Vanguard Heating VN30TA, VP22ITA, VP16TA, VP16ITA, VP16A User Manual

...
®
UNVENTED (VENT-FREE) INFRARED GAS HEATER
SAFETY INFORMATION AND INSTALLATION MANUAL
Model VN30A Shown
VN18A, VN18TA, VP16A, VP16TA, VP26A, VP26TA
VN30A, VN30TA, VP16ITA, VP22ITA
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a quali-
fied installer, service agency, or the gas supplier.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, altera­tion, service, or maintenance can cause injury or prop­erty damage. Refer to this manual for correct installation and operational procedures. For assistance or addi­tional information consult a qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to
Ventilation
section on page 5 of this manual.
Air for Combustion and
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
TABLE OF CONTENTS
Safety Information ............................................... 3
Local Codes ........................................................ 4
Product Identification .......................................... 4
Unpacking ........................................................... 4
Product Features ................................................ 4
Air For Combustion and Ventilation ....................5
Installation ........................................................... 7
Operating Heater .............................................. 14
Inspecting Heater .............................................. 18
Cleaning and Maintenance ...............................19
2
www.desatech.com 113052-01A
Troubleshooting ................................................20
Specifications .................................................... 23
Illustrated Parts Breakdown and Parts List ....... 24
Replacement Parts ........................................... 32
Service Publications..........................................32
Service Hints ..................................................... 32
Technical Service .............................................. 32
Accessories.......................................................33
Parts Central ..................................................... 33
Warranty Information.......................... Back Cover
SAFETY INFORMATION
WARNING: This product con­tains and/or generates chemicals known to the State of California to cause cancer or birth defects, or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this heater. Im­proper use of this heater can cause serious injury or death from burns, fire, explosion, elec­trical shock, and carbon mon­oxide poisoning.
DANGER: Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of car-
bon monoxide poisoning resemble the flu, with head­aches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alco­hol, and those at high altitudes.
Natural and Propane/LP Gas:
gases are odorless. An odor-making agent is added to these gases. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warn­ings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Any change to this heater or its controls can be dangerous.
WARNING: Do not use any accessory not approved for use with this heater.
Natural and Propane/LP
Due to high temperatures, the appliance should be located out of traffic and away from furni­ture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Surface of heater becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will re­main hot for a time after shut­down. Allow surface to cool be­fore touching.
Carefully supervise young chil­dren when they are in the same room with heater.
Make sure grill guard is in place before running heater.
Keep the appliance area clear and free from combustible ma­terials, gasoline and other flam­mable vapors and liquids.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appli­ance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) in­side any structure. Locate propane/LP supply tank(s) outdoors.
3. This heater shall not be installed in a bedroom or bathroom.
4. If you smell gas
• Shut off gas supply
• Do not try to light any appliance
• Do not touch any electrical switch; do not
use any phone in your building
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions
• If you cannot reach your gas supplier, call
the fire department
www.desatech.com 3113052-01A
SAFETY INFORMATION
Continued
5. Always run heater with plaque control knob at the 1, 2, 3, or 4 locked positions. Never set control knob between locked positions. Poor combustion and higher levels of carbon mon­oxide may result.
6. This heater needs fresh, outside air ventila­tion to run properly. This heater has an Oxy­gen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air for Com- bustion and Ventilation, pages 5 through 7.
7. If heater shuts off, do not relight until you pro­vide fresh, outside air. If heater keeps shut­ting off, have it serviced.
8. Do not run heater
• where flammable liquids or vapors are used
or stored
• under dusty conditions
9. Do not use heater if any part has been under water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
10. Turn off and unplug heater and let cool be­fore servicing. Only a qualified service per­son should service and repair heater.
11. Operating heater above elevations of 4,500 feet could cause pilot outage.
12. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. ca­pacity.
13. Before using furniture polish, wax, carpet cleaner, or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
14.
Provide adequate clearances around air open­ings.
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
PRODUCT
IDENTIFICATION
Ignitor Button
Heater Cabinet
Figure 1 - Vent-Free Gas Heater
Control Knob
Grill Guard
Plaque
Front Panel
UNPACKING
1. Remove heater from carton.
2. Remove all protective packaging applied to heater for shipment.
3. Check heater for any shipping damage. If heater is damaged, promptly return to where you bought heater.
PRODUCT FEATURES
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/ pilot is a required feature for vent-free room heat­ers. The ODS/pilot shuts off the heater if there is not enough fresh air.
IGNITION SYSTEM
This heater has an electronic ignitor to light heater fuel supply.
THERMOSTATIC HEAT CONTROL
(Thermostat Models Only)
Thermostat models have a thermostat sensing bulb and a control valve. This results in the greatest heater comfort. This can also result in lower gas bills.
4
www.desatech.com 113052-01A
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ven­tilation air. Read the following in­structions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’ s homes are built more ener gy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy effi­cient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFP A 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol­lowing ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 5 through 7 will help
you classify your space and provide adequate ven­tilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ven­tilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings e xposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 or less with openings gasketed or sealed and
b. weather stripping has been added on
openable windows and doors
c. caulking or sealants are applied to ar-
eas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, be­tween wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of these three crite­ria, you must provide additional fresh air. See
Ventilation Air From Outdoor s
If your home does not meet all of the three criteria above, proceed to
Fresh-Air Flow For Heater Location
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose vol-
ume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an un­confined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all ap­pliances installed in that space. Rooms communi­cating directly with the space in which the appli­ances are installed*, through openings not fur­nished with doors, are considered a part of the un­confined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills be­tween them.
-11
kg per pa-sec-m2)
and
, page 7
Determining
.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless pas­sageways or ventilation grills between the rooms.
.
www.desatech.com 5113052-01A
AIR FOR COMBUSTION
AND VENTILATION
Continued
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft. (volume of space)
Example:
(width) x 8 ft. (ceiling height) = 2560 cu. ft. (vol­ume of space)
If additional ventilation to adjoining room is sup­plied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example:
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater __________ Btu/Hr Gas water heater* __________ Btu/Hr Gas furnace __________ Btu/Hr Vented gas heater __________ Btu/Hr Gas fireplace logs __________ Btu/Hr Other gas appliances* + __________ Btu/Hr Total = __________ Btu/Hr * Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater ______________ Btu/Hr Vent-free heater ______________ Btu/Hr Total ______________ Btu/Hr
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
________ ________
Example:
The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi­mum Btu/Hr the space can support. You must pro­vide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an uncon­fined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 7.
6
Space size 20 ft. (length) x 16 ft.
2560 cu. ft. (volume of space) x 20 =
40,000 + 20,000 = 60,000
Btu/Hr (maximum the space can support) Btu/Hr (actual amount of Btu/Hr used) 51,200 Btu/Hr (maximum the space
can support) 60,000 Btu/Hr (actual amount of
Btu/Hr used)
www.desatech.com 113052-01A
C. Install a lower Btu/Hr heater, if lower Btu/Hr size
makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an uncon­fined space. Y ou will need no additional fresh air ven­tilation.
WARNING: If the area in which the heater may be oper­ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the
National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section
5.3
or applicable local codes
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un­confined space. When ventilating to an adjoining unconfined space, you must provide two perma­nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). Y ou can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of
ventilation grills or ducts.
Ventilation Grills
12"
Building
Into Adjoining Room,
Option 2
Ventilation
Grills
into Adjoining
Room,
Option 1
Or
Remove Door into Adjoining
Room,
Option 3
Figure 2 - Ventilation Air from Inside
.
12"
AIR FOR COMBUSTION
AND VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent open­ings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT:
or outlet air into attic if attic has a thermostat-con­trolled power vent. Heated air entering the attic will activate the power vent.
Outlet Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors
Do not provide openings for inlet
Outlet Air
Inlet Air
Ventilated Attic
Crawl Space
Ventilated
To Attic
To
Crawl
Space
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri­mary heat source. If you have a central heating system, you may run systems circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
CHECK GAS TYPE
Use only the correct type of gas (natural or pro­pane/LP). If your gas supply is not the correct gas type, do not install heater. Call dealer where you bought heater for proper type heater.
INSTALLATION ITEMS
Before installing heater, make sure you have the items listed below.
• for propane/LP gas, external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• sediment trap
• tee joint
• pipe wrench
• for natural gas, test gauge connection*
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. The optional CSA design­certified equipment shutoff valve can be purchased from your dealer. See Accessories, page 33.
LOCATING HEATER
WARNING: Maintain the mini­mum clearances shown in Figure 4. If you can, provide greater clearances from floor, ceiling, and joining wall.
You can locate heater on the floor, away from a wall. A wall mounting bracket and floor base stand are included with this heater. Determine which method is best for your application.
CEILING
36"
10"
Minimum From Sides Of Heater
Left Side
Minimum
Right Side
WARNING: A qualified ser­vice person must install heater. Follow all local codes.
www.desatech.com 7113052-01A
2"
Minimum To
FLOOR
Top Surface Of Carpeting, Tile Or Other Combustible Material
Figure 4 - Mounting Clearances As
Viewed From Front of Heater
INSTALLATION
Continued
WARNING: Never install the heater
in a bedroom or bathroom
in a recreational vehicle
where curtains, furniture,
clothing, or other flammable objects are less than 36 inches from the front, top, or sides of the heater
as a fireplace insert
in high traffic areas
in windy or drafty areas
CAUTION: If you install the heater in a home garage
heater pilot and burner must
be at least 18 inches above floor
locate heater where moving
vehicle will not hit it
CAUTION: This heater cre­ates warm air currents. These currents move heat to wall sur­faces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning flu­ids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
IMPORTANT:
the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much mois­ture. See Air for Combustion and Ventilation, pages 5 through 7. If high humidity is experi­enced, a dehumidifier may be used to help lower the water vapor content in the air.
For convenience and efficiency, install heater
• where there is easy access for operation, inspec­tion, and service
• in coldest part of room
8
Vent-free heaters add moisture to
www.desatech.com 113052-01A
An optional fan kit is available from your dealer. See Accessories, page 33. If planning to use fan, locate heater near an electrical outlet.
THERMOSTAT SENSING BULB
(Thermostat Models Only)
The thermostat sensing bulb has been placed be­low the heater.
1. Place clamp on thermostat sensing bulb as shown in Figure 5. Clamp is provided in hard­ware package.
2. Snap clamp into upper mounting hole as shown in Figure 5. Mounting hole is located on lower left edge on back of heater. Make sure the ther ­mostat sensing bulb is pointing up.
Thermostat Sensing Bulb
Clamp
Figure 5 - Attaching Thermostat Sensing
Bulb
INSTALLING HEATER TO WALL
Mounting Bracket
Locate mounting bracket in heater carton. Remove mounting bracket from heater carton.
Figure 6 - Mounting Bracket
Removing Front Panel Of Heater
1. Remove the four painted screws, two on each side of front panel.
2. Pull bottom of front panel forward, then out.
3. Remove any remaining packaging materials.
Front Panel
Figure 7 - Removing Front Panel Of
Heater
Screw
INSTALLATION
Continued
Methods For Attaching Mounting Bracket To Wall
Only use last hole on each end of mounting bracket to attach bracket to wall. These two holes are 14 inches apart from their centers. Attach mounting bracket to wall in one of two ways:
1. Attaching to wall stud
2. Attaching to wall anchor
Attaching to W all Stud: This method provides the
strongest hold. Insert mounting screws through mounting bracket and into wall studs.
Attaching to W all Anchor: This method allows you
to attach mounting bracket to hollow walls (wall areas between studs) or to solid walls (concrete or masonry).
Decide which method better suits your needs. Ei­ther method will provide a secure hold for the mounting bracket.
Marking Screw Locations
1. Tape mounting bracket to wall where heater will be located. Make sure mounting bracket is level.
WARNING: Maintain mini­mum clearances shown in Fig­ure 8. If you can, provide greater clearances from floor and join­ing wall.
2. Mark screw locations on wall (see Figure 8).
Note:
Only mark last hole on each end of mounting bracket. Insert mounting screws through these holes only.
3. Remove tape and mounting bracket from wall.
16"
Min.
Only Insert Mounting Screws Through Last
Adjoining Wall
14"
Hole On Each End
Floor
25 3/4"
Optional
19 3/4"
Min.
4 and 5 Plaque Heaters
12"
Min.
Only Insert Mounting Screws Through Last
Adjoining Wall
14"
Hole On Each End
Floor
25 3/4"
Optional
19 3/4"
Min.
3 Plaque Heater
Figure 8 - Mounting Bracket Clearances
Attaching Mounting Bracket To Wall
Note:
Wall anchors, mounting screws, and spac­ers are in hardware package. The hardware pack­age is provided with heater.
Attaching To Wall Stud Method
For attaching mounting bracket to wall studs
1. Drill holes at marked locations using 9/64"
drill bit.
2. Place mounting bracket onto wall. Line up last
hole on each end of bracket with holes drilled in wall.
3. Insert mounting screws through bracket and
into wall studs.
4. Tighten screws until mounting bracket is
firmly fastened to wall studs.
Attaching To Wall Anchor Method
For attaching mounting bracket to hollow walls (wall areas between studs) or solid walls (concrete or masonry)
1. Drill holes at marked locations using 5/16"
drill bit. For solid walls (concrete or masonry), drill at least 1" deep.
www.desatech.com 9113052-01A
INSTALLATION
Continued
2. Fold wall anchor as shown in Figure 9.
3. Insert wall anchor (wings first) into hole. T ap anchor flush to wall.
4. For thin walls (1/2" or less), insert red key into wall anchor. Push red key to “pop” open anchor wings.
IMPORTANT:
For thick walls (over 1/2" thick) or solid walls, do not pop open wings.
5. Place mounting bracket onto wall. Line up last hole on each end of bracket with wall anchors.
6. Insert mounting screws through bracket and into wall anchors.
7. Tighten screws until mounting bracket is firmly fastened to wall.
Figure 9 - Folding Anchor
Do not hammer key!
Installing Bottom Mounting Screws
1. Locate two bottom mounting holes. These holes are near bottom on back panel of heater (see Figure 12).
2. Mark screw locations on wall.
3. Remove heater from mounting bracket.
4. If installing bottom mounting screws into hol­low or solid wall, install wall anchors. Fol­low steps 1 through 4 under Attaching T o W all Anchor Method, pages 9 and 10.
If installing bottom mounting screw into wall stud, drill holes at marked locations using 9/64" drill bit.
5. Replace heater onto mounting bracket.
6. Place spacers between bottom mounting holes and wall anchor or drilled hole.
7. Hold spacer in place with one hand. With other hand, insert mounting screw through bottom mounting hole and spacer. Place tip of screw in opening of wall anchor or drilled hole.
8. Tighten both screws until heater is firmly se­cured to wall. Do not over tighten.
Note:
Do not replace front panel at this time. Replace front panel after making gas connections and checking for leaks (see pages 12 and 13).
Figure 10 - Popping Open Anchor Wings
For Thin Walls
Placing Heater On Mounting Bracket
1. Locate two horizontal slots on back panel of heater.
2. Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mount­ing bracket.
Stand-Out Tab
Horizontal Slots
Mounting Bracket (attached to wall)
Figure 11 - Mounting Heater Onto
Mounting Bracket
10
www.desatech.com 113052-01A
Front View
Wall
Heater
Spacer
Side View
Figure 12 - Installing Bottom Mounting
Screws
INSTALLATION
Continued
MOUNTING HEATER TO FLOOR
Mounting Base Feet to Heater
1. Lay heater cabinet on its back on a table with the heater bottom overhanging the table edge.
2. Align holes in base foot with mounting holes on bottom of cabinet (see Figure 13).
3. Secure base foot to heater using sheet metal screws.
4. Repeat for other side.
Mounting Base Feet to Floor (Where required by local code)
1. Remove front cover (see Removing Front Panel of Heater, page 8).
2. Position heater with base feet in desired loca­tion. Mark holes for drilling. Remove heater with base.
3. For carpeted floors, make a small cut with a sharp knife at marked locations prior to drill­ing. If mounting base to a wood floor, drill 1/8 inch diameter hole, 3/4 inch deep. (Do not use anchors in wood floors).
If mounting base to a concrete floor, drill with 1/4 inch diameter concrete drill bit, 1 into floor. Insert anchors completely into holes.
4. Reposition heater with base feet over holes. Secure base to floor with wood screws. See Figure 13.
Base Foot
Sheet Metal Screw
Figure 13 - Installing Base Feet
3
/8 inches
Wood Screw
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualified service person must connect heater to gas supply. Follow all local codes.
WARNING: For natural gas, never connect heater to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
IMPORTANT:
pressure before connecting heater to gas line. Gas line pressure must be no greater than 14 inches of water. If gas line pressure is higher , heater regula­tor damage could occur.
For natural gas, check gas line
CAUTION: For propane/LP gas, never connect heater directly to the propane/LP supply. This heater requires an external regu­lator (not supplied). Install the ex­ternal regulator between the heater and propane/LP supply.
For propane/LP gas, the installer must supply an external regulator. The external regulator will re­duce incoming gas pressure. You must reduce in­coming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pres­sure, heater regulator damage could occur. Install the external regulator with the vent pointing down as shown in Figure 14. Pointing the vent down protects it from freezing rain or sleet.
Propane/LP Supply Tank
External Regulator
Vent Pointing Down
Figure 14 - External Regulator With Vent
www.desatech.com 11113052-01A
Pointing Down
Loading...
+ 25 hidden pages