand’ setpoint values may be adjusted to suit the AC loads by using the optional TSR-2 Remote Control. T he Load Demand feature may be turned OFF by selecting Load Demand enabled/DISABLED. This is recomm ended if very small AC loads under 5 watts, such as clocks or LCD displays, must be operated.
2.2 Battery Charger
The battery charger’s advanced design incorporates an automatic, multi-stage charger. This design enables
TruSine 4.5 kW Inverter Page 7 Owner’s Manual
Descriptions of Operation
the unit to automatically charge batteries which maintains the battery’s integrity and reduces the likelihood of premature battery failure. The battery charger is des igned to be used with lead-acid type batteries inc luding sealed and gel types, but not for nickel-cadmium (Ni-Cad) or nickel-iron types.
Battery Charging Sequence
Stage 1: Bulk Charge Stage The charger always starts in the Bulk Charge Stage each time shore power becomes present and/or each time the charger is turned ON. In Bulk Charge the system charges at the ‘Bulk Charge Amps’ setpoint until battery voltage rises to the ‘Bulk Charge Voltage’ setpoint. Then the voltage is held at that setpoint until charging amps have fallen to 5 amps above the ‘Battery Absorption Amps’ setpoint. This ends the Bulk Charge Stage and begins the Absorption Charge Stage. The charger will not enter the Bulk Stage again until shore power is reapplied, or until the charger or the system is turned ON again.
Stage 2: Absorption Charge Stage The Absorption Charge Stage provides a contr olled “overcharging” of the battery which is necess ary to bring the battery up to full charge. The batter y is charged at the ‘Absor ption Charge Amps’ until one of following three conditions occur which signals the end of the Absorption Stage;
VOLTAGE
CURRENT
TIME
BULK ABSORPTION
TRIGGER POINT
OPTIONAL EQUALIZE
FLOAT
Time: The Absorption Maximum Time setpoint is reached Time: The Absorption Charge Stage has reached ½ of the duration of the Bulk Charge Stage. Voltage: Battery voltage reaches the ‘Absorption Voltage’ setpoint
Stage 2A Equalize Charge Cycle When Equalize Mode is ENABLED, one Equalize Charge Cycle will follow the Absor ption Charge Stage. The Equalize Cycle will last for the ‘Equalize Time’ setpoint. Equalize Mode will automatically switch to DISABLED at the end of the Equalize Charge Cycle. During the Equalize Cycle the battery is charged at the ‘Absorption Charge Amps’ setpoint and the Equalize Voltage setpoint.
The Equalize Charge Cycle provides a deliberate overcharging of the battery to remove sulfate which accumulates on the battery plates through norm al use. Equalizing returns battery cells to equal perform ance levels which improves battery performance and extends battery life. Consult the battery manufactur er for their recommendation regarding equalize voltages how often the Equalize Cycle should be performed.
CAUTION Do not equalize sealed (valve regulated lead acid or gel) batteries!
Consult battery manufacturer for equalizing guidelines. Do not equalize more often than approximately once a month. Check battery fluids after equalizing is complete, as gassing will occur. Use Equalize Mode only while batteries are well ventilated!
Stage 3: Float Charge Stage - Maintenance Mode In the Float Stage the charging voltage is reduced to the ‘Float Charge Voltage’ setpoint and char ging cur r ent is limited to the ‘Absorption Charge Amps’ setpoint. The charger will remain in the Float Stage until shore power is reapplied, or until the charger or system is turned OFF and then ON again.
Charging Setpoints
The TruSine’s battery charger fac tory setpoints are for wet batteries. Do not use the f actory setpoints for gel batteries. If gel batteries are used, consult the batter y manufacturer for charging recomm endations. Setpoints for typical gel batteries are listed and may be used if specif ic recomm endations are not available from the gel battery manufacturer.
Caution: Do not operate DC loads, such as DC lights, pum ps, etc., during battery charging. The loads may cause overcharging by preventing the charging stages from reaching their ‘trigger points’ or may cause the battery to run down even though the charger is ON.
TruSine 4.5 kW Inverter Page 8 Owners Manual
Description of Operation
Battery Charger Factory Setpoints (Factory Setpoints are for wet batteries, 4 size 8-D minimum.) All Charging Setpoints are Password Protected in the TSR-2 Remote Control Bulk Charge Volts 26.0 - 32.0 28.4 VDC 28.1 VDC Bulk Charge Amps 20% C Rate 0 - 100 100 Amps 20% C Rate Absorption Charge Volts 28.0 - 34.0 30.0 VDC 28.2 VDC Absorption Charge Amps 5% C Rate
Absorption Maximum Time 10 - 255 10 Minutes 10 minutes Float Charge Volts 26.0 - 30.0 26.4 VDC 27.2 VDC Equalize Volts Wet only 26.0 - 34.0 31.0 VDC Not used Equalize Maximum Time Wet only 5 - 30 15 Minutes Not used Battery ‘C Rate’ is equal to battery Amp Hour capacity.
Guideline Setpoint
Range
10 - 50 50 Amps 5% C Rate
minimum
Factory Setpoint (for Wet Battery)
Typical setpoint
for
Gel Battery
minimum
Automatic Power Management (APM)
A key feature of the battery charger operation is Automatic Power Management (APM). T his feature m onitors the Aux AC input amps and will reduce the battery charger output as necessary to keep the Aux AC input amps under the APM setpoint. The APM circuit will not limit power to the passthrough AC loads. If the passthrough AC loads exceed the APM setpoint the battery charger output will be reduced to zero.
Adjust the “APM Limit” setpoint to match the circuit breaker at the Aux AC source. This will reduce the chance of tripping the source’s circuit breaker due to battery charging.
On model TSC24-4500D (240VAC) the APM feature m onitors L1 and L2. APM decisions are based on the heavier loaded line.
Example: With the APM Limit on a TSR24-4500D set at 15 amps, L1 loaded to 15 amps and L2 has no load, then the APM will allow no power to go to charging. If the load on L1 is reduced to 10 am ps then the charger will be allowed to use 5 amps.
2.3 Automatic Transfer Switch with Solar Mode
The Automatic T ransfer Switch consists of electro-mechanical relays contr olled by circuits which m onitor Aux AC input voltage, Aux AC Input frequency and battery voltage.
In the normal mode of operation, Solar Mode OFF , the Automatic Tr ansfer Switch will autom atically accept ‘in­tolerance’ Aux AC input power whenever it is available within tolerance for the ‘AC Line Stabilization’ time delay. The Aux AC input power will be used to operate the battery charger and to passthrough to operate AC loads. Upon loss of ‘in-tolerance’ Aux AC input power, the transf er s witch will autom atic ally transfer the AC loads bac k to inverter power. Transfer tim e is approxim ately 40 milliseconds (0.040 seconds). T he 0.040 second transfer time allows all but the most sensitive loads to transfer from inverter power to shore power and back without interruption.
The Transfer Switch will function properly as long as the System O N/OFF s witch is ON even while the Inverter is disabled, while the Battery Charger is disabled or while the batteries are disconnected from the system.
The Transfer Switch switches both hot and neutral. For safety purposes the inverter output neutral is c onnec ted to the inverter chassis ground only when the system is in inverter mode. This is a requirement of the National Electric Code for all systems of this type that neutral should be connected to gr ound only at the source of AC power, which is the inverter when in inverter mode. When Aux AC input (shore power, or generator) is available, the Transfer Switch system breaks the connection between neutral and inverter chas sis ground. T he neutral-to-ground connection for passthrough power is then expected to be provided by the Aux AC input source. This transfer schem e presents no problems for a proper ly installed system. The installer should verify that all AC circuits connected to the inverter AC output are an ins ulated neutr al type as r equired by the National Electrical Code (NEC) article 551.
Solar Mode
Turn Solar Mode ON in applications where it is preferred to oper ate on battery power while ‘in tolerance’ Aux AC input (shore power) is avaliable. With Solar Mode ON, the inverter will operate on battery power while Aux AC input is available until battery voltage falls below the Low Battery Warning setpoint. Then the s ystem will
TruSine 4.5 kW Inverter Page 9 Owner’s Manual
Descriptions of Operation
accept Aux AC input, the batteries will be Bulk charged and the system will switch to inverter again.
2.4 Gen Start
The Gen Start feature is designed for use in installations having a generator to provide Aux AC input power for battery charging. The Gen Start feature provides a contac t closure to signal the generator to start when battery voltage falls below the ‘Gen Start Volts’ setpoint. The Gen Star t contacts open when bulk charging am ps fall below the ‘Gen Stop Amps’ setpoint. Bulk charging amps are sampled every 4 minutes, therefore the minumum generator ON time is 4 minutes. The contacts are NEC Class 2, rated 2 amps at 12 or 24 VDC.
Gen Stop Amps should be set higher than the Absorption Charge Amps setpoint. Caution: The battery charging process will be affected if 24VDC loads are being powered during battery
charging. The increased char ger output, required to power those loads, may keep the charger from reaching the ‘Gen Stop Amps’ setpoint.
3 TSR-2 Remote Control Panel (optional)
3.1 General Description
The TSR-2 TruSine Remote Control Panel is an optional display/keypad module that allows the installer to adjust the system operation factory setpoints and allows the user to monitor and control in detail the TruSine Inverter/Charger operation. The TSR-2 connects to the inverter at the V-NET Port. One or more contr ol panels may be installed to provide the necessary level of system control and flexibility. The TruSine Inverter/Charger System setpoints will not change after removal of the TSR-2 Remote.
TSR-2 Control Panel
The TSR-2 TruSine Remote Control Panel contains a 32 character (two 16 character lines) liquid crystal display (LCD), a red Alarm LED indicator, and a f unctional keypad. A menu schem e is used to allow the operator to select and control system functions, and to display information. In the event of a system fault the Alarm LED will illuminate and a fault mes sage will be displayed. The T SR- 2 Remote connects to the invert er’s V- Net Port via a 6 conductor modular data communic ation cable. The unit is supplied with a 25’ long cable with a 6-pin RJ-11 connector at each end.
Early production TSR-1 Remotes, used with earlier model Vanner inverter/chargers, are identical to the TSR-2 but will need the software upgraded to A88769-A to access the GenStar t and other new features in the TruSine 4500 Inverter/Charger. TSR-2 software is identified in the General Information Menu step 52. TSR-1 software is identified in System Information step 53 for theTSC24-4000D.
TruSine 4.5 kW Inverter Page 10 Owners Manual
TSR-1 Remote Control
3.2 Adjustable Factory Setpoints for the TruSine 4500
The following chart lists the Factory Setpoints for all System functions which may be adjusted, Enabled/Disabled, or turned ON/OFF using the optional TSR-2 Remote Control. (Software
Inverter/Charger Model TSC24-4500 TSC24-4500D Non-Password Protected
Function
Inverter Same Same Load Demand Same Same
Adj.
Range
Factory
Setpoint
Adjustment
Range
Enabled/Disabled Enabled/Disabled
Enter Load Demand Same Same 0 – 70 20 Watts Exit Load Demand Same Same 0 – 255 40 Watts Charger Same Same Equalize Cycle Same Same
Basic Control
Enabled/Disabled Enabled/Disabled
APM Limit Amps Same 30 Amps 0 – 60 30 Amps
Password Protected Function
Inverter Output Voltage 110 - 125 120 VAC 110 – 125 120 VAC /phase Low Battery Warning Voltage Same Same 20.0 - 25.0 22.0 VDC Low Bat. Shutdown Voltage Same Same 20.0 - 22.0 21.0 VDC
Inverter
High Bat. Shutdown Voltage Same Same 25.0 - 34.0 34.0 VDC Bulk Charge Voltage Same Same 26.0 - 32.0 28.4 VDC Bulk Charge Amps Same Same 0 – 100 100 Amps Absorption Charge Voltage Same Same 28.0 - 34.0 30.0 VDC Absorption Charge Amps Same Same 10 – 50 50 Amps Absorption Maximum Time Same Same 10 – 255 10 Minutes Float Charge Voltage Same Same 26.0 - 30.0 26.4 VDC Equalize Voltage Same Same 26.0 - 34.0 31.0 VDC Equalize Maximum Time Same Same 5 – 30 15 Minutes
Battery Charger
Battery Temp Compensation Same Same On - OFF OFF Battery Temp Coefficient Same Same 0 – 25.5 4.0 mV/ºC/Cell Battery Temp Shut Down Same Same 0 – 255 50ºC Gen Start Mode Same Same Gen Start Batt Voltage Same Same 20.0 - 25.0 22.0 VDC
Gen
Gen Stop Charging Amps same Same 0 – 50 10 Amps
ON/OFF
AC Line Stabilization Time Same Same 10 – 120 10 seconds
A88769-A)
Factory
Setpoint
Enabled Enabled
Enabled Disabled
ON
Solar Mode Same Same
Trans
Switch
ON/OFF
OFF
(address) Look for inverters? Yes - No No Inverter Address (*see Note) Same Same 1 – 10 1
I D
Remote Address Same Same 1 – 10 1 *Note - Inverter Address, Step 92, applies only to systems having multiple inverters and multiple TSR-2 Remotes. Do not change Inverter Address from 1 in a single inverter s ystem. The TSR-2 will im mediately stop responding if Inverter Address is changed. Use Demo Mode to change Step 92 ‘Inverter Address’ back to 1.
3.3 Operation
The TSR-2 Remote Contr ol Panel contains: a Menu button; an Escape button; a two-line display; four control buttons located at the corners of the two-line display; and an Alarm indicator light. The two-line display will contain information that will instruc t the operator to take action based on display characters at each “ corner” of the display. For example, if the display has an ‘up arrow’ in the left position of the upper display line, press the upper left control button to step up in the m enu sequenc e. Likewise, a ‘down arrow’ would instruct you to press the corresponding control button to move down in the menu sequence. For data values, press the control button corresponding a displayed +(plus sign) or – (m inus s ign) to inc reas e or decr eas e the data value. System functions are turned ON or OFF by selecting ‘ENABLED’ or ‘DISABLED’ from the display. Capital letters indicate the selected status.
TruSine 4.5 kW Inverter Page 11 Owner’s Manual
TSR-2 Remote Control
The TSR-2 Remote uses a menu approach to select desired system functions. When menu command messages are shown on the display, the operator may select the desired function by pressing the corresponding control button. Press the ESC (Escape) button at any time to step back one level. Pres s the MENU button at any time to return to the Main Menu.
The MAIN MENU and all submenus are structured as follows:
MAIN MENU
BASIC CONTROL MONITOR
AUTOSCAN (display)
MANUAL SCAN (display) GENERAL INFO (display) ADVANCED CONTROL
ADVANCED CONTROL
COMMUNICATIONS
The MAIN MENU is made up of the following two displays. Select the arrows to scroll up or down.
BSCONTROL ALARMS MONITOR
GENERAL INFO ADV CONTROL
Select the BSCONTROL (BASIC CONT ROL) subm enu fr om the f irst display by pressing the upper left Control Button. The TSR-2 will then display the BASIC CONTROL submenu which is Step 10. The following figure shows Step 10 and describes how the buttons on the TSR-2 work while Step 10 is displayed.
Step 10 from the Control Menu
PUSH TO SCROLL UP
PUSH TO SCROLL DOWN
INVERTER
PUSH TO ENABLE
(SHOWN ENABLED)
PUSH TO GO BACK ONE MENU LEVEL
ENABLED disabled
MENUESC
Adjustable Contrast Control
The TSR-2 Display has an adjustable contrast control. To increase intensity: hold down the lower left control button and press the upper right control button repeatedly until the desired level is obtained. To decrease intensity: hold down the lower left control button and press the lower right control button r epeatedly until the desired contrast level is obtained.
Demo Mode
Use Demo Mode to become f amiliar with the TSR-2 m enu sequences. T he TSR-2 is placed in Dem o Mode by connecting the Data Cable while both the Escape button and the Menu button are held down. Discontinue Demo Mode by disconnecting the data cable. If someone accidentally changes the Inverter Address, Step 92, the TSR-2 im mediately will stop responding. Use Demo Mode to reset Step 92 ‘Inverter Addres s’ to 1. The Comm unication Addresses are the only settings selected in Demo Mode which carry back to normal operation.
PUSH TO DISABLE
PUSH TO RETURN TO MAIN MENU
Placing changes into effect
The only changes which go into effect without resetting the system are ‘enabling or disabling’ the inverter and
TruSine 4.5 kW Inverter Page 12 Owners Manual
TSR-1 Remote Control
the charger. Changes to other system func tions or setpoints will not go into effect until the system is reset. Reset the system by turning the System ON/OFF Switch, located on the front of the inverter, OFF for 5 seconds and then back ON. When changing setpoint values you must leave that screen before resetting the system.
The system also can be reset via the T SR-2. W hen changing inverter func tions, disable/enable the inver ter to reset the inverter. When changing char ger functions, disable/enable the charger to reset the charger. Reset both if in doubt.
Password
Acceptance of factory setpoints or adustments to setpoints should be made only by qualified personnel. If certain setpoints are incorrect then system performance degradation or external equipment damage could occur; i.e. battery damage due to improper charging, etc. The most sensitive system adjustments are located in the Advanced Control Menu which is password protected. The password for gaining acc ess to the Advanced Control Menu consists of pres sing the four Control Buttons in the following sequence: upper left, lower right, lower left, upper right.
3.4 Menu Map
Initial Display (Push any button to enter main menu.)
TSR-2 A88769-A
MAIN MENU:
Ref. Step Display Function Action 1 BSCONTROL Selects the BASIC CONTROL submenu Go to Step 10 2 MONITOR Selects the MONITOR display submenu Go to Step 20 3 ALARMS Selects the ALARMS display submenu Go to Step 100 4 Down Arrow Scrolls down in the menu Go to Step 5 5 GENERAL INFO Selects the GENERAL INFO display submenu Go to Step 50 6 ADV CONTROL Selects the ADVANCED CONTROL submenus Go to Step 60 7 Up Arrow Scrolls up in the menu Go to Step 1
BASIC CONTROL Menu:
10 Inverter Allows inverter to operate automatically Controls inverter
ENABLED disabled (ENABLED) or turns inverter OFF (DISABLED).
11 Load Demand Allows Load Demand to operate automatically Controls inverter
ENABLED disabled or turns Load Demand OFF (DISABLED).
12 Enter Load Dmd Selects the size of the AC load at which the Controls inverter
+ XX Watts - inverter goes into Load Demand (asleep)
13 Exit Load Dmd Selects the size of the AC load at which the Controls inverter
+ XX Watts - inverter turns fully ON (wakes up)
14 Charger Allows charger to operate automatically Controls Charger
ENABLED disabled or turns the charger OFF (DISABLED)
15 Equalize Cycle Allows Equalize Cycle to operate automatically Controls Charger
ENABLED disabled or turns the Equalize Cycle OFF (DISABLED)
16 APM Limit Sets Automatic Power Management Amps Controls Charger
+ XX Amps AC -
TruSine 4.5 kW Inverter Page 13 Owner’s Manual
TSR-2 Remote Control
MONITOR Menu:
20 AUTOSCAN System status display Go to Step 30 21 MANUAL SCAN System status display Go to Step 40
AUTOSCAN Menu:
30 Press ESC to quit. Go to 31 31 Inverter/Charger/System Displays inverter status message Go to 32
SYSTEM STATUS
32 APM Limit Displays APM setpoint Go to 33
XX Amps AC
33 Aux AC Input Displays if Aux AC Input is within voltage Go to 34
ERROR and frequency tolerance
34 System AC Volts Displays Aux AC input volts or Go to 35
XXX VAC inverter AC output volts
35 System AC Amps Displays Aux AC input amps or Go to 36
XXX Amps AC inverter AC output amps
36 Battery Volts Displays battery voltage Go to 37
XX.XX VDC
37 Battery Status Displays if battery is within operating range Go to 38
GOOD (within high and low battery setpoints)
38 Batt Temperature Displays battery temperature if optional Go to 31
XXX º C battery temperature sensor is installed
MANUAL SCAN Menu:
40 Inverter/Charger/System Displays inverter status message Go to 41
SYSTEM OFF
41 APM Limit Displays APM setpoint Go to 42
XX Amps AC
42 Aux AC Input Displays if Aux AC Input is within voltage Go to 43
ERROR and frequency tolerance
43 System AC Volts Displays Aux AC input volts or Go to 44
XXX VAC inverter AC output volts
44 System AC Amps Displays Aux AC input amps or Go to 45
XXX Amps AC inverter AC output amps
45 Battery Volts Displays battery voltage Go to 46
XX.XX VDC
46 Battery Status Displays if battery is within operating range Go to 47
GOOD (between high and low battery setpoints)
47 Batt Temperature Displays battery temperature if optional Go to 40
TruSine 4.5 kW Inverter Page 14 Owners Manual
TSR-1 Remote Control
XXX º C battery temperature sensor is installed
GENERAL INFORMATION Menu:
Press right control buttons to scroll up. Press left control buttons to scroll down.
50 INVERTER SW (↓)
() REV. 1.13
51 ()Model: (↓)
() TSC24-4500(D) ()
52 () TSR-2 (↓)
() A88769-A ()
53 ()VANNER POWER GRP(↓)
()4282 REYNOLDS DR ()
54 ()HILLIARD, OHIO (↓)
()43026-1297, USA ()
55 ()PH: 614-771-2718 (↓)
()FAX: 614-771-4904 ()
56 ()http:// (↓)
()www.vanner.com ()
57 ()mail to:pwrsales (↓)
()@vanner.com ()
ADVANCED CONTROL Menus:
60 Password Use control buttons to enter password: If correct go to
XXXX upper left, lower right, lower left, upper right. Step 61 if not
Go to Step 6 61 ADVANCED CONTROL Selects ADVANCED CONTROL submenu Go to Step 70 62 COMMUNICATIONS Selects the COMMUNICATIONS submenu Go to Step 90
ADVANCED CONTROL Menu:
70 InverterOutput Adjusts inverter AC output voltage setpoint Go to Step 71
+ XXX VAC - and the ±10% range for Aux AC input voltage
71 LowBatt Warn Adjusts inverter Low Battery Warning Go to Step 72
+ XX.XX VDC - DC Volts setpoint
72 LowBatt ShutDn Adjusts inverter Low Battery Shutdown Go to Step 73
+ XX.XX VDC - DC Volts setpoint
73 HighBat ShutDn Adjusts inverter High Battery Shutdown Go to Step 74
+ XX.XX VDC - DC Volts setpoint
74 BulkChrg Volts Adjusts Bulk Charge DC Volts setpoint Go to Step 75
+ XX.XX VDC -
75 Bulk Chrg Amps Adjusts Bulk Charge DC Amps setpoint Go to Step 76
TruSine 4.5 kW Inverter Page 15 Owner’s Manual
TSR-2 Remote Control
+ XX ADC -
76 AbsorpChrgVolt Adjusts Absorption Charge DC Volts setpoint Go to Step 77
+ XX.XX VDC -
77 AbsorpChrgAmps Adjusts Absorption Charge DC Amps setpoint Go to Step 78
+ XX ADC -
78 Absorp MaxTime Adjusts Absorption Charge maximum time Go to Step 79
+ XXX minutes - duration setpoint
79 FloatChrgVolts Adjusts Float Charge DC Volts setpoint Go to Step 80
+ XX.XX VDC -
80 Equalize Volts Adjusts Equalize Cycle DC Volts setpoint Go to Step 81
+ XX.XX VDC -
81 EqualizMaxTime Adjusts Equalize Cycle maximum time Go to Step 82
+ XX minutes - duration setpoint
82 Batt Temp Comp Turns ON/OFF Battery Temperature Go to Step 83
ON off Compensation for Battery Charger
83 Batt Temp Coef Adjusts Battery Temperature Compensation Go to Step 84
+ XX.XmV/ºC/Cell - Coeficient
84 BattTempShutDn Adjusts battery charger High Battery Temperature Go to Step 85
+ XXºC - shutdown setpoint
85 Gen Start Mode Allows Gen Start to operate automatically (ON) Go to Step 86
on OFF or turns Gen Start OFF.
86 GenStart Volts Adjusts battery voltage setpoint at which the Go to Step 87
+ XX.XX VDC - Gen Start contacts close
87 Gen Stop Amps Adjusts Bulk Charging amps setpoint at which Go to Step 88
+ XX ADC - the Gen Start contacts open
88 Aux AC Delay Sets time delay after Aux AC input power Go to Step 89
+ XXX Seconds - is present until AC transfer occurs
89 Solar Mode Allows inverter to operate in Solar Mode or Go to Step 70
on OFF turns Solar Mode OFF (DISABLED)
COMMMUNICATIONS Menu Used only for multiple inverter and/or multiple TSR-2 applications.
90 Look for Inverters? Starts automatic Remote configuration. If yes, go to
yes NO The default setting is NO. Step 91, If no
go to Step 92
91 Remote Addr: 1 Displays the addresses of the Remote(s) and
Inverter Addr: 1 the Inverter(s)
92 Inverter Addr: The Address of the system’s first inverter is 1. Go to Step 93
+ 1 - Do not change. See Demo Mode if changed.
93 Remote Addr: Sets the Remote address number. Go to Step 90
+ 1 - The remote address will match the inverter(s).
TruSine 4.5 kW Inverter Page 16 Owners Manual
TSR-1 Remote Control
ALARM Menu:
100 ALARM If system faults exist the ALARM LED will be Go to next step
(message) ON and Alarm message(s) will be displayed.
101 Getting Alarms (↓)
from Inverter... Press lower right control button to scroll through Alarm Messages.
Alarm Message Displayed Description of Problem
1. AC Input ERROR There is no Aux AC input voltage or the Aux AC input is out of voltage or frequency tolerance limits.
2. Battery High Battery voltage is above High Battery Shutdown setpoint (will shut down system).
3. Battery Low Battery voltage is below Low Battery Warning setpoint and soon will reach Low Battery Shutdown setpoint.
4. Current Limit Inverter AC output amps are at the Maximum Current allowed. The AC voltage will be fall if load increases. Overload Shutdown will occur if voltage falls below tolerance for 3 seconds.
5. Overload Inverter has shut down due to overload. High AC load caused inverter output voltage to fall below tolerance for three seconds.
6. Hardware Fault Internal circuit failure or power brick high temperature (will shut down system.
7. Overheat 1) High internal temperature (transformer, triac plate or power brick). System shutdown will occur. 2) AC output circuit breaker tripped.
TruSine 4.5 kW Inverter Page 17 Owner’s Manual

Front Panel Wiring Identification

4 Front Panel Wiring Identification
AC IN
AC OUT
CHASSIS GROUND
POWER ON
POWER
OFF / ON
BATTERY TEMP SENSOR
V-NET PORT
SERIAL PORT
AC OUTPUT
CIRCUIT BREAKER
INV . O N LOW BA TT. GEN START
FOR CONNECTION TO
CLASS 2 CIRCUITS ONLY
BATT. BATT.
4.5 kW Power Inverter
Front Panel
All field wiring enters the TruSine housing through the front panel. This is the bottom surface when the unit is oriented in the wall mounted position.
4.1 AC Input & Output Wiring
The AC wiring compartment is located on the left side of the unit. The compartment contains a removable access cover and two cable clamps for the AC input and AC output wiring. Inside the compartment is a terminal strip for making AC input and AC output connections.
NOTE
The AC output voltage and the required Aux AC input voltage of Model
TSC24-4500
is 120 VAC, 60Hz.
The AC output voltage and the required Aux AC input voltage of Model
TSC24-4500D
is 120/240 VAC, 60Hz, single phase, 3 wire. L1 and L2 are 180 degrees out of phase and cannot be tied together . T he unit may be damaged if the AC input power is not 180 degrees out of phase. Exam ples of unacceptable power are two phases from a three phase generator or power from two separate 120 volt generators.
4.2 DC (Battery) Wiring
A DC wiring compartment is located behind the wiring panel on the right side of the unit. T he compartment contains a removable access cover and two cable c lamps for the battery positive and battery negative cables. The inverter’s battery cable terminal lugs can accommodate cable sizes up to 250 MCM.
4.3 System ON Indicator
The light emitting diode (LED) indicates that the System ON/OFF Switch is ON.
4.4 Battery Temperature Sensor Port
This is an RJ-11 (4-wire) jack for optional Battery Temperature Sensor.
4.5 V-NET Port / TSR-2 Remote Control Port
This is an RJ-11 (6-Wire) jack for communications with the optional TSR-2 Remote Control / Operator Interface Panel.
4.6 Serial Interface Port
This is an RJ-11 (6-Wire) jack for RS-232 serial communications.
4.7 Inverter Output Circuit Breaker
This 20-Amp cir cuit br eaker provides over current pr otection f or Inver ter AC output and the Battery Charger AC input. This breaker does not protect the Aux AC passthrough power.
TruSine 4.5 kW Inverter Page 18 Owners Manual
Front Panel Wiring Identification
4.8 System ON/OFF Switch
Use this rocker switch to tur n the system ON and OFF and to reset the system. The System ON/OFF Switch does not interrupt Aux AC input power or DC input power to the system.
4.9 Remote Signal Contacts
Three sets of contacts provide signals (continuity) for Remote Inver ter ON/O FF indication, Rem ote Low Battery Warning indic ation and Gen Start control. Contacts are rated 2 amps for 12 or 24 volt, Class 2 c ircuits. W ir ing connections are made through a 6 c onduc tor plug- in terminal block. Screw pres sur e- clamp terminals ac cept up to 14 gauge wire.
5 INSTALLATION
Unpacking the Inverter
Inspect the shipping container and equipment for loose or damaged parts. If any damage is found, im m ediately notify the freight carrier.
5.1 Basic Guidelines
The wiring of your inverter installation should conform to the National Electric Code ( NEC) and any other state or local codes in effect at the time of ins tallation. These codes have been written f or your protection and their requirements should be followed.
Mounting Locate a secure, dry, flat horizontal or vertical surfac e large enough to m ount the invert er. T he location should be as close to the battery as possible without being in the same com partment and should provide adequate ventilation to maintain room tem perature while the inverter is operating. The location must allow unobstructed cooling air flow at sides and bottom of the unit, and the loc ation must be free from road spray, dripping water or other moisture contamination. A recommended minimum clearance of 4 inches (102 mm) should be maintained on all sides of the unit.
WARNING:
compartments, or other areas hazardous locations requiring ignition protection.
NOTE
The wiring of your inverter installation should conform to the National Electric Code ( NEC) and any other state or local codes in effect at the time of installation. Article 551 of the NEC requires any DC cable from a batter y, which measures longer than 18 inches along its length, be protec ted by a fuse. Other codes m ay require each ungrounded output conductor from a storage battery, other than to the engine cranking motor, to have a manually reset trip-free circuit breaker or fuse within 72 inches of the battery as measured along the conductor.
Risk of fire or explosion. The inverter must not be mounted in fuel storage areas, battery
5.2 DC Wiring Preliminary Considerations
1.
BE AWARE
THERE WILL BE A LARGE SPARK
occur every time the batteries are connected.
2. The DC cables should be as short as possible. It is electrically mor e efficient to run the lower current AC wiring longer distances than the DC cables. (See DC Cable Sizing Chart for proper size.)
3. Route the DC positive and negative cables as c lose together as possible, and use cable ties to keep them together. This reduces some electromagnetic radiation that could interfere with some sensitive electronics.
3. On vehicle installations do not use the vehicle chassis as the DC negative conductor. Use a cable the same size as the DC positive to go directly from the inverter to the battery negative.
4. Route the AC and DC power wiring separately, and with as much physical separation as poss ible, from low voltage wiring such as audio and video signal wires.
that, as a large number of capacitors become charged upon completion of the DC circuit,
when the last battery connection is made. The spark is norm al and will
TruSine 4.5 kW Inverter Page 19 Owner’s Manual
Installation
5. DC power input cables which pass through steel or other ferrous metal walls need to pass through the same hole. If two holes are required, cut a slot connecting the two holes to prevent a transformer effect.
6. Do not allow wire fragments or metal shavings to fall into the DC wiring c ompartment or to enter the inverter in any way. Severe inverter damage will result which is not covered by the warranty.
7. Do not connect the inverter to the battery at this time. Final battery connections will be made after all installation issues have been inspected.
8. WARNING:
9. WARNING:
inverter and is not covered under warranty. Risk of f ire or ex plosion of batteries m ay occur due to very high currents.
10.A DC fuse is required to properly protect the inverter.
11.T he table below shows the recommended m inimum cable size which should be used. W ire sizing charts published in the NEC may allow a greater amp capacity than we recommend. We have sized the cable for a maximum voltage drop to maintain better performance of your inverter installation. The inverter’s DC cable terminal lugs can accommodate cable sizes up to 250 MCM.
Fuse Fuse Holder
A poorly made high current connection may result in risk of fire and personal injury.
Be sure of the polarity of the DC input wiring. Reverse polarity may severely damage your
TruSine 4500 DC Cable and Fuse Sizing Chart
Model Number
Cable Size
4/0 16
250MCM 19
Bussmann ANL500 Vanner 03646
Bussmann 4164 Vanner 03637
TSC24-4500 and TSC24-4500D
Distance from battery to inverter in feet
(Length of cable is 2 times the distance.)
DC Wiring Installation
The DC input terminals are located in the f ield wiring com partm ent located at the f ront right side of the unit and accessed from the top. The connections are compression terminals which require a stripped cable and are tightened by an Allen wrench. The positive and negative cables enter the com partm ent through separ ate strain reliefs located at the right front of the unit.
WARNING
Never make electric al connections "live". Mak e the connections to the inverter fir st and the battery last. Mak e certain the ON/OFF control switch on front of inverter is in the OFF position before connecting to the battery.
NOTE
Severe damage to the inverter will result, which is not covered under warranty, if wire fragments or other m etal particles enter the inverter through the DC wiring compartment. Procedure Step 1: T urn the inverter OFF and disconnect all AC and DC power to the wiring harness. Mak e sure power
to the inverter wiring is disconnected. Verify that the inverter is turned OFF (the Inverter ON-OFF switch is in the OFF position).
Step 2: Select a location for the unit. An ideal installation location has the following characteristics:
Close to the battery (usually within six feet).
Protected from the weather.
Well ventilated.
Step 3: Route DC input cables. Route the negative and positive DC input cables from the inverter to the
battery. If required, protect cables where they contact hard, sharp edges.
Step 4: Install the in-line fuse. Install the in-line fuse in the r ed, positive DC input cable between the battery
and inverter, within 18 in. of the battery or DC wiring bus system.
Step 6: Connect the inverter to the battery.
A) Remove the cover plate on the DC cable compar tment exposing the positive and negative Allen head
terminal lugs. B) Remove the two Allen screws from the terminal lugs. C) Strip the positive and negative DC cable ends 3/4 in.
TruSine 4.5 kW Inverter Page 20 Owners Manual
Installation
D) Insert the black, negative ( -) cable end through the s train relief and into the negative term inal lug. Be
sure that all cable strands are completely in the lug. E) Insert the Allen screw into the negative terminal block and tighten to 275 inch-pound. F) Insert the red, positive ( +) cable end through the strain relief and into the positive ter minal lug. Be
sure that all cable strands are completely in the lug. G) Insert the Allen screw into the positive terminal block and tighten to 275 inch-pounds. H) Tighten the two cable clamps. I) Inspect the DC cable compartment to ensure that no foreign particles are present. J) Replace the cover plate over the DC cable compartment. K) Repeat steps E and G every 30 days.
Step 7: Verify Installation. Verify all connections are tight and bright and the cables are secure.
5.3 AC Wiring Preliminary Considerations
1. Output and Input Voltages The AC output voltage and required Aux AC input voltage of Model
TSC24-4500
is 120 VAC, 60Hz.
The AC output voltage and required Aux AC input voltage of Model single phase, 3 wire. L1 and L2 are 180 degrees out of phase and cannot be tied together. T he unit may be damaged if the AC input power is not 180 degrees out of phase. Exam ples of unacceptable power ar e two phases from a three phase generator or power from two separate 120 volt generators.
2. AC Wire Size To properly size the AC input and output wiring the installer must consider the inver ter output c apability, the inverter passthrough capability and the battery charger input requirement. The AC input/output terminal strip is a compression lug style which will accept up to #6 AWG wire. Model TSC24-4500 – The 37.5 am p at 120 volt (4500 watt) inver ter output c apability requires #8 AWG wire minimum be used for the AC output. The AC transfer switch is rated 30 amps at 120 volts. Use input wire up to #6 AWG sized to suit the AC input source. The AC output wire should be the same size as the AC input wire but not less than #8 AWG. Model TSC24-4500D – The 18.75 am p at 240 volt (4500 watt) inverter output c apability requires #12 AWG wire minimum be used for the AC output. The AC transfer switch is rated 30 amps at 240 volts. Use input wire up to #10 AWG sized to suit the AC input source. The AC output wire should be the same size as the AC input wire but not less than #12 AWG.
3. The AC Input and Output wiring compartment is access ed from the top left s ide of the unit. F ield wires are brought in through two cable clamps to the terminal strip identifying the “AC Input” and “AC Output” terminals. Model TSC24-4500 – The 120VAC Input and AC output terminals are labeled L1, N, and G. Model TSC24-4500D – The 240VAC input and AC output terminals are labeled L1, L2, N and G.
4. AC feedback will cause damage to the inverter! The power dis tribution c irc uits must be designed to prevent AC power from an external sour ce (shore power or a generator) from feeding back into the inver ter's AC output.
TSC24-4500D
is 120/240 VAC, 60Hz,
5. The inverter AC output must be wired to a Ground Fault Circuit Interrupter (GFCI) to ensure a safe installation. Always maintain an isolated neutral downstream from the GFCI to prevent nuisance tripping.
6. NEC ‘Branch Circuit Rated’ circuit breakers must be installed in all installations having Aux AC input. The CHASSIS BONDING LUG located on the front of the unit has been provided for safety to prevent
7.
possible shock hazards. Connect a #8 AW G m inimum size wire to this terminal and then to chas sis of the vehicle, the installation's grounding system, or to earth ground. Failure to connect the chassis bonding lug to the chas s is of the vehicle, the installation's grounding system, or to earth ground may result in a lethal shock hazard.
AC Wiring Procedure
Step 1: Connect the AC output. Remove the cover of the AC wiring compartment to expose the AC
TruSine 4.5 kW Inverter Page 21 Owner’s Manual
Installation
input/output terminal strip. Identify the lower terminals labeled “AC Output”. Insert the field wires through the lower strain relief into the AC wiring compar tment. Tighten the strain relief. Connect the field wires to the proper AC output terminals.
Step 2: Connect AC Input. Identify the terminal strip’s upper terminals labeled “AC Input”. Insert the field
wires through the upper strain relief into the AC wiring compartment. Tighten the strain relief. Connect the field wires to the proper AC input terminals. Replace the AC wiring compartment cover.
Step 3: Connect Bonding Lug. Use a #8 AWG or larger copper c onductor to c onnect the chas sis bonding lug
to the chassis of the vehicle, the installation’s grounding system, or to earth ground.
Step 4: Verify Installation. Verify all connections are tight and secure for maximum performance.
5.4 TSR-2 TruSine Remote Control Panel Installation Unpacking the Optional TSR-2 TruSine Remote Control Panel
Inspect the shipping container and equipment for loose, damaged, or missing parts. If any damage is found, immediately notify the freight carrier.
Installing the TSR-2 TruSine Remote Control Panel
The TSR-2 TruSine Remote Control Panel may be located near the inverter or at a c onvenient remote location. The unit is supplied with a 25’ long twisted data cable with a 6-pin RJ-11 connector at each end.
Step 1: Locate a suitable clean dry location for installation. T he TSR-2 f ront panel is 6½ wide x 5¼ high. The
back housing is 5¾ wide x 4½ high x 1¾” deep with cable entry on the right side. Step 2: Route the data cable from the remote panel mounting area to the inverter. Step 3: Plug the data cable into the RJ-11 modular jack labeled “V-NET” on the front of the inverter. Step 4: Plug the data cable into the RJ-11 modular jack on right side of the TSR-2. Step 5: Mount the TSR-2 Remote Panel using four #8 screws (not included).
5.5 System Start-up and Testing
Step 1: Completely install the TruSine 4500 Inverter/Charger following the system design considerations and
instructions provided previously in this manual. Step 2: Place the System On/Off switch located on the front of the inverter in the OFF position. Step 3: Verify that the external GFCI breaker is reset and connect an AC load, such as a 100-Wattlight. Step 4: Turn ON the battery DC power to the inverter. Step 5: Turn ON the AC shore power (or generator) to supply the AC input power to the system. Step 6: Place the System On/Off switch located on the front of the inverter to the ON position. Step 7: The green Power On LED on the front of the inverter should come ON. Step 8: The TSR-2 TruSine Remote Control Panel (optional), if used, should display the main menu. Step 9: The AC output test light should be ON, indicating the presenc e of shore power and corr ect operation
of the AC transfer switch. Step 10: Disconnect the AC shor e power input. T he AC output tes t light s hould immediately quickly blink onc e,
indicating the transfer switch transferred the test light from shore power to inverter power. Step 11: At this point, apply AC loads up to 4,500 watts to verify full-power operation. Step 12: Apply shore power. After a delay the AC output test light should blink indicating the transfer of the
load from inverter power to shore power. Step 13: Test the battery charger operation:
TruSine 4.5 kW Inverter Page 22 Owners Manual
Installation
A) Discharge the battery by placing the AC load on the system and operating the inverter, (rem ove shore
power input). B) When the battery charge level is low, the inverter will turn off. C) Apply shore power and observe the battery charger operation. Connect an am meter to the DC cables
between the inverter and the battery to monitor the current (DC amps ), and a volt meter to the battery to
monitor the battery voltage. The battery charger will step through its sequence and stop in the float
mode.
Step 14: The system is now ready for operation.

6 GENERAL INFORMATION SECTION

6.1 Generic Inverter Description
In general, an inverter converts DC electrical power into AC power. T h is power c an be us ed to operate var ious AC-driven appliances. Typical DC power sources include batteries that store electrical energy, power generated from a vehicle alternator or renewable energy sources such as photovoltaic (solar) panels.
The most com mon battery systems are 12 or 24 volt. Some systems, however, operate on higher voltages such as 32, 36, 48, or 120 volts. The most comm on inver ter AC output power is 120 volts at a fr equency of 60 Hz. Some inverters, however, are designed to produce 240 volts, or both 120 and 240 volts at 60 Hz. Because some countries use power of dif ferent voltage and frequency (e.g., 230 volts at 50 Hz), inverters ar e available to conform to these requirements.
The three available inverter types are distinguished by the type of AC output wave form they produce. This wave form affects the AC loads they operate. This section provides an overview of these inverter types, including the advantages and disadvantages associated with using each type.
Sine Wave Inverter
Sine wave inverters produce an AC output wave form like power pr oduced by the electric utility com panies and rotating generators. The sine wave inverter’s wave form is characterized by the highest peak voltage and smooth voltage transitions (no square wave components). Such inverters are the most costly of the three inverter types because they contain additional electronics to produce the required wave form. A measure of the sine wave quality is Total Harmonic Distortion (THD), and is expressed in a perc entage. The lower the THD the higher the quality of the sine wave power.
Modified Sine Wave Inverter
Modified sine wave inverters are sometimes called “quasi sine wave inverters” or “modified square wave inverters.” Modified sine wave inverters gener ally cost more than square wave inverter s because they contain additional electronic circuitry to produce true RMS regulated AC output. Modified sine wave inverters have higher AC peak voltages than square wave inverters, and automatic ally control the width of the AC output wave form to regulate the output voltage (pulse- width modulation). The shape of the modified sine wave invert er’s wave form includes a square wave com ponent. It is stepped in such a way, however, to c losely approximate the true sine wave produced by the electric utility companies. Although this wave form has a higher peak voltage than do square wave inverters, its peak voltage is not as high as a pure sine wave. Therefore, AC loads containing power supplies might not always operate properly on the modified sine wave inverter.
Square Wave Inverter
The square wave inverter is a low cost device that produces a pure square wave AC power output. This AC power can be an accurate 60 Hz frequency if it is crystal controlled. It does not have the necessary peak voltage to properly operate many AC appliances that contain electronic power supplies (e.g., com puters, TVs , and VCRs). The square wave is appropriate when operating AC loads such as resistive heating devices.
6.2 Inverter Sizing
Output Power Rating - Power output is an important consideration when purchasing an inverter. Power is defined as the rate that a device produces (or uses) electrical energy. This rate is measured in watts or kilowatts (one kilowatt equals 1,000 watts), or sometimes in voltamps. Voltamps are roughly equal to watts and
TruSine 4.5 kW Inverter Page 23 Owner’s Manual
General Information
are obtained by multiplying volts times amps produced or used by a device To properly determine an inverter size (in watts) for your application decide which AC loads you plan to operate.
Inverter size is the sum of the wattages of the AC loads that you wish to run at the s ame time, plus a safety factor, say 10 to 20 percent.
Continuous Output Power - Continuous power is defined as the AC power in watts (or voltamps) an inverter can produce on a continuous basis. The ambient temperature can affect the continuous rating of the inverter, and is normally specified, e.g., 25° C. or 40°C.
Surge Output Power - Inverter power can also be rated in terms of surge power. Surge power is the shor t ter m duration of AC power that the inverter can produce. It is often specified as the watts (or voltam ps) that can operate a resistive load for two or three sec onds. Som etim es this is s pecif ied in AC am ps because the inver ter may allow output voltage to drop (which would reduce is wattage). Like continuous power, the surge rating is affected by ambient temperature.
Note - Regardless of an inverter’s power r atings, an inverter’s AC output capability is only as s trong as the DC source. To achieve optim um perfor mance an inverter m ust be installed with properly sized cable and have an ample DC supply. Recommended cable sizes are listed in the DC Cable and Fuse Chart. The following sections in this manual will cover the basic information required to properly size the inverter battery and the vehicle alternator. Keep in mind that if information in this manual directly conflicts with instructions from a specific battery or other equipment manufacturer, Vanner recommends that those manufacturer's recommendations be followed.
6.3 DC Power Consumption
An inverter takes in DC power, and produces AC power to operate AC loads . In general, we can see a direct relationship between DC input power and AC output power. This allows us to establish the f ollowing rule of thumb:
For 12 volt DC inverters: Output Watts ÷ 10 = DC Input Amps. For 24 volt DC inverters: Output Watts ÷ 20 = DC Input Amps.
This rule of thum b can be used to estimate the minim um alternator size required for your application. It may also be used in calculating the minimum size battery required when operating from an alternator and battery combination; a photovoltaic panel and battery combination; or when operating f rom battery alone. The following examples should help to clarify the use of this rule of thumb.
Example A
What is the DC current draw of a 12 volt DC input inverter when it is operating a vacuum cleaner with a name plate rating of 6 amps at 120 volts AC?
The appliance rating is given in amperes , so we must f irst calculate the power it consum es. T hen the rule of thumb can be used to find the DC input current of the inverter.
Output power = 120 volts x 6 amps = 720 watts, and DC input current = 720 ÷ 10 = 72 amps DC.
Example B
What is the DC current draw of a 24 volt DC input inverter when it is operating a toaster with a name plate rating of 1050 watts at 120 volts AC?
Since the appliance is rated in watts, the rule of thumb can be applied directly: DC input current = 1050 ÷ 20 = 52.5 amps DC.
This information on estimating the DC input current requirement for an inverter will allow you to size an alternator or charging system to supply an inverter for c ontinuous operation. This rule of thumb will be used later in the discussions on battery sizing.
TruSine 4.5 kW Inverter Page 24 Owners Manual
General Information
6.4 Battery Terminology and Ratings
Batteries used for automotive applications generally are lead-acid storage batteries. They can be separated into two categories according to their use: engine cranking batteries and deep cycle batteries. The engine cranking battery is specifically designed to supply hundreds of amps for a short period of time to start an engine. Cranking an engine usually uses a small portion of the battery's total capacity and once the engine is running, the battery is quickly recharged by the engine's alternator. The deep cycle battery is specifically designed to deliver current for extended periods of time and can be almost totally discharged before recharging.
The "deep cycle" lead-acid battery is designed to withstand the deep discharge/recharge cycling that is typical of most inverter installations. These batteries are available in the "maintenance free" style where the electrolyte does not need to be checked or replenished and they also are available in the gelled electr olyte style or "Gel Cells". Deep cycle batteries are generally advertised for use in recreational vehicles or boats and are sometimes referred to as RV or marine batteries.
Battery Council International (BCI) is a voluntary industry organization which has helped to standar dize battery ratings. Ratings in use at this date are:
CCA (Cold Cranking Amperes): Rating in am ps a battery cold soaked at 0°F or –20°F will carry for 30
seconds and maintain a minimum terminal voltage of 7.2.
MCA (Marine Cranking Amperes): Rating in amps a battery cold soaked at 30°F will carry for 30 seconds
and maintain a minimum terminal voltage of 7.2.
RC (Reserve Capacity): Rating in minutes a battery will carry a 25 amp load at 80°F and maintain a
minimum terminal voltage of 10.5.
AH (Amp Hour): At the “20 Hour Rate”, also called the C Rate, a battery having a 100 AH rating mus t
carry a 5 amp load for 20 hours (100AH ÷ 20 hours = 5 amps) and maintain a term inal voltage of
10.5 at 80°F. (Two 100AH 12volt batteries connected in series provides 100AH at 24 volts . Two 100 AH 12volt batteries connected in parallel provides 200 AH at 12 volts.).
CCA and MCA are used for sizing an engine cranking battery and have no bearing on a batter y's cycling ability. RC is a rating given to cranking batteries to pr ovide an idea of how long a vehic le c ould be driven if the vehicle charging system were to fail.
The most important and probably least understood battery capacity rating is the ampere-hour. One simple reason the AH rating is misunders tood is that a battery rated at 100 AH cannot always deliver 100 AH. The underlying reason is the efficiency with which the battery converts its chemic al energy into electric energy. The AH capacity of a battery is affected in the following ways:
Discharge rate: A battery becomes less efficient as the dischar ge current increases. For example, a typical 100 AH battery is specified to be able to deliver 5 amps for a period of 20 hours . If the dischar ge current were increased to 25 amps, the capacity will be reduced to approximately 75 AH (25 amps x 3 hours = 75 AH).
Operating temperature: A battery becomes less efficient at lower tem peratures. Most battery manufacturers specify the battery AH capacity at 80° F. At a temperature of 32° F, the same batter y will have only about 65% of its rated capacity even though it may be fully charged. At a temperature of 0° F , a battery's capacity will be reduced to about 40% of its rated capacity.
Battery age: As a battery is used, the active material on the battery plates will gradually deteriorate and become useless. As the battery gets older, there will be less and less useful material left on the plates and the operating time will become noticeably shorter. A batter y will age faster (loose active m aterial from its plates faster) if it is deeply discharged regularly, if it is left in a discharged state for extended periods of time, or if it is repeatedly overcharged.
Series and/or Parallel Connected Batteries: Up to this point we have spok en of the batter y as if it were a s ingle battery. In some cases this may be true, but in general, the battery may be made up of several individual batteries electrically connected together to form a "Bank" of batteries. Batteries can be connected in series, parallel, or a combination of s eries and parallel as long as all of the batteries in the bank are of equal ratings, are from the sam e manuf acturer, and are the sam e age. Old and new batteries should never be m ixed in the same battery bank. Mixed batteries will result in accelerated battery failure due to the unequal discharge and recharge rates.
A series connection is where two or mor e batteries are connec ted positive (+) to negative (- ). T he total voltage
TruSine 4.5 kW Inverter Page 25 Owner’s Manual
General Information
of the battery bank is the sum of the voltage of each battery in the bank. For exam ple, most large custom coaches require a 24 volt battery to crank the large diesel engine. The 24 volts is usually provided by connecting two 12 volt batteries in series, and sometim es by connecting four 6 volt batteries in s eries. The ratings of the series connected batter y bank remain the same as the individual battery's rating. If the battery bank is made up of two 8D size batteries in series , eac h with a CCA of 1050 amps, 425 m inutes RC, and amp­hour capacity of 200 AH, then these individual battery ratings are also the ratings of the entire 24 volt battery bank.
Parallel connected batteries are batteries which are connected pos itive to positive and negative to negative. They form a battery bank that has the same voltage as each individual battery. The ratings of a parallel connected battery bank, in general, are the sum of the individual batteries. For instanc e, if two 8D batteries are connected in parallel, and each battery has the ratings given in the paragraph above, then the ratings for the battery bank become 2100 CCA, 900 minutes RC, and approximately 400 amp-hours. Parallel connected batteries should be of the same voltage and rating to achieve optimum battery life and performance.
6.5 Sizing the Inverter Battery
Sizing a battery system for an inverter application can be a very tedious task if all the dif ferent variables, suc h as discharge rate, depth of discharge, and operating life time are included in the calculations . T o simplify these calculations and get a reasonably correct battery size, we will assume: 1) A 50% depth of discharge for the purpose of obtaining a reasonable life tim e for a reas onable battery system cost, 2) there is no charge cur rent into the battery system, 3) the batteries are in a fully charged state at the beginning of the dis charge cycle, and
4) the DC current draw from the battery does not exceed 1/3 the C rate for any length of time. Follow the steps listed below to find the AH capacity required for your application. Step 1: Mak e a list of each appliance, its power require ment in watts, and the amount of time in hours it will
be operating between charging cycles. Note: If the appliance is rated in am peres (am ps) instead of watts, multiply the amps by the voltage (120 or 240) to get watts.
Step 2: Calculate the watt-hours required for each appliance by multiplying the power requirement by the
operating time of that appliance. Step 3: Calculate the total watt-hours needed by adding together the watt-hours of each appliance. Step 4: Find the amp-hours consumed by dividing the total watt-hours found in step 3 by 10 for 12 volt DC
systems or by 20 for 24 volt DC systems. Step 5: Multiply the amp-hours consumed by 2 (for 50% depth of discharge) to get the battery amp-hour
capacity desired.
Example 1: Follow Steps 1 through 3 (above)
Appliance Power Rating
TV, VCR, Stereo 225 watts 2.5 hours 563 watt-hours
Small Refrigerator 300 3.8 1,140
Microwave 800 0.3 240
TOTALS 1,943 watt-hours
Step 4: Amp-hours consumed = 1943 watt-hours ÷ 20 = 97.15 amp-hours for 24 a volt system. Step 5: The minimum battery size for this application is 2 x 97.15 = 194.3 amp-hours.
Operating Time Watt-Hours Consumed
6.6 Battery and Charging System Considerations
The Battery and DC Charging System is a very important part of your inverter installation respons ible to supply all of the DC power required by the inverter. The system normally consists of the primary charger (engine alternator or photovoltaic array), a secondary charger, if used, the battery, and other equipment which may be used such as battery isolator diodes. The com plexity of the system depends on the way the inverter is us ed. In some cases, such as utility or service vehicles, the system may be as simple as the engine alternator and the cranking battery which also powers the inverter. In most cases, additional equipment is needed to provide additional DC power and/or protection. These systems c an be grouped into two categories, the single battery
TruSine 4.5 kW Inverter Page 26 Owners Manual
General Information
and the dual battery systems. In the single battery system, there is one battery which is shared for starting the engine and operating the
inverter. This is a common practice in a service vehicle where the engine runs all the time and allows the alternator to provide continuous charging for the battery. In this case, the inverter can be connected dir ectly to the engine cranking battery. The most important detail of this system is the alternator output rating. The continuous output of the alternator needs to be at least as m uch as the total DC cur rent draw on the system. The total DC current draw must include the inverter, warning lights, radios, engine controls, and any other device connected to the DC system. Care should be used when operating this type of system while the engine is shut off. The inverter will shut its elf OFF for low battery but most other DC loads will not. The vehicle battery may be drained too low to restart the engine.
The dual battery system uses two separate batteries, one for starting the engine and operating the vehicle's systems, and one for operating the inverter. T he two batteries are usually referr ed to as the "crank ing battery" and the "house or auxiliary battery" respectively. The two separate batteries are usually charged from the same source, the engine alternator , but are s epar ated by a device called a battery isolator. The battery isolator allows DC current to flow from the alternator into each battery, but blocks curr ent from f lowing from one batter y to the other. This is a must to protect the cranking battery in recreation vehicles, boats and other vehicles where the inverter needs to be operated when the engine (therefore the alternator) is not running.
6.7 Battery Charging Guidelines
CAUTION
The following information on batter y charger setup adj ustments should be used as guidelines only. Vanner strongly recommends that you contact the m anufacturer of your batteries to obtain the specif ic charging setup values for the type and model of battery you are using. This is due to the fact that battery charging parameters such as bulk, absorption, float and equalize voltages vary from one manufacturer to another, and that gel cell batteries have different param eters than wet lead acid batteries. An im properly adjusted battery charger may cause damage to your batteries!
The maximum charging current for a battery is usually equal to 20% of the battery's Amp hour capacity (“C”) for lead acid batteries, and 50% of the battery's C for gel cell batteries. T he C rate is numerically equal to the amp-hour capacity for the battery. For example, a 280 amp-hour battery has a C rate of 280 amps, and the maximum charge rate would be 56 amps DC. (Note that this is not the same as the batter y's Cold Cranking Amp rating.) You should also take into consideration that if two batteries ar e connected in parallel their amp­hours add but if batteries are connected in series their amp-hours remain the same.
7 MAINTENANCE & TROUBLESHOOTING
7.1 Preventative Maintenance
There are no user serviceable com ponents inside the TruSine Inverter/charger. For servic e refer to Vanner Power Group or other qualified service personnel.
Maintenance Items: For continued reliability and safety, a monthly maintenance program should be implemented to include the
following:
1. Check to insure that all AC and DC wiring is secure and connections are tight and corrosion free.
2. Check air ventilation openings for dust and other obstructions.
3. Examine receptacle, indicators and switches for cracks and breaks.
Trouble Shooting Problem: The TSR-2 Remote Control Panel does not respond. Check: Suspect Step 92 Inverter Address has been changed from 1. Change back to 1 using Demo
TruSine 4.5 kW Inverter Page 27 Owner’s Manual
General Information
Mode. See TSR-2 Remote Control Panel operation.
TruSine 4.5 kW Inverter Page 28 Owners Manual

Warranty

8 Warranty
NORTH AMERICAN LIMITED WARRANTY
Vanner Inc., doing business as The Vanner Power Group, referred to herein as Vanner, warrants that this product is free from def ects in m aterials and work m anship f or a period of two (2) years from date of installation or two and one half (2 1/2) years from date of manufacture, whichever is less if and only if the following requirements are complied with:
1. The product is installed and checked out properly according to all guidelines, instructions, and checkout procedures set forth in the product Installation and Operating Manual.
2. The installer records all checkout data required and completes, signs, and returns the warranty registration card to Vanner within ten (10) days after installation.
3. The product was purchased after January 1, 2000.
Vanner does not warrant its products against any and all defects when: defect is a result of material or workmanship not provided by Vanner; normal wear and tear , or defec ts caus ed by misuse or us e in c ontrary to instructions supplied, neglect, accident, reversed polarity, unauthorized repairs and/or replacements.
All warranties of merchantability and fitness for a particular purpose: written or oral, ex pressed or implied, shall extend only for a period of two (2) years from date of installation or two and one half (2 1/2) years fr om date of manufacture, whichever is f irst. T her e are no other warranties that extend beyond those described on the face of this warranty. Some states do not allow limitation on how long an implied warranty lasts, so the above limitations may not apply to you.
Vanner does not undertake responsibility to any purchaser of its produc t f or any undertak ing, r epr esentation, or warranty made by any dealers or distributors selling its products beyond those herein expressed unless expressed in writing by an officer of Vanner.
Vanner does not assume res ponsibility for incidental or consequential damages, including, but not limited to, responsibility for loss of use of this product, removal or replacement labor, loss of time, inconvenience, expense for telephone calls, shipping expense, loss or damage to property, or loss of revenue. Some states do not allow the exclusion or limitation of incidental or consequential damages , so these lim itations may not apply to you.
Vanner reserves the right to repair, replace, or allow credit for any material returned under this warranty. Any damage caused by the customer will be charged or deducted from the allowance.
All warranty work will be performed at Vanner’s fac tory, or authorized repair facility utilizing a valid W arranty Authorization Number (WAN) prior to repair. Products shall be delivered to Vanner’s facility, freight prepaid and fully insured. Products repaired under warranty, or replacement parts or products will be returned to North American location prepaid via sam e transportation means and level of service as received, unless directed otherwise. Prepaid freight policy does not apply to locations outside North America.
TruSine 4.5 kW Inverter Page 29 Owner’s Manual
TruSine
4.5 kW Inverter/Charger System
Vanner Power Group 4282 Reynolds Drive Hilliard, Ohio 43026
1-800-AC POWER (1-800-227-6937) Tel: 614-771-2718 Fax: 614-771-4904
www.vanner.com e-mail: pwrsales@vanner.com
Manual Number D98771 Rev B March 1, 2000 Printed in USA
TruSine 4.5 kW Inverter Page 30 Owners Manual
Loading...